BPL150-12 - BB

VRLA Rechargeable Battery
Measures
BPL150-12
Technology
Values
Innovation
APPLICATION
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Filtered with explosion proof filter.
Flame-arrestor is installed to ensure safety.
Carry handles for easy installation.
Absorbent Glass Mat technology for efficient gas recombination.
UPS
Telecom
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
12 V
150.0Ah @ 20 hour rate F.V.(1.75V/cell)
51.8Kg(114.2lbs.)
B9 (Fitting M8 bolt & nut) I3 is optional
2.7m (Fully Charged )
800 A (5 sec.)
45 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Container Material
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
Standard: ABS( UL 94-HB) BPL150-12
Optional: Flame Retardant ABS(UL 94-V0) BPL150-12FR
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
483±2.0 (19.02±0.08)
Terminal I3
Terminal B9
M8x1.25
Width
3.5(0.14)
171±2.0 (6.73±0.08)
Container Height
240±2.0 (9.45±0.08)
[M8 BOLT & NUT]
Total Height
240±2.0 (9.45±0.08)
Terminal Hardware Initial Torque: B9/ I3(10.0Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF
Discharge
Time
[M8 BOLT]
Unit: W
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
2749
1903
1092
437.1
301.5
168.4
88.9
1.75V
2876
1976
1124
445.9
306.0
171.0
90.0
1.70V
2965
2021
1145
450.0
307.7
171.9
90.5
1.65V
3033
2049
1158
453.2
308.8
172.3
90.7
1.60V
3094
2070
1170
455.8
309.6
172.3
90.7
F.V.
(V/cell)
o
o
Constant current discharge characteristics at 25 C/77 F
Discharge
Time
Unit: A
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
239
161
91.7
36.4
25.1
14.04
7.41
1.75V
250
167
94.5
37.2
25.5
14.25
7.50
1.70V
258
171
96.2
37.5
25.6
14.32
7.54
1.65V
264
174
97.3
37.8
25.7
14.36
7.56
1.60V
269
175
98.3
38.0
25.8
14.36
7.56
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/2
REV. Mar. 2013
Powered by