FTB110-12 - BB

VRLA Rechargeable Battery
Measures
Technology
Values
Innovation
FTB110-12
FEATURES
APPLICATION
Telecom
UPS
Broadband
Electric Utility
Railroad Signal
Central Office
Absorbent Glass Mat technology for efficient gas recombination
Thermally welded case-to-cover bond to ensure a leak-proof case
Front accessible terminal for ease of assembly
Carry handles for ease of installation
Strengthened rib design to maintain structural integrity
Flame-arrestor is installed to ensure safety
Battery design allows for 48VDC configuration in a standard 23'' rack
One-way self-resealing safety valve for long life guarantee
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
12 V
110Ah @ 8 hour rate F.V.(1.75V/cell)
41.1Kg(90.6lbs.)
L1 (M8 Male Stud)
(Fully Charged )
3.0m
800 A (5 sec.)
27.5 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Operating Temperature Range
Safety Valve
Container Material
FTB110-12
Standard: PP( UL 94-HB)
Optional: Flame Retardant PP(UL 94-V0) FTB110-12FR
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
560.0±2.0 22.05±0.08
Terminal L1
560±2.0 (22.05±0.08)
57.1 (2.25)
Constant power discharge characteristics at 25 oC/77 oF
F.V.
(V/cell)
Discharge
Time
1.90V
1.85V
1.80V
1.75V
1.70V
1.65V
1.60V
F.V.
(V/cell)
1.90V
1.85V
1.80V
1.75V
1.70V
1.65V
1.60V
24.9 (0.98)
3.0 (0.12)
M8 x 1.25
Terminal Hardware Initial Torque: 10.0Nm ±5%
Unit: W
15 Min
30 Min
45 Min
1 Hr
2 Hr
3 Hr
4 Hr
5 Hr
8 Hr
10 Hr
20 Hr
1467
1731
1957
2148
2300
2400
2444
1226
1348
1433
1486
1519
1542
1556
895
978
1033
1068
1089
1104
1113
712.1
791.9
836.6
856.5
870.6
882.4
887.7
433.7
477.5
496.5
505.9
510.7
515.4
517.5
322.6
352.5
365.6
370.4
374.0
377.6
378.9
255.6
279.6
289.2
294.0
296.4
298.8
299.7
213.6
232.8
240.0
244.8
246.0
247.2
247.9
145.20
157.10
162.30
165.00
165.00
165.00
165.36
118.44
128.76
133.32
134.64
134.64
134.64
134.88
62.88
68.40
70.80
72.00
72.00
72.00
72.07
Constant current discharge characteristics at 25 oC/77 oF
Discharge
Time
10.5 (0.41)
207.6±2.0 (8.17±0.08)
Total Height
230.0±2.0 9.06±0.08
230±2.0 (9.06±0.08)
4.92±0.08
Container Height
230.0±2.0 9.06±0.08
12.0 (0.47)
23.8 (0.94)
125±2.0 (4.92±0.08)
Width
125.0±2.0
IEC60896
BS6290/4
GB/T 19638
Eurobat guide
Opening pressure 10~35 kPa
Unit: A
15 Min
30 Min
45 Min
1 Hr
2 Hr
3 Hr
4 Hr
5 Hr
8 Hr
10 Hr
20 Hr
123.9
146.5
167.9
187.7
203.0
212.3
216.2
102.1
113.5
121.4
125.9
128.8
130. 6
131.9
74.6
82.1
87.1
90.0
91.8
93.1
93.9
60.60
67.40
71.20
72.90
74.10
75.10
75.55
36.60
40.30
41.90
42.70
43.10
43.50
43.67
27.00
29.50
30.60
31.00
31.30
31.60
31.71
21.30
23.30
24.10
24.50
24.70
24.90
24.97
17.80
19.40
20.00
20.40
20.50
20.60
20.66
12.10
13.09
13.53
13.75
13.75
13.75
13.78
9.87
10.73
11.11
11.22
11.22
11.22
11.24
5.24
5.70
5.90
6.00
6.00
6.00
6.01
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/2
REV. Jul. 2013
Powered by B.B. Battery Co., Ltd.