Using BCM® Bus Converters in High Power Arrays

APPLICATION NOTE | AN:016
Using BCM® Bus Converters
in High Power Arrays
Paul Yeaman
Director, VI Chip® Application Engineering
Februrary 2011
ContentsPage
Introduction
Introduction1
This application note provides methods and guidelines for designing BCM® bus
converters into high power arrays.
Theory1
Design1
Symmetrical Input / Output Resistances
2
ROUT Matching
2
Uniform Cooling
3
Arrays Powered
From Multiple Inputs
3
Design Example
4
General Guidelines
6
Conclusion6
Theory
BCM modules current share when their respective inputs and outputs are connected in
parallel. Sharing accuracy is a function of a) input and output interconnect impedance
matching, b) the output impedances (ROUT) of the BCM modules, and c) uniform cooling.
In theory, a very large number of modules can be paralleled. In practice arrays larger
than 10 become difficult due to “a” and “c” above. Please contact Vicor Applications
Engineering if you are designing an array with more than 10 modules.
Since bus converters are isolated transformers, their outputs may be paralleled with
inputs powered from different sources. The lower the ROUT of the module, the more
closely input voltages must match to avoid excessive current imbalance. As such, the
input voltages must be equal to ensure evenly distributed sharing.
Figure 1.
+IN
BCM parallel array
block diagram
+OUT
BCM® Module 1
Common
Input Voltage
Source
–IN
–OUT
+IN
+OUT
BCM® Module 2
–IN
–OUT
+IN
+OUT
Isolated
Output
Bus
BCM® Module 3
–IN
AN:016
vicorpower.com –OUT
Applications Engineering: 800 927.9474
Page 1
RSV
TM
Symmetrical Input / Output Resistances
+IN
+OUT
The primary design concern for a high power array is the layout of a symmetrical input
-IN
-OUT
and output feed. Figure 2 represents a simplified model of BCM® bus converter
sharing
for an array of 2.
In this case, the circuit has been reduced to its core elements and each BCM module
is represented as a resistor with resistance ROUT. This model can easily be expanded to
represent larger arrays.
Figure 2.
PRIMARY
Simplified model of BCM®
module sharing
RINPUT1
SECONDARY
BCM® Module 1
ROUTPUT1
ROUT
I1 • K
I1
I2 • K
I2
VIN
Load
RINPUT2
ROUT
ROUTPUT2
BCM Module 2
®
If RINPUT1 = RINPUT2 and ROUTPUT1 = ROUTPUT2 then the current through both legs will be
equal. An increase in ROUTPUT1 will decrease I1 proportionally. It is important to note,
®
BCM
1 For
however, that an increase in RINPUT1 will decrease I1 to the square of
the Module
K factor.
R
OUT
BCM modules having a small K factor (<<1) the matching of the input impedance is less
VIN1
critical. For example, assume the following:
K
I1
= 1/32
ROUT
= 10 mohm
ROUTPUT1 = ROUTPUT2 = RINPUT1 = 0.
VIN2
I2
RINPUT2 = 1 ohm
ROUT
BCM® Module 2
Solving for I1 :
I2
I1 • ROUT + (I1 • K• RINPUT1) • K = I2 • ROUT + (I2 • K• RINPUT2) • K
RINPUT1 = 0 so:
I1 • ROUT = I2 • ROUT + I2 • K2 • RINPUT2
Substituting values yields:
I1 •
I1
I2
1
100
=
= I2 •
( 1
100
+
1 )
1024
11
10
This indicates that BCM module 1 carries approximately 10% more current with a 1
ohm impedance in series with the input of BCM module 2 for K=1/32. However, if K
were equal to 1, then BCM module 1 would carry essentially 100% of the current.
AN:016
vicorpower.com Applications Engineering: 800 927.9474
Page 2
TM
VIN
C1
400 µF
+IN
ROUT Matching
+OUT
-IN
-OUTdata sheet and has a positive
® bus converter
ROUT is specified as a range in the BCM
temperature coefficient with the specified range that reinforces sharing. As the modules
temperature increases due to increased dissipation, the ROUT increases. This decreases
the amount of current flowing through
the
PCthat BCM module in an array, reducing
VOUT
module power dissipation.
RSV
TM
Uniform Cooling
+IN
+OUT
Due to the positive temperature coefficient of ROUT, BCM modules mounted close to
each other and cooled equally will tend
power dissipation.
-INto equalize
-OUT
The true power limitation on the module is based on dissipation. Therefore, the module
that has a lower ROUT may have a higher current when connected in an array (thus
a higher power), but given that its dissipation is the same as neighboring units in an
array, it will have similar MTBF characteristics.
The power rating of an array of BCM modules is equal to the power rating of the
individual
module times the number of modules in an array. Even under the ideal
SECONDARY
PRIMARY
circumstances,
the current
through each module will not be equal, so under full power
BCM® Module
1
the
current
may
RINPUT1 conditions
ROUTPUT1not be perfectly balanced. However, assuming that the
ROUT
module array is cooled equally, and the input and output impedances are matched, a
I1
current imbalance is acceptable
if the dissipation of this BCM module is the same as
I1 K
others in the array. It is important never to exceed the maximum rated DC current of
Load
the module under any circumstances.
•
VIN
I2 • K
I2
ROUT
ROUTPUT2
RINPUT2 Arrays Powered
From
Multiple Inputs
®
BCM
Module
2
Figure 3 addresses an arrangement in which the BCM modules are powered from
separate inputs.
Figure 3.
Parallel arrays fromseparate
inputs
VIN1
BCM® Module 1
ROUT
I1
Load
VIN2
I2
ROUT
BCM® Module 2
In this example, input and output impedances are considered negligible. If VIN1 = VIN2
then the currents in both legs are equal. However assume the following:
VIN1 = 48 V
VIN2 = 49 V
ROUT = 1 mohm
K
= 1/32
ILOAD = 100 A
The two BCM modules must satisfy the following equation:
VIN1 • K-IOUT1 • ROUT = VIN2 • K-IOUT2 • ROUT
AN:016
vicorpower.com Applications Engineering: 800 927.9474
Page 3
Also,
IOUT1 + IOUT2 = 100 A
Solving the simultaneous equations for IOUT1 and IOUT2 yields:
IOUT1 = 35 A
IOUT2 = 65 A
The same technique can be extended to include arrays with a larger number of BCM
modules.
If VIN1 - VIN2 > IOUT1 • ROUT, then BCM® module 1 will attempt to backfeed current
through BCM module 2 to increase VIN2. To prevent reverse current in this situation,
diodes can be added in series with +In of each BCM module.
Design Example
Figure 4 shows an example array of 7 high voltage input 300 W BCM bus converters
to provide a total power of 2.1 kW. Table 1 illustrates the measured currents for the
laboratory layout shown in Figure 5. Even with less than ideal layout conditions (long
wires, separate boards, use of standoffs to carry current), the overall sharing of the array
is within 5%.
BCM modules switch at >1 MHz and have an effective output ripple of 2 times the
switching frequency, so output filtering is provided using a small point-of-load
capacitor in conjunction with trace inductance. The use of the input inductors confines
the high-frequency ripple current of each module. Some input inductance between
the modules inputs is necessary to minimize interactions between parallel connected
modules and allow for proper operation for the array. Input inductance also reduces
EMI and promotes the overall stability of the system by reducing (or eliminating) beat
frequencies caused by the asynchronous switching of the BCM modules.
Connecting the PC pins of the BCM modules in the array allows all units in the array
to be enabled and disabled simultaneously. Simultaneous startup is required in cases
where the array will start up into more current than one BCM module is sized to handle.
AN:016
vicorpower.com Applications Engineering: 800 927.9474
Page 4
Figure 4.
PC
RSV
TM
®
BCM bus converter array
using 7 modules
L1
1.5 µH
B352F110T30
F2
350 Vdc
+IN
+OUT
-IN
-OUT
PC
RSV
TM
2A
2A
-OUT
B352F110T30
F1
F4
+OUT
-IN
PC
RSV
TM
L2
1.5 µH
1A
+IN
L3
1.5 µH
B352F110T30
+IN
+OUT
-IN
-OUT
+OUT
PC
RSV
TM
L4
1.5 µH
B352F110T30
C1
400 µF
F3
+IN
+OUT
11 Vdc
-IN
-OUT
190 A
PC
RSV
TM
2A
L5
1.5 µH
B352F110T30
+IN
+OUT
-IN
-OUT
– OUT
PC
RSV
TM
L6
1.5 µH
B352F110T30
+IN
+OUT
-IN
-OUT
PC
RSV
TM
L1
1.5 µH
B352F110T30
+IN
+OUT
-IN
-OUT
PC
Table1.
Module #
®
7 BCM bus converter array
current sharing
U1
U2
U3
U4
U5
U6
U7
Worst Case
deviation
from
nominal (%)
AN:016
48 A Load
(6.86 A / BCM)
95 A Load
(13.6 A / BCM)
143 A Load
(20.4 A / BCM)
192 A Load
(27.5 A / BCM)
IBCM
% Deviation
IBCM
% Deviation
IBCM
% Deviation
IBCM
% Deviation
5.9
7.1
6.7
7.4
7.1
7.2
6.8
14.0
3.4
2.4
7.9
3.4
5.0
0.9
12.6
13.2
13.6
14.4
14.0
14.0
13.5
7.4
2.9
0.0
5.9
2.9
2.9
0.7
19.2
19.9
20.6
21.3
20.8
20.9
20.4
5.9
2.5
1.0
4.4
2.0
2.5
0.0
27.6
27.3
27.7
27.4
27.5
27.7
27.2
0.4
0.7
0.7
0.4
0.0
0.7
1.1
14.0
vicorpower.com 7.4
5.9
Applications Engineering: 800 927.9474
1.1
Page 5
Figure 5.
Laboratory demonstration
of the 7 BCM®
bus converter array
General Guidelines
1.Always ensure that the BCM® bus converters are fused according to safety agency requirements.
2.PC pins of BCM modules should be connected together to enable and disable the modules simultaneously.
3.All signal and power traces should be laid out on the PCB to minimize noise coupling and impedance. For more details on PCB layout guidelines, please see AN:005.
4.An inductor should be placed in series with the +In of each BCM bus converter in the array to minimize high frequency circulating currents in the primary as well as beat frequencies caused by asynchronous switching.
5.BCM modules fed from different sources with outputs in parallel must have appropriately matched inputs as the input voltage matching plays a critical role in current sharing.
6.In large arrays, routing issues may cause mismatching input and output impedances to each BCM module. In that case, varying trace widths should be used to equalize impedances between close and distant modules.
7.In large arrays, it may be difficult to match cooling for each BCM module in the array. In that case, heat sink design or airflow routing should be adjusted to equalize module cooling as much as possible. To optimize reliability, overall temperature should be as low as possible.
8. Load capacitors should be placed near the load. Refer to the BCM datasheet for the maximum output capacitor value in an array. In cases where the load bypassing capacitance must be placed near the BCMs, they should be created with individual capacitors distributed across each BCM output, rather than lumped on a single BCM output.
AN:016
vicorpower.com Applications Engineering: 800 927.9474
Page 6
Conclusion
High power arrays can be created using the bus converters in parallel provided that care
is taken in designing the input and output connections. BCM modules share inherently
with inputs and outputs connected in parallel, with the positive temperature coefficient
of ROUT reinforcing sharing. Assuming equal cooling, an array can operate at full
power with accurate sharing and no derating. The array should be designed based on
guidelines that optimize protection, efficiency, reliability, and minimize noise.
Information furnished by Vicor is believed to be accurate and reliable. However, no
responsibility is assumed by Vicor for its use. Vicor components are not designed to
be used in applications, such as life support systems, wherein a failure or malfunction
could result in injury or death. All sales are subject to Vicor’s Terms and Conditions
of Sale, which are available upon request.
Specifications are subject to change without notice.
The Power Behind Performance
Rev 1.6
11/13
vicorpower.com Applications Engineering: 800 927.9474
Page 7