Delcon EX series Relays

EX
- SERIES -
10 years
Ex-relays
warranty
for hazardous locations
Interface Relays
Introduction
Delcon was founded in 1975 as a specialist manufacturer of solid
state interface relays. Our relay design utilizes pulse transformer
technology which gives unique advantages over traditional opto
coupler based solid state relays and electro mechanical relays. This
helps ensure a long lifetime and trouble free performance in harsh
industrial applications where difficult loads, noise and interference can
cause big problems.
Delcon has distributors in more than 20 countries. The largest
customer segments are the energy industry, cargo handling at ports,
as well as the pulp and paper industry. Delcon’s customers include a
number of companies that are the market leaders in their own fields.
Explanations for EX-relay classifications are on page 7.
Problems with interference
Problems with signaling
• Power cables installed adjacent to signal cables, especially
over long cable runs, create a capacitive effect that can
cause opto coupler/electro mechanical relays to switch on or
remain on after the control signal switches off
• Electrical disturbances can cause the LED indicator of the
opto coupler / electromechanical relays to glow when the
relay is switched off and no input signal present. This makes
it difficult to quickly diagnose faults and rectify problems
• Transients in the power supply causes damage to relay coils/
opto coupler relays
• Interference from frequency inverters can provide false on/off
switching
Solution
Delcon relays have built in capacitive suppression to allow
safe, reliable operation even with very long cable runs. An RC
circuit protects the relays from transients and high frequency
interference.
Hysteresis
Puls
transformer
Output
Protection
circuitSwitch on
Switch off
I
U
y
Current mA
Interference
Suppression
Solution
The Delcon LED is synchronized with the output so it is
impossible for it to glow without being on. The relays have
good hysteresis with clearly defined on / off points for reliable
operation in high noise environments.
ela
lr
a
nic
ha
ec
M
n
o
elc
y
la
re
D
Opto
r relay
couple
Voltage V
Interface Relays
Problems with inductive loads
Problems with high dc voltage
• Contactors and solenoid valves are commonly used
throughout the industry, they are also problematic inductive
loads for electromechanical relays to handle
• Reduced switching capacity
• Electromechanical relays are significantly derated at higher
DC voltages
• Contacts weld
• Usually require special version electromechanical relays that
are physically bigger and take up more space
• Short lifetime
Solution
Delcon AC output relays are rated at 3A and can switch inductive
loads without any derating. Delcon DC output relays have no
derating up to 24Vdc and thereafter still offer significantly less
derating compared to electromechanical relays.
Solution
Delcon DC output relay types CHA & CHA4 can switch up to
300Vdc with no derating compared to electromechanical relay
and in a smaller package. Example EXO 24CHA4 switching
40ms inductive load at 3A / 110Vdc will give service life of 15
years or more.
10
E-mech relay resistive loads, DC1
E-mech relay inductive loads, L/R 40 ms
Delcon relayy inductive loads, L/R 50 ms
Amps.
1
0,1
Volts
0
25
75
125
175
www.weidmuller.com
225
275
325
Weidmuller, USA | 800.849.9343 | [email protected]
Weidmuller, Canada | 800.268.4080 | [email protected]
Weidmuller, Mexico | 01.222.2686267 | [email protected]
375
Interface Relays
Changing relays is a costly business
Compared to the total system cost, a relay is a relatively
inexpensive component. However, a relay that fails in a system runs
the risk of becoming the most expensive component. Choosing a
relay with a shorter life span than the entire system will probably
result in costly unwanted system downtime!
The life span of an industrial system is typically considered to be 15
years.
If your application has any of the following requirements then select
Delcon relays for a hassle free and safe operation that spans the
entire system life.
• Frequent switching - relays operate at least once per minute
• Inductive loads – fitting clamp diodes can help but increases
switch off time
• Inductive loads combined with high switching frequency
• High dc voltages
Cost of Delcon
Cost of third
replacement
Cost of E-Mech relay
Cost of first
replacement
Cost of second
replacement
Cost
Cost of downtime
ce
Cost pri
n
o
Delc
ce
Cost pri lay
re
h
c
e
E-M
9 year
Lifetime
6 year
3 year
Choosing Delcon relays for your system will improve your long
term profitability. The cost of system downtime differs depending
on the type of industry but is usually very expensive. If we
consider only the cost of trouble shooting and replacing a faulty
relay for the first time then the initial cost of choosing Delcon is
already exceeded.
Delcon is the default choice in many Scandinavian paper mills
which is a well known, tough industrial environment. These
customers choose Delcon for reliable, safe operation and long
term cost savings through minimal maintenance and avoiding
costly downtime.
Interface Relays
Quick guide
CH
AC input relays
DC input relays
•
•
•
•
CHP
Long signal cables (> 100 m)
Parallel signal & load cables
Radio frequency noise
Transient noise
• 2 wire sensor version for leakage current
immunity up to 3.5mA
CH
CHF
• Parallel signal & load cables
• Radio frequency noise
• Transient noise
• High switching frequency
TR
AC output
relays
• high switching frequency
• resistive loads
• inductive loads
CH
DC output
relays
CHA & CHA4
• high switching frequency
• resistive loads
• inductive loads
• high DC-loads
IHA
DC output relay
for AC/DC
loads
• all AC- and DC-loads
• high switching
• 0,5 ms off-delay
Mounting bases for EXI-relays:
• MIS 1GNEX (screw connectors)
• MIS 1CCNEX (spring connectors)
• MIS 1TNEX (screw connectors with test contacts)
Mounting bases for EXO-relays:
• MOS 1GNEX (screw connectors)
• MOS 1CCNEX (spring connectors)
• MOS 1TNEX (screw connectors with test contacts)
Accessories
For more information please call or visit our website www.delcon.fi
www.weidmuller.com
Weidmuller, USA | 800.849.9343 | [email protected]
Weidmuller, Canada | 800.268.4080 | [email protected]
Weidmuller, Mexico | 01.222.2686267 | [email protected]
Interface Relays
Delcon’s unique interface relays
Field of application
Delcon’s interface relays are designed to withstand tough
industrial environments. Reliable activation and drop out, very high
interference immunity, 4 kV isolation and high load currents provide
a maintenance-free process with low service costs and reliable
operation. Lifetime is estimated at up to 20 years, depending on
the type.
Interference
Suppression
Interference
Suppression
Puls
transformer
Hysteresis
I
Hysteresis
Puls
transformer
nce
sion
Interference
Suppression
Output
Interference
circuit
Protection
Hysteresis
Output
circuit
Protection
Transient & High Frequency Suppression
The relays have integrated protection against transients and
EMI
can occur on the primary side.
I that U
Hysteresis
I
Puls
transformer
Hysteresis
InterferenceOutput
Suppressioncircuit
Puls
transformer
Hysteresis
Protection
Puls
transformer
Switching Points & Hysteresis
The relays have defined activation and drop-out points.
I
Uvoltage and drop
Puls at 2/3 of the
U
Output
Activation occurs
nominal
Hysteresis
Protection
transformer
circuit
out occurs
at 1/2 of the nominal
voltage. Current hysteresis
entails that the relay’s impedance is changed at the
activation
point; less current is required to hold the relay
I
U
in the activated position. The two functions above ensure
a hysteresis between the activation and drop-out point.
Activation and drop out are always reliably conducted, even
in environments with high interference.
The diagram shows the change-over levels/hysteresis for Delcon’s
interface relays compared with mechanical relays and optocouplers.
C u r re n t
mA
On
Of f
De
Re
Protection
Puls
transformer
Output
circuit
Protection
Pulse transformer
Delcon uses a pulse transformer for
transmission of the signal from the primary
to secondary side, resulting in high energy
transfer. This permits the
use of heavy duty output components of high quality.
In comparison with an optocoupler, which utilises the load side
for supply to the internal electronics, the pulse transformer and
Delcon’s circuit solution offer many benefits:
• Creep distance of 8 mm
• 4 kV isolation
• Very low leakage current
• No demand for min. load
• High immunity to load transients
• High load currents
• High dV/dt values
Output
circuit
Protection
Solid State Switch & Protection
Components
AC output
TRIAC output semi-conductor. Thanks to the
pulse transformer’s strong signal transmission,
TRIACs can be used that are less sensitive to
rapid load voltage (dV/dt) rise/fall times. Sensitive TRIACs can be
activated by rapid voltage changes. This problem is eliminated with
Delcon’s interface relays. The SLO24TR standard relay has very low
leakage current (0.05 mA) and has varistor protection against load
transients. Other AC relays have varistors and RC protection on the
secondary side. No minimum load is required and all modules have
a wide voltage range. The relays can handle resistive and inductive
loads without load currents needing to be reduced.
DC output
Power MOSFET output semi-conductor.
Available for load currents up to 10A in the
same compact casing. Transient protection is
provided by a zener diode or varistor, which
entails that there is no leakage current. Low
reduction of load current for inductive loads
compared with mechanical relays.
Voltage /current - signal diagram
n
lco
Output
circuit
U
Suppression
Capacitive Suppression
When power cables with AC voltage are installed alongside
I
a signal cable,
aUcapacitance occurs between the cables.
I
U
This capacitance creates an undesired current in the signal
cable that can affect optocouplers/mechanical relays so that they
are activated or do not disconnect when the control signal ceases.
Delcon’s relays have integrated protection that prevents capacitive
cross-talk from incorrectly activating relays. Installation of power
cables beside unshielded signal cables for long distances (>1.5 km)
is therefore feasible.
Interference
Suppression
Interference protection
Delcon’s interface relays have interference protection in several
layers that effectively prevent false signals from affecting the relays.
Only actual control signals pass through the filter.
lay
elay
cal R
ha ni
c
e
er
t ro m
coupl
El e c
Opto
Voltage
DC
Interface Relays
Quick guide
HazLoc:
•
•
•
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, IIC
T4 (Ta ≤ 70 °C)
Where...
Class I = Gases and Vapors
Division 2 = Not normally present in an explosive
concentration (but may accidentally exist)
Groups = A: Acetylene
B: Hydrogen, etc.
C: Ether, etc.
D: Hydrocarbons, fuels, solvents, etc.
Zone 2 = Place in which an explosive atmosphere
consisting of a mixture with air of flammable
substances in the form of gas, vapor or mists is
not likely to occur in normal operation but, if it
does occur, will persist for a short period only.
T4 (Ta ≤ 70 °C) = Maximum surface temperature
ATEX: II 3 G Ex nA IIC Gc
Where...
II = Device group II; There are 2 groups of devices.
Devices of Group I, Category M are for use in
underground mines and their above ground
equipment, which are at risk from firedamp and/
or inflammable dusts. All other areas at risk of
explosion are combined in Device Group II.
3G = Category 3; equipment ensuring a normal level of
protection. Explosive atmospheres are unlikely
to occur.
Ex = explosion protection identifier.
nA = Protection principle non sparking device.
IIC = Explosion group; IIC can be used for all explosion
groups (IIA, IIB and IIC).
Gc = Protection level; Assured level of protection against
becoming an ignition source in normal operation.
IECEx: Ex nA IIC Gc
Where...
Ex = explosion protection identifier.
nA = Protection principle non sparking device.
IIC = Explosion group; IIC can be used for all explosion
groups.
Gc = Protection level; Assured level of protection against
becoming an ignition source in normal operation
www.weidmuller.com
Weidmuller, USA | 800.849.9343 | [email protected]
Weidmuller, Canada | 800.268.4080 | [email protected]
Weidmuller, Mexico | 01.222.2686267 | [email protected]
Interface Relays
Ex-output relays: DC-control, DC-load
Relay type EXI 12CH EXI 24CH EXI 24CHF EXI 24CHL EXI 48CH EXI 125CH EXI 250CH Application Limit switches Limit switches Fast connection Increased input current Limit switches Limit switches Limit switches Control voltage 12 VDC 24 VDC 24 VDC 24 VDC 48 VDC 120 VDC 250 VDC Load voltage 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC Max. current
50 mA
50 mA
50 mA
50 mA
50 mA
50 mA
50 mA
Load voltage 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC 0...28 VDC Max. current
50 mA
50 mA
50 mA
100 mA
50 mA
50 mA
100 mA
50 mA
50 mA
Load voltage 0...60 VDC 0...250 VDC 0...28 VDC 0...28 VDC 0...60 VDC 0...250 VDC 0...28 VDC 0...28 VDC 0...60 VDC 0...250 VDC 0...250 VDC 0...28 VDC 0...28 VDC 0...250 VDC 0...250 VDC 0...28 VDC 0...28 VDC 0...250 VDC 0...250 VDC 0...250 VDC 0...250 VDC Max. current
3A
1,8 A
10 A*
10 A
3A
1,8 A
10 A*
10 A
3A
1,8 A
4A
10 A*
10 A
1,8 A
4A
10 A*
10 A
1,8 A
4A
1,8 A
4A
Load voltage 0...240 VAC/250 VDC 0...240 VAC 0...240 VAC 0...240 VAC/250 VDC 0...240 VAC 0...240 VAC Max. current
1,2 A
3A
3A
1,2 A
3A
3A
Load voltage 0...240 VAC 0...240 VAC Max. current
3A
1,5 A
Ex-input relays: AC-control, DC-load
Relay type EXI 25CH EXI 49CH EXI 120CH EXI 120CHI EXI 120CHP EXI 230CH EXI 230CHI EXI 230CHP EXI 230CHR Application Limit switches Limit switches Limit switches Normally closed operation 2-wire proximity switches Limit switches Normally closed operation 2-wire proximity switches Output current limited Control voltage 24 VAC 48 VAC 120 VAC 120 VAC 120 VAC 230 VAC 230 VAC 230 VAC 230 VAC Ex-output relays: DC-control, DC-load
Relay type Application EXO 5CH Resistive loads EXO 5CHA Inductive loads EXO 5CHX Resistive loads EXO 5CHXSN Resistive loads EXO 12CH Resistive loads EXO 12CHA Inductive loads EXO 12CHX Resistive loads EXO 12CHXSN Resistive loads, DIN-rail EXO 24CH Resistive loads EXO 24CHA Inductive loads EXO 24CHA4 Inductive loads EXO 24CHX Resistive loads EXO 24CHXSN Resistive loads, DIN-rail EXO 48CHA Inductive loads EXO 48CHA4 Inductive loads EXO 48CHX Resistive loads EXO 48CHXSN Resistive loads, DIN-rail EXO 120CHA Inductive loads EXO 120CHA4 Inductive loads EXO 220CHA Inductive loads EXO 220CHA4 Inductive loads * 6,3 A when used with a mounting base
Control voltage 5 VDC 5 VDC 5 VDC 5 VDC 12 VDC 12 VDC 12 VDC 12 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 48 VDC 48 VDC 48 VDC 48 VDC 120 VDC 120 VDC 220 VDC 220 VDC Ex-output relays: DC-control, AC-load
Relay type EXO 5IHA EXO 5TH EXO 12TH EXO 24IHA EXO 24TH EXO 24TR Application Fast switch-off AC loads AC loads Fast switch-off Wider operation temperature range AC loads Control voltage 5 VDC 5 VDC 12 VDC 24 VDC 24 VDC 24 VDC Ex-output relays: AC-control, AC-load
Relay type EXO P120TH EXO P230TH Application AC loads AC loads Mounting bases for EXI-relays:
• MIS 1GNEX (screw connectors)
• MIS 1CCNEX (spring connectors)
• MIS 1TNEX (screw connectors with test contacts)
Control voltage 120 VAC 230 VAC Mounting bases for EXO-relays:
• MOS 1GNEX (screw connectors)
• MOS 1CCNEX (spring connectors)
• MOS 1TNEX (screw connectors with test contacts)
www.weidmuller.com
Weidmuller, USA | 800.849.9343 | [email protected]
Weidmuller, Canada | 800.268.4080 | [email protected]
Weidmuller, Mexico | 01.222.2686267 | [email protected]