WL 500 - Laird Technologies

WL 500
Liquid to Air Heat Exchanger System
Innovative Technology
for a Connected World
WATER COOLED HEAT EXCHANGER UNITS
FOR MEDICAL AND INDUSTRIAL SYSTEMS
The WL500 is a re-circulating liquid to air heat exchanger that offers dependable, compact
performance by removing large amounts of heat from a liquid circuit. The coolant is
re-circulated using a high pressure pump to assure maximum flow rate. Heat from coolant is
absorbed by a radiant heat exchanger and dissipated into the ambient environment using brand
name fan. Manual adjustments can be made to control flow switch. Customized features are
available, however, MOQ applies.
FEATURES
Applications
• Compact design
• Reliable Operation
• Adjustable Flow Switch
• Bypass Valve Protection
• Medical Imaging Systems
• Photonics Laser Systems
• X-Ray Scanning Systems
• Semiconductor Fabrication
Specifications
Performance
Cooling capacity1
Flow Rate
500 Watts
> 2.3 lpm @ 4 bar
Operation
Coolant
Operational temperature range2
Water or Water/Glycol
5°C to 40°C
Storage temperature range (w/o coolant)
-25°C to 70°C
Humidity range
20% to 80%
Input Voltage
230 VAC
Frequency
50/60 Hz
Current Draw
1.2 Amps
Noise
< 60 dB(A)
Flow switch open
≤ 0.9 lpm
Maximum forward pressure
2.5 bar
Physical
Dimensions (H x W x D)
Weight (w/o coolant)
Coolant Capacity
Couplings
37.0 x 30.7 x 15.1 cm
11 kg
1.7 L
Press fit (8 mm ID hose)
1 Capacity rating is given at a temperature of 25°C (77°F) for the ambient air and water outlet temperature of 13°C.
2 For ambient conditions outside this range, please contact Laird Technologies.
global solutions: local support
Americas: +1.888.246.9050
Europe: +46.31.704.67.57
Asia: +86.755.2714.1166
[email protected]
www.lairdtech.com/thermal
TM
WL 500
Liquid to Air Heat Exchanger System
Innovative Technology
for a Connected World
performance curves
Temperature Difference
Inlet and Amient Temperature (°C)
Thermal Capacity
Water-Glycol 50 / 50%
Water-Glycol 60 / 40%
Water-Glycol 70 / 30%
Water
Achievement (Watts)
Delivery Volume (L)
Pump Capacity
Line Pressure ((p) bar)
WL 500
Liquid to Air Heat Exchanger System
Innovative Technology
for a Connected World
Isometric Drawings
Notes
1. C
heck coolant level regularly. For optimal cooling performance,
coolant level should always be above MIN fill level.
2.Hose selection should be of material and thickness to support pressure
resistance and coolant type.
3. Wall mountable. Four mounting holes are available to accommodate
S6 fixings and 5 x 40 mm machine screws.
4.Multiple cord plug options available to accommodate regional socket outlet
requirements. Consult with Laird Technologies on cord plug selection.
Ordering information
Part Number Example
W
L
Water
Air
5
0
0
Capacity (Watts)
THR-DS-WL 500 0412
Any information furnished by Laird Technologies, Inc. and its agents is believed to be accurate and reliable. All specifications are subject to change without notice. Responsibility for the use and
application of Laird Technologies materials rests with the end user, since Laird Technologies and its agents cannot be aware of all potential uses. Laird Technologies makes no warranties as to
the fitness, merchantability or suitability of any Laird Technologies materials or products for any specific or general uses. Laird Technologies shall not be liable for incidental or consequential
damages of any kind. All Laird Technologies products are sold pursuant to the Laird Technologies’ Terms and Conditions of sale in effect from time to time, a copy of which will be furnished upon
request. © Copyright 2012 Laird Technologies, Inc. All Rights Reserved. Laird, Laird Technologies, the Laird Technologies Logo, and other marks are trade marks or registered trade marks of Laird
Technologies, Inc. or an affiliate company thereof. Other product or service names may be the property of third parties. Nothing herein provides a license under any Laird Technologies or any third
party intellectual property rights.