600 WATT DC-DC CONVERTER MODEL MV380-56

600 WATT DC-DC CONVERTER
MODEL MV380-56
DATA SHEET
Distributed Power in Telecom, Industrial Control, Wireless, & Computer Applications
INPUT: 380VDC • OUTPUT: 56VDC @ 10.7A • 600 WATTS
Size: 2.4 x 4.6 x 0.5 inches
DESCRIPTION
MEGAVERTER DC-DC converters are high density, feature rich modules packaged in the
industry standard “full brick” size (2.4 x 4.6 x 0.5 inches) for circuit board mounting. They are
used where large blocks of DC power are required. The MV380-56 is designed for use with a
PFC front end and provides up to 600 Watts of low noise, 56Vdc power from a universal ac
line.
MODEL SELECTION
FEATURES
• High Efficiency: 91%
• -40 to +100°C
Operation
• Constant Frequency
• Trim Range: 48V to
60V
• Non-Shutdown Over
Voltage Protection
• Remote Sense
Astrodyne Corporation
• High Power Density:
109 W/cu. in.
• Low Noise
• Encapsulated
• Parallelable with Current
Sharing for n+m Redundancy
• 105°C Over Temperature
Protection
• Safety Agency Compliant
PH: 800-823-8082
Model
Input
Number
Voltage
MV380-56
Output
Voltage Current
(Vdc)
(Vdc)
(A)
360-400
56
10.7
Application Notes and
Evaluation Boards are Available
FX: 508-339-0375
www.astrodyne.com
Output
Email: [email protected]
www.roassoc.com
MEGAVERTER® DC-DC Converter
MV380-56
ELECTRICAL SPECIFICATIONS (continued)
ISOLATION PARAMETERS
MIN
MAX
UNITS
Input/Output Isolation
Input/Baseplate Isolation
4500
2500
Vdc
Vdc
Output/Baseplate Isolation
Input-to-Output Capacitance
500
4300
Vdc
pF
Input-to-Output Resistance
TYP
10
MECHANICAL PARAMETERS
TYP
UNITS
CONDITIONS
230 (7.4)
0.5 x 2.4 x 4.6
g (oz.)
Inches
See Outline Drawing
3.3
°C/W
Case Temperature = 100 °C
Thermal Resistance, Case-toAmbient
FEATURE PARAMETERS
MIN
Power Sharing Accuracy
Trim Range
Remote Sense Compensation
Over Voltage Protection (NonShutdown, Auto. Recovery)
Over Temperature Shut-down
Case Floating
M Ohms
MIN
Weight
Size
CONDITIONS
MAX
MAX
UNITS
CONDITIONS
%F.L.
Vdc
10 to 100% Full Load (F.L.)
48
±5
60
66
0.5
72
Vdc
Vdc
+100
TYP
+105
Turn-On Time
+110
600
°C
msec
25 °C Case
Case Temperature
F.L., Vout within 1% of Steady State
Enable *
Vout = 0
Logic Off Threshold
0.8
V
@Venable = 0 V
Enable Current (Logic Off)
1.0
mA
Logic On Threshold
2.4
V
F.L., Vout within 1% of Steady State
Turn-On Time
2.0
msec
* An open collector connection or equivalent is recommended for on/off control.
TRIM CIRCUIT CONFIGURATIONS
+Out
+Out
+Sense
+Sense
Trim
Rtrim-up
Load
Trim
-Sense
-Sense
-Out
-Out
Trim Up
Astrodyne Corporation
TRIM RESISTOR CALCULATIONS
 47.81− 10 × ∆Vo 
 kohms
R trim−up = 
∆
V


o
Rtrim-down
Load
Trim Down
PH: 800-823-8082
 1023 − 29.12 × ∆Vo
R trim−down = 
∆Vo


 kohms

∆Vo = Desired Output Voltage Change (Volts)
R trim−up = External Resistor Value to Increase Vo
R trim−down = External Resistor Value to Decrease Vo
FX: 508-339-0375
www.astrodyne.com
Email: [email protected]
www.roassoc.com
MEGAVERTER® DC-DC Converter
MV380-56
ABSOLUTE MAXIMUM RATINGS
Exceeding absolute maximum ratings may cause permanent damage and may reduce reliability.
PARAMETER
MIN
MAX
UNITS
Input Voltage (+In to –In)
Enable Voltage (Enable to –In)
-0.3
-0.3
420
6.0
Vdc
Vdc
Parallel Pin Voltage (Parallel Pin to –In)
Storage Temperature
-0.3
-55
5.0
+125
Vdc
°C
Operating Temperature
Soldering Temperature (Wave Solder)
-40
+100
260
°C
°C
Baseplate
< 5 sec.
390
°C
< 7 sec.
Soldering Temperature (Hand Solder)
CONDITIONS
ELECTRICAL SPECIFICATIONS
Electrical specifications apply over the entire range of input voltage, output current, and temperature unless indicated.
INPUT PARAMETERS
MIN
TYP
MAX
UNITS
Input Voltage
360
380
400
Vdc
2.5
A
dB
Maximum Input Current
Input Ripple Rejection
OUTPUT PARAMETERS
60
CONDITIONS
See Input Characteristic Curve
@120 Hz
MIN
TYP
MAX
UNITS
55.50
56
56.50
Vdc
Load Regulation
0.3
0.6
%
Line Regulation
0.02
0.1
%
0 A to Full Load
Over Vin Range
1
0.02
2
%/°C
%Vp-p
-40 to +100 °C
5 Hz to 20 MHz
10.7
600
A
W
130
% F.L.
Vout = 95% Vout nominal
150
% F.L.
Vout = 250 mV
5
% Vout
100
µsec
Load Change from 25% to 75% to 25%
Full Load
Vout within 1% Vout nominal
91
%
Voltage Set Point
Voltage Drift w/Temperature
Ripple
Rated Current
Output Power
Current Limit Inception
0
115
120
Short Circuit Current
Transient Response Peak
Deviation (0.5A/µsec slew rate)
Transient Response Settling Time
(0.5 A/µsec slew rate)
Efficiency
External Load Capacitance
Astrodyne Corporation
0
1,000
PH: 800-823-8082
CONDITIONS
380 Vin, 25°C, Full Load
Vin = 380 V, Full Load, 70 °C Case
µF
FX: 508-339-0375
www.astrodyne.com
Email: [email protected]
www.roassoc.com
MEGAVERTER® DC-DC Converter
MV380-56
Efficiency
Transient Response
95
30
Vin = 380V
20
10
85
1V/div.
Efficiency (%)
90
0
80
75
-10
70
-20
65
-30
0
2
4
6
8
10
-50 -40 -30 -20 -10 0
12
Load Current (Amps)
10 20t, 50µsec/div
30 40 50
Iout = 2.675A – 8.025A – 2.675A
Current Slew Rate = 0.5A/µsec
Outline Drawing
.20
4.60
4.20
.143 DIA. THRU
4 PLACES
.20
2.40
.15
NC
.27
.56
-OUT
PARALLEL
NC
TRIM
+IN
.15
.12
.20
+OUT
+S
-S
.25
2.00
.20
.15
.28 DIA. X .19 DEEP
4 PLACES
4.30
.098 DIA. PIN
2 PLACES
.040 DIA. PIN
9 PLACES
.50
.20 MIN.
ALUMINUM HEATSINK
SURFACE
Astrodyne Corporation
35 Hampden Rd
www.astrodyne.com
www.roassoc.com
Tel: (800) 823-8082
Fax: (508) 339-0375
[email protected]