ETC MV380-56

600 WATT DC-DC CONVERTER
MODEL MV380-56
DATA SHEET
Distributed Power in Telecom, Industrial Control, Wireless, & Computer Applications
INPUT: 380VDC • OUTPUT: 56VDC @ 10.7A • 600 WATTS
Size: 2.4 x 4.6 x 0.5 inches
DESCRIPTION
MEGAVERTER DC-DC converters are high density, feature rich modules packaged in the
industry standard “full brick” size (2.4 x 4.6 x 0.5 inches) for circuit board mounting. They are
used where large blocks of DC power are required. The MV380-56 is designed for use with a
PFC front end and provides up to 600 Watts of low noise, 56Vdc power from a universal ac
line.
MODEL SELECTION
FEATURES
• High Efficiency: 91%
• -40 to +100°C
Operation
• Constant Frequency
• Trim Range: 48V to
60V
• Non-Shutdown Over
Voltage Protection
• Remote Sense
RO Associates, Inc.
• High Power Density:
109 W/cu. in.
• Low Noise
• Encapsulated
• Parallelable with Current
Sharing for n+m Redundancy
• 105°C Over Temperature
Protection
• Safety Agency Compliant
Sunnyvale, CA
408 744-1450
Model
Input
Number
Voltage
MV380-56
Output
Output
Voltage Current
(Vdc)
(Vdc)
(A)
360-400
56
10.7
Application Notes and
Evaluation Boards are Available
fax:408 744-1521
email:[email protected]
MEGAVERTER® DC-DC Converter
MV380-56
ABSOLUTE MAXIMUM RATINGS
Exceeding absolute maximum ratings may cause permanent damage and may reduce reliability.
PARAMETER
MIN
MAX
UNITS
Input Voltage (+In to –In)
Enable Voltage (Enable to –In)
Parallel Pin Voltage (Parallel Pin to –In)
Storage Temperature
Operating Temperature
Soldering Temperature (Wave Solder)
Soldering Temperature (Hand Solder)
-0.3
-0.3
-0.3
-55
-40
420
6.0
5.0
+125
+100
260
390
Vdc
Vdc
Vdc
°C
°C
°C
°C
CONDITIONS
Baseplate
< 5 sec.
< 7 sec.
ELECTRICAL SPECIFICATIONS
Electrical specifications apply over the entire range of input voltage, output current, and temperature unless indicated.
INPUT PARAMETERS
MIN
TYP
MAX
UNITS
Input Voltage
Maximum Input Current
Input Ripple Rejection
360
380
400
2.5
Vdc
A
dB
OUTPUT PARAMETERS
MIN
TYP
MAX
UNITS
55.50
56
56.50
Vdc
0.3
0.02
0.6
0.1
%
%
0 A to Full Load
Over Vin Range
0.02
2
10.7
600
130
%/°C
%Vp-p
A
W
% F.L.
-40 to +100 °C
5 Hz to 20 MHz
150
% F.L.
60
Voltage Set Point
Load Regulation
Line Regulation
Voltage Drift w/Temperature
Ripple
Rated Current
Output Power
Current Limit Inception
1
0
115
120
Short Circuit Current
Transient Response Peak
Deviation (0.5A/µsec slew rate)
Transient Response Settling Time
(0.5 A/µsec slew rate)
Efficiency
External Load Capacitance
RO Associates, Inc.
5
% Vout
100
µsec
91
%
0
1,000
Sunnyvale, CA
408 744-1450
CONDITIONS
See Input Characteristic Curve
@120 Hz
CONDITIONS
380 Vin, 25°C, Full Load
Vout = 95% Vout nominal
Vout = 250 mV
Load Change from 25% to 75% to 25%
Full Load
Vout within 1% Vout nominal
Vin = 380 V, Full Load, 70 °C Case
µF
fax:408 744-1521
email:[email protected]
MEGAVERTER® DC-DC Converter
MV380-56
ELECTRICAL SPECIFICATIONS (continued)
ISOLATION PARAMETERS
MIN
Input/Output Isolation
Input/Baseplate Isolation
Output/Baseplate Isolation
Input-to-Output Capacitance
Input-to-Output Resistance
TYP
MAX
4500
2500
500
4300
10
MECHANICAL PARAMETERS
MIN
Weight
Size
Thermal Resistance, Case-toAmbient
TYP
MAX
MIN
Power Sharing Accuracy
Trim Range
Remote Sense Compensation
Over Voltage Protection (NonShutdown, Auto. Recovery)
Over Temperature Shut-down
Turn-On Time
TYP
48
66
+100
+105
600
CONDITIONS
Vdc
Vdc
Vdc
pF
Case Floating
M Ohms
UNITS
CONDITIONS
g (oz.)
Inches
°C/W
See Outline Drawing
Case Temperature = 100 °C
MAX
UNITS
CONDITIONS
±5
60
0.5
72
%F.L.
Vdc
Vdc
Vdc
10 to 100% Full Load (F.L.)
25 °C Case
+110
°C
msec
Case Temperature
F.L., Vout within 1% of Steady State
230 (7.4)
0.5 x 2.4 x 4.6
3.3
FEATURE PARAMETERS
UNITS
Enable *
Vout = 0
Logic Off Threshold
0.8
V
@Venable = 0 V
Enable Current (Logic Off)
1.0
mA
Logic On Threshold
2.4
V
F.L., Vout within 1% of Steady State
Turn-On Time
2.0
msec
* An open collector connection or equivalent is recommended for on/off control.
TRIM CIRCUIT CONFIGURATIONS
+Out
+Out
+Sense
+Sense
TRIM RESISTOR CALCULATIONS
 47.81− 10 × ∆Vo 
 kohms
R trim−up = 
∆
V

o

Rtrim-up
Trim
Load
Trim
Load
Rtrim-down
-Sense
-Sense
-Out
-Out
 1023 − 29.12 × ∆Vo
R trim−down = 
∆Vo


 kohms

∆Vo = Desired Output Voltage Change (Volts)
R trim−up = External Resistor Value to Increase Vo
Trim Up
RO Associates, Inc.
Trim Down
Sunnyvale, CA
R trim−down = External Resistor Value to Decrease Vo
408 744-1450
fax:408 744-1521
email:[email protected]
MEGAVERTER® DC-DC Converter
MV380-56
Efficiency
Transient Response
95
30
Vin = 380V
20
10
85
1V/div.
Efficiency (%)
90
0
80
75
-10
70
-20
65
-30
0
2
4
6
8
10
-50 -40 -30 -20 -10 0
12
Load Current (Amps)
10 20t, 50µsec/div
30 40 50
Iout = 2.675A – 8.025A – 2.675A
Current Slew Rate = 0.5A/µsec
Outline Drawing
4.60
4.20
.20
.143 DIA. THRU
4 PLACES
.20
2.40
-OUT
NC
.15
.27
PARALLEL
NC
TRIM
+IN
+OUT
+S
-S
2.00
.25
.20
.15
.56
.15
.12
.20
.28 DIA. X .19 DEEP
4 PLACES
4.30
.098 DIA. PIN
2 PLACES
.040 DIA. PIN
9 PLACES
.50
.20 MIN.
ALUMINUM HEATSINK
SURFACE
RO Associates, Inc.
P.O. Box 61419
Sunnyvale, CA 94088
www.roassoc.com
rev 052901
email:[email protected]
800 443-1450
408 744-1450
fax: 408 744-1521