ATEX Red Obstruction Light Installation Manual

Document No: 9100-127-1004-99 Rev. B
Issued: August 31, 2007
Sheet 1 of 5
INSTALLATION INSTRUCTIONS and PARTS LIST
ATEX Zone 2
L-810 OBSTRUCTION LIGHT [SINGLE FIXTURE] 120 and 230 VAC
------------------------------------------------------------------------------------------------------------------------------------------PART No:
860-9R01-001 [120V]
860-9R02-001 [230V]
WARNING:
DE-ENERGIZE CIRCUIT BEFORE INSTALLING OR WORKING ON FIXTURE
CAUTION
To retain seal integrity (and preserve warranty) do not loosen or remove the
clamp holding the light assembly together
REMOVAL OR LOOSENING OF THE CLAMP WILL VOID ALL WARRANTIES
If the light fixture is mounted in any position, other than upright, it will not meet
the designed light output specifications
Mounting the fixture in a position other than upright means that the light fixture is
now a visual signal fixture ** and not intended as an obstruction fixture
INSTALLATION STEPS:
•
•
•
•
•
The wire housing [2] has a 1” NPT [3/4" bushing] end to be assembled
to conduit … right angle or vertical
o Use a 1-1/2” wrench to tighten and attach the wire housing [2]
to the conduit
o Use 1” NPT plug [4] to close threaded opening not being used
o Remove reducing bushing [5] if threading into 1” NPT conduit
Feed the supply wires through the conduit and wire housing [2] leaving
approx 6” of wire for termination inside the wire housing [2]
Electrically connect the supply wires to the light assembly [1] wires
o Connect the light assembly wire (with voltage label) to
the Hot AC line
o Connect the light assembly wire [without label] to
the Neutral AC line
o Connect the grounding wire [from green screw] to the Ground line
Tuck the connected wires inside the wire housing [2]
Position light assembly [1] on the wire housing [2] and use the holding screws [3] to secure the light assembly in
place
** Units being installed as a visual signal as mentioned above, will require a continuous
bead of silicone sealing the gap between the base of the light assembly [1] and the housing [2]
•
Restore power and verify operation
Please refer to product data sheet for electrical parameters if required
U.S. Patent 6,425,678 *
PARTS LIST
Item
1
2
Catalog No.
860-9R01
Description
Red Light Assy 120V Atex
860-9R02
860-1001
Item
Catalog No.
Description
Red Light Assy 240V Atex
3
4
-----
1" NPT Plug
Wire Housing
5
---
1" to 3/4" Bushing
1501 Route 34 South, Farmingdale, NJ 07727
1/4-20 x 1/2 Holding Screw
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Document No: 9100-127-1004-99 Rev. B
Issued: August 31, 2007
Sheet 2 of 5
INSTALLATION INSTRUCTIONS and PARTS LIST
ATEX Zone 2
L-810 OBSTRUCTION LIGHT [SINGLE FIXTURE] 120 and 230 VAC
------------------------------------------------------------------------------------------------------------------------------------------Instructions specific to hazardous area installations
(reference European ATEX Directive 94/9/EC, Annex II, 1.0.6.)
The following instructions apply to equipment covered by certificate number Sira 06ATEX4372X:
1. The equipment may be used with flammable gases and vapours with apparatus groups IIA, IIB and IIC and with
temperature classes T1, T2, T3 and T4.
2. The equipment is certified category 3G
3. The equipment is only certified for use in ambient temperatures in the range -55oC to +55oC and should not be
used outside this range
4. The certificate number has an ‘X’ suffix which indicates that special conditions of installation and use apply.
Those installing or inspecting this equipment must have access to the contents of the certificate. However the
special condition is repeated below: Special Condition for Safe Use
5. As aluminium is used at the accessible surface of this equipment, ignition sources due to impact and friction
sparks could occur. This shall be considered when the L810 beacon is being installed.
6. Installation shall be carried out in accordance with the applicable code of practice by suitably-trained personnel.
7. Repair of this equipment is not possible.
8. If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user
to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection
is not compromised.
a. Aggressive substances e.g. acidic liquids or gases that may attack metals, or solvents that may
affect polymeric materials
b. Suitable precautions
e.g. regular checks as part of routine inspections or establishing from the
material’s data sheet that it is resistant to specific chemicals
9. There are no special checking or maintenance conditions other than a periodic check, however removing the
security seal will invalidate the warrantee.
Product Marking Details
1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Document No: 9100-127-1004-99 Rev. B
Issued: August 31, 2007
Sheet 3 of 5
INSTALLATION INSTRUCTIONS and PARTS LIST
ATEX Zone 2
L-810 OBSTRUCTION LIGHT [SINGLE FIXTURE] 120 and 230 VAC
-------------------------------------------------------------------------------------------------------------------------------------------
1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Document No: 9100-127-1004-99 Rev. B
Issued: August 31, 2007
Sheet 4 of 5
INSTALLATION INSTRUCTIONS and PARTS LIST
ATEX Zone 2
L-810 OBSTRUCTION LIGHT [SINGLE FIXTURE] 120 and 230 VAC
-------------------------------------------------------------------------------------------------------------------------------------------
1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Document No: 9100-127-1004-99 Rev. B
Issued: August 31, 2007
Sheet 5 of 5
INSTALLATION INSTRUCTIONS and PARTS LIST
ATEX Zone 2
L-810 OBSTRUCTION LIGHT [SINGLE FIXTURE] 120 and 230 VAC
-------------------------------------------------------------------------------------------------------------------------------------------
1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com