Installation Manual

Document No: 9100-127-1231-99
Issued: November, 2011
Sheet 1 of 2
INSTALLATION INSTRUCTIONS and PARTS LIST
SINGLE, DUAL and RETRO FIXTURES
MINI L-810 OBSTRUCTION LIGHT
------------------------------------------------------------------------------------------------------------------------------------------Model No
RTO 1x07 xxx
RTO 1x06 xxx
RTO BW07 xxx
RTO 1R18 xxx
Description
120-240 VAC, FAA
277 VAC
120-277 VAC
12-48 VDC
Model No
RTO 6x07 xxx
RTO 1x08 xxx
RTO CR07 xxx
RTO 6CR7 xxx
5th digit ... x = color
last 3
Description
Model No
120-240 VAC, Canada
RTO 0x07 xxx
12-48 VDC
RTO 2x07 xxx
120-240 VAC, IR
RTO CR08 xxx
120-240 VAC, Canada IR
digits ... 001 = Single 002 = Dual 004 = Retro
Description
120-240 VAC, NonFAA
120-240 VAC, C1D2
12-48 VDC, IR
WARNING:
DE-ENERGIZE CIRCUIT BEFORE INSTALLING OR WORKING ON FIXTURE
The light assembly fixture can be mounted in any position. When mounted 'upright' [as illustrated] the fixture will meet the
designed optical specifications for Aircraft Obstruction Warnings. When mounted in any other position, the fixture will not
meet the designed optical specifications mentioned and will be considered as a visual signal fixture.
SINGLE FIXTURE INSTALLATION STEPS:
► The wire housing 2A has a 1” NPT [3/4" bushing] end to be assembled to
conduit [right angle or vertical]
 Use a 1-1/2” wrench to tighten and attach the wire housing 2A to the conduit
 Remove reducing bushing 5 if threading into 1” NPT conduit
 Use 1” NPT plug 4 to close threaded opening not being used
► Feed the supply wires through the conduit and wire housing 2A leaving
approx 6” of wire for termination inside the wire housing 2A .
► Electrically connect the supply wires to the light assembly 1 wires
 Connect the light assembly wire [with voltage label]
to the Hot AC line or Positive [+] line
 Connect the light assembly wire [without label]
to the Neutral AC line or Negative [-] line
 Connect the light assembly green grounding wire to the Ground line
► Tuck the connected wires inside the wire housing 2A .
► Position light assembly 1 over the wire housing 2A and secure using the holding screws 3 .
► Restore power and verify operation
DUAL FIXTURE INSTALLATION STEPS:
► The dual housing 2B has a 1” NPT end to be assembled to conduit
 Remove reducing bushing 5 if threading into 1” NPT conduit
 Use a 1-1/2” wrench to tighten and attach the dual housing 2B to the conduit
 Tighten the 1/4 screw 3 to secure the dual wire housing in position
► Feed the supply wires through the conduit and dual housing 2B leaving
approx 6” of wire for termination inside the wire housing 2B .
► Electrically connect the supply wires to the light assembly 1 wires

same as SINGLE FIXTURE installation
► Tuck the connected wires inside the dual housing 2B .
► Position each light assembly 1 over the dual housing 2B and use
the holding screws 3 to secure the light assembly in place
► Restore power and verify operation
------------------------------------------------------------------------------------------------------------------------------------------1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Document No: 9100-127-1231-99
Issued: November, 2011
Sheet 2 of 2
INSTALLATION INSTRUCTIONS and PARTS LIST
SINGLE, DUAL and RETRO FIXTURES
MINI L-810 OBSTRUCTION LIGHT
------------------------------------------------------------------------------------------------------------------------------------------RETRO INSTALLATION STEPS:
► Remove existing lens and clamp 6 from existing fixture
► Do not discard clamp 6 since it will be used to secure light assembly 1A .
► Remove and discard all internal components required for use with incandescent bulb
► Leave only the source wires that lead into the existing base 2C .
► Electrically connect the supply wires to the light assembly 1A wires

same as SINGLE FIXTURE installation
► Tuck the connected wires inside the existing base 2C .
► Place light assembly 1A on existing base 2C and secure using existing clamp 6 .
► Restore power and verify operation
RETRO ONTO 3/4-14 NPT CONDUIT INSTALLATION STEPS:
► Electrically connect the supply wires to the light assembly 1A wires

same as SINGLE FIXTURE installation
► Use a 1-1/4” wrench to tighten and attach the light assembly 1A to the conduit
► Restore power and verify operation
Please refer to product data sheet for electrical parameters if required
Single Housing Fixture
Dual Housing Fixture
Retro Fixture [Housing]
Retro Fixture [Conduit]
Patent Pending
Item
1
1A
2A
2B
2C
Part No.
.
.
860-1000
860-2000
.
PARTS LIST
Description
Item
Light Assembly (w/ Adapter)
3
Light Assembly (w/o Adapter)
4
Single Housing
5
Dual Housing
6
Existing Installed Housing
.
Part No.
.
.
.
.
.
Description
1/4-20 x ½ Holding Screw
1” Plug
1” to 3/4" Bushing
Existing Installed Clamp
Rev
E
ECO No
5156
Drn
AV
Chk
ALV
App
SM
CM
JB
------------------------------------------------------------------------------------------------------------------------------------------1501 Route 34 South, Farmingdale, NJ 07727
Tel: [732] 919-3119
Fax: [732] 751-5778
www.dialight.com
Date
12-2-11