Document # 9100127212299 Rev.C September 2014 FLOOD LIGHT - “FL” SERIES INSTALLATION INSTRUCTIONS __________________________________________________________________________________________________________________________________________________________________________________________________ IMPORTANT: Please read carefully before installation and retain for future reference To prevent possible shock hazard, the fixture should be installed by a qualified licensed electrician. All electrical connections must be in accordance with local codes, ordinances and National Electrical Code. The use of safety protection such as safety eye glasses and protective gloves are recommended Proper grounding of the fixture is essential for protection from shock, correct operation and the elimination of electrical interference. DANGER: RISK OF ELECTRICAL SHOCK. TURN OFF MAIN POWER SOURCE BEFORE SERVICE Always transport and store the equipment in its original packaging and keep in a dry location. When unpacking check for any cracks or damage to casting and glass lens, if in doubt do not install! Contact your local Dialight sales representative or visit us at www.dialight.com for contact information INSTALLATION STEPS: IMPORTANT: Make sure application surface can handle weight of light fixture * Dialight is not responsible for damage to application surface or fixture, if mounted onto a surface that can not handle weight of fixture Securely mount lower mounting bracket to application surface If installing other than 90°, loosen, but do not remove, pivoting bolts 6 . Remove angle locking bolts 7 . Pivot to desired angle, replace and tighten angle locking bolts 7 to 5 ft.lb. [6.8 N m] Tighten pivoting bolts 6 to 25 ft.lb [33.9 N m] 6 7 Page 1 of 3 1501 Route 34 South, Farmingdale, NJ 07727 Tel: 732.919.3119 Fax: 732.751.5778 www.dialight.com Dialight de México S.R.L de C.V. Calle Lirios s/n Col. Carlos Pacheco, Ensenada Baja California, México C.P. 22830 +52 (646) 156-70-80 Document # 9100127212299 Rev.C September 2014 FLOOD LIGHT - “FL” SERIES INSTALLATION INSTRUCTIONS __________________________________________________________________________________________________________________________________________________________________________________________________ WIRING STEPS: 1- Once the module has been mounted in place, remove access cover 1 by unthreading cover screws 2- Insert source wire cable through a cable gland 2 not provided on module 3- If necessary slip source wire cable through cable holder 3 provided to secure cable during installation 4- Connect source wires to terminal block 4 as shown described below: • CONNECT THE SOURCE GROUND WIRE TO TERMINAL POSITION MARKED WITH GROUND SYMBOL • CONNECT THE SOURCE NEUTRAL WIRE TO TERMINAL POSITION MARKED WITH "N" • CONNECT THE SOURCE LINE WIRE TO TERMINAL POSITION MARKED WITH "L1" > to connect the source wires, press down on the tabs on top of the terminal block and hold, insert stripped source wire > release tab _ the terminal should now have engaged the inserted wire > lightly tug on the inserted wire to ensure engagement has occurred 5- Once source wires are secured and connected, restore power to module and check for illumination CAUTION: Do not look directly into module once powered and lit. Use protective shaded eye wear when viewing 6- Replace access cover 1 by securing the screws on the access cover _ recommended torque _ 13 in.lb [1.5 N m] WARNING: To retain seal integrity (and preserve warranty) do not loosen or remove any of the bolts around the perimeter of the module. There are no serviceable components in the module. Removal or loosening of any of these bolts will void all warranties. 3 1 2 4 SAFETY CABLE Safety cable [or chain] can be fed through the corner openings design into the module These openings are indicated by the arrows on the module Page 2 of 3 1501 Route 34 South, Farmingdale, NJ 07727 Tel: 732.919.3119 Fax: 732.751.5778 www.dialight.com Dialight de México S.R.L de C.V. Calle Lirios s/n Col. Carlos Pacheco, Ensenada Baja California, México C.P. 22830 +52 (646) 156-70-80 Document # 9100127212299 Rev.C September 2014 FLOOD LIGHT - “FL” SERIES INSTALLATION INSTRUCTIONS __________________________________________________________________________________________________________________________________________________________________________________________________ Mechanical Information Module Dimensions Weight Single Module = 27 lbs [ 12.3 kg ] Page 3 of 3 1501 Route 34 South, Farmingdale, NJ 07727 Tel: 732.919.3119 Fax: 732.751.5778 www.dialight.com Dialight de México S.R.L de C.V. Calle Lirios s/n Col. Carlos Pacheco, Ensenada Baja California, México C.P. 22830 +52 (646) 156-70-80