K3G355-AY43-22 Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 D-74673 Mulfingen Phone +49 (0) 7938 81-0 Fax +49 (0) 7938 81-110 [email protected] www.ebmpapst.com 1. SAFETY REGULATIONS AND NOTES Please read these operating instructions carefully before starting to work with the device. Observe the following warnings to prevent malfunctions or physical damage to both property and people. These operating instructions are to be regarded as part of this device. If the device is sold or transferred, the operating instructions must accompany it. These operating instructions may be duplicated and forwarded for information about potential dangers and their prevention. Translation of the original operating instructions CONTENTS 1. SAFETY REGULATIONS AND NOTES 1 1.1 Levels of hazard warnings 1 1.2 Staff qualification 1 1.3 Basic safety rules 1 1.4 Electrical voltage 1 1.5 Safety and protective functions 2 1.6 Electromagnetic radiation 2 1.7 Mechanical movement 2 1.8 Emission 2 1.9 Hot surface 2 1.10 Storage 2 1.11 Disposal 2 2. PROPER USE 3 3. TECHNICAL DATA 4 3.1 Product drawing 4 3.2 Nominal data 5 3.3 Data according to ErP directive 5 3.4 Technical features 5 3.5 Mounting data 5 3.6 Transport and storage conditions 5 4. CONNECTION AND START-UP 6 4.1 Connecting the mechanical system 6 4.2 Connecting the electrical system 6 4.3 Connection in terminal box 7 4.4 Factory settings 7 4.5 Connection screen 8 4.6 Checking the connections 9 4.7 Switch on device 9 4.8 Switching off the device 9 ; Check the electrical equipment of the device at regular intervals, refer to chapter 6.2 Safety test. 5. INTEGRATED PROTECTIVE FUNCTIONS 9 ; Replace loose connections and defective cables immediately. 6. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES AND REMEDIES 10 6.1 Cleaning 10 6.2 Safety test 10 1.1 Levels of hazard warnings These operating instructions use the following hazard levels to indicate potentially hazardous situations and important safety regulations: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Compliance with the measures is mandatory. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Exercise extreme caution while working. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or damage of property. NOTE A potentially harmful situation can occur and, if not avoided, can lead to property damage. 1.2 Staff qualification The device may only be transported, unpacked, installed, operated, maintained and otherwise used by qualified, trained and authorised technical staff. Only authorised specialists are permitted to install the device, to carry out a test run and to perform work on the electrical installation. 1.3 Basic safety rules Any safety hazards stemming from the device must be re-evaluated once it is installed in the end device. Observe the following when working on the unit: ; Do not make any modifications, additions or conversions to the device without the approval of ebm-papst. 1.4 Electrical voltage DANGER Electrical load on the device Risk of electric shock → Stand on a rubber mat if you are working on an electrically charged device. WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock → Wait five minutes after disconnecting the voltage at all poles before opening the device. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 1 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions CAUTION In the event of failure, there is electric voltage at the rotor and impeller The rotor and impeller are base insulated. → Do not touch the rotor and impeller once they are installed. CAUTION If control voltage is applied or a speed setpoint is stored, the motor automatically restarts, e.g. after a power failure. Danger of injury → Keep out of the danger zone of the device. → When working on the device, switch off the mains supply voltage and secure the latter from being switched on again. → Wait until the device stops. → After working on the device, remove any used tools or other objects from the device. 1.5 Safety and protective functions DANGER Missing safety device and non-functioning safety device If there is no safety device, you could be seriously injured, for example if you reach into the running device or your hands are sucked into it. → Operate the device only with a fixed and isolating safety protection and a fixed guard grille. The guard must withstand the kinetic energy of a fan blade detaching at maximum speed. → The device is a built-in component. You, the owner/ operator, are responsible for providing adequate protection for the device. → Shut down the device immediately if you detect a missing or ineffective protective feature. 1.6 Electromagnetic radiation Translation of the original operating instructions Interference from electromagnetic radiation is possible, e.g. in conjunction with open and closed-loop control devices. If unacceptable emission intensities occur when the fan is installed, appropriate shielding measures have to be taken by the user. NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer's side. → Verify that the entire setup is EMC compliant. 1.7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured. DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds, causing bodily harm. → Take appropriate safety measures. WARNING Rotating device Long hair, loose items of clothing and jewellery could become entangled and pulled into the device. You could be injured. → Do not wear any loose clothing or jewellery while working on rotating parts. → Protect long hair by wearing a cap. 1.8 Emission WARNING Depending on the installation and operating conditions, a sound pressure level greater than 70 dB(A) may arise. Danger of noise-induced hearing loss → Take appropriate technical safety measures. → Protect operating personnel with appropriate safety equipment, e.g. hearing protection. → Also observe the requirements of local agencies. 1.9 Hot surface CAUTION High temperature at the electronics enclosure Danger of burn injuries → Ensure that sufficient protection against accidental contact is provided. 1.10 Storage ; Store the device, partially or fully assembled, in a dry and weatherproof manner in the original packing in a clean environment. ; Protect the device from environmental impacts and dirt until the final installation. ; We recommend storing the device for a maximum up to one year to guarantee proper operation and longest possible service life. ; Even devices explicitly suited for outdoor use are to be stored as described prior to being commissioned. ; Maintain the storage temperature, see chapter 3.6 Transport and storage conditions. ; Please make sure that all screwed cable glands are fitted with dummy plugs. 1.11 Disposal When disposing of the device, please comply with all relevant requirements and regulations applicable in your country. → Secure the device against accidental contact. → Before working on the system/machine, wait until all parts have come to a standstill. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 2 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions 2. PROPER USE The device is exclusively designed as a built-in device for conveying air according to its technical data. Any other usage above and beyond this does not conform with the intended purpose and constitutes misuse of the device. Customer equipment must be capable of withstanding the mechanical and thermal stresses that can arise from this product. This applies for the entire service life of the equipment in which this product is installed. Proper use also includes: ● Only using the device in stationary systems. ● Carrying out all maintenance. ● Conveying of air at an ambient air pressure of 750 mbar to 1050 mbar. ● Using the device in accordance with the permitted ambient temperature, see chapter 3.6 Transport and storage conditions and chapter 3.2 Nominal data. ● Operating the device with all protective features in place. ● Minding the operating instructions. Improper use Translation of the original operating instructions Using the device in the following ways is particularly prohibited and may cause hazards: ● Operating the device with an imbalance, e.g. caused by dirt deposits or icing. ● Operation in medical equipment with a life-sustaining or lifesaving function. ● Operation with external vibrations. ● Moving solids content in flow medium. ● Painting the device ● Connections (e.g. screws) coming loose during operation. ● Opening the terminal box during operation. ● Moving air that contains abrasive particles. ● Moving highly corrosive air, e.g. salt spray mist. Exceptions are devices that are intended for salt spray mist and protected accordingly. ● Moving air that contains dust pollution, e.g. suctioning off saw dust. ● Operating the device close to flammable materials or components. ● Operating the device in an explosive atmosphere. ● Using the device as a safety component or for taking on safetyrelated functions. ● Operation with completely or partially disassembled or modified protective features. ● In addition, all application options that are not listed under proper use. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 3 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions 3. TECHNICAL DATA 3.1 Product drawing All measures have the unit mm. Translation of the original operating instructions 1 2 3 4 Inlet nozzle with bleeder connection for pressure relief (k-factor: 148) Cable diameter: min. 4 mm, max. 10 mm, tightening torque: 4±0.6 Nm Tightening torque 3.5±0.5 Nm Mounting position: shaft horizontal (install the support struts only vertically as shown in the view!) or rotor on bottom; rotor on top on request Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 4 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com Operating instructions K3G355-AY43-22 Condensate discharge holes Operation mode Motor bearing Technical features 3.2 Nominal data Motor M3G112-GA Phase Nominal voltage / VAC Nominal voltage range / VAC Frequency / Hz 1~ 230 200 .. 277 Type of data definition Speed / min-1 Power input / W Current draw / A Min. ambient temperature / °C Max. ambient temperature / °C ml 2450 1400 6.0 -25 50/60 50 ml = Max. load · me = Max. efficiency · fa = Running at free air cs = Customer specs · cu = Customer unit Subject to alterations 3.3 Data according to ErP directive Measurement category Efficiency category Variable speed drive Specific ratio* * A Static Yes 1.01 Specific ratio = 1 + pfs / 100 000 Pa Actual Overall efficiency ηes / % Efficiency grade N Power input Ped / kW Air flow qv / m³/h Pressure increase total psf / Pa Speed n / min-1 63.5 72.5 1.4 3755 794 2380 Request 2013 49 58 Request 2015 53 62 Data definition with optimum efficiency. Translation of the original operating instructions The ErP data is determined using a motor-impeller combination in a standardised measurement configuration. 3.4 Technical features Mass Size Surface of rotor Material of electronics housing Material of impeller Material of mounting plate Material of support bracket Material of inlet nozzle Number of blades Direction of rotation Type of protection Insulation class Humidity class Mounting position Touch current acc. IEC 60990 (measuring network Fig. 4, TN system) Electrical leads Motor protection Protection class Product conforming to standard Approval Rotor-side S1 Ball bearing - Output 10 VDC, max. 10 mA - Output 20 VDC, max. 50 mA - Output for slave 0-10 V - Tach output - Input for sensor 0-10 V or 4-20 mA - External 24 V input (programming) - External release input - Alarm relay - Integrated PID controller - Output limit - Motor current limit - PFC, active - RS485 MODBUS RTU - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Over-temperature protected electronics / motor - Line undervoltage / phase failure detection <= 3.5 mA Via terminal box Thermal overload protector (TOP) wired internally I (if protective earth is connected by customer) EN 61800-5-1; CE EAC For cyclic speed loads, note that the rotating parts of the device are designed for maximum one million load cycles. If you have specific questions, contact ebm-papst for support. 3.5 Mounting data 23 kg 355 mm Coated in black Die-cast aluminium ; Secure the mounting screws against accidentally coming loose (e.g. by using self-locking screws). Aluminium sheet Sheet steel, hot-galvanised You can obtain additional mounting data from the product drawing if necessary. Steel, coated in black Sheet steel, hot-galvanised 7 Clockwise, seen on rotor IP 54 "B" F4-1 Refer to product drawing Strength class for mounting screws 8.8 3.6 Transport and storage conditions ; Use the device in accordance with its protection type. Max. permissible ambient motor temp. (transp./ storage) Min. permissible ambient motor temp. (transp./storage) +80 °C -40 °C Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 5 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions Connect the device only to circuits that can be switched off using an all-pole disconnecting switch. 4. CONNECTION AND START-UP 4.1 Connecting the mechanical system CAUTION Cutting and crushing hazard when removing the fan from the packaging 4.2.1 Prerequisites ; Check whether the data on the type plate agree with the connection data. → Carefully remove the fan from its packaging. Make sure to avoid any shock. ; Before connecting the device, ensure that the supply voltage matches the operating voltage of the device. → Wear safety shoes and cut-resistant safety gloves. ; Only use cables designed for current according to the type plate. For determining the cross-section, follow the basic principles in accordance with EN 61800-5-1. The protective earth must have a cross-section equal to or greater than the outer conductor crosssection. We recommend the use of 105°C cables. Ensure that the minimum cable cross-section is at least AWG26/0.13 mm². CAUTION Heavy load when taking out the device Bodily harm, e.g. back injuries, are possible. → Two people should remove the device out of its packaging together. ; Check the device for transport damage. Damaged devices must no longer be installed. ; Install the undamaged device according to your application. Earth wire contact resistance to EN 61800-5-1 → Always install a protective earth first. Compliance with the impedance specifications to EN 61800-5-1 for the protective earth circuit must be verified in the end application. Depending on the installation situation, it may be necessary to install an additional protective earthing conductor via the additional protective earth connection point available on the device. The protective earth connection point is located on the housing and has a protective earth symbol and a bore hole. → Check the protective earth. 4.2.2 Idle current 4.2 Connecting the electrical system DANGER Electric voltage on the device Electric shock DANGER Incorrect insulation Risk of fatal injury from electric shock → Use only cables that meet the specified installation requirements for voltage, current, insulation material, load etc. → Route cables such that they cannot be touched by any rotating parts. Translation of the original operating instructions DANGER Electrical load (>50 µC) between mains wire and protective earth connection after switching of the supply when switching multiple devices in parallel. Electric shock, risk of injury → Make sure that sufficient protection against accidental contact is provided. Before working on the electrical connection, the connections to the mains supply and PE must be shorted. CAUTION Electrical voltage The fan is a built-in component and features no electrically isolating switch. → Only connect the fan to circuits that can be switched off with an all-pole separating switch. Because of the EMC filter integrated for compliance with EMC limits (interference emission and interference immunity), idle currents in the mains cable can be measured even when the motor is at a standstill and the mains voltage is switched on. ● The values lie in a range of typical < 250 mA. ● The effective power in this operating state (readiness for operation) is simultaneously at typical < 4 W. 4.2.3 Residual current operated device Only universal (type B or B+) RCD protective devices are permitted. Like frequency inverters, RCD protective devices cannot provide personal safety while operating the device. When switching on the power supply of the device, pulsed charge currents from the capacitors in the integrated EMC filter can lead to the RCD protective devices triggering without delay. We recommend residual current devices with a trigger threshold of 300 mA and delayed triggering (super-resistant, characteristic K). 4.2.4 Locked-rotor protection Due to the locked-rotor protection, the start-up current (LRA) is equal to or less than the nominal current (FLA). → When working on the fan, you must switch off the installation/machine in which the fan is installed and secure it from being switched on again. NOTE Water penetration into leads or wires Water enters at the cable end on the customers side and can damage the device. → Make sure that the cable end is connected in a dry environment. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 6 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions 4.3 Connection in terminal box 4.3.1 Preparing connection lines for the connection Strip the cable just enough so that the screwed cable gland is tight and the terminals are relieved of strain. Tightening torque, see chapter 3.1 Product drawing. Fig. 1: Recommended stripping lengths in mm (inside the terminal box) Legend: CL = control lines 4.3.2 Connecting cables with terminals WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock → Wait five minutes after disconnecting the voltage at all poles before opening the device. ; Remove the cap from the screwed cable gland. Fig. 2: Connecting the wires to terminals Remove the cap only in those places where cables are inserted. ; Seal the terminal box. ; Mount the screwed cable glands with the seal inserts provided in the terminal box. ; Insert the line(s) (not included in the standard scope of delivery) into the terminal box. ; First connect the "PE" (protective earth) connection. Translation of the original operating instructions ; Connect the lines to the corresponding terminals. Use a screwdriver to do so. During the connection work, ensure that no cables splice off. 4.3.3 Cable routing No water may penetrate along the cable in the direction of the cable gland. 4.4 Factory settings Factory settings with which the device is pre-set by ebm-papst. Control mode parameter set 1 Control mode parameter set 2 Fan / device adress Max. PWM / % Min. PWM / % Save set value to EEPROM Set value control Control function parameter set 1 Control function parameter set 2 PWM controlling PWM controlling 1 100 0 Yes Analogue (linear) Positive (heating) Positive (heating) Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 7 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions Translation of the original operating instructions 4.5 Connection screen No. KL1 KL1 PE KL2 KL2 Conn. 1 2 1 2 Designation L1 N PE NO COM KL2 3 NC KL3 KL3 KL3 KL3 1 2 3 4 RSA RSB GND Ain1 U KL3 5 +10 V KL3 6 Ain1 I KL3 7 Din1 KL3 8 Din2 KL3 9 Din3 KL3 KL3 10 11 GND Ain2 U KL3 12 +20 V KL3 13 Ain2 I KL3 14 Aout Function / assignment Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz Mains supply connection, supply voltage 1~200-277 V AC; 50/60 Hz Earth connection, PE connection Status relay, floating status contact; option 1: close with error; option 2: close with run monitor error message Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max. 2 A (AC1) / min. 10 mA Status relay, floating status contact; option 1: break with error; option 2: break with error for run monitor error message Bus connection RS485; RSA; MODBUS RTU Bus connection RS485; RSB; MODBUS RTU Signal ground for control interface Analog input 1 (set value); 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to input Ain1 I Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext. devices (e.g. potentiometer) Analog input 1 (set value); 4-20 mA; Ri= 100 Ohm; parametrisable curve; only usable as alternative to input Ain1 U Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridge to GND or applied voltage < 0.8 VDC; reset function: triggers software reset after a level change to <0.8 V Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set is selectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC; parameter set 2: bridge to GND or applied voltage < 0.8 VDC Digital input 3: control characteristic of the integrated controller; according to EEPROM setting, the control characteristic of the integrated controller is normally/inversely selectable per BUS or per digital input; normal: open pin or applied voltage 5 to 50 VDC; inverse: bridge to GND or applied voltage < 0.8 VDC Signal ground for control interface Analog input 2; actual sensor value 0-10 V; Ri= 100kOhm; parametrisable curve; only usable as alternative to input Ain2 I Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; power supply for ext. devices (e.g. sensors) Analog input 2; actual sensor value 4-20 mA; Ri= 100 Ohm; parametrisable curve; only alternative to input Ain2 U Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/ of the actual motor speed. Parametrisable curve. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 8 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Operating instructions 4.6 Checking the connections 5. INTEGRATED PROTECTIVE FUNCTIONS ; Make sure that the power is off (all phases). ; Secure it from being switched on again. The integrated protective functions cause the motor to switch off automatically in case of faults described in the table. ; Check the correct fit of the connection lines. Malfunctions ; Screw the terminal box cover closed again. Terminal box tightening torque, see chapter 3.1 Product drawing. ; Route the connecting cables in the terminal box so that the terminal box cover closes without resistance. ; Use all plug screws (the entire number). In doing so, insert the screws manually to avoid damage to the thread. ; Make sure that the terminal box is correctly closed and sealed and that all screws and screwed cable glands are properly tightened. Rotor position detection error Locked rotor Line under-voltage (mains input voltage outside of permitted nominal voltage) Description / Function of safety feature An automatic restart occurs. ; After the blockage is removed, the motor restarts automatically. ; If the mains supply voltage returns to permitted values, the motor restarts automatically. 4.7 Switch on device The device is not to be switched on until it has been installed properly and in accordance with its intended use, including the required protective devices and professional electrical connection. This also applies to devices which have already been equipped with plugs and terminals or similar connectors by the customer. WARNING Hot motor housing Fire hazard → Ensure that no combustible or flammable materials are located close to the fan. ; Inspect the device for visible external damage and the proper function of the protective features before switching it on. ; Check the air flow paths of the fan for foreign objects and remove any that are found. ; Apply the nominal voltage to the voltage supply. ; Start the device by changing the input signal. 4.8 Switching off the device Switching off the device during operation: ; Switch off the device via the control input. ; Do not switch the motor (e.g. in cyclic operation) on and off via power supply. Translation of the original operating instructions Switching off the device for maintenance work: ; Switch off the device via the control input. ; Do not switch the motor (e.g. in cyclic operation) on and off via power supply. ; Disconnect the device from the supply voltage. ; When disconnecting, be sure to disconnect the earth wire connection last. Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 9 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com Operating instructions K3G355-AY43-22 6. MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES AND REMEDIES Overtemperature of electronics/motor Insufficient cooling Do not perform any repairs on your device. Return the device to ebmpapst for repair or replacement. WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Ambient temperature too high → Wait five minutes after disconnecting the voltage at all poles before opening the device. CAUTION If control voltage is applied or a speed setpoint is stored, the motor automatically restarts, e.g. after a power failure. Danger of injury → Keep out of the danger zone of the device. → When working on the device, switch off the mains supply voltage and secure the latter from being switched on again. → Wait until the device stops. → After working on the device, remove any used tools or other objects from the device. If the device remains out of use for some time, e.g. when in storage, we recommend switching the device on for at least two hours to allow any condensate to evaporate and to move the bearings. Malfunction/error Impeller running roughly Translation of the original operating instructions Motor does not turn Possible cause Imbalance in rotating parts Mechanical blockage Mains supply voltage faulty Faulty connection Thermal overload protector responded Possible remedy Clean the device; if imbalance is still evident after cleaning, replace the device. If you have attached any weight clips during cleaning, make sure to remove them afterwards. Switch off, deenergise, and remove mechanical blockage. Check mains supply voltage, restore power supply, apply control signal. De-energise, correct connection, see connection diagram. Allow motor to cool off, locate and rectify cause of error, if necessary cancel restart lock-out Unacceptable operating point Improve cooling. Let the device cool down. To reset the error message, switch off the mains supply voltage for a min. of 25 s and switch it on again. Reduce the ambient temperature. Reset by reducing control input to 0. Correct the operating point. Let the device cool down. If you have any other problems, contact ebm-papst. 6.1 Cleaning NOTE Damage to the device during cleaning. Malfunction possible → Do not clean the device using a water jet or high-pressure washer. → Do not use any cleaners containing acids, bases or solvents. → Do not use any pointed or sharp-edged objects to clean. 6.2 Safety test NOTE High-voltage test The integrated EMC filter contains Y capacitors. Therefore, the trigger current is exceeded when AC testing voltage is applied. → Test the device with DC voltage when you carry out the high-voltage test required by law. The voltage to be used corresponds to the peak value of the AC voltage required by the standard. What has to be tested? Check the protective casing against accidental contact for damage and to ensure that it is intact Check the device for damage to blades and housing Mounting the connection lines Check the insulation of the wires for damage How to test? Frequency Visual inspection At least every 6 months Which measure? Repair or replacement of the device Visual inspection At least every 6 months Replacement of the device Visual inspection At least every 6 months Visual inspection At least every 6 months Fasten Replace wires Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 10 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com K3G355-AY43-22 Clean or replace impeller Retighten, replace if damaged Open bore holes Translation of the original operating instructions Impeller for Visual inspection At least every wear/deposits/ 6 months corrosion and damage Tightness of Visual inspection At least every screwed cable 6 months gland Condensate Visual inspection At least every discharge holes 6 months for clogging, as necessary Operating instructions Item no. 51309-5-9970 · ENG · Revision 84866 · Release 2015-07-03 · Page 11 / 11 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com