Operating instructions W3G910GS2201 - ebm

W3G910-GS22-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com
1. SAFETY REGULATIONS AND NOTES
Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.
Translation of the original operating instructions
CONTENTS
1. SAFETY REGULATIONS AND NOTES
1
1.1 Levels of hazard warnings
1
1.2 Staff qualification
1
1.3 Basic safety rules
1
1.4 Electrical voltage
1
1.5 Safety and protective functions
2
1.6 Electromagnetic radiation
2
1.7 Mechanical movement
2
1.8 Emission
2
1.9 Hot surface
2
1.10 Transport
2
1.11 Storage
2
1.12 Disposal
3
2. PROPER USE
3
3. TECHNICAL DATA
4
3.1 Product drawing
4
3.2 Nominal data
5
3.3 Data according to ErP directive
5
3.4 Technical features
5
3.5 Mounting data
5
3.6 Transport and storage conditions
6
3.7 Electromagnetic compatibility
6
1.3 Basic safety rules
4. CONNECTION AND START-UP
6
4.1 Connecting the mechanical system
6
Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:
4.2 Connecting the electrical system
6
4.3 Connection in terminal box
7
4.4 Factory settings
8
4.5 Connection screen
9
4.6 Checking the connections
10
; Check the electrical equipment of the device at regular intervals, refer
to chapter 6.2 Safety test.
4.7 Switch on device
10
; Replace loose connections and defective cables immediately.
4.8 Switching off the device
10
5. INTEGRATED PROTECTIVE FUNCTIONS
10
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
11
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
6.1 Cleaning
12
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
6.2 Safety test
12
1.1 Levels of hazard warnings
These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.
WARNING
Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.
NOTE
A potentially harmful situation can occur and, if not avoided, can
lead to property damage.
1.2 Staff qualification
The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by qualified, trained and authorised
technical staff.
Only authorised specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.
; Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.
1.4 Electrical voltage
CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller
The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 1 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
WARNING
Rotating device
Long hair, loose items of clothing and jewellery could become
entangled and pulled into the device. You could be injured.
→ Keep out of the danger zone of the device.
→ Do not wear any loose clothing or jewellery while working
on rotating parts.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
1.5 Safety and protective functions
DANGER
Missing safety device and non-functioning safety device
If there is no safety device, you could be seriously injured, for
example if you reach into the running device or your hands are
sucked into it.
→ Operate the device only with a fixed and isolating safety
protection and a fixed guard grille.
The guard must withstand the kinetic energy of a fan blade
detaching at maximum speed.
→ The device is a built-in component. You, the owner/
operator, are responsible for providing adequate protection for
the device.
→ Shut down the device immediately if you detect a
missing or ineffective protective feature.
1.6 Electromagnetic radiation
Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.
NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.
Translation of the original operating instructions
→ Verify that the entire setup is EMC compliant.
1.7 Mechanical movement
→ Protect long hair by wearing a cap.
1.8 Emission
WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.
Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety
equipment, e.g. hearing protection.
→ Also observe the requirements of local agencies.
1.9 Hot surface
CAUTION
High temperature at the electronics enclosure
Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is
provided.
1.10 Transport
WARNING
Transport of fan
Injuries from slipping or falling.
→ Only transport the fan in its original packaging. # Transport
the fan "lying flat", in other words with the axis vertical.
→ Secure the fan(s) so that nothing can slip or fall, for
example using a lashing strap.
1.11 Storage
; Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.
; Protect the device from environmental impacts and dirt until the final
installation.
DANGER
Rotating device
Body parts that come into contact with the rotor and impeller
can be injured.
; We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.
→ Secure the device against accidental contact.
; Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.
→ Before working on the system/machine, wait until all
parts have come to a standstill.
DANGER
Flying parts
Missing safety devices may cause balancing weights or
broken fan blades to be ejected at high speeds, causing bodily
harm.
; Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.
; Please make sure that all screwed cable glands are fitted with
dummy plugs.
→ Take appropriate safety measures.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 2 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
1.12 Disposal
2. PROPER USE
When disposing of the device, please comply with all relevant
requirements and regulations applicable in your country.
The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.
Proper use also includes:
●
Use the device in power systems with earthed neutral (TN/TT power
systems) only.
●
Only using the device in stationary systems.
●
Carrying out all maintenance.
●
Moving air with a density of 1.2 kg/m³.
●
Using the device in accordance with the permitted ambient
temperature, see chapter 3.6 Transport and storage conditions and
chapter 3.2 Nominal data.
●
Operating the device with all protective features in place.
●
Minding the operating instructions.
Improper use
Translation of the original operating instructions
Using the device in the following ways is particularly prohibited and
may cause hazards:
●
Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
●
Operation in medical equipment with a life-sustaining or lifesaving
function.
●
Operation with external vibrations.
●
Moving solids content in flow medium.
●
Painting the device
●
Connections (e.g. screws) coming loose during operation.
●
Opening the terminal box during operation.
●
Moving air that contains abrasive particles.
●
Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
●
Moving air that contains dust pollution, e.g. suctioning off saw dust.
●
Operating the device close to flammable materials or components.
●
Operating the device in an explosive atmosphere.
●
Using the device as a safety component or for taking on safetyrelated functions.
●
Operation with completely or partially disassembled or modified
protective features.
●
In addition, all application options that are not listed under proper use.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 3 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
3. TECHNICAL DATA
3.1 Product drawing
All measures have the unit mm.
Direction of air flow "V"
Cable diameter: min. 4 mm, max. 10 mm, tightening torque: 4±0.6 Nm
Tightening torque 3.5±0.5 Nm
Translation of the original operating instructions
1
2
3
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 4 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
W3G910-GS22-01
Humidity class
Mounting position
3.2 Nominal data
Motor
M3G150-FF
Phase
Nominal voltage / VAC
Nominal voltage
range / VAC
Frequency / Hz
3~
400
380 .. 480
Type of data definition
Speed / min-1
Power input / W
Current draw / A
Max. back pressure / Pa
Min. ambient temperature
/ °C
Max. ambient
temperature
/ °C
ml
800
1550
2.4
130
-25
Condensate discharge
holes
Operation mode
Motor bearing
Technical features
50/60
60
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category
Efficiency category
Variable speed drive
Specific ratio*
*
A
Static
Yes
1.00
Specific ratio = 1 + pfs / 100 000 Pa
Actual
Overall efficiency ηes / %
Efficiency grade N
Power input Ped / kW
Air flow qv / m³/h
Pressure increase total psf / Pa
Speed n / min-1
42.7
47.8
1.59
17690
130
795
Request
2013
30.9
36
Request
2015
34.9
40
Translation of the original operating instructions
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass
Size
Surface of rotor
Material of electronics
housing
Material of blades
Material of wall ring
Material of guard grille
Number of blades
Blade angle
Direction of air flow
Direction of rotation
Type of protection
Insulation class
47.8 kg
910 mm
Coated in black
Die-cast aluminium, coated in black
Aluminium sheet insert, sprayed with PP
plastic
Sheet steel, pre-galvanised and coated in
black plastic (RAL 9005)
Steel, coated in black plastic (RAL9005)
5
0°
"V"
Clockwise, seen on rotor
IP 54
"F"
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
Electrical leads
Motor protection
Protection class
Product conforming
to standard
Approval
F4-1
Shaft horizontal or rotor on bottom; rotor
on top on request
Rotor-side
S1
Ball bearing
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- External release input
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection
<= 3.5 mA
Via terminal box
Reverse polarity and locked-rotor
protection
I (if protective earth is connected by
customer)
EN 61800-5-1; CE
EAC; UL 1004-7 + 60730; C22.2 Nr.77
+ CAN/CSA-E60730-1
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 5 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
W3G910-GS22-01
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
Min. permissible
ambient motor temp.
(transp./storage)
+80 °C
-40 °C
4. CONNECTION AND START-UP
4.1 Connecting the mechanical system
CAUTION
Cutting and crushing hazard when removing the device
from the packaging
Blades can be bent
→ Carefully remove the device from its packaging, only
touching the wall ring. Make sure to avoid any shock.
3.7 Electromagnetic compatibility
→ Wear safety shoes and cut-resistant safety gloves.
EMC interference
immunity
EMC interference
emission
CAUTION
Heavy load when taking out the device
Bodily harm, e.g. back injuries, are possible.
Acc. to EN 61000-6-2 (industrial
environment)
Acc. to EN 55022 (Class B, household
environment)
If several devices are switched in parallel on the mains side so
that the line current of the arrangement is in the range of 16 - 75
A, then this arrangement conforms to IEC 61000-3-12 provided
that the short-circuit power Ssc at the connection point of the
customer system to the public power system is greater than or
equal to 120 times the rated output of the arrangement.
It is the responsibility of the installation engineer or operator/
owner of the device to ensure, if necessary after consultation
with the network operator, that this device is only connected to
a connection point with a Ssc value that is greater than or equal
to 120 times the rated output of the arrangement.
→ Two people should remove the device out of its packaging
together.
; Check the device for transport damage. Damaged devices must no
longer be installed.
; Install the undamaged device according to your application.
4.2 Connecting the electrical system
DANGER
Electric voltage on the device
Electric shock
→ Always install a protective earth first.
→ Check the protective earth.
DANGER
Incorrect insulation
Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation
requirements for voltage, current, insulation material, load etc.
→ Route cables such that they cannot be touched by any
rotating parts.
Translation of the original operating instructions
DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.
Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact
is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.
CAUTION
Electrical voltage
The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with
an all-pole separating switch.
→ When working on the fan, you must switch off the
installation/machine in which the fan is installed and secure it
from being switched on again.
NOTE
Interferences and failures are possible
Maintain a distance to the power supply line when routing the
control lines of the device.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 6 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
W3G910-GS22-01
→ Ensure a sufficiently large clearance.
Recommendation: clearance > 10 cm (separate cable
routing)
NOTE
Water penetration into leads or wires
Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry
environment.
Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.
4.2.1 Prerequisites
; Check whether the data on the type plate agree with the connection
data.
; Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.
; Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor crosssection.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².
Earth wire contact resistance to EN 61800-5-1
Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
connection point available on the device.
The protective earth connection point is located on the housing and has
a protective earth symbol and a bore hole.
4.2.2 Power supply connection, fuse protection
4.2.3 Idle current
Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.
●
The values lie in a range of typical < 250 mA.
●
The effective power in this operating state (readiness for operation) is
simultaneously at typical < 5 W.
4.2.4 Residual current operated device
Only universal (type B or B+) RCD protective devices are
permitted. Like frequency inverters, RCD protective devices
cannot provide personal safety while operating the device.
When switching on the power supply of the device, pulsed
charge currents from the capacitors in the integrated EMC filter
can lead to the RCD protective devices triggering without
delay. We recommend residual current devices with a trigger
threshold of 300 mA and delayed triggering (super-resistant,
characteristic K).
4.2.5 Leakage current
For asymmetrical power systems or if a phase fails, the
leakage current can increase to a multiple of the nominal value.
4.2.6 Locked-rotor protection
Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).
4.3 Connection in terminal box
4.3.1 Preparing connection lines for the connection
Strip the cable just enough so that the screwed cable gland is tight and
the terminals are relieved of strain. Tightening torque, see chapter 3.1
Product drawing.
Translation of the original operating instructions
Assignment of conductor cross-sections and the fuse protection required
for them (overload protection only, no device protection).
Nominal
voltage
3/PE AC
380 - 480
VAC
3/PE AC
380 - 480
VAC
3/PE AC
380 - 480
VAC
3/PE AC
380 - 480
VAC
Safety
fuse
VDE
16 A
UL
15 A
Automatic
circuit
breaker
VDE
C16A
Wire
crosssection
mm²
1.5
Wire
crosssection
*AWG
16
20 A
20 A
C20A
2.5
14
25 A
25 A
C25A
4.0
12
32 A
30 A
C32A
6.0
10
Fig. 1: Recommended stripping lengths in mm (inside the terminal box)
Legend: CL = control lines
* AWG = American Wire Gauge
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 7 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
4.3.2 Connecting cables with terminals
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
4.3.3 Cable routing
No water may penetrate along the cable in the direction of the cable gland.
Fans installed lying flat
Make sure that the cable is routed in the form of a loop (water trap).
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
; Remove the cap from the screwed cable gland.
Remove the cap only in those places where cables are inserted.
; Mount the screwed cable glands with the seal inserts provided in the
terminal box.
; Insert the line(s) (not included in the standard scope of delivery) into
the terminal box.
; First connect the "PE" (protective earth) connection.
; Connect the lines to the corresponding terminals.
Use a screwdriver to do so.
During the connection work, ensure that no cables splice off.
Fig. 3: Fan installed lying flat, cable routed as a water trap.
Fans installed in upright position
When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.
Fig. 4: Cable routing for fans installed upright.
Translation of the original operating instructions
4.4 Factory settings
Factory settings with which the device is pre-set by ebm-papst.
Fig. 2: Connecting the wires to terminals
; Seal the terminal box.
Control mode
parameter set 1
Control mode
parameter set 2
Fan / device adress
Max. PWM / %
Min. PWM / %
Save set value to
EEPROM
Set value control
Control function
parameter set 1
Control function
parameter set 2
PWM controlling
PWM controlling
1
100
5
Yes
Analogue (linear)
Positive (heating)
Positive (heating)
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 8 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
Translation of the original operating instructions
4.5 Connection screen
No.
KL 1
KL 1
KL 1
PE
KL 2
KL2
Conn.
1
2
3
1
2
Designation
L1
L2
L3
PE
NO
COM
KL2
KL 3
KL 3
KL 3
KL 3
3
1
2
3 / 10
4
NC
RSA
RSB
GND
Ain1 U
KL 3
5
+ 10 V
KL 3
6
Ain1 I
KL 3
7
Din1
KL 3
8
Din2
KL 3
9
Din3
KL 3
11
Ain2 U
KL 3
12
+ 20 V
KL 3
13
Ain2 I
KL 3
14
Aout
Function / assignment
Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
Earth connection, PE connection
Status relay, floating status contact; normally open; close with error
Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA
Status relay, floating status contact; break with error
Bus connection RS-485, RSA, MODBUS RTU; SELV
Bus connection RS-485, RSB, MODBUS RTU; SELV
Signal ground for control interface; SELV
Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain1; SELV
Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. potentiometer), SELV
Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV
Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC
disabling: bridge to GND or applied voltage <1 VDC
reset function: triggers software reset after a level change to <1 VDC; SELV
Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV
Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV
Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
devices (e.g. sensors); SELV
Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV
Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 9 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
W3G910-GS22-01
Operating instructions
4.6 Checking the connections
5. INTEGRATED PROTECTIVE FUNCTIONS
; Make sure that the power is off (all phases).
; Secure it from being switched on again.
The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.
; Check the correct fit of the connection lines.
Malfunctions
; Screw the terminal box cover closed again. Terminal box tightening
torque, see chapter 3.1 Product drawing.
; Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.
; Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.
; Make sure that the terminal box is correctly closed and sealed and
that all screws and screwed cable glands are properly tightened.
4.7 Switch on device
The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.
Rotor position detection error
Locked rotor
Line under-voltage (mains input
voltage outside of permitted
nominal voltage)
Phase failure
Description / Function of
safety feature
An automatic restart occurs.
; After the blockage is
removed, the motor restarts
automatically.
; If the mains supply voltage
returns to permitted values, the
motor restarts automatically.
A phase of the supply voltage
fails for at least 5 s.
; If all phases are correctly
supplied again, the motor
automatically restarts after 10 40 s.
WARNING
Hot motor housing
Fire hazard
→ Ensure that no combustible or flammable materials are
located close to the fan.
; Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
; Check the air flow paths of the fan for foreign objects and remove any
that are found.
; Apply the nominal voltage to the voltage supply.
; Start the device by changing the input signal.
4.8 Switching off the device
Switching off the device during operation:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
Translation of the original operating instructions
Switching off the device for maintenance work:
; Switch off the device via the control input.
; Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
; Disconnect the device from the supply voltage.
; When disconnecting, be sure to disconnect the earth wire connection
last.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 10 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
W3G910-GS22-01
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Insufficient cooling
Do not perform any repairs on your device. Return the device to ebmpapst for repair or replacement.
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
→ Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
Ambient temperature
too high
→ Wait until the device stops.
→ After working on the device, remove any used tools or
other objects from the device.
If the device remains out of use for over four months, we
recommend switching the device on for at least three hours at
full speed to allow any condensate to evaporate and to move
the bearings.
Translation of the original operating instructions
Malfunction/error
Impeller running
roughly
Motor does not turn
Possible cause
Imbalance in rotating
parts
Mechanical blockage
Mains supply
voltage faulty
Faulty connection
Motor winding broken
Possible remedy
Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.
Switch off, deenergise, and
remove mechanical
blockage.
Check mains supply
voltage,
restore power
supply.
Important! The error
message resets
automatically.
The device starts
up again
automatically without
advance warning.
De-energise, correct
connection, see
connection diagram.
Replace device
Unacceptable
operating point (e.g.
counterpressure is
too high)
Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.
Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.
Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message
by applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.
If you have any other problems, contact ebm-papst.
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 11 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
Operating instructions
W3G910-GS22-01
6.1 Cleaning
NOTE
Damage to the device during cleaning.
Malfunction possible
→ Do not clean the device using a water jet or high-pressure
washer.
→ Do not use any cleaners containing acids,
bases or solvents.
→ Do not use any pointed or sharp-edged objects to clean.
6.2 Safety test
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
Translation of the original operating instructions
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
What has to
be tested?
Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact
Check the
device for
damage to
blades and
housing
Mounting the
connection lines
Check the
insulation of
the wires for
damage
Tightness of
screwed cable
gland
Condensate
discharge
holes for
clogging, as
necessary
Weld seams
for crack
formation
How to test?
Frequency
Visual inspection At least every
6 months
Which
measure?
Repair or
replacement of
the device
Visual inspection At least every
6 months
Replacement
of the device
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Fasten
Visual inspection At least every
6 months
Retighten,
replace if
damaged
Open bore holes
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Replace wires
Replace device
Item no. 50227-5-9970 · ENG · Revision 83184 · Release 2014-10-23 · Page 12 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com