Liebert APM UPS Modular & Scalable Digital UPS with integrated Power Distribution Unit User & Installation Manual Version Revision date BOM V1.0 January 04, 2010 31012118 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China Homepage: www.emersonnetworkpower.com.cn E-mail: [email protected] Safety Precautions This manual contains information concerning the installation and operation of this Liebert APM modular UPS This manual must be read prior to installation. The UPS must be commissioned and serviced by engineers approved by the manufacturer (or its agent). Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty. The UPS has been designed for commercial or industrial use only, and is not for use in any life support application. This is a Class A UPS product. In a residential environment, this product may nevertheless cause radio interference, in which case, the user may be required to take additional measures. Conformity and standards This equipment complies with CE directives 73/23 & 93/68 (low votlage safety) and 89/336 (EMC), with Australia and New Zealand EMC Framework (C-Tick), and with the following product standards for UPS: IEC62040-1-1 — General and safety requirements for use in operator access area z IEC62040-2 — EMC, Class C3 z IEC62040-3 — Performance requirements and test methods z Please refer to Chapter 6 for more details Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only. Warning: high leakage current Earth connection is essential before connecting the input supply (including the AC mains and battery). This equipment must be earthed in accordance with local electrical codes. Earth leakage current exceeds 3.5mA and is less than 1000mA. Transient and steady state earth leakage currents, which may occur when the equipment is started, should be taken into account when selecting instantaneous residual current circuit breaker (RCCB) or residual current detector (RCD) devices. RCCBs must be selected insensitive to DC unidirectional pulses (Class A) and transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. Warning: backfeed protection This UPS is fitted with a voltage-free contact closure signal for use with an external automatic disconnect device (supplied by others) to protect against back-feeding voltage into the static bypass input. If this signal is not used by the installer, a label must be added at the external bypass input disconnect device to warn service personnel that the circuit is connected to a UPS. The text to use is the following or equivalent: Isolate the UPS before working on this circuit. User-serviceable parts All equipment maintenance and servicing procedures involving internal access requires the use of a tool and should be carried out only by trained personnel. There are no user-serviceable parts behind covers requiring a tool for removal. This UPS is fully compliant with safety regulations for equipment located in an operator accessible area. Hazardous voltage is present within the UPS but out of reach of non-service personnel. Contact with hazardous voltage is minimized with live parts housed behind safety panels that require a tool for their removal. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. Battery voltage exceeds 400Vdc All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel. Special care should be taken when working with the batteries. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities. Warning The area around the cover of the monitoring board is a static sensitive area, please make anti-static processing when in contact with this area. Contents Chapter 1 Installation .......................................................................................................................................................... 1 1.1 Introduction ........................................................................................................................................................... 1 1.2 Preliminary Checks ............................................................................................................................................... 1 1.3 Location ................................................................................................................................................................ 1 1.3.1 Power Distribution Room ........................................................................................................................... 1 1.3.2 Battery Room............................................................................................................................................. 2 1.3.3 Storage ...................................................................................................................................................... 2 1.4 Positioning ............................................................................................................................................................ 2 1.4.1 UPS Composition ...................................................................................................................................... 3 1.4.2 Moving The Cabinet .................................................................................................................................. 3 1.4.3 Clearances ................................................................................................................................................ 4 1.4.4 Front Access And Rear Access ................................................................................................................. 4 1.4.5 Final Positioning ........................................................................................................................................ 4 1.4.6 Installing Power Modules And Output Distribution Modules (Optional)...................................................... 4 1.4.7 Cable Entry................................................................................................................................................ 5 1.5 Protective Devices ................................................................................................................................................ 5 1.5.1 Rectifier and Bypass Input......................................................................................................................... 5 1.5.2 Battery ....................................................................................................................................................... 6 1.5.3 UPS Output ............................................................................................................................................... 6 1.6 Power Cables ....................................................................................................................................................... 6 1.6.1 Maximum Steady State AC And DC Currents ........................................................................................... 6 1.6.2 Distance From Floor To Connection Point On The Equipment.................................................................. 7 1.6.3 Cable Connection ...................................................................................................................................... 7 1.6.4 Battery Cabinet.......................................................................................................................................... 8 1.7 Control Cables And Communication Cables ......................................................................................................... 9 1.7.1 Input Dry Contact Port ............................................................................................................................. 10 1.7.2 BCB Port.................................................................................................................................................. 11 1.7.3 Maintenance Bypass Switch And Output Switch State Port .................................................................... 11 1.7.4 Output Dry Contact Port .......................................................................................................................... 12 1.7.5 Remote EPO Input Port ........................................................................................................................... 12 1.7.6 RS232 Port And SNMP Card Port ........................................................................................................... 13 1.8 Installation Drawing............................................................................................................................................. 13 Chapter 2 Operation.......................................................................................................................................................... 16 2.1 Brief Introduction................................................................................................................................................. 16 2.1.1 Operating Theory..................................................................................................................................... 16 2.1.2 Static Switch ............................................................................................................................................ 16 2.2 Operation Mode .................................................................................................................................................. 17 2.2.1 Normal Mode ........................................................................................................................................... 17 2.2.2 Battery Mode ........................................................................................................................................... 17 2.2.3 Automatic Restart Mode .......................................................................................................................... 17 2.2.4 Bypass Mode........................................................................................................................................... 17 2.2.5 Maintenance Bypass Mode ..................................................................................................................... 18 2.2.6 ECO Mode............................................................................................................................................... 18 2.2.7 Frequency Converter Mode ..................................................................................................................... 18 2.3 Battery Management........................................................................................................................................... 18 2.3.1 Normal Function ...................................................................................................................................... 18 2.3.2 Advanced Function——Battery Self-Test And Self-Service..................................................................... 19 2.4 Battery Protection ............................................................................................................................................... 19 Chapter 3 Operating Procedures ...................................................................................................................................... 20 3.1 Power Switches .................................................................................................................................................. 20 3.2 UPS Start-Up Procedures ................................................................................................................................... 20 3.2.1 Start-Up Procedures (Into Normal Mode) ................................................................................................ 21 3.2.2 Start-Up Procedures (Into Battery Mode) ................................................................................................ 21 3.3 Procedures Of Transfer Between Operation Modes ........................................................................................... 22 3.3.1 Tansfer From Normal Mode To Battery Mode ......................................................................................... 22 3.3.2 Tansfer From Normal Mode To Bypass Mode......................................................................................... 22 3.3.3 Tansfer From Bypass Mode To Normal Mode......................................................................................... 22 3.3.4 Transfer From Normal Mode To Maintenance Bypass Mode .................................................................. 22 3.4 Powering Down The UPS ................................................................................................................................... 23 3.5 Emergency Shutdown Procedures...................................................................................................................... 23 3.6 UPS Reset Procedures....................................................................................................................................... 23 3.7 Selecting Language ............................................................................................................................................ 23 3.8 Changing The Current Date And Time................................................................................................................ 24 3.9 Command Password........................................................................................................................................... 24 Chapter 4 Operator Control And Display Panel................................................................................................................. 25 4.1 Introduction ......................................................................................................................................................... 25 4.1.1 LED Indicators ......................................................................................................................................... 26 4.1.2 Audible Alarm (Buzzer)............................................................................................................................ 26 4.1.3 Control Keys ............................................................................................................................................ 26 4.1.4 LCD And Menu Keys ............................................................................................................................... 27 4.2 LCD Screen Types.............................................................................................................................................. 27 4.2.1 Start Screen............................................................................................................................................. 27 4.2.2 Primary Screen........................................................................................................................................ 28 4.2.3 Default Screen......................................................................................................................................... 29 4.3 Detailed Description Of Menu Items ................................................................................................................... 29 4.4 Prompt Windows................................................................................................................................................. 31 4.5 Alarm List ............................................................................................................................................................ 32 Chapter 5 Service ............................................................................................................................................................. 35 5.1 Service Procedures Of Power Module, Bypass Module And Output Distribution Module ................................... 35 5.1.1 Notes ....................................................................................................................................................... 35 5.1.2 Power Module Service Procedures ......................................................................................................... 35 5.1.3 Power Module Service Procedures ......................................................................................................... 35 5.1.4 Output Distribution Module Service Procedures ...................................................................................... 36 5.2 Replacement Procedures Of Air Filter ................................................................................................................ 36 Chapter 6 Specifications ................................................................................................................................................... 37 6.1 Conformity And Standards .................................................................................................................................. 37 6.2 Environmental Characteristics ............................................................................................................................ 37 6.3 Mechanical Characteristics ................................................................................................................................. 37 6.4 Electrical Characteristics (Input Rectifier) ........................................................................................................... 38 6.5 Electrical Characteristics (Intermediate DC Circuit) ............................................................................................ 38 6.6 Electrical Characteristics (Inverter Output) ......................................................................................................... 39 6.7 Electrical Characteristics (Bypass Mains Input) .................................................................................................. 40 6.8 Efficiency, Heat Losses And Air Exchange ......................................................................................................... 40 Appendix 1 BCB Model Selection And Connection ........................................................................................................... 41 Chapter 1 Installation 1 Chapter 1 Installation This chapter introduces the installation of Liebert APM modular UPS, including preliminary checks, location, positioning, cable connection and installation drawings. 1.1 Introduction This chapter describes the requirements that must be taken into account when planning the positioning and cabling of the UPS. This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures. Warning: professional installation required 1. Do not apply electrical power to the UPS equipment before being authorised to do so by the commissioning engineer. 2. The UPS shall be installed by a qualified engineer in accordance with the information contained in this manual. All the equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information. Note: 3-phase, 5-wire input supply required The standard UPS is suitable for connection to 3-phase, 5-wire (A, B, C, N, PE) TN, TT and IT AC power distribution systems (IEC60364-3). Warning: battery hazards Special care should be taken when working with the batteries. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Eye protection should be worn to prevent injury from accidental electrical arcs. z Remove rings, watches and all other metal objects. z Use only tools with insulated handles. z Wear rubber gloves. z If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to z sulfuric acid and disposed of in accordance with local regulations. If electrolyte comes into contact with the skin, the affected area should be washed immediately with water. z 1.2 Preliminary Checks Before installing the UPS, please carry out the following preliminary checks: 1. Visually examine the UPS rack for any transit damage, both internally and externally. Report any damage to the shipper immediately. 2. Verify that the correct UPS is being installed. The UPS has an identification tag on the back of the front door reporting the model, capacity and main parameters of the UPS. 1.3 Location 1.3.1 Power Distribution Room The UPS is intended for indoor installation and should be located in an environment with clean air and with adequate ventilation to keep the ambient temperature within the specified operating range. The UPS is air-cooled with the aid of internal fans. Cold air enters the UPS through the ventilation grilles at the front of the cabinet and hot air is released through the grilles at the back. Do not cover the ventilation openings. Liebert APM Modular UPS User & Installation Manual 2 Chapter 1 Installation If necessary, install a system of room extractor fans to avoid room temperature build-up. Optional air filters are available if the UPS is to operate in a dusty environment. Note: The UPS is suitable for mounting on concrete or other non-combustible surface only. 1.3.2 Battery Room The batteries will generate small amount of hydrogen and oxygen at the end of battery charge. Therefore, make sure that the new air ventilation amount in the battery room meets the EN50272-2001 requirement. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature of 20°C. Operating above 20°C will reduce the battery life while operation below 20°C will reduce the battery capacity. Provided that the average battery operating temperature increases from 20°C to 30°C, the battery life will be reduced by 50%; provided that the average battery operating temperature is above 40°C, the battery life will be reduced by an exponential multiple. In a normal installation the battery temperature is maintained between 15°C and 25°C. Keep batteries away from main heat sources and main air inlets. When using external batteries, the battery protection device (e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries and connecting cables should be as short as possible. 1.3.3 Storage Should the UPS not be installed immediately, it must be stored in a room for protection against excessive humidity and heat sources. The batteries should be stored in a dry, cool environment with adequate ventilation, at temperature ranging from 20°C to 25°C at best. Warning: During storage, periodically charge the battery according to the battery user manuals. In charging process, temporarily connect the UPS to mains and activate it for the time required for recharging the batteries. 1.4 Positioning Jacking feet are provided at the bottom of the UPS cabinet to prevent the UPS from moving once it has been placed to its final position. For optimal design life, the place chosen must offer: z easy connection z enough space to easily work on the UPS z sufficient air exchange to dispel heat produced by UPS z protection against atmospheric agents z protection against excessive humidity and high heat sources z protection against dust z compliance with the current fire prevention requirements z For VRLA (Valve Regulated Lead Acid) batteries the operating environment temperature is kept between 20°C and 25°C. VRLA batteries are at maximum efficiency in this temperature range (see Table 6-2) Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation 3 1.4.1 UPS Composition The UPS structure is shown in Figure 1-1. The UPS configuration is provided in Table 1-1. SPM monitoring module Output distribution modules Output distribution modules Switch unit Bypass module Power modules Figure 1-1 Libert APM Internal General Arrangement Drawing (Front View) Table 1-1 UPS configuration list Component Quantity (pcs) Remark SPM Brach Circuit monitoring module 1 Optional, installed at site Output Power distribution module 0~3 Optional, installed at site Switch unit 1 Static Bypass module 1 UPS Power module 1~5 Requisite, installed at site 1.4.2 Moving The Cabinet Warning 1. Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity. 2. The UPS is fitted with casters. Take extra caution when unbolting the UPS from its shipping pallet. Ensure that adequate personnel and lifting aids are available when removing the shipping pallet. 3. The cabinet can be pushed forward or backward only. Pushing it sideward is not allowed. When pushing the cabinet, take care not to overturn it as the gravity center is high. Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. The cabinet can be moved by means of a forklift or similar equipment. It can also be moved in short distances only by using its casters. Liebert APM Modular UPS User & Installation Manual 4 Chapter 1 Installation 1.4.3 Clearances The UPS has no ventilation grilles at either side; therefore, no clearance is required at either side. To enable routine tightening of power terminations within the UPS, in addition to meeting any local regulations, it is recommended to provide adequate clearance in the front and at the back of the cabinet for unimpeded passage of personnel with the doors fully opened for accessing cable termination. Refer to Figure 1-15 for the positioning of the cabinet. It is recommended to have at least 150mm of rear clearance for ventilation purposes. 1.4.4 Front Access And Rear Access The component layout of the UPS supports front access and minimal rear access in UPS service, diagnosis and repair, thus reducing the space requirement for side access. 1.4.5 Final Positioning Warning Casters are strong enough for movement across even surfaces only. Caster failure could occur in movement across uneven surfaces. When the UPS has been finally positioned, ensure the adjustable feet are set so that the UPS will remain stationary and stable. 1.4.6 Installing Power Modules And Output Distribution Modules (Optional) The installation positions of the power modules and output distribution modules are shown in Figure 1-1. Please install the power modules and output distribution modules from bottom to top, so as to ensure cabinet’s stability. Installation procedures of power modules Refer to Figure 1-2, and use the following procedures to install the power module: 1. Use the DIP switch on the front panel of each Power module to set the module address. The setting range is from 1 to 5. The module address should be exclusive. The setting method is shown in Table 1-2. Table 1-2 DIP switch setting method Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Module address 1 0 0 0 0 1 0 1 0 0 0 2 1 1 0 0 0 3 0 0 1 0 0 4 1 0 1 0 0 5 2. Place the ready switch on the front panel of the module to the up position (i.e., in unready state). 3. Insert the module in the installation position, and push it into the cabinet. 4. Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module. 5. Place the ready switch to the down position (i.e., in ready state). Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation 5 DIP switch Fixing holes Ready switch A amplified view Power module A Figure 1-2 Installing power module Installation procedures of Optional output distribution modules Use the following procedures of install the output distribution module: 1. Insert the module in the installation position, and push it into the cabinet. 2. Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module. 1.4.7 Cable Entry The Rack cabinet uses top cable entry or bottom cable entry, with cable entry punch-holes provided both at the bottom and on the top of the cabinet.. 1.5 Protective Devices It is recommended to install circuit breakers or other protective devices in the AC supply, external to the UPS. This section provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed. 1.5.1 Rectifier and Bypass Input Overcurrent Overcurrent protection must be installed at the distribution panel of the incoming main supply. The protection must discriminate with the power cable current capacity and with the overload capacity of the system (see Table 6-6 and Table 6-7). As a guideline, a thermomagnetic circuit breaker, with an IEC60947-2 trip curve C (normal) for 125% of the current listed in Table 1-3 is suitable. Note For IT power systems, four-pole protective devices must be used upstream of the input distribution panel, external to the UPS. Liebert APM Modular UPS User & Installation Manual 6 Chapter 1 Installation Earth Leakage Any residual current detector (RCD) installed upstream of the UPS input supply must: z be sensitive to DC unidirectional pulses (Class A) in power distribution network z be insensitive to transient current pulses z have an average sensitivity, adjustable between 0.3 and 1A Residual current circuit breaker (RCCB) must be sensitive to DC unidirectional pulses (Class A) in power distribution network, and insensitive to transient current pulses, as respectively shown in Figure 1-3. Figure 1-3 RCCB symbols 1.5.2 Battery The battery system must be fitted with a battery circuit breaker (BCB) or Switch Fuse Unit for over-current protection and isolating battery string during battery maintenance. 1.5.3 UPS Output Liebert APM is fitted with an output isolator for disconnecting the UPS from the load. An optional internal output distribution unit is available for load distribution. In the eventuality that an external distribution panel is used for load distribution, the selection of protective devices must provide discrimination with those that are used at the input to the UPS 1.6 Power Cables The cable design must comply with the instructions provided in this section, follow local wiring practices, take the environmental conditions into consideration, and refer to IEC60950-1 Table 3B. Warning Before cable connection, ensure that you are aware of the location and state of the breaker that connect the UPS input to the mains distribution panel. Check that this breaker is off, and post any necessary warning sign to prevent inadvertent operation of the breaker. 1.6.1 Maximum Steady State AC And DC Currents Table 1-3 Maximum steady state AC and DC currents Rated current (A) UPS rating (kVA) Input mains current 1,2 with full battery recharge 2 Output current at full load Battery discharge current at end of discharge (EOD) 380V 400V 415V 380V 400V 415V 150 280 265 255 225 215 205 525 120 224 212 204 180 172 164 420 90 168 159 153 135 129 123 315 60 112 106 102 90 86 82 210 30 56 53 51 45 43 41 105 Note: 1. Rectifier and bypass input mains current. 2. Non-linear loads (switch mode power supplies) affect the design of the output and bypass neutral cables. The current circulating in the neutral cable may exceed the nominal phase current. A typical value is 1.732 times the rated current Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation 7 1. Protective earth cable: Follow the most direct route possible to connect the earth cable to the cabinet. The earth cable shall be sized in accordance with the AC supply fault rating, cable lengths and type of protection. Typical 2 cross sectional area (CSA) is 80mm (150kVA) according to AS / IEC60950-1. 2. When sizing battery cables, a maximum volt drop of 4Vdc is permissible at the current ratings given in Table 1-3. Do not form coils, so as to minimize the formation of electromagnetic interference. 3. For terminal location, refer to Figure 1-16 and Figure 1-17. Warning Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards involving electric shock and fire. 1.6.2 Distance From Floor To Connection Point On The Equipment Table 1-4 Distance from floor to connection point on the equipmen UPS connection point Minimum distance (mm) AC input supply 1087 UPS AC output 1156 Battery power 1087 1.6.3 Cable Connection Important The operations described in this section must be performed by authorised personnel. If you have any questions, please contact the local customer service center of Emerson immediately. Once the equipment has been finally positioned and secured, refer to Figure 1.8 the power cables as described in the following procedures. Installation Drawing, and connect 1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. 2. Open the rear door of the UPS cabinet and remove the protective cover to gain access to the input terminals, battery terminals and earth terminals. 3. Connect the input earth cable to the input earth terminal. Note: The earth cable connection must be in accordance with local and national codes of practice. 4. The UPS uses common bypass and rectifier input. Connect the AC input cables to the input terminals (U-V-W-N) of the UPS and tighten the connections to 13Nm (M8 bolt). Ensure correct phase rotation. 5. Connect the battery cables between the battery terminals of the UPS and the battery circuit breaker (BCB). Ensure correct battery cable polarities. Warning–hazardous battery terminal voltage 400Vdc Ensure correct polarity of string end connections to the BCB and from the BCB to the UPS terminals, i.e., positive to positive and negative to negative, but disconnect one or more battery cell links in each tier. Do not reconnect these links or close the BCB without permission of the commissioning engineer. 6. Connection of the load cables. z In case output distribution modules are installed, please connect the output cables between the output terminals of the output distribution modules and the loads, and connect the output earth cables to the output earth bars Liebert APM Modular UPS User & Installation Manual 8 Chapter 1 Installation at the rear of the UPS cabinet. Tighten the output neutral bar connections to 5Nm (M6 bolt). Ensure correct phase rotation. z In case output distribution modules are not installed, please connect the output cables between the output terminals in the front of the UPS cabinet and the loads, and connect the output earth cable to the output earth terminal at the rear of the UPS cabinet. Warning If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their ends. 7. Replace the protective cover. 1.6.4 Optional Matching Battery Cabinet The matching battery cabinet structure is shown below. Figure 1-4 Battery Cabinet Outline Drawing Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation Figure 1-5 Battery Cabinet Details Figure 1-6 Battery Connection 1.7 Control And Communications As shown in Figure 1-7, the bypass module provides dry contact ports (J5 ~ J10) and communication ports (RS232 port and SNMP card ports) on the front panel. Liebert APM Modular UPS User & Installation Manual 9 10 Chapter 1 Installation J8 J5 J9 J6 J10 J7 Figure 1-7 RS232 port SNMP card ports Dry contact ports and communication ports The UPS accepts external signalling from voltage-free (dry) contacts connected to push-in input dry contact terminal. Subject to prior software programming, the signalling is accepted by the UPS when relevant terminals and the +12V terminals are shorted. All control cables must be routed separately from the power cables, and must be double 2 2 insulated. A typical 0.5mm to 1.5mm CSA for maximum runs between 25m and 50m, respectively. 1.7.1 Input Dry Contact Port The input dry contact ports J7 and J8 provide environmental, battery ground fault and generator contacts. The ports are shown in Figure 1-8 and described in Table 1-5. 12V Figure 1-8 Table 1-5 BAT-IN +12V BAT-OUT GND ENV BtG J8 +12V J7 Input dry contact ports J7 and J8 Description of input dry contact ports J7 and J8 Position Name J7.1 ENV3 Description J7.2 BtG1,2 J7.4 +12V +12V power J8.2 +12V +12V power J8.3 BAT_OUT J8.4 GND Battery room environment detection (normally closed) On generater (normally open) Battery temperature detection Power GND Note: 1. Must be configured by configuration software before becoming active. 2. When activated, the charger current can be limited, through software, to a percentage of the full charger current (0%-100%). 3. Activating this feature turns the battery charger off Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation 11 1.7.2 BCB Port J6 is the battery circuit breaker (BCB) port. The port is shown in Figure 1-6 and described in Table 1-9. 12V 12V 12V Figure 1-9 Table 1-6 Position Name J6.1 DRV J6.2 FB J6.3 GND J6.4 OL DRV FB GND OL J6 BCB port BCB port description Description BCB driver signal – (reserved) BCB contact state – (reserved) Power GND BCB on line – input (normally open): This pin will become active when the BCB port is connected The connection between the BCB port and the BCB is shown in Figure 1-10. OL GND FB DRV J10 Aux-N.O. Aux-N.O. BCB 电池开关 Figure 1-10 Connection between BCB port and BCB 1.7.3 Maintenance Bypass Switch And Output Switch State Port J9 is the maintenance bypass switch and output switch state port. The port is shown in Figure 1-8 and described in Table 1-7. Figure 1-11 Table 1-7 Maintenance bypass switch and output switch state port Description of maintenance bypass switch and output switch state port Position Name J9.2 IN_S J9.3 EXT_OUT J9.4 GND Description Maintenance bypass switch state Output switch state Power GND Liebert APM Modular UPS User & Installation Manual 12 Chapter 1 Installation 1.7.4 Output Dry Contact Port J5 is the output dry contact port, providing two relay output dry contact signals. The port is shown in Figure 1-12 and described in Table 1-8. Figure 1-12 Table 1-8 Position BFP_O BFP_S BFP_C J5 Output dry contact port Description of output dry contact port Name Description BFP_O Bypass feedback protection relay (normally silicon-controlled rectifier (SCR) is shorted J5.3 BFP_S Bypass feedback protection relay common J5.4 BFP_C Bypass feedback protection relay (normally closed), open when bypass SCR is shorted J5.2 open), closed when bypass 1.7.5 Remote EPO Input Port The UPS has an Emergency Power Off (EPO) function that can be operated by pressing a button on the operator control and display panel of the UPS or by a remote contact provided by the user. The EPO switch is under a hinged, plastic shield. J10 is the remote EPO input port. The port is shown in Figure 1-13 and described in Table 1-9. +12V Figure 1-13 Table 1-9 EPO NC +12V +12V EPO NO J10 Remote EPO input port Description of remote EPO input port Position Name Description J10.1 EPO_NC EPO activated when shorted to J10.2 J10.2 +12V EPO activated when shorted to J10.1 J10.3 +12V EPO activated when opened to J10.4 J10.4 EPO_NO EPO activated when opened to J10.3 EPO is triggered when pins 3 and 4 of J10 are shorted or pins 2 and 1 of J10 are opened. If an external EPO facility is required, pins 1 and 2 or 3 and 4 of J10 are reserved for this function. The external EPO facility is also connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable. If this function is not used, pins 3 and 4 of J10 must be opened or pins 1 and 2 of J10 must be shorted. Note 1. The UPS EPO action shuts down the rectifiers, inverters and static bypass. But it does not internally disconnect the input power supply. To disconnect all power to the UPS, open the upstream input breaker when EPO is activated. 2. Pins 1 and 2 of J10 are shorted as default setting of UPS. Liebert APM Modular UPS User & Installation Manual Chapter 1 Installation 13 1.7.6 Other Communication Interface The RS232 port provides serial data and is intended for use by authorized commissioning and service personnel in UPS commissioning and service. Liebert APM UPS has facility of internally fitted SNMP and Modbus card options. 1.8 Installation Drawing Earth To user safety earth QF1~QF18 PM150 QF1~QF18 Distribution module output QF1~QF18 Power cables A B Bypass module SNMP card C Mains/bypass input N PE RS-485 Input ENV J7 EXT J9 J5 BPS BAT+ N Battery input BATAFC J8 Transfer board External EPO J10 J6 BCB Figure 1-14 UPS electrical connection diagram Liebert APM Modular UPS User & Installation Manual Installation 1100 1126 1137 Chapter 1 1677 14 2000 971 Top view 600 Front view Figure 1-15 UPS installation size (unit: mm) SPM monitoring module Output terminals Output terminals Output earth bars (2 pcs respectively on both sides) Output neutral bars (2 pcs respectively on both sides) Input earth terminal Battery terminals + N - U Input terminals V W N A Output earth terminal A amplified view Figure 1-16 Rear view of UPS (door open) with output distribution modules Liebert APM Modular UPS User & Installation Manual Chapter 1 Output terminals A N C B A A amplified view Figure 1-17 Front view of UPS (door open) without output distribution modules Liebert APM Modular UPS User & Installation Manual Installation 15 16 Chapter 2 Operation Chapter 2 Operation This chapter introduces the basic knowledge of UPS operation, including the operating theory, operation mode, battery management and battery protection of the UPS. Warning: hazardous mains and battery voltage present behind covers 1. No user-serviceable parts are located behind covers that require a tool for their removal. 2. Only qualified service personnel are authorised to remove such covers. 2.1 Brief Introduction The UPS provides continuous, high-quality AC power to your critical equipment, such as telecommunications and data processing equipment. The UPS supplies power that is free of the disturbances and variations in voltage and frequency common to mains power, which is subject to brownouts, blackouts, surges and sags. The UPS uses the latest in high frequency, double-conversion pulse width modulation (PWM) technology and fully digital control (DSP) technology to enhance its reliability and increase the ease of use. 2.1.1 Operating Theory As shown in Figure 2-1, the AC mains source is converted by the rectifiers into DC power. The inverters convert that DC power from the rectifiers or the DC power from the batteries into AC power, and provide the AC power for the load through the output distribution modules. The batteries power the load through the inverters in the event of a power failure. When the inverters are faulty or turned off, the mains source can also power the load through the static bypass. If maintenance or repair of the UPS is necessary, the load can be transferred without power interruption to the maintenance bypass. QF1 Maintenance bypass switch Q2 Output distribution module 1 QF18 Rectifier AC input 380V Input switch Q1 Inverter Maximally five power modules Rectifier Inverter Output switch Q3 QF1 Output distribution module 2 QF18 Static switch QF1 + Battery input N - Output distribution module 3 QF18 Figure 2-1 System schematic diagram 2.1.2 Static Switch The circuit block labeled static switch in Figure 2-1 contains an electronically controlled switching circuit that enables the load to be connected to either the inverter output or to a bypass power source through the static bypass line. During normal system operation, the load is connected to the inverters; but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static bypass line. Liebert APM Modular UPS User & Installation Manual Chapter 2 Operation 17 During normal operating conditions, the inverter output and bypass supply must be fully synchronized so as to achieve a clean (no-break) load transfer between the inverter output and static bypass line. The synchronization between the inverter output and static bypass is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window. A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the maintenance bypass supply while the UPS is shut down for routine maintenance and repair. Note When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is not protected from power failures or surges and sags. 2.2 Operation Mode The UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these modes: z Normal mode z Battery mode z Auto-restart mode z Bypass mode z Maintenance bypass mode (manual bypass) z ECO mode 2.2.1 Normal Mode The UPS rectifiers derive power from the AC mains input source and supply DC power to the inverters, which continuously supply the AC load. Simultaneously, the charger, which derives power from the rectifiers, float or boost charges the associated backup battery of the UPS. 2.2.2 Battery Mode The UPS is operating in battery mode when the battery is supplying backup power to the load through the inverters. Upon mains failure, the UPS automatically transfers to battery mode without power interruption to the load. Upon restoration of the AC mains, the UPS automatically transfers back to normal mode without the necessity of user intervention, without power interruption to the load. Note: Battery start function is available for switching the UPS on into Battery (charged) mode directly during mains failure. Thus, the battery power can be used independently to increase the UPS utility. 2.2.3 Automatic Restart Mode The battery becomes exhausted following an extended AC mains failure. The inverters shut down when the battery reaches the EOD voltage. The UPS can be programmed to automatic restart after EOD after a set variable delay time. This mode and any delay time are programmed by the commissioning engineer. During the delay time before automatic restart, the UPS charges the battery so as to avoid power interruption to load in case of a following power failure. In case the UPS is not programmed to automatic restart, you can use the FAULT CLEAR key to manually start the UPS. 2.2.4 Bypass Mode During normal mode operation, if the inverters fail, are overloaded or turned off, the static switch will perform a transfer of the load from the inverters to the bypass source, with no interruption in power to the load. Should the inverters be asynchronous with the bypass, the static switch will perform a transfer of the load from the inverters to the bypass, with interruption in power to the load. This is to avoid paralleling of unsynchronized AC sources. This Liebert APM Modular UPS User & Installation Manual 18 Chapter 2 Operation interruption is programmable but typically set to be less than 3/4 of an electrical cycle, for example, less than 15ms (50Hz) or less than 12.5ms (60Hz). 2.2.5 Maintenance Bypass Mode If UPS maintenance or repaired is needed, you may use the manual maintenance bypass switch to transfer to the load to the maintenance bypass, with no interruption in power to the load. Warning: risk after load transfer to maintenance bypass After the UPS is transferred to maintenance bypass, the power modules and bypass module are inoperative and the LCD has no display, only the green indicator of the input surege protective device (SPD) shows the UPS has mains input, but the output terminals corresponding to closed output distribution switches and the neutral bars are energized. 2.2.6 ECO Mode IF economical (ECO) mode is selected, the double-conversion UPS operation is inhibited at most times for the purpose of saving energy. In this mode of operation, the bypass is the preferred source, and only when the voltage and frequency of the bypass supply are outside specifications will the load be transferred to the inverters. This transfer takes place with an interruption of less than 3/4 of an electrical cycle, for example, less than 15ms (50Hz) or less than 12.5ms (60Hz). 2.3 Battery Management 2.3.1 Normal Function The following functions are configured by the commissioning engineer through dedicated configuration software. 1. Constant current boost charge The charge current can be set. 2. Constant voltage boost charge The boost charge voltage can be set as required by the type of battery. For valve regulated lead acid (VRLA) batteries, the maximum boost charge voltage should not exceed 2.4V/cell. 3. Float charge The float charge voltage can be set as required by the type of battery. For VRLA batteries, the float charge voltage should be between 2.2V and 2.3V. 4. Float charge temperature compensation (optional) The temperature compensation coefficient can be as required by the type of battery. 5. EOD protection When the battery voltage drops to the EOD voltage, the battery converter will shut down automatically and the battery is isolated to avoid further battery discharge. The EOD voltage is settable from 1.6V/cell to 1.75V/cell (VRLA) or 0.9V/cell to 1.1V/cell (NiCd). 6. Battery low warning time The setting range is between 3 minutes and 60 minutes. The default setting is 5 minutes. Liebert APM Modular UPS User & Installation Manual Chapter 2 Operation 19 2.3.2 Advanced Function——Battery Self-Test And Self-Service At periodic intervals 20% of the rated capacity of the battery will be discharged automatically. The minimum amount of load must exceed 20% of the nominal rating of the UPS. If the load is less than 20%, auto-discharge cannot be executed. The periodic interval can be set from 30 days to 360 days. The periodic testing can also be inhibited. Conditions: Battery float charge for at least 5 hours, load 20% ~ 100% of rated UPS capacity. Trigger: Manually through the Battery maintenance test command on LCD, or automatically. Battery self-test interval: 30 days ~ 360 days (default setting: 60 days). 2.4 Battery Protection The following functions are configured by the commissioning engineer through dedicated configuration software. Battery low warning The battery low warning occurs before the EOD. After this warning, the battery should have the capacity for 3 remaining minutes discharging at full load. The time is settable from 3 minutes to 60 minutes. Battery EOD protection If the battery voltage is lower than the EOD voltage, the battery converter will shut down. The EOD voltage is settable from 1.6V/cell to 1.75V/cell (VRLA) or 0.9V/cell to 1.1V/cell (NiCd). Battery circuit breaker (BCB) open warning This warning occurs when the BCB opens. The battery is connected to the UPS through the BCB, which is manually closed and electronically tripped by the UPS control circuits. Liebert APM Modular UPS User & Installation Manual 20 Chapter 3 Operating Procedures Chapter 3 Operating Procedures This chapter provides detailed operating procedures of the UPS. All control keys and LED indication mentioned in these procedures are identified in Chapter 4 Operator Control And Display Panel. Audible alarm may sound at various points during these procedures. It can be canceled at any time by pressing the SILENCE ON/OFF key. Warning: hazardous mains and battery voltage present behind covers 1. No user-serviceable parts are located behind covers that require a tool for their removal. 2. Only qualified service personnel are authorised to remove such covers. 3.1 Power Switches As shown in Figure 3-1, opening the UPS front door reveals the power switches, including the input switch, output switch, maintenance bypass switch (locked) and output distribution switches. Output distribution switches Input switch Output distribution switches Output switch Maintenance bypass switch (locked) Figure 3-1 Positions of power switches 3.2 UPS Start-Up Procedures Before startup, the UPS must be fully installed and commissioned, and the external input breaker must be closed. Once those general conditions are met, the UPS may be started. Liebert APM Modular UPS User & Installation Manual Chapter 3 Operating Procedures 21 3.2.1 Start-Up Procedures (Into Normal Mode) Procedures are as follows for starting the UPS from a fully powered-down condition: Warning During these procedures the output terminals are live. If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, open the corresponding output distribution switch. 1. Close the UPS output switch and input switch in turn. At this point, the LCD displays the start screen. The rectifier indicator flashes green while the rectifiers are starting up. It stops flashing and becomes solid green about 30 seconds after the rectifiers enter normal operation. After initialization, the bypass static switch closes. The states of the indicators are shown in Table 3-1. Table 3-1 Indicator state Indicator State Rectifier indicator Green Battery indicator Off Bypass indicator Green Inverter indicator Off Load indicator Green Status indicator Yellow 2. Press and hold the INVERTER ON key for two seconds. Note You must close the UPS output switch first, then close the input switch, and finally turn on the inverter. Otherwise, the inverter will not start, and the UPS will generate Bypass STS fail alarm. At this point, the inverter start and the inverter indicator flashes green. After the inverter enter normal operation, the UPS transfers from the bypass to the inverters, the bypass indicator turns off and the inverter and load indicators turn on. The UPS begins to operate in normal mode, and the states of the indicators are as shown in Table 3-1. Table 3-2 Indicator state Indicator State Rectifier indicator Green Battery indicator Off Bypass indicator Off Inverter indicator Green Load indicator Green Status indicator Green 3.2.2 Start-Up Procedures (Into Battery Mode) 1. Verify that the battery is properly connected. 2. Press the battery start button (see Figure 3-2) on the front panel of any power module. At this point, the LCD displays the start screen, and the battery indicator flashes green. It stops flashing and becomes solid green about 30 seconds after the rectifiers enter normal operation. 3. Press and hold the INVERTER ON key for two seconds, and the UPS operates in battery mode. Liebert APM Modular UPS User & Installation Manual 22 Chapter 3 Operating Procedures Battery start button Figure 3-2 Location of battery start button 3.3 Procedures Of Transfer Between Operation Modes 3.3.1 Transfer From Normal Mode To Battery Mode Open the input switch to cut off the mains input, and the UPS enters battery mode. To return to normal mode, wait a few seconds and close the input switch to connect the mains power to the UPS. The rectifiers will restart automatically after 10 seconds and resume feeding power to the inverters. 3.3.2 Transfer From Normal Mode To Bypass Mode Press and hold the INVERTER OFF key for two seconds to transfer the UPS to bypass mode. Note In bypass mode, the load is being powered by the mains input and is not receiving conditioned power through the inverters. 3.3.3 Transfer From Bypass Mode To Normal Mode In bypass mode, press and hold the INVERTER ON key for two seconds. When the inverters are ready, the UPS transfers to normal mode. 3.3.4 Transfer From Normal Mode To Maintenance Bypass Mode When the UPS is operating in normal mode, use the following procedures to transfer the load from the inverter output to the maintenance bypass. Caution Before performing this operation, read the messages on the LCD to be sure that bypass supply is normal and the inverters are synchronous with it. If these conditions are not present, there is a risk of a short interruption in powering the load. 1. Press and hold the INVERTER OFF key on the right side of the operator control and display panel for two seconds. The inverter indicator turns off, the status indicator turns yellow and an audible alarm sounds. The load is transferred to the static bypass and the inverters turn off. Note Pressing the SILENCE ON/OFF key cancels the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified. 2. Close the maintenance bypass switch. The load is now on maintenance bypass. Warning If a module needs repair, wait about 10 minutes for the internal DC bus capacitors to discharge before removing the faulty module. Liebert APM Modular UPS User & Installation Manual Chapter 3 Operating Procedures 23 3. Open the input switch and output switch. Caution 1. The load is not protected from normal supply aberrations when the UPS is operating in maintenance bypass mode. 2. After the UPS is transferred to maintenance bypass, the power modules and bypass module are inoperative and the LCD has no display, only the green indicator of the input surege protective device (SPD) shows the UPS has mains input, but the output terminals corresponding to closed output distribution switches and the neutral bars are energized. 3.4 Powering Down The UPS To power down the UPS completely, follow the procedures in 3.3.4 Transfer From Normal Mode To Maintenance Bypass Mode to transfer the UPS from normal mode to maintenance bypass mode. To completely isolate the UPS from the AC supplies, open the external power input isolator. 3.5 Emergency Shutdown Procedures The Emergency Power Off (EPO) switch on the UPS operator control and display panel is designed to switch off the UPS in emergency conditions, for example, fire, flood, and so on. The system will turn off the rectifiers, inverters and stop powering the load immediately (including the inverters and bypass), and the battery stops charging or discharging. If the mains input is present, the UPS control circuit will remain active; however, the output will be turned off. To remove all power from the UPS, the UPS input switch should be opened. 3.6 UPS Reset Procedures After UPS shutdown due to an EPO action, inverter over temperature or overload, battery overvoltage, excessive transfer, and so on, once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the LCD, carry out the following reset procedures to restore the UPS to normal operation 1. Press the FAULT CLEAR key to let the system exit the emergency off state. 2. Press and hold the INVERTER ON key for two seconds. Note 1. The rectifiers will start again, and the bypass will begin to power the load. The Rectifier indicator flashes while the rectifiers are starting up. When the rectifiers enter the normal operation state (about 30 seconds), the rectifier indicator turns solid green. 2. The rectifiers will turn on automatically when the overtemperature fault disappears five minutes after the disappearance of overtemperature signals. 3. After the EPO switch is pressed, if the mains input is removed, the UPS will shut down completely. When the mains input returns, the UPS will start up on bypass. There will be power at the output terminals of the UPS. 3.7 Selecting Display Language The UPS provides two LCD languages for your selection: English. and Chinese Carry out the following procedures to select the language: 1. From the Output menu, press the F3 or F4 (left or right) key as needed to select the Language menu. 2. Press the F5 (enter) key to move the cursor to the data window on the screen. 3. Use the F3 or F4 (up or down) key to select the required language. 4. Press the F5 (enter) key to accept the language selection. 5. Return to the Output menu by repeatedly pressing the F2 (ESC) key as needed; all text on the LCD will now be displayed in the selected language. Liebert APM Modular UPS User & Installation Manual 24 Chapter 3 Operating Procedures 3.8 Changing The Current Date And Time To change the system date and time, carry out the following procedures: 1. From the Output menu, press the F3 or F4 (left or right) key as needed to select the Settings menu. 2. Press the F5 (enter) key to move the cursor to the data window on the screen. 3. Use the F3 or F4 (up or down) key to select the Date & time option, then press the F5 (enter) key. 4. Move the cursor to the row in which the date and time are displayed, then press the F5 (enter) key. 5. Use the F3 or F4 (up or down) key to enter the current time and date information. 6. Press the F5 (enter) key to save the settings, then press the F2 (ESC) key to return to the Output menu. 3.9 Command Password Password protection is used to limit the control functions accessible to the operator. The default password is ‘123456’. This password provides access to UPS and battery test functions. Liebert APM Modular UPS User & Installation Manual Chapter 4 Operator Control And Display Panel 25 Chapter 4 Operator Control And Display Panel This chapter expounds the functions and use of the components on the operator control and display panel of the UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm list. 4.1 Introduction The operator control and display panel is located on the front door of the UPS. It is the access point for operator control and monitoring of all measured parameters, UPS and battery status, and alarms. The operator control and display panel is divided into three functional areas: mimic power flow chart, LCD display with menu keys, control keys, as shown in Figure 4-1. Control keys LCD display with menu keys Mimic power flow chart 3 1 5 4 ADAPT PM150 12:30:36 EPO 2 INVERTER ON INVERTER OFF 6 STATUS FAULT CLEAR SILENCE ON/OFF 按任意键返回主菜单 F2 F1 Figure 4-1 Table 4-1 Indicator No. 1 F3 F4 F5 Operator control and display panel Description of operator control and display panel Function Control key Function Rectifier indicator EPO 2 Battery indicator INVERTER ON Inverter start switch 3 Bypass indicator INVERTER OFF Inverter shutdown switch 4 Inverter indicator FAULT CLEAR Fault reset switch 5 Load indicator SILENCE ON/OFF Audible alarm silencing switch 6 Status indicator F1 ~ F5 LCD menu keys Liebert APM Modular UPS User & Installation Manual Emergency power off (EPO) switch 26 Chapter 4 Operator Control And Display Panel 4.1.1 LED Indicators The LED indicators mounted on the mimic power flow chart represent the various power paths and current UPS operational status. The indicators are described in Table 4-2. Table 4-2 Indicator Solid green Rectifier indicator Battery indicator Bypass indicator Inverter indicator Load indicator Status indicator Indicator description State Description Rectifiers in normal operation Flashing green Mains input normal, but rectifiers not operating Solid red Rectifiers failed Off Rectifiers not operating, mains input abnormal Solid green Load on battery Flashing green Battery EOD pre-warning Solid red Battery abnormal (failed, absent or polarity reversed) or battery converter abnormal (failed, overcurrent or overtemperature) Off Battery nad battery converter normal, battery charging Solid green Load on bypass Solid red Bypass power abnormal or outside specifications, or static bypass switch fault Off Bypass normal Solid green Load on inverters Flashing green Inverters turning on, starting up, synchronizing, or standing by (ECO mode) Solid red Inverter fault Off Inverters not operating Solid green UPS output on and normal Solid red UPS output on and overloaded Off UP output off Solid green Normal operation Solid yellow Alarm (for example, AC input failure) Solid red Fault (for example, fuse or hardware fault) 4.1.2 Audible Alarm (Buzzer) UPS activity is accompanied by the two kinds of sound listed in Table 4-3. Table 4-3 Audible alarm description Alarm sound Meaning Beep every other second UPS alarm, for example, AC input failure Continuous beep UPS fault, for example, fuse or hardware fault 4.1.3 Control Keys The operator control and display panel provides five control keys, as described in Table 4-4. Table 4-4 Description of control keys Control key Description Emergency power off (EPO) switch Disconnects power to the load, disables rectifier, inverter, static bypass and battery operation Inverter start switch Enables inverter operation Inverter shutdown switch Disables inverter operation Fault reset switch Restore UPS functions (subject to any fault being cleared) Audible alarm silencing switch When an alarm is active, pressing this key silences the audible alarm. Pressing this key again enables the buzzer again Liebert APM Modular UPS User & Installation Manual Chapter 4 Operator Control And Display Panel 27 4.1.4 LCD And Menu Keys The operator control and display panel provides an LCD and five menu keys (F1, F2, F3, F4, F5). The menu keys are described in Table 4-5. Key Table 4-5 Menu key description F1 F2 F3 F4 F5 Left Right Enter Up Down ESC Function 1 Escape HOME Function 2 Providing 320×240 dot matrix graphic display, the user-friendly and menu-driven LCD allows you to easily browse through the input, output, load and battery parameters of the UPS, learn current UPS status and alarm information, perform functional setting and control operation. The LCD also stores up to 512 historical records that can retrieve for reference and diagnosis. 4.2 LCD Screen Types 4.2.1 Start Screen Upon UPS start, the UPS executes self-test, and the start screen appears and remains approximately 15 seconds, as shown in Figure 4-2. F1 F2 Figure 4-2 F3 F4 F5 Start screen Liebert APM Modular UPS User & Installation Manual 28 Chapter 4 Operator Control And Display Panel 4.2.2 Primary Screen After the UPS starts and finishes self-test, the primary screen appears, as shown in Figure 4-3. The primary screen is divided into four windows: system information window, menu window, data window and keypad window. ADAPT PM150 相电压(V) 相电流(A) 频率(Hz) 线电压(V) 功率因数 A(AB) 220 20.5 50.1 380 0.99 System information window 12:30:36 B(BC) 220 20.5 50.1 380 0.99 C(CA) 220 20.5 50.1 380 0.99 Data window 交流输出 Menu window Keypad window ESC F1 F2 F3 F4 Figure 4-3 F5 Primary screen The function of menu keys F1 ~ F5 is shown by a self-explanatory icon as appropriate for the particular window. From any menu on the primary screen, pressing the F1 key returns to the Output menu, and pressing the F3 + F4 keys enters the screen displayed in Figure 4-4, where you can select the required power module. ADAPT PM150 相 电压(V) 相 电流(A) 频率(Hz) 线 电压(V) 功率 因数 12:30:36 A(AB) B(BC) 220 220 Please select module module 1 m odule 2 m odule 3 C(CA) 220 20.5 50.1 380 0.99 交 流输出 ESC F1 F2 Figure 4-4 F3 F4 F5 Selecting power module Liebert APM Modular UPS User & Installation Manual Chapter 4 Operator Control And Display Panel 29 4.2.3 Default Screen During UPS operation, if there is no alarm within two minutes, the default screen will appear, as shown in Figure 4-5. After a short delay, the LCD backlight will turn off. Pressing any keys (F1 ~ F5) restores the default screen. Liebert APM F1 F2 Figure 4-5 F3 12:30:36 F4 F5 Default screen 4.3 Detailed Description Of Menu Items The description that follows refers to the LCD primary screen shown on Figure 4-3. System information window The system information window displays the current time and UPS name. This window requires no user operation. For details, see Table 4-6. Table 4-6 Item discription of system information window Item Explanation Liebert PM 150kVA UPS name 12: 30: 36 Current time (24hr, HH:MM:SS format) Menu window and data window The menu window provides the menus of the data window. The data window displays the items of the menu selected in the menu window. UPS parameters can be browsed and functions can be set through the menu window and data window. Details are provided in Table 4-7. Table 4-7 Menu L-N voltage (V) Mains Bypass Output Item discription of menu window and data window Item Explanation Phase voltage L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (V) Line voltage Power factor Power factor L-N voltage (V) Phase voltage Frequency (Hz) Bypass frequency L-L voltage (V) Line voltage L-N voltage (V) Phase voltage L-N current (A) Pahse current Frequency (Hz) Output frequency L-L voltage (V) Line voltage Liebert APM Modular UPS User & Installation Manual 30 Chapter 4 Operator Control And Display Panel Menu Load System Battery Item Power factor Sout (kVA) Sout: apparent power Pout (kW) Pout: active power Qout (kVAR) Qout: reactive power Load level (%) The percentage of the UPS rating load Crest factor Output current crest factor Sout (kVA) Sout: apparent power Pout (kW) Pout: active power Qout (kVAR) Qout: reactive power Battery voltage (V) Battery bus voltage Battery current (A) Battery bus current Battery temperature (°C) Battery temperature°C Battery remain time (min) Battery run time remaining Battery capacity (%) The percentage of the capacity of the new battery Battery boost charging Battery is boost charging Battery float charging Battery is float charging Battery is not connected Battery is not connected I (A) SPM Branch In (A) Load (%) Electric energy (kwh) SPM Meter State Current ripple coefficient Pout (kW) SPM Loads Explanation Power factor Sout (kVA) Power factor Displays the current, rated current and current percentage of each SPM output route (up to 54 routes). When ‘-’ is displayed, it means the corresponding output route is not connected or the measurement point of this output route is defined as input measurement Displays the current, current harmonic percentage and switch status of each SPM output route (up to 54 routes). When ‘-’ is displayed, it means the corresponding output route is not connected or the measurement point of this output route is defined as input measurement Optional. Set by commissioning engineer Displays the active power, apparent power and power factor of each SPM output route (up to 54 routes). When “-” is displayed, it means the corresponding output route is not connected Event (active alarm) Displays the active alarms. For the list of the alarms that may be displayed on the LCD on the UPS operator control and display panel, refer to Table 4-9 Records (alarm history) Displays the alarm history. For the list of the alarms that may be displayed on the LCD on the UPS operator control and display panel, refer to Table 4-9 Language Settings (language option) Provides two optional LCD languages Display contrast Adjusts the LCD contrast Date format set Four formats selectable: MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD Date & time Sets the date and time Comm1 baud rate Sets the communication baud rate of the RS232 port Comm2 baud rate For internal communicaiton. Not settable Comm3 baud rate Sets the communication baud rate of the SNMP card ports Communication address Applicable to RS485 communication Communication mode Set the communcation mode Callback times If the communcation mode of the SNMP card port is modem mode, this parameter sets the number of times of a number is redialed to send an alarm notificiaton Phone No.1 If the communcation mode of the SNMP card port is modem mode, this is the first phone number to be dialed (to send an alarm notification) Phone No.2 If the communcation mode of the SNMP card port is modem mode, this is the second phone number to be dialed (to send an alarm notification) Phone No.3 If the communcation mode of the SNMP card port is modem mode, this is the third phone number to be dialed (to send an alarm notification) Command password The user can modify the command password Liebert APM Modular UPS User & Installation Manual Chapter 4 Menu Command (initiate, stop battery, system test or freshening charge Version Operator Control And Display Panel Item 31 Explanation Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate of the battery capacity. Load must be between 20% and 100% Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of the battery capacity. Load must be between 20% and 100% System test This is a self-test of the UPS. When the user activates this function, a window appears about five seconds later to show the test result Stop testing Manually stops a battery maintenance test, battery capacity test or system test Freshening charge Manually initiates a battery freshening charge Stop freshening charge Manually stops a battery freshening charge Monitor Version Provides the monitoring software version Rectifier Version Provides the rectifier software version Inverter Version Provides the inverter software version Bypass Version Provides the bypass software version SPM Version Provides the SPM DSP software version Keypad window The function of menu keys F1 ~ F5 is shown by a self-explanatory icon as appropriate for the particular window. 4.4 Prompt Windows A prompt window is displayed during the operation of the system to alert you to certain conditions or to require your confirmation of a command. The prompts are provided in Table 4-8. Table 4-8 Prompts and meanings Prompt Meaning Transfer with interrupt, confirm or cancel The inverter and bypass supplies are not synchronized and any load transfer between the inverters and bypass will cause a brief load interruption This operation leads to output shutdown, confirm or cancel The bypass is abnormal, turning off the inverters will cause the load to be dis-engergised Turn on more UPS to carry current load The number of inverters already turned on is insufficient to carry the exisitng load. The user is required to turn on more inverters Battery will be depleted, confirm or cancel If you select battery maintenance test, the battery will discharge until the UPS shuts down. This prompt appears to require your confirmation. Cancelling the test will ends the test and transfers the UPS to Normal mode System self test finished, everything is OK No action required Please check the current warnings Check the active alarm messages Enter control password Required for battery or UPS test (default: 123456) Battery Self Test aborted, conditions not met Battery selt-test condition is not met. Please check whether the battery is in boost charge state and the load is more than 20% Battery Refresh Charge aborted, conditions not met This prompt appears when you select the Freshening charge command while the a battery freshening charge condition (such as no battery, charger failure) is not met Liebert APM Modular UPS User & Installation Manual 32 Chapter 4 Operator Control And Display Panel 4.5 Alarm List The following table provides the complete list of UPS alarm messages supported for display either on the Event menu or on the Records menu as described in Table 4-9. Table 4-9 Alarm list Alarm Explanation Inverter comm. fail Internal communication failure between monitoring board and inverters Rectifier comm. fail Internal communication failure between monitoring board and rectifiers Parallel comm. fail Communication between different power modules failed. 1.Check if there are some power modules not powered. If so, power on these power modules and check if the alarm disappears. 2. Press the FAULT CLEAR key Battery overtemp. The battery temperature is over limit. Check the battery temperature and ventilation Ambient overtemp. The ambient temperature is over limit. Check the ventilation of the UPS room Battery fault The battery is aged (reserved) Replace battery Battery test failed. The battery needs replacement Battery low pre-warning Before the EOD, battery low pre-warning will occur. After this pre-warning, the battery will have the capacity for three minutes discharging with full load. The time is user-settable from 3 minutes to 60 minutes. Please shut down the load in time Battery end of discharge Inverters turned off due to battery EOD. Check the mains failure and try to recover it Mains volt. abnormal The mains voltage is outside specifications and results in rectifier shutdown. Check the rectifier input phase voltage Mains undervoltage Mains voltage is under-voltage with derated load. Check the rectifier input line voltage Mains freq. abnormal The mains frequency is outside specifications and results in rectifier shutdown. Check the rectifier input frequency Rectifier fault Rectifiers detected faulty, rectifiers shut down, battery discharges Rectifier overtemp. The heatsink temperature is too high and results in rectifier stop. The UPS can recover automatically. Check the environment and ventilation Charger fault The voltage of the battery charger is too high Control power 1 fail The UPS is operating but the control power is abnormal or not available Mains phase reversed The AC input phase rotation is reversed Rectifier overcurrent The rectifiers are overloaded Soft start fail The rectifiers could not start due to low DC bus voltage Bypass unable to trace This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is outside specifications. The amplitude threshold is fixed for ±10% rating. This alarm automatically resets once the bypass voltage goes normal. 1. First verify that the bypass voltage and frequency displayed on the LCD are within the selected ranges. Note that here the rated voltage and frequency are specified by Output voltage level and Output frequency level respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external supply if it is found faulty Bypass abnormal This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage exceeds the limit. The amplitude threshold is fixed for ±10% rating. This alarm automatically resets once the bypass voltage goes normal. 1. First check if there are some relevant alarms such as Bypass phase reverse and Mains neutral lost. If they appear, solve them first. 2. Then verify that the bypass voltage and frequency displayed on the LCD are within the bypass limits. Note that here the rated voltage and frequency are specified by Output voltage level and Output frequency level respectively. 3. If the displayed voltage is believed to be abnormal, then measure the bypass voltage and frequency presented to the UPS. If the bypass voltage and frequency are abnormal, check the external bypass supply. 4. If the mains is likely to trigger this alarm frequently, the bypass limits can be changed a little larger through the configuration software according to the user’s agreement Liebert APM Modular UPS User & Installation Manual Chapter 4 Alarm Inverter asynchronous Operator Control And Display Panel 33 Explanation This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than six degrees in phase. The amplitude threshold is fixed for ±10% rating. This alarm resets automatically once the condition is no longer true. 1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so, solve it first. 2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek any possible measurements Inverter fault Inverter output voltage outside specifications. Load transfers to bypass Inverter overtemp. The temperature of the inverter heatsink is too high and reusults in inverter stop. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heatsink. The UPS will recover automatically after a five minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true, then check for: 1. high ambient temperature. 2. obstructed cooling airway. 3. any fan failure. 4. prolonged inverter overload Fan fault At least one of the cooling fans failed Main STS fail At least one of the static switches at the inverter side is open or shorted. This fault is locked until power off Bypass STS fail At least one of the static switches at the bypass side is open or shorted. This fault is locked until power off Operation invalid This record is registered following an incorrect operation Output fuse fail At least one of the inverter output fuses is blown. The inverters shut down, and the load transfers to bypass Control power 2 fail The UPS is operating but the redundant control power is abnormal or not available Unit over load The UPS is confirmed to be overload when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the load percent indicated on the LCD to determine which phase is overloaded. 2. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect uncessary load and ensure the safety Byp. abnormal shutdown Both bypass and inverter voltages are abnormal, and the load power is interrupted Inverter over current Overcurrent of inverter pulse width modulation module Bypass phase reverse The phase rotation of the bypass voltage is reverwed. Normally, phase B lags 120 degrees behind phase A, and phase C lags 120 degrees behind phase B. Check that the phase rotation of the UPS bypass supply is correct, and rectify it if it is found to be in error Load impact transfer A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverters Transfer time-out The load remains on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour DC bus abnormal The DC bus voltage is abnormal and results in inverter shutdown. The load transfers to bypass Parallel board fault Parallel board is faulty. This may result in UPS transfer to bypass DC bus over voltage Rectifiers, inverters and battery converter were shutdown because the DC bus voltage is too high. Check whether there is a fault at the rectifier side. If no, then check whether overload occurs. Restart the inverters after resetting the fault Bypass over current The bypass current is above 135% rating. The UPS just alarms and does nothing Setting save error Alarm history not saved (reserved) Mains neutral lost The neutral line of the AC input mains is not detected Protocol version clash Protocol version incompatibility between the monitoring board and DSP board Battery ground fault The battery ground fault dry contact alarms Inv. turned ON manually One used the INVERTER ON key on the operator control and display panel to turn on the inverters Inv. turned OFF manually One used the INVERTER OFF key on the operator control and display panel to turn off the inverters EPO EPO switch pressed or external EPO command received Transfer confirm Prompt to press the enter key to acknowledge an interrupted load transfer to bypass Transfer cancel Prompt to press the ESC key to avoid an interrupted load transfer to bypass Fault reset FAULT CLEAR key pressed Liebert APM Modular UPS User & Installation Manual 34 Chapter 4 Operator Control And Display Panel Alarm Explanation Alarm silence SILENCE ON/OFF key pressed Turn on fail Inverters failed to turn on when the INVERTER ON key was pressed. This may be the result of an invalid operation (maintenance bypass on) or DC bus or rectifiers not ready Alarm reset FAULT CLEAR or SILENCE ON/OFF key pressed Bypass mode The UPS is in bypass mode Normal mode The UPS is in normal mode Battery mode The UPS is in battery mode Check UPS output UPS shutdown with no output power Generator connected Generated connection signal is received BCB open BCB status (open) BCB closed BCB status (closed) Battery float charging Battery status (float charge mode) Battery boost charging Battery status (boost charge mode) Battery discharging Battery status (discharge mode) Battery period testing The battery is under automatic periodic battery maintenance test (20% capacity discharge) Batt. capacity testing The user initiated a battery capacity test (100% capacity discharge) Batt. maint. testing The user initiated a maintenance test (20% capacity discharge) UPS system testing The user initiated a UPS self-test Inverter in setting Inverters starting up and synchronising Rectifier in setting Rectifiers starting up and synchronising MBP-T cabinet Fans Fault Maintenance bypass cabinet fan fault Ext Input TX Overtemp External input isolation transformer overtemperature Ext Output TX Overtemp External output isolation transformer overtemperature Battery Room Alarm Environment in battery room needs attention Battery reverse Connect the battery again and check the battery cable connection No battery Check the battery and the battery cable connection Auto start After the UPS shut down at EOD, the inverters automatically start upon mains restoration REC FLASH UPDATE Rectifier software is being updated INV FLASH UPDATE Inverter software is being updated MONITOR FLASH UPDATE Monitor software is being updated Input contactor fault Input contactor fault Contactor P.S. 1 fault Contactor power supply board 1 fault Contactor P.S. 2 fault Contactor power supply board 2 fault DSP firmware error The inverter software does not match the rectifier firmware SPM Board Not Ready The acquisition board is not properly connected. Seek technical assistance from the local customer service center of Emerson SPM CRC Check Error Data check error of acquisition arithmetic module. Seek technical assistance from the local customer service center of Emerson SPM Branch Curr Over LL Load too large, exceeding route current low threshold (set by commissioning engineer, 60% of rated route current by default) SPM Branch Curr Over HL Load too large, exceeding route current high threshold (set by commissioning engineer, 80% of rated route current by default) SPM Branch Over Current Load too large, exceeding route overcurrent point (set by commissioning engineer, 105% of rated route current by default) SPM Branch 1 Inrush OC Load too large, exceeding route impact overcurrent point (set by commissioning engineer, 130% of rated route current by default) SPM Branch Breaker Fail Output distribution switch open. Check whether it was caused by human intervention or fault. Check the load if was caused by fault SPM Internal Comm Failure Power interruption between bypass module and SPM monitoring module SPM Maitainance Bypass Breaker Close The maintenance bypass switch of the UPS is closed SPM Output Breaker Open The output switch of the UPS is open Note: If the alarms are caused by the values set by the Emerson-authorized commissioning engineer using the configuration software, and the user need to change the setting values, please contact the local customer service center of Emerson Liebert APM Modular UPS User & Installation Manual Chapter 5 Service 35 Chapter 5 Service This chapter introduces the UPS service, including the service procedures of the power module, bypass module and output distribution module, and the replacement of air filter. 5.1 Replacement Procedures Of Power Module, Bypass Module And Output Distribution Module 5.1.1 Notes 1. Only the customer service engineers shall service the power modules, bypass module and output distribution modules. 2. Remove the power modules, bypass module and output distribution modules from top to bottom, so as to prevent cabinet toppling due to high centre of gravity . 3. To ensure safety, before servicing the power modules and bypass module, be sure to use a multimeter to verify that the DC bus capacitor voltage is lower than 60Vdc, and that the voltages between the earth and the components you are going to work on are under dangerous voltage values, that is, lower than 60Vdc or 42.4Vac peak value. 4. The static bypass module is not hot pluggable. It should be replaced only when the UPS is in maintenance bypass mode or completely powered off. 5. The power modules and bypass module should be serviced five minutes, and installed in the cabinet again 10 minutes, after they are removed. 5.1.2 Power Module Replacement Procedures Provided that the UPS is in normal mode, and that the bypass is normal: 1. Press and hold the INVERTER OFF key on the operator control and display panel for two seconds to manually turn off the inverters, and the UPS transfers to bypass mode. 2. Place the ready switch on the front panel of the power module to the up position (i.e., in unready state). 3. Two minutes later, remove the fixing screws on both sides of the front panel of the module, and pull the module out of the cabinet. Note: The module will be blocked by a spring piece at the left side of the module when the module is pulled out of the cabinet halfway. At this point, you must press the spring piece before you continue to pull the module out. 4. After servicing the module, confirm that the DIP switch of the module is set correctly, and that the ready switch is in unready state. 5. Push the module (at least 10s after another) into the cabinet, and tighten the screws on both sides. 6. Wait for two seconds, place the ready switch of the module to the down position, and the module is ready. Then the module will be added into the system automatically and begin to work. 5.1.3 Power Module Service Procedures Provided that the UPS is in normal mode, and that the bypass is normal: 1. Press and hold the INVERTER OFF key on the operator control and display panel for two seconds to manually turn off the inverters, and the UPS transfers to bypass mode. 2. Close the maintenance bypass, and the UPS transfers to maintenance bypass mode. 3. Open the UPS output switch and input switch. 4. Press the EPO switch, and open the battery circuit breaker (BCB). 5. Remove the fixing screws on both sides of the front panel of the bypass module, and pull the module out of the cabinet. Liebert APM Modular UPS User & Installation Manual 36 Chapter 5 Service 6. After servicing the module, push the module (at least 10s after another) into the cabinet, and tighten the screws on both sides. 7. Close the UPS output switch and input switch in turn. Two minutes later, the bypass indicator on the operator control and display panel turns on, indicating the UPS is operating in bypass mode. 8. Open the maintenance bypass switch, press and hold the INVERTER ON key on the operator control and display panel for two seconds to manually turn on the inverters, and the UPS transfers to normal mode. 5.1.4 Output Distribution Module replacement Procedures 1. Open each output distribution switch of the output distribution module. 2. Remove the cables connected to the output terminals of the output distribution module. 3. Remove the fixing screws on both sides of the front panel of the module, and pull the module out of the cabinet. 4. After servicing the module, confirm that all output distribution switches of the module are open. 5. Push the module into the cabinet, and tighten the screws on both sides. 6. Restore the cable connection to the output terminals of the module. 5.2 Replacement Procedures Of Air Filter As shown in Figure 5-1, the UPS provides four air filters on the back of the front door, each fixed by a fixing bar on both sides. The air filter replacement procedures are as follows: 1. Open the front door of the UPS to reveal the air filters on the back of the door. 2. Remove a fixing bar on either side of the air filter. 3. Remove the air filter, and insert a clean one. 4. Replace the fixing bar. Fixing bar Air filters Figure 5-1 Air filters on the back of the UPS front door Liebert APM Modular UPS User & Installation Manual Chapter 6 Specifications 37 Chapter 6 Specifications The chapter provides the UPS specifications. 6.1 Conformity And Standards The UPS has been designed to conform to the European and international standards listed in Table 6-1. Table 6-1 European and international standards Item Normative reference General and safety requirements for UPS used in operator access areas EN50091-1-1/IEC62040-1-1/AS 62040-1-1 Electromagnetic compatibility (EMC) requirements for UPS EN50091-2/IEC62040-2/AS 62040-2 (C3) Method of specifying the performance and test requirements of UPS EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111) Note: The product standards in this table incorporate relevant compliance clauses with generic IECand ENstandards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529) 6.2 Environmental Characteristics Table 6-2 Item Environmental characteristics Unit Noise within 1m dB Altitude m Relative humidity %RH Specifications 56.0 ≤1000, derate power by 1% per 100m between 1000m and 2000m 0 ~ 95, non condensing Operating temperature °C 0 ~ 40; battery life is halved for every 10°C increase above 20°C Storage and transport temperature for UPS °C -20 ~ 70 Recommended battery storage temperature °C -20 ~ 30 (20°C for optimum battery storage) 6.3 Mechanical Characteristics Table 6-3 Rated power (kVA) Dimensions, W × D × H Weight Mechanical characteristics Unit 30 ~ 150 mm 600 × 1100 × 2000 kg 300 Color N/A Black Protection degree, IEC(60529) N/A IP20 (front door and back door open or closed) Liebert APM Modular UPS User & Installation Manual 38 Chapter 6 Specifications 6.4 Electrical Characteristics (Input Rectifier) Table 6-4 Rectifier AC input (mains) Rated power (kVA) Unit 150 Rated AC input voltage1 Vac 380/400/415 (3-phase and sharing neutral with the bypass input) Input voltage tolerance2 Vac 305 ~ 477; 304 ~ 208 (output derated below 70%) Frequency2 Hz 50/60 (tolerance: 40Hz ~ 70Hz) Power factor kW/kVA, full load (half load) 0.99 (0.98) Input power kVA rated3 (maximum4) 30 ~ 150 Input current A rated 3 (maximum4) 60 ~ 300 Harmonic current distortion THDI% FL <3 Duration of progressive 10s to reach full ratd current (selectable 5s through 30s in s power walk-in 5-second intervals) Note: 1. Rectifiers operate at any of the rated supply voltages and frequencies without further adjustment. 2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged battery. 3. IEC62040-3/EN50091-3: at rated load and input voltage 400V, battery charged. 4. IEC62040-3/EN50091-3: at rated load and input voltage 400V, battery charging at maximum rated power 6.5 Electrical Characteristics (Intermediate DC Circuit) Table 6-5 Rated power (kVA) Battery bus voltage Number of lead-acid cells Float voltage Temperature compensation Ripple voltage Battery Vdc Intermediate DC circuit 30 60 90 120 Nominal: 432V (VRLA float charge is 540V), range: 400V ~ 616V Nominal 216 (6cells x 36 12V battery block) Maximum 240 (6cells x 40 12V battery block) Minimum 180 (6cells x 30 12V battery block) V/cell(VRLA) 2.25V/cell (selectable from 2.2V/cell to 2.3V/cell) Constant current and constant voltage charge mode mV/ /cl -3.0 (selectable from 0 to -5.0 around 25°C or 30°C, or inhibit) Unit % V float ≤1 Ripple current % C10 Boost voltage VRLA ≤5 2.35V/cell (selectable from 2.30V/cell to 2.40V/cell) Constant current and constant voltage charge mode Float-boost current trigger 0.050C10 (selectable from 0.030 to 0.070) Boost-float current trigger 0.010C10 (selectable from 0.005 to 0.025) 24hr safety time timeout (selectable from 8hr to 30hr) Boost mode inhibit also selectable 1.63V/cell (selectable from 1.60V/cell to 1.750V/cell) Automatic inverse EOD voltage × discharge current mode (the EOD voltage increases at low discharge currents) 2.4V/cell (selectable from 2.3V/cell to 2.4V/cell) Constant current and constant voltage charge mode Programmable automatic trigger or inhibit of boost mode 6 12 18 24 Boost control EOD voltage V/cell(VRLA) Battery charge V/cell 150 Battery kW 30 charging power1 max current A 11 22 33 44 55 (adjustable)2 Note: 1. At low input voltage the UPS recharge capability increases with load decrease (up to the maximum capacity indicated). 2. Max currents listed are for EOD voltage of 1.67V/cell for 240 cells Liebert APM Modular UPS User & Installation Manual Chapter 6 Specifications 6.6 Electrical Characteristics (Inverter Output) Table 6-6 Rated power (kVA) Inverter output (to critical load) Unit 30 ~ 150 Rated AC voltage1 Vac 380/400/415 (three-phase four-wire, with neutral reference to the bypass neutral) Frequency2 Hz 50/60 Overload % 110% for 60min 125% for 10min 150% for 1min >150% for 200ms Fault current % 340% current limitation for 200ms Non-linear load capability3 % 100% Neutral current capability % 170% Steady state voltage stability % ±1 (balanced load), ±2 (100% unbalanced load) Transient voltage response4 % ±5 Tatal harmonic voltage % <1 (linear load), <4 (non-linear load3) Synchronisation window Slew rate (max change rateof synchronisation frequency) Inverter voltage tolerance Rated frequency ±2Hz (selectable from ±0.5Hz to ±3Hz) Hz/s %V(ac) 1; selectable from 0.1 to 3 ±5 Note: 1. Factory set to 400V. 380 or 415V selectable by commissioning engineer. 2. Factory set to 50Hz. 60 Hz selectable by commissioning engineer. 3. EN 50091-3 (1.4.58) crest factor 3:1. 4. IEC 62040-3 / EN 50091-3 also for 0% ~ 100% ~ 0% load transient. Transient recovery time: return to within 5% of steady state output voltage within half a cycle Liebert APM Modular UPS User & Installation Manual 39 40 Chapter 6 Specifications 6.7 Electrical Characteristics (Bypass Mains Input) Table 6-7 Rated power (kVA) Rated AC voltage Bypass mains input Unit 1 Vac 30 ~ 150 380/400/415, three-phase four-wire, sharing neutral with the rectifier input and providing neutral reference to the output Rated current A 225, 380V 215, 400V 205, 415V Overload % 135% long term 170% for 10min 1000% for 100ms Upstream protection, bypass line N/A Thermomagnetic circuit breaker, rated up to 125% of nominal output current. IEC 60947-2 curve C Current rating of neutral cable A 1.7 × In Frequency2 Hz 50/60 Transfer time (between bypass and inverter) ms Synchronous transfer: ≤1ms Asynchronous transfer (default): 15ms (50Hz), 13.3ms (60Hz) Or 40ms, 60ms, 80ms, 100ms selectable %Va c Bypass voltage tolerance Upper limit: +10, +15 or +20, default: +15 Lower limit: -10, -20, -30 or –40, default: -20 (delay time to accept steady bypass voltage: 10s) Bypass frequency tolerance % ±2.5, ±5, ±10 or ±20, default: ±10 Synchronixation window Hz Rated frequency: ±2Hz (selectable fromm ±0.5Hz to ±3Hz) Note: 1. Factory set to 400V. 380V or 415V selectable by commissioning engineer. 2. Factory set to 50Hz. 60Hz selectable by commissioning engineer. 6.8 Efficiency, Heat Losses And Air Exchange Table 6-8 Efficiency, heat losses and air exchange 30 Unit Overall efficiency Rated power (kVA) 60 90 Normal mode (double conversion) % 96 ECO mode % 98 120 150 Inverter efficiency (DC/AC) (battery at nominal voltage 432Vdc and full-rated linear load) % Battery mode 96 Heat losses and air exchange Normal mode kW 1.2 2.4 3.6 4.8 6 ECO mode kW 0.6 1.2 1.8 2.4 3 No load kW 0.6 1.2 1.8 2.4 3 Maximum forced air cooling (front intake, back exhaust) L/s 48 96 144 192 239 Note: input and output voltage 400Vac battery charged, full rated linear load Liebert APM Modular UPS User & Installation Manual Appendix 1 BCB Model Selection And Connection 41 Appendix 1 BCB Model Selection And Connection Table 1 Selection reference table of BCB rated current and connection cable cross CSA Unit 30 60 90 120 150 Max battery discharge current at full load Rated power (kVA) A 105 210 315 420 525 Reference rated current of circuit breaker A 150 250 350 450 550 35 70 105 140 175 CSA of connection cable mm 2 Note : 1. In the case the battery is configured for independent wiring for positive group and negative group respectively (that is, lead four cables from battery terminals), for the UPS, due to the limitation of the rated current, it is recommended to use a 4P DC moulded-case circuit breaker (MCCB) (DC rated voltage of the breaker meeting 1-pole 250Vdc, 2-pole 500Vdc, 3-pole 750Vdc, rated breaking capacity limit being 35kA) or two 2P DC MCCBs (DC rated voltage of single breaker meeting 1-pole 250Vdc, 2-pole 500Vdc, rated breaking capacity limit being 35kA). Connections between the battery, breaker and UPS are shown in Figure 1. 2. In the case the battery is configured for center tap wiring (that is, lead three cables from battery terminals), it is recommended to use a 4P DC MCCB, with DC rated voltage of the breaker meeting 1-pole 250Vdc, 2-pole 500Vdc, 3-pole 750Vdc, and rated breaking capacity limit being 35kA. Connections between the battery, breaker and UPS are shown in Figure 2 N N − Figure 1 + N UPS + − Connections between the battery, breaker and UPS (four cables connected to battery) + N N UPS + − − Figure 2 Connections between the battery, breaker and UPS (three cables connected to battery) Liebert APM Modular UPS User & Installation Manual