Liebert® GXT4™ UPS 120V/208V 500VA-3000VA User Manual TABLE OF CONTENTS IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.1 1.3.2 Front Panel and Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4 Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.5 Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.5.1 1.5.2 1.5.3 1.5.4 1.5.5 1.5.6 Mains Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Active ECO Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.1 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2 What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.3 Preparation for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.3.1 2.4 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.4.1 2.4.2 2.5 Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.5.1 2.5.2 2.6 Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Connecting to AC Mains and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.6.1 2.6.2 Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Installing the Optional Liebert IntelliSlot® Card and Communication Cables . . . . . . . . . . . 15 3.0 OPERATION AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.1 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.2 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.3 LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.4 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 Startup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prompt List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Warning List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i 19 20 20 30 30 31 4.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 4.1 Startup Checklist for the Liebert GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.2 Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.3 Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.4 Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.5 Shut Down the Liebert GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 4.6 Disconnecting Input Power from the Liebert GXT4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 5.0 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.1 Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.1.1 5.2 Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.2.1 Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 5.3 RS-232 Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 5.4 Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 5.4.1 5.4.2 5.4.3 5.4.4 Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 37 37 37 6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.1 Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 6.2 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 6.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 6.4 Checking UPS Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 6.5 Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 7.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 7.1 UPS Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 7.1.1 7.1.2 Indicator and LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 7.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 8.0 BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 9.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 9.1 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 9.2 Technical Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 ii FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Liebert GXT4 rack/tower models—front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Rear panel components—Liebert GXT4 120V rack/tower, 500, 700, 1000VA model . . . . . . . . . . . 5 Rear panel components—Liebert GXT4 120V rack/tower, 1500VA model . . . . . . . . . . . . . . . . . . . 6 Rear panel components—Liebert GXT4 120V rack/tower, 2000VA model . . . . . . . . . . . . . . . . . . . 6 Rear panel components—Liebert GXT4 120V rack/tower, 3000VA model . . . . . . . . . . . . . . . . . . . 7 Rear panel components—Liebert GXT4 208V rack/tower, 3000VA model . . . . . . . . . . . . . . . . . . . 7 Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Rotate the operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Cable strain relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Battery cable attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Startup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Startup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Starting and Start Successful screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Main Menu screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 CONFIGURATION screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 UPS screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Battery screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 ECO Mode screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Outlet1 screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Outlet Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Outlet Setting screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Outlet2 setting screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 LCD screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Language screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Color screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Factory Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Turn UPS On or Off screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Alarm Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Batt Test screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Log screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Clear Log screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 About screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Network screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Terminal Block Communication pin layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Removing the front bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Disconnecting the battery plug and battery receptacle (front view) . . . . . . . . . . . . . . . . . . . . . . . 39 Pull out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 iii TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Input circuit breaker specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 System prompts and meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Warning list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Fault list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Output voltage option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Replacement internal battery pack model number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Description of the displayed fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Specifications of GXT4-500RT120 - GXT4-700RT120 and GXT4-1000RT120 models . . . . . . . . . 44 Specifications of GXT4-1500RT120 - GXT4-3000RT120 and GXT4-3000RT208 models . . . . . . . 45 Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 iv IMPORTANT SAFETY PRECAUTIONS ! WARNING Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not attempt to service this product yourself. Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone. SAVE THESE INSTRUCTIONS This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS. UPS Safety Notes This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass push button does not electrically isolate internal parts. Under no circumstances attempt to gain internal access other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Emerson Network Power representative or Emerson Network Power Channel Support. This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the UPS is not connected to utility input power. Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard. To ensure human safety and normal UPS operation, the UPS must be properly grounded before use. When the UPS is connected to an IT power distribution system, a short-circuit protection device must be installed on the neutral line. Install and use the Liebert GXT4 in the following environments: • Temperature: 32°F - 104°F (0°C - 40°C), relative humidity: 0% ~ 95% non-condensing • Out of direct sunlight • Away from heat sources • Stable surface, not subject to vibrations or shocks • Away from dust and other particulates • Away from corrosive substances, salts and flammable gases Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal temperature of the UPS and can adversely affect the UPS and its batteries. Keep liquid and foreign objects away from the UPS. In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may cause electric shock. This UPS is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or Emerson representative. This UPS is not for use in a computer room as defined in the standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75. The Liebert GXT4-3000RT120™ was tested under 30A branch circuit in accordance with the National Electrical Code, ANSI/NFPA 70. To reduce the risk of fire, connect only to a circuit provided with 30A maximum branch overcurrent protection. 1 Liebert® GXT4™ The Liebert GXT4-3000RT208 was tested under 20A branch circuit in accordance with the National Electrical Code, ANSI/NFPA 70. To reduce the risk of fire, connect only to a circuit provided with 20A maximum branch overcurrent protection. Battery Safety ! CAUTION Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate the batteries. Released electrolyte is toxic and is harmful to skin and eyes. Dispose of used batteries according to the instructions. ! CAUTION A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries: • Remove watches, rings and other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. • Disconnect charging source prior to connecting or disconnecting battery terminals. • Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit). ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT4 complies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense. The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson. Information for the Protection of the Environment UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers. Liebert® GXT4™ 2 GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions AC input AC output i - Requests the user to consult the manual + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage WEEE 3 Liebert® GXT4™ Product Description 1.0 PRODUCT DESCRIPTION The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The Liebert GXT4 is designed to supply microcomputers and other sensitive equipment with clean sine wave input power. Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment. The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges its batteries from utility power, enabling it to supply power to connected loads, even when utility power fails. This sections describes the UPS, its features, models, appearance and components, operating principles and operating mode. 1.1 Features • • • • • • • • • • • • 1.2 Intelligent battery management to extend the battery life LCD for user-friendly operation and local monitoring and configuration of operational parameters Controllable outlet groups Flexible network management with Liebert MultiLink™ software Fan fault self-inspection and automated diagnostic function Intelligent fan operation, automatically changing rotation speed depending on system requirements, to decrease power consumption and noise Input circuit breaker to ease recovery from overloads Safety approval from UL and cUL Communication options: USB port, Liebert IntelliSlot® port and terminal block communication Dry contacts for remote monitoring Input power factor greater than 0.99 Output voltage selection function Available Models Eight UPS models are available. Table 1 UPS models, power ratings Model Nominal Power Rating GXT4-500RT120 500VA/450W GXT4-700RT120 700VA/630W GXT4-1000RT120 1000VA/900W GXT4-1500RT120 1500VA/1350W GXT4-2000RT120 2000VA/1800W GXT4-3000RT120 3000VA/2700W GXT4-3000RT208 3000VA/2700W Liebert® GXT4™ 4 Product Description 1.3 Appearance and Components 1.3.1 Front Panel and Controls The Liebert GXT4 rack/tower models in various power ratings have the same general appearance, controls and features (see Figure 1). The various rack/tower and minitower models differ largely in the type of receptacles each has. Figure 1 Liebert GXT4 rack/tower models—front view Ventilation Slots 1.3.2 Operation and Display Panel Rear Panel Features The rear panel of the Liebert GXT4 has these features: • • • • • • • • • • • • Figure 2 Liebert IntelliSlot® Port USB port Input Circuit Breaker Input Receptacle General Output Receptacles Programmable Output Receptacles Cable Strain Relief Attachment Hole External Battery Connector Cooling Fan RS-232 port Terminal Block Communication Output Circuit Breakers (only on 3000VA models) Rear panel components—Liebert GXT4 120V rack/tower, 500, 700, 1000VA model Liebert IntelliSlot Port USB Port Terminal Block Communication RS232 Port Strain Relief Attachment Cooling Fan External Battery Connector 5 General Output Receptacle Programmable Output Receptacle Programmable Output Receptacles #1 Input Circuit Breaker Input Power Plug and Cable Liebert® GXT4™ Product Description Figure 3 Rear panel components—Liebert GXT4 120V rack/tower, 1500VA model Input Power Plug and Cable Liebert IntelliSlot Port USB Port Terminal Block RS232 Communication Port Figure 4 Input Circuit Breaker Cooling Fan External Battery Connector General Output Receptacle Strain Relief Attachment Programmable Output Receptacle #2 Programmable Output Receptacle #1 Rear panel components—Liebert GXT4 120V rack/tower, 2000VA model Input Power Plug and Cable Liebert IntelliSlot Port USB Port Terminal Block RS232 Communication Port Liebert® GXT4™ Input Circuit Breaker Cooling Fan External Battery Connector General Output Receptacle Strain Relief Attachment 6 Programmable Output Receptacle #2 Programmable Output Receptacle #1 Product Description Figure 5 Rear panel components—Liebert GXT4 120V rack/tower, 3000VA model Liebert IntelliSlot Port Terminal Block Communication Input Power Plug and Cable USB Port RS232 Port General Output Receptacle Input Circuit Breaker Cooling Fan External Battery Connector Programmable Output Receptacle #2 Programmable Output Receptacle #1 Output Output Circuit Breaker Strain Relief Attachment Figure 6 Rear panel components—Liebert GXT4 208V rack/tower, 3000VA model Input Power Plug and Cable, L6-20P Liebert IntelliSlot Port Input Circuit Breaker USB Port Terminal Block Communication Cooling Fan Output Circuit Breakers External Battery Connector Programmable Output Receptacle 1 L6-15R Programmable Output Receptacle 2 L6-15R Non-Programmable Output Receptacle 2 L6-20R 7 Liebert® GXT4™ Product Description 1.4 Major Components The operating principle of the UPS is illustrated in Figure 7. Figure 7 Operating principle diagram Dynamic Bypass L N/L2* G TVSS EMI/RFI Input Filter Rectifier/ PFC Inverter L EMI/RFI Output N/L2* Filter G Programmable Outlet Group 1 Programmable Outlet Group 2 General Outlet Group DC-DC Converter General Outlet (3000 VA Only) Battery Charger Battery * NOTE: ONLY the GXT4-3000 RT208 model (208V) requires L 2 (L6-20P). All other models covered in this manual are 120 V L-N wired The UPS is composed of utility input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output. Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters The Liebert GXT4 has surge protection and filters that protect the connected load from power surges, electromagnetic interference (EMI) and radio frequency interference (RFI). These features can minimize any surges or interference present in the utility power. The filters also prevent surges or interference generated by the UPS from adversely affecting devices connected on the same branch as the UPS. Rectifier/Power Factor Correction (PFC) Circuit In normal operation, the Liebert GXT4’s rectifier/power factor correction (PFC) circuit converts utility power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives: • Efficient power use by the UPS • Reduced reflected harmonics This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT4. Inverter In normal operation, the Liebert GXT4’s inverter utilizes the DC output of the PFC to produce precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power. Battery Charger The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT4 is plugged in, even when the UPS is not turned On. Liebert® GXT4™ 8 Product Description DC-to-DC Converter The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability. Battery The Liebert GXT4 uses valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the Liebert GXT4 in an ambient temperature of 32°F to 77°F (0°C to 25°C). Optional external battery cabinets are available to extend battery run times. Dynamic Bypass The Liebert GXT4 provides an alternate path for utility power to the connected loads in the unlikely event of a UPS malfunction. Should the Liebert GXT4 have an overload, overtemperature or UPS failure condition, the UPS automatically transfers the connected loads to bypass. NOTE The bypass power path does not protect the connected loads from disturbances on the utility. 1.5 Operating Mode The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery Recharge Mode, Active ECO Mode and Frequency Converter Mode. Refer to 9.0 - Specifications for details about the operating mode indicators and control buttons. 1.5.1 Mains Mode During Mains Mode, the mains provides input power to the Liebert GXT4. The filters, PFC circuit and inverter process this power to provide high-quality sine wave power to connected loads. The UPS maintains the batteries in a fully charged state. 1.5.2 Manual Bypass Mode Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD display menu to select 3 Control > 1 Turn On & Off > Turn UPS Bypass. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the connected load. NOTICE Risk of loss of power to the connected load. Can cause equipment damage. Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load. 9 Liebert® GXT4™ Product Description 1.5.3 Battery Mode The Liebert GXT4 enters Battery Mode when mains power fails or is outside acceptable limits. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads. When the Liebert GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable). In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt utility power not available. Press either the Up or Down button once, then press the Enter button to clear the prompt and silence the audible alarm. Once the alarm prompt has been acknowledged, the screen showing the estimated battery run time and battery capacity will be visible. Refer to 7.0 - Troubleshooting. For approximate battery run times, refer to Table 17. NOTICE Risk of loss of power to the connected load. Can cause equipment damage. Turning Off the Liebert GXT4 when it is in Battery Mode will result in loss of output power to the connected load. If the UPS is turned Off manually, it must be manually restarted after mains power returns. If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as set in the configuration program for Auto-Restart (Refer to 5.2.1 Configuration Program). 1.5.4 Battery Recharge Mode Once mains power is applied to the Liebert GXT4, the Battery Charger begins charging the batteries. 1.5.5 Frequency Converter Mode All models of the Liebert GXT4 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include: • • • • Auto Sensing - 50Hz or 60Hz – Bypass Enabled Auto Sensing - 50Hz or 60Hz – Bypass Disabled Frequency Converter - 50Hz – Bypass Disabled Frequency Converter - 60Hz – Bypass Disabled NOTE The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass Enabled.” ! CAUTION Risk of electric shock. Can cause injury or death. Never touch the AC input receptacle while the UPS is operating. Voltage may still be present even when the AC input indicator is Off. 1.5.6 Active ECO Mode All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is powered through the bypass path to increase efficiency, reducing the electrical costs. Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the acceptable parameters, the UPS will return to Active ECO Mode operation. The default setting is Active ECO Mode Off. Liebert® GXT4™ 10 Installation 2.0 INSTALLATION 2.1 Unpacking and Inspection Unpack the UPS and conduct the following checks: • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or your Emerson representative immediately. • Check the accessories included in packaging list. If there is any discrepancy, contact your local dealer or your Emerson representative immediately. 2.2 What’s Included • Terminal Block Communication Terminals • Compact Disk with: • Liebert MultiLink® Shutdown Software • Configuration Program • User Manual • USB Cable—one, 1.2m (3.9 ft.) long • RS-232 Cable—one, 2m (6-1/2 ft) long • Cable Strain Relief—two pieces • Rack mounting hardware, including screws, handles and mounting rail kit (not included with model numbers ending with an “E”) • Plastic tower stand sets—two (four pieces) • Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)) NOTE The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers for tower configuration and one DC power cable and rack mounting hardware, including screws, handles and mounting rail kit (not included with model numbers ending with an “E”). 2.3 Preparation for Installation 2.3.1 Installation Environment • Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off. The installation environment should meet the specifications listed in 9.0 - Specifications). • Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Avoid direct sunlight. NOTE Operating the Liebert GXT4 in temperatures above 77°F (25°C) reduces battery life. Installation Clearances Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT4. Do not obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT4. 11 Liebert® GXT4™ Installation 2.4 Mechanical Installation The Liebert GXT4 may be installed as a tower or in a rack, depending on space and use considerations. The Liebert GXT4 may be used alone, as a single UPS, or with up to four battery cabinets. NOTE When installing the UPS or making input and output connections, comply with all relevant safety codes and standards 2.4.1 Tower Installation To install the Liebert GXT4 as a tower: 1. Take out support bases from the accessories (see Figure 8). Figure 8 Support bases Connectors Spacers Support Bases 2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the spacers shipped with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 8. Each Liebert GXT4 needs two assembled support bases, one in the front and one in the rear. 4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4. a. Remove the front plastic bezel cover as shown in Figure 9. Figure 9 Remove the front plastic bezel cover Front Bezel Cover b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown in Figure 10. Liebert® GXT4™ 12 Installation Figure 10 Rotate the operation and display panel Rotate Operation and Display Panel 90 degrees clockwise c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 11. d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs two support assemblies, as shown in Figure 11. Figure 11 Tower installation Liebert GXT4 UPS and External Battery Cabinet Liebert GXT4 UPS Operation and Display Panel Rotated for Tower Operation Support Bases Support Bases 2.4.2 Rack Installation The Liebert GXT4 UPS and external battery cabinets (EBC), when installed in a rack enclosure, must be supported by a shelf or rack-mount rails. The Liebert GXT4 UPS and EBC units ship with all required hardware to allow rack-mount installation (not included with model numbers that end in “E”). Because different rack-mount options install differently, refer to the installation instructions provided with the rack mount kit being used. 13 Liebert® GXT4™ Installation 2.5 Cable Connection The Liebert GXT4 rear panel has an input cable and plug, output receptacles and output cable(s) (Output cables are on GXT4-3000 models only). Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet. 2.5.1 Connecting to AC Mains and Loads NOTE Ensure that all the loads are turned Off. Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded. Emerson recommends installing an upstream circuit breaker of the same series as the Liebert GXT4’s input circuit breaker. The specification of input circuit breaker on the rear panel of UPS is given in Table 2.. Table 2 Input circuit breaker specification Rated Circuit Breaker Model GXT4-500RT120 8A GXT4-700RT120 10A GXT4-1000RT120 10A GXT4-1500RT120 15A GXT4-2000RT120 20A GXT4-3000RT120 30A GXT4-3000RT208 20A Liebert GXT4 models 700-1500VA and 2000VA have three groups of outlets as shown in Figure 2. One group is always On; the other two groups may be controlled with either programmed responses or over an SNMP network. The 3000VA GXT4 UPS has four groups of outlets: two groups are not controlled (always On), and two groups may be controlled with either programmed responses or over an SNMP network. Verify that the equipment is plugged into the appropriate outlets if any outlets will be controlled with these features. 1. Plug equipment into the appropriate output receptacles on the rear of the Liebert GXT4. NOTE 1. Do not overload any output receptacle. 2. Output cable length should not exceed 10m (32.8 ft). 2. Plug the input receptacle of the Liebert GXT4 into the input power connection. 3. Install the two cable strain relief fixtures to secure either the input or output cables to prevent accidental disconnection. a. Insert one end into the provided holes on the rear of the unit. b. Place the power cord(s) inside the loop. c. Tighten the loop around the cables. Figure 12 Cable strain relief Hold the cable Liebert® GXT4™ Insert into the provided hole to secure the line buckle 14 Installation 2.5.2 Connecting Battery Cables 1. Switch Off the input breaker of the battery cabinet. 2. Take out the battery cable included with the battery cabinet. 3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet. 4. Switch On the battery breaker on the rear of the external battery cabinet. 5. Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT4. See Table 17 for approximate battery run times. Figure 13 Battery cable attachment Battery Cable Liebert GXT4 External Battery Cabinet 2.6 Connecting Communication Cables Communication cable connection includes: USB and cables for option cards. 2.6.1 Connecting USB Communication Cables 1. Take the USB communication cables out of the accessories bag. 2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert GXT4 (see Figures 2 and 1.4). 3. Insert the other end of the USB communication cable to the USB port of the computer. 2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables 1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT4 and set it aside. 2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws. 3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided with the card. To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual. Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site: www.liebert.com 15 Liebert® GXT4™ Operation and Display Panel 3.0 OPERATION AND DISPLAY PANEL This chapter describes the Liebert GXT4 controls, particularly the operation and display panel on the front of the Liebert GXT4. The panel has four control buttons, seven LED indicators and a liquid crystal display (LCD), as shown in Figure 14. Figure 14 Operation and display panel Inverter Indicator Battery Indicator Bypass Indicator Fault Indicator Programmable Outlet 1 Indicator LCD Panel Programmable Outlet 2 Indicator ECO Mode Indicator ESC Button ENTER Button UP Button 3.1 DOWN Button LED Indicators The seven LED indicators on the front of the operation and display panel are: • • • • • • • Inverter Battery Bypass Programmable Outlet1 Programmable Outlet2 ECO Mode Fault Figure 14 shows the indicators’ locations; their descriptions and functions are shown in Table 3. Table 3 LED indicators LED Indicators LED Color Description Inverter Green On when the inverter is supplying power Bypass Amber On when the load is supplied by the mains through automatic/manual bypass Battery Amber On when the load is supplied by the battery Fault Red On when an error has occurred within the UPS Programmable Outlet1 Green On when programmable Outlet1 is On Programmable Outlet2 Green On when programmable Outlet2 is On ECO Mode Green On when the UPS is in ECO Mode Liebert® GXT4™ 16 Operation and Display Panel 3.2 Control Buttons The four control buttons on the front of the operation and display panel are: • • • • ESC Up Down Enter Figure 14 shows the buttons’ locations; their descriptions and functions are shown in Table 4. Table 4 3.3 Control buttons Control Buttons Description ESC Button Pressing this button returns to the previous menu or aborts any change in the input data field before confirming. Up Button Pressing this button can move the cursor up or increase the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll up. Down Button Pressing this button can move the cursor down or decrease the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll down. Enter Button Pressing this button can enter the next level menu or confirm the parameter setting value. LCD The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating through the Liebert GXT4’s menu (see 3.4 - Menu Structure). 17 Liebert® GXT4™ Operation and Display Panel 3.4 Menu Structure The menu structure of the LCD is shown in Figure 15. Figure 15 Menu structure Audible Alarm Output Startup on Bypass Load Status UPS Battery Enable Auto Restart Time Since Startup Frequency Selection Start Windows System Status Enable Auto Shutdown Input Output Level Selection Configuration Battery Cabinets Turn UPS On/Off Turn UPS On Turn UPS Off BATT Low Battery Time Warning Batt Test Interval Main Menu Control Alarm Control 1. Audible Alarm On 2. Audible Alarm Off Batt Test 1. Start 2. Cancel 3. Batt Test Result Batt Replace Time Enable /Disable Voltage Tolerance ECO Mode View Log Frequency Tolerance Log Requalification Time Clear Log About Outlet 1 PN/SN/Firmware Version Control Setting Address: MAC Outlet 2 Address: IPV4 Network Factory Default Address: IPV6STATIC Address: IPV6AUTO Address: IPV6LINK Language LCD Color Liebert® GXT4™ 18 Turn On Turn Off Reboot Settings as Outlet1 (only Outlet2) Turn On Delay Turn Off When UPS On Battery and On Overload Turn Off When UPS On Battery for Some Time Turn On When Power Returns for Some Time Turn Off When Runtime Less Than Some Time Turn Off When Batt Capacity Less Than Some Time 1 English 2 French Operation and Display Panel 3.4.1 Startup Screen When the Liebert GXT4 is starting up, it initiates a self-test and displays the screen shown in Figure 16 for about 10 seconds. Figure 16 Startup screen EMERSON Network Power After about 10 seconds, the LCD shows one of the On screens in Figure 17; the screen shown depends on whether input power is available. Figure 17 Startup screens O/P: 0V HZ 0.0A I/P : 120 V 60HZ 0.0A BATT: 100 % 320 MINS LOAD: 0% AC NOT AVAILABLE START ON BATTERY? YES NO O/P: 0V 0HZ 0.0A I/P : 120V 60HZ 0.0A BATT: 100% 320MINS LOAD: 0% Input Power is Available Input Power is not Available TURN ON UPS YES NO To turn On the UPS, press either the Up or Down button to select YES and press the Enter button. The UPS will start up, the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is turned On, as shown in Figure 18. Figure 18 Starting and Start Successful screens UPS STARTING START SUCCESSFUL O/P: 0V 0HZ 0.0A I/P : 120V 60HZ 0.0A BATT: 100% 320MINS LOAD: 0% O/P: 120V 60HZ 4.6A I/P : 120V 60HZ 5.0A BATT: 100% 15MINS LOAD: 40% 19 Liebert® GXT4™ Operation and Display Panel 3.4.2 Default Screen Press any button in the START SUCCESSFUL screen to enter the default interface, shown in Figure 19. Figure 19 Default screen GXT4-UPS 3KVA Values shown will vary according to installation and configuration. O/P: 120V 60HZ 11.7A I /P: 120V 60HZ 13.1A BATT: 100 % 3MINS LOAD: 100% In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery capacity with run time estimate and load percentage. The UPS operation mode (online /inverter, ECO, Battery or Bypass) will be indicated by the LED indicators. If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen saver mode (backlight turns off). It will remain off until a control button is pressed. 3.4.3 Main Menu Screen Press the Enter button in the default screen to enter the MAIN MENU screen, as shown in Figure 20. Figure 20 Main Menu screen 1 2 3 4 5 6 STATUS CONFIGURATION CONTROL LOG ABOUT NETWORK To select a submenu, press the Up or Down button to move the cursor to the required item, then press the Enter button to enter its submenu or set its parameter. Liebert® GXT4™ 20 Operation and Display Panel STATUS Screen In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD, INPUT, BATTERY and TIME SINCE STARTUP, as shown in Figure 21. Figure 21 Status screens OUTPUT LOAD VOLTAGE : 120V FREQUENCY : 60HZ CURRENT : 17.6A POWER : 2112 KWH CAP : WATT : VA : INPUT VOLT FREQ CURR POWER 90% 1620W 1800VA : : : : 120V 60 HZ 18.6A 97KWH BATTERY TIME SINCE STARTUP CAPACITY : RUNTIME : VOLTAGE : 90% 100 MINS 80V 05D 15H 30M CONFIGURATION Screen Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven submenus, as shown in Figure 22. Figure 22 CONFIGURATION screen 1. 2. 3. 4. 5. 6. 7. UPS BATTERY ECO MODE OUTLET 1 OUTLET2 LCD FACTORY DEFAULT In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required item, then press the Enter button to enter a submenu or set its parameters. 21 Liebert® GXT4™ Operation and Display Panel UPS Screen Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens, as shown in Figure 23. Figure 23 UPS screens AUDIBLE ALARM STARTUP ON BYPASS GUARANTEE SHUTDOWN OFF NO NO ENABLE AUTO RESTART FREQUENCY SELECTION VOLTAGE SELECTION YES AUTO - BYPASS ENABLE 230 Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Battery Screen Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu has four screens, as shown in Figure 24. Figure 24 Battery screen EXT BATT CABINET 0 LOW BATTERY TIME CABINETS 2 BATT TEST INTERVAL 8 MINS BATT REPLACE TIME WEEKS 2014 Y 1M 1D Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button to confirm it. Liebert® GXT4™ 22 Operation and Display Panel ECO Mode Screens Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens, as shown in Figure 25. Figure 25 ECO Mode screen ECO MODE VOLTAGE TOLERANCE ON 10% FREQUENCY TOLERANCE REQUALIFICATION TIME 3 Hz 5 MINS Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Outlet1 Screen Select MAIN MENU > 2 CONFIGURATION > 4 OUTLET1 to enter the OUTLET1 screen. This menu has two submenus, as shown in Figure 26. Figure 26 Outlet1 screen OUTLET1 1 OUTLET CONTROL 2 OUTLET SETTING 23 Liebert® GXT4™ Operation and Display Panel Select 1 OUTLET CONTROL and press the Enter button to enter the OUTLET CONTROL screen, as shown in Figure 27. Figure 27 Outlet Control screen OUTLET CONTROL OUTLET CONTROL TURN OFF REBOOT TURN ON Outlet Control is On Outlet Control is Off Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Select 2 Outlet Setting and press the Enter button to enter the OUTLET SETTING screen, as shown in Figure 28. Figure 28 Outlet Setting screen TURN ON DELAY TURN OFF WHEN UPS ON OVERLOAD AND ON BATTERY 0 MINS NO TURN OFF WHEN RUNTIME LESS THAN OFF TURN ON WHEN POWER RETURNS: 0 MINS TURN OFF WHEN UPS ON BATTERY FOR OFF TURN ON WHEN POWER RETURNS: 0 MINS TURN OFF WHEN BATT CAPACITY LESS THAN OFF TURN ON WHEN POWER RETURNS: 0 MINS Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Liebert® GXT4™ 24 Operation and Display Panel Outlet2 Screen The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, the Liebert GXT4 offers a programming shortcut, as shown in Figure 29. When configuring the Outlet2 group, the select YES and press the Enter button to apply the Outlet1 settings to the Outlet2 screen. Figure 29 Outlet2 setting screen APPLY THE SAME SETTINGS AS OUTLET1 YES NO LCD screen Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two submenus, LANGUAGE and COLOR, as shown in Figure 30. Figure 30 LCD screen 1 LANGUAGE 2 COLOR Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen, as shown in Figure 31. The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages and instructions on how to upload them, refer to the Configuration Program user manual on the included CD. Figure 31 Language screen 1 English 2 25 Liebert® GXT4™ Operation and Display Panel Select ‘2 COLOR’ and press the Enter button to enter the COLOR screen, as shown in Figure 32. Figure 32 Color screen EMERSON EMERSON EMERSON EMERSON FACTORY DEFAULT screen Select MAIN MENU -> 2 CONFIGURATION -> 7 FACTORY DEFAULT to enter the FACTORY DEFAULT screen, as shown in Figure 33. Figure 33 Factory Default screen RESET ALL SETTINGS TO FACTORY DEFAULT SETTINGS? YES NO Control Screen Select MAIN MENU -> 3 CONTROL to enter the CONTROL screen. This screen has three submenus, TURN ON & OFF, ALARM CONTROL and BATT TEST, as shown in Figure 34. Figure 34 Control screen 1 TURN ON & OFF 2 ALARM CONTROL 3 BATT TEST In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press the Enter button to enter its submenu. Liebert® GXT4™ 26 Operation and Display Panel TURN ON & OFF screen Select MAIN MENU -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen. This screen shows one of two displays, TURN ON UPS and TURN OFF UPS, depending on the state of the UPS, as shown in Figure 35. Figure 35 Turn UPS On or Off screen TURN OFF UPS TURN ON UPS BYPASS TURN ON UPS UPS is Off UPS is On ALARM CONTROL screen Select MAIN MENU -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen, as shown in Figure 36. This section allows active audible alarms to be silenced. To completely turn off the audible alarm, refer to CONFIGURATION > UPS as shown in Figure 23. Figure 36 Alarm Control screen 1 AUDIBLE ALARM ON 2 AUDIBLE ALARM OFF BATT TEST screen Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in Figure 37. Figure 37 Batt Test screen 1 START 2 CANCEL 3 BATT TEST RESULT 27 Liebert® GXT4™ Operation and Display Panel Log Screen Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, VIEW LOG and CLEAR LOG, as shown in Figure 38. Figure 38 Log screens 254 /255 1 VIEW LOG 2 CLEAR LOG 255 OD 1H 17m AGO UPS switch to Online mode CLEAR LOG Screen Select MAIN MENU > LOG > CLEAR LOG to enter the CLEAR LOG screen, as shown in Figure 39. Figure 39 Clear Log screen DO YOU WANT TO CLEAR EVENT LOGS? YES NO Press the Up or Down button to move the cursor to the required item. Press the Enter button to confirm the settings. ABOUT Screen Select MAIN MENU> ABOUT to enter the ABOUT screen, as shown in Figure 40. The ABOUT screen displays UPS model, serial number, software version and hardware version. Figure 40 About screen PN: GXT4-2000 RT230 SN:1XXX60XXX1AFCXX FW VER: U100D100 HW VER: H100 Liebert® GXT4™ 28 Operation and Display Panel Network Select MAIN MENU>NETWORK to enter the NETWORK screen. The NETWORK screen displays the MAC address and the IPv4 IP address. If the Liebert GXT4 is fitted with an optional Liebert IntelliSlot® Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP address settings (IPv6 requires configuration), as shown in Figure 41. Figure 41 Network screens ADDRESS MAC ADDRESS IPV4 ADDRESS IPV6 STATIC 00-02-11-4X-AX 10.163.226 .231 /24 :: ADDRESS IPV6 LINK ADDRESS IPV6 AUTO Fe80::202:99ff:fe0f:4ba 2%1 :: 29 Liebert® GXT4™ Operation and Display Panel 3.4.4 Prompt List A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command or other operation. See Table 5 for the prompts and meanings. Table 5 3.4.5 System prompts and meanings Prompt Meanings Mains Power Restored The mains power returns and the UPS transfers back to mains (AC) mode. UPS Return From A Low Battery Condition The UPS transfers back to mains (AC) mode from battery low mode. UPS Return From Battery Mode The UPS transfers back to mains (AC) mode from battery mode. UPS Self Test Successful The UPS self-test is successfully performed. UPS Shutdown Command Received The UPS shut down was initiated through communication. UPS Turn Off The UPS shuts down and has no output power. UPS Turn On The UPS starts up successfully and supplies protected power to the load. UPS Shutdown Process Had Been Cancelled The shutdown command sent through Liebert MultiLink or SNMP card to the UPS is canceled, ECO Mode Enabled The UPS is configured to ECO mode operation, ECO Mode Disabled The UPS is configured to Online mode, supplying protected power to the load through the inverter. UPS Internal Temperature Return To Normal The internal temperature of the UPS recovers to normal range. UPS Load Return From Overload The loads are reduced, and the UPS recovers to normal state from overload. Load On Inverter The inverter is on and supplies protected power to the load. Load On ECO Bypass The UPS is on ECO mode; the mains is supplying power to the load directly to reduce energy usage. OUTLET1 Closed Auto / Manual The programmable output receptacle 1 received a turn-off command and is turned Off. OUTLET1 Open Auto / Manual The programmable output receptacle 1 received a Turn-On command and is turned On OUTLET2 Closed Auto / Manual The programmable output receptacle 2 received a Turn-Off command and is turned Off. OUTLET2 Open Auto / Manual The programmable output receptacle 2 received a turn-on command and is turned On. Bypass Power Restored The bypass power recovered and the UPS can now transfer to bypass. Warning List All UPS warning messages are described in Table 6. Table 6 Warning list Warning Description Mains Power Not Available The mains power is not available, or it cannot satisfy the input requirements for the UPS to operate from mains power UPS Batteries Low And Exhausted Soon The battery capacity is low and will be exhausted soon UPS Has Switched To Battery Mode The mains power is abnormal or the PFC side is faulty, the UPS transfers back to Battery mode Load On Bypass The UPS transfers to Bypass mode, at this point, the input mains power supplies power to the load directly, and the load is not protected Input Power Wiring Error L-N line reverse or PE not connected. Bypass Power Not Available The bypass power is not available, or it cannot satisfy the requirements for the UPS transfers to bypass UPS Maintenance Bypass Output The UPS transfers to maintenance bypass. Liebert® GXT4™ 30 Operation and Display Panel 3.4.6 Fault List All UPS fault messages are described in Table 7. Table 7 Fault list Fault Description UPS Self-Test Failed The battery is bad or weak or not connected. UPS Overload The UPS is overloaded. Inverter Out Of Order The inverter has failed. Battery Weak/Bad The battery is bad or weak. Output Short Circuit The output connection is short-circuited. DC Bus Overvoltage The DC bus is faulty. UPS Overtemperature Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode. Charger Out Of Order The charger has failed. Fan Out Of Order At least one fan is failed. DC Bus Discharge Fail DC-DC failure occurs. Rectifier Out Of Order Rectifier failure occurs. If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be maintained only in the case of a battery disconnection fault. The fault message alternates with UPS Mode once a second, the red fault indicator on the operation and display panel lights up and the alarm sounds continuously. If a fault occurs: 1. Enter the ALARM CONTROL screen (see Figure 36), and select AUDIBLE ALARM ON or AUDIBLE ALARM OFF to switch the alarm On or Off. 2. Enter the EVENT LOG screen (see Figure 38), and select VIEW LOG to view the entire Event log. NOTE There will be a short delay before the EVENT LOG screen displays the historical fault log to allow the log to load. 31 Liebert® GXT4™ Operation 4.0 OPERATION This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS. NOTE The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service. 4.1 Startup Checklist for the Liebert GXT4 Before starting the UPS, perform these checks: ___ 1. Check that the input plugs and loads are connected properly and reliably. ___ 2. Check that the battery cable is connected properly. ___ 3. Check that the communication cables are connected properly. 4.2 Starting the UPS 1. Plug the UPS into the appropriate AC outlet. 2. 3000VA models only: Close the input breaker on the rear of the unit. 3. The UPS will begin the startup sequence once AC power is present. The UPS will sound an audible alarm, this is normal. 4. On the LCD, press either the Up or Down button once, then press the Enter button to turn On the UPS. The UPS will sound the audible alarm again as the output receptacles are now being powered by the internal bypass, then will sound one more time as the inverter powers the connected equipment. 5. Check the LCD and LED indicators to ensure that the UPS is operating normally. 6. Check the load percentage on the default screen to ensure that the connected equipment is not exceeding the UPS’s rated capacity. The UPS is now providing conditioned and protected power to the connected equipment. 4.3 Manual Battery Test To initiate a manual battery test, select MAIN MENU > CONTROL>BATT TEST>START. • If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours. • Retest the batteries after 24 hours of charging. • After the batteries have been retested, if the battery test still shows FAILED, contact your local Emerson® representative or Emerson Network Power Channel Support. 4.4 Manual Bypass To manually transfer the connected equipment to the internal bypass: 1. From the main menu select Control then press enter. 2. Select TURN ON & OFF and press Enter. 3. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of input power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting.) Liebert® GXT4™ 32 Operation 4.5 Shut Down the Liebert GXT4 To shut down the UPS from the LCD: 1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF. 2. Press the Enter key. 3. Select TURN UPS OFF, then press Enter. Press either the Up or Down button to move the cursor to confirm the turn off command and press Enter. The UPS will sound an audible alarm; this is normal. 4. Power to the connected equipment is now Off. The UPS display will still be illuminated because the batteries are still being charged. The UPS may now be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds. 4.6 Disconnecting Input Power from the Liebert GXT4 1. After the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert GXT4, disconnect the input cable from the wall socket. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete. 3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet. After powering Off the UPS, the UPS ceases output and the load is powered Off. 33 Liebert® GXT4™ Communication 5.0 COMMUNICATION This section describes the four types of communication ports on the rear of the UPS: • • • • Liebert IntelliSlot® port USB port (standard B-type) Terminal Block Communication RS232 port (DB9F) ! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables. 5.1 Liebert IntelliSlot Communication Cards The Liebert IntelliSlot port accepts four optional cards: • • • • Liebert IntelliSlot Web Card (IS-WEBCARD) Liebert IntelliSlot Relay Card (IS-RELAY) Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) Liebert IntelliSlot Unity Card (IS-UNITY-DP) The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network. The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for Liebert MultiLink® shutdown software. The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that have Liebert MultiLink installed. The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external temperature, humidity and contact closure inputs using external sensors. (The Liebert IS-UNITY-DP compatibility will be a future release, contact your Emerson sales representative for availability.) Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT4. These instructions are available at: multilink.liebert.com 5.1.1 Liebert MultiLink Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS. Liebert MultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via terminal block or over the network via SNMP using the Liebert IS-WEBCARD. An optional Liebert MultiLink license kit permits shutting down multiple computers that are protected by the UPS. For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert MultiLink License Kits, visit the Liebert Web site (www.liebert.com) or contact your local Emerson® representative. 5.2 USB Port Communication The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink®. A standard B-type USB port is provided to allow connection to a computer or network server. The USB port can be used to communicate with the Liebert GXT4 configuration program (see section5.2.1 - Configuration Program for details) or Liebert MultiLink (refer to 5.1.1 - Liebert MultiLink for description) that is provided on the CD that is included with the UPS. Liebert® GXT4™ 34 Communication 5.2.1 Configuration Program The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration setting changes from the LCD panel. The configuration program communicates to a computer running a Microsoft® Windows® operating system via the included USB cable. For most users, the factory default settings are adequate. This section give a brief overview of the features and parameters that are available for modification, as well as the factory default settings. Should any changes be necessary, refer to the Configuration Program User Manual that is located on the included CD for further details. The configuration program allows these features of the Liebert GXT4 to be changed: • Change and set the display language • Enable/Disable Auto-Restart (default is Enable) • Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled (default is Auto-Select with bypass enabled) • Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes) • Enable/Disable the Auto-Battery test (default is Enable) • Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable) • Set the wiring mode of Remote shutdown (default is normally open) • Set the Auto-Enable output after remote shutdown (default is Disable) • Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks) • Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Emerson® software products (default is zero) • Select one of multiple output voltages to match various voltages (see Table 8). Table 8 Output voltage option UPS Model Factory Default, VAC Output Voltage Option, VAC GXT4-500RT120 - GXT4-3000RT120 120 110, 115, 120 and 127 GXT4-3000RT208 208 208 / 220 / 230 / 240 NOTICE The output voltage settings cannot be changed while the UPS is On and powering connected loads. NOTE • Setting the output voltage of the Liebert GXT4-500RT120, GXT4-700RT120, and GXT4-1000RT120 models to 110VAC automatically derates both the VA and Watt ratings to 95% of the unit’s rating. • Setting the output voltage of the Liebert GXT4-1500RT120 and GXT4-2000RT120 models to 110VAC automatically derates both the VA and Watt ratings to 85% of the unit’s ratings, and programming the output voltage to 115VAC automatically derates both the VA and Watt ratings to 95% of the unit’s rating. • Setting the output voltage of the Liebert GXT4-3000RT120 model to 110VAC automatically derates both the VA and Watt ratings to 90% of the unit’s ratings (refer to 9.0 Specifications for the VA and Watt ratings). NOTE • This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS. • A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or Windows 8 is required to set up and run the configuration program. 35 Liebert® GXT4™ Communication 5.3 RS-232 Port The RS-232 port uses an Emerson® proprietary protocol that is for use with Liebert MultiLink®. This port enables a more secure connection instead of the USB cable, to the computer or server that has Liebert MultiLink installed. 5.4 Terminal Block Communication The Terminal Block includes eight pins, as shown in Figure 42. Figure 42 Terminal Block Communication pin layout 5.4.1 1 2 Any Mode Shutdown 3 4 Battery Mode Shutdown 5 6 On Battery Mode 7 8 Low Battery Any Mode Shutdown The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads. Any Mode Shutdown can be operated locally or remotely: • Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2. • Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and mounted at a remote location. NOTE Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings in the configuration program. A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS. The connection to the UPS for remote connection will be via terminal block connector. Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations. ! WARNING When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the Liebert GXT4’s output can turn On automatically and without warning if the Pin 1 and Pin 2 connection is changed. Liebert® GXT4™ 36 Communication 5.4.2 Battery Mode Shutdown Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active. Battery Mode Shutdown can be performed locally or remotely: • Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4. • Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and mounted at remote location. NOTE Remote Power Off will be performed by NO contact. A current-limited source (+12VDC, 50mA) will be available from UPS. The connection to the Liebert GXT4 for remote connection will be via terminal block connector. Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws. This signal must last for 1.5 seconds or longer. A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the mains power returns during this countdown, the Liebert GXT4 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting. 5.4.3 On Battery On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed. 5.4.4 Low Battery Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed. NOTE The rated values for the dry contacts for the On Battery and Low Battery signals are: • Rated Voltage: 30V (AC or DC) • Rated Current: 300mA 37 Liebert® GXT4™ Maintenance 6.0 MAINTENANCE This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s status and checking UPS functions. ! WARNING The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the battery pack: • Remove rings, watches and other metal objects. • Use tools with insulated handles. • Do not lay tools or other metal objects on the batteries. • If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson representative immediately. • Do not dispose of batteries in a fire. The batteries may explode. • Handle, transport and recycle batteries in accordance with local regulations. 6.1 Replacing the Internal Battery Pack The Liebert GXT4 is designed to allow the user to replace the internal battery pack safely. Refer to Table 9 for internal battery pack part numbers for Liebert GXT4 UPS: Table 9 Replacement internal battery pack model number Replacement Internal Battery Pack Model Number Quantity Required Liebert GXT4-500RT120 GXT4-5A48BATKIT 1 Liebert GXT4-700RT120 GXT4-5A48BATKIT 1 Liebert GXT4-1000RT120 GXT4-5A48BATKIT 1 Liebert GXT4-1500RT120 GXT4-9A48BATKIT 1 Liebert GXT4-2000RT120 GXT4-9A48BATKIT 1 Liebert GXT4-3000RT120 GXT4-9A72BATKIT 1 Liebert GXT4-3000RT208 GXT4-9A72BATKIT 1 UPS Model Number Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or Emerson representative to obtain the pricing of the appropriate replacement battery pack. ! CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions. Liebert® GXT4™ 38 Maintenance 6.1.1 Battery Replacement Procedures 1. Remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 43. 3. Lay the battery door and screws aside for reassembly. Figure 43 Removing the front bezel cover and battery door 4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in Figure 44. Figure 44 Disconnecting the battery plug and battery receptacle (front view) Battery Connector Battery Receptacle 5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in Figure 45. Figure 45 Pull out the battery Internal Battery Pack Battery Handle Pull Out with Battery Handle 39 Liebert® GXT4™ Maintenance 6. Unpack the new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery pack to make sure they are the same type and model. If so, proceed with Step 7; if they are different, stop and contact your local Emerson representative, or Emerson Channel Support. 7. Line up and slide in the new internal battery pack. 8. Reconnect the battery plug and battery receptacle 9. Push the battery wire and internal battery pack back into the UPS. 10. Reattach the front battery door with the six screws. 11. Reattach the front plastic bezel cover to the UPS. NOTE The internal battery pack is hot-swappable. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages. Do not replace the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will drop the connected load. 6.2 Battery Charging The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT4 charges the batteries continuously when it is connected to the utility input power. If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries. 6.3 Precautions Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions: • • • • 6.4 Turn Off and unplug the Liebert GXT4 before cleaning it. Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners. Never block or insert any objects into the ventilation holes or other openings of the Liebert GXT4. Do not place the Liebert GXT4 power cord where it might be damaged. Checking UPS Status Emerson recommends checking the UPS operation status every six months. • Check if the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm? • Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal Mode; if it is operating in Bypass Mode, stop and contact your local Emerson representative or Emerson Channel Support. • Check if the battery is discharging: When the utility input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel Support. 6.5 Checking UPS Functions NOTE UPS function check procedures may interrupt power supply to the connected load. Emerson recommends checking the UPS functions once every six months. Back up the load data before conducting the UPS functions check. Procedures are as follows: 1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal. 2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are On and the UPS is operating normally. 3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode; the UPS should initiate battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your local Emerson representative or Emerson Channel Support. Liebert® GXT4™ 40 Troubleshooting 7.0 TROUBLESHOOTING This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation. 7.1 UPS Symptoms The following symptoms indicate the Liebert GXT4 is malfunctioning: • The relative indicators illuminate, indicating the UPS has detected a problem. • An alarm buzzer sounds, alerting the user that the UPS requires attention. 7.1.1 Indicator and LCD In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on the LCD is described in Table 10 Table 10 Description of the displayed fault Displayed Fault Cause Corrective Steps UPS self test failed The battery is bad or weak. Contact customer service. UPS shutdown command received The UPS shuts down through communication. Contact customer service. UPS overload The UPS is overloaded. Reduce the load and contact customer service. Inverter Out of Order The inverter is faulty. Contact customer service. Battery Weak/Bad The battery is bad or weak. Replace the battery. Output Short Circuit The output connection is short-circuited. Shut down the equipment and contact customer service. DC Bus Overvoltage The DC bus is faulty. Contact customer service. UPS Overtemperature Over-temperature occurs to the UPS and the UPS will transfer to Bypass mode. Reduce the load and contact customer service. Charger Out of Order The charger is faulty. Contact customer service. Fan Out of Order At least one fan is faulty. Contact customer service. DC Bus Discharge Fail A DC-DC failure occurs. Contact customer service. NOTE If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD backlight will flash (on 1 second and off 1 second) as an alert. Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD backlight will flash again until the UPS fault is corrected. 41 Liebert® GXT4™ Troubleshooting 7.1.2 Audible Alarm An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 11. Table 11 Audible alarm description Condition Alarm Battery discharge Half-second beep every 10 seconds Low battery Two half-second beeps every 5 seconds UPS fault, load on bypass 1-second beep every 4 seconds UPS fault, no power to load Continuous Overload Half-second beep every half second Battery replacement 2-second beep every 2 minutes Battery loss Continuous Wiring problem (loss of proper grounding for UPS) Continuous Bypass reminder 1-second beep every 60 seconds 7.2 Troubleshooting In the event of an issue with the UPS, refer to Table 12 to determine the cause and solution. If the fault persists, contact Emerson® Channel Support. Table 12 Troubleshooting table Problem UPS fails to start Cause Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally. Batteries are not charged enough or not connected Check to ensure the internal battery is connected. If it is not, make the connection and try to start the unit. If the battery is connected, leave the UPS connected to input power for 24 hours to recharge batteries, then try to start the unit. UPS is not plugged in UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle. Battery indicator UPS input protection fuse has is illuminated blown/opened UPS has reduced battery backup time Solution UPS is short-circuited or overloaded UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS. Mains power is out of tolerance UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS. Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries. UPS is overloaded Check load level indicator and reduce the load on the UPS. Batteries may not be able to hold a full charge due to age Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit. Battery indicator Battery source is not available; is flashing. continuous horn. Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed. Because the voltage or Bypass indicator frequency is outside acceptable is flashing. limits, the bypass is disabled. The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable. When reporting a UPS issue to Emerson, include the UPS model and serial number. These are located in several places for your ease of location: on the top panel (rack mount orientation); the left side (tower orientation); the rear panel; on the front of the unit behind the front plastic bezel; and on the LCD select Main Menu > About. Liebert® GXT4™ 42 Battery Cabinet 8.0 BATTERY CABINET Optional battery cabinets are available for the Liebert GXT4. The battery connectors and input breaker are on the battery cabinet’s rear panel, as shown in Figure 46. For battery cabinet specifications, refer to Table 15. The Liebert GXT4 may be equipped with a maximum of six extension battery packs. For battery run times, refer to Table 17. Figure 46 Battery cabinet Isolation Breaker Battery Connectors ! WARNING Do not contact the battery connectors and ground without wearing protective gloves and clothing and taking other precautions against electrical shock. The battery loop and AC input are not insulated, which may cause a dangerous voltage between the battery connectors and ground. NOTE External Battery Connectors are wired in parallel. Either connector can be connected to the UPS or to another battery cabinet. NOTE The standard battery cable delivered with the battery cabinet is 0.65m (2.13ft) long 43 Liebert® GXT4™ Specifications 9.0 SPECIFICATIONS Table 13 Specifications of GXT4-500RT120 - GXT4-700RT120 and GXT4-1000RT120 models Product Model GXT4-500RT120 (500VA/450W) Parameters GXT4-700RT120 (700VA/630W) GXT4-1000RT120 (1000VA/900W) Dimensions, D × W × H, in. (mm) Unit 16.2 x 16.9 x 3.4 (408 x 430 x 85) Shipping 25.5 x 23.9 x 10.6 (647 x 607 x 270) Weight, lb (kg) Unit 40 (18.2) Shipping 47 (21.4) Input AC Voltage Range (typical) 120VAC nominal; variable based on output load 90% ~ 100% loading 90VAC/140VAC 70% ~ 90% loading 86VAC/140VAC 30% ~ 70% loading 77VAC/140VAC 0 ~ 30% loading 60VAC/140VAC Frequency 40Hz ~ 70Hz; Auto Sensing Input Power Cord 10 ft. attached w/ NEMA 5-15P plug Output AC Output Receptacles Voltage 5-15R × 6 110/115/120VAC (user-configurable); ±3% Waveform Utility (AC) Mode Overload Sine wave 200% for 2 seconds; 150% for 50 seconds with transfer to bypass Battery Type Valve-regulated, nonspillable, lead acid Qty × V× Rating Battery Mfr./Part # 4 × 12V × 5.0Ah YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245 Backup Time Recharge Time See Table 17 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only) Environmental Requirements Operating Temperature, °F (°C) 32 to 104 (0 to 40); see Table 16 - Operating temperature parameters Storage Temperature, °F (°C) 5ºF to 122ºF (-15ºC to 50ºC) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating Storage Elevation Audible Noise 50,000 ft. (15000m) maximum <43dBA max @ 3ft. (1m) front and sides <46dBA max @ 3ft. (1m) rear < 50 dBA, at 3ft. (1m) rear < 45 dBA, at 3ft. (1m) front and sides Agency Safety UL 1778, cUL Listed RFI/EMI Liebert® GXT4™ FCC Class A Surge Immunity IEC 62040-2 2nd Ed Transportation ISTA Procedure 1A 44 Specifications Table 14 Specifications of GXT4-1500RT120 - GXT4-3000RT120 and GXT4-3000RT208 models Product Model GXT4-1500RT120 (1500VA/1350W) Parameters GXT4-2000RT120 GXT4-3000RT120 (2000VA/1800W) (3000VA/2700W) GXT4-3000RT208 (3000VA/2700W) Dimensions, D × W × H, in. (mm) Unit Shipping 19.7 x 16.9 x 3.4 (497 × 430 × 85) 25.5 x 23.9 x 10.6 (647 x 607 x 270) 23.7 x 16.9 x 3.4 (602 × 430 × 85) 29.4 x 23.4 x 10.6 (747 x 607 x 270) Weight, lb. (kg) Unit Shipping 54.6 (24.8) 69.6 (31.6) 56.1 (25.5) 70.5 (32) 71.4 (32.4) 86 (39) Input AC Voltage Range (typical) 120VAC nominal; variable based on output load 90 - 100% loading 70 - 90% loading 30 - 70% loading 0 - 30% loading Frequency Input Power Cord 10 ft. attached w/ NEMA 5-15P plug 102VAC/140VAC 96VAC/140VAC 84VAC/140VAC 60VAC/140VAC 40 - 70Hz; Auto Sensing 10 ft. attached w/ 10 ft. attached w/ NEMA 5-20P plug NEMA L5-30P plug 208VAC nominal; variable based on output load 177VAC/280VAC 168VAC/280VAC 150VAC/280VAC 115VAC/280VAC 10 ft. attached w/ NEMA L6-20P plug Output AC Output Receptacles Voltage 5-15R × 6 5-20R × 6 L6-20R×1+L6-15R×2 208/220/230/240 VAC (user-configurable); ±3% 110/115/120VAC (user-configurable); ±3% Waveform Utility (AC) Mode Overload L530R×1+5-20R×6 Sine wave 200% for 2 seconds 150% for 50 seconds 200% for 2 seconds 150% for 10 seconds Battery Type Qty×V×Rating Battery Mfr./Part # Backup Time Recharge Time to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only) Environmental Operating Temperature, °F (°C) Storage Temperature, °F (°C) Relative Humidity Operating Elevation Valve-regulated, nonspillable, lead acid 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah 6 × 12V × 9.0Ah Panasonic/UP- RW1245; CSB/HR 1234W F2; CSB UPS12460F2 See Table 17 4 Hours 3 Hours +32 to +104 (0 to 40); see Table 16 - Operating temperature parameters 5 to +122 (-15 to 50) 0% to 95%, non-condensing Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating Storage Elevation 50,000 ft. (15000m) maximum < 45dBA at 3ft (1m) rear Audible Noise < 46 dBA at 3ft. (1m) front and side <48dBA max @ 3ft (1m) front and side <48dBA max @ 3ft. (1m) rear Agency Safety RFI/EMI Surge Immunity Transportation UL 1778, c-UL Listed FCC Class A IEC 62040-2 2nd Ed ISTA Procedure 1A 45 Liebert® GXT4™ Specifications Table 15 Battery cabinet specifications Model Number Parameter GXT4-48VBATT GXT4-72VBATT Used w/UPS Model GXT4-500RT120,GXT4-700RT120 GXT4-1000RT120,GXT4-1500RT120, GXT4-2000RT120 GXT4-3000RT120 GXT4-3000RT208 Unit 19.7 x 16.9 x 3.3 (497 × 430 × 85) 23.7 x 16.9 x 3.3 (602 × 430 × 85) Shipping 24.3 x 22.4 x 10.3 (617 x 570 x 262) 28.2 x 22.4 x 10.3 (717 x 570 x 262) 57.3 (26) 83.8 (38) 86 (39) 110 (50) Dimensions, D × W × H, in (mm) Weight, lb (kg) Unit Shipping Battery parameters Type Qty × V× Rating Battery Mfr./Part # Valve-regulated, nonspillable, lead acid 2 × 4 × 12V × 9.0Ah 2 × 6 × 12V × 9.0Ah Panasonic/UP-RW1245; CSB/HR 1234W F2; CSB UPS12460F2 Backup Time See Table 17 Environmental Operating Temperature, °F (°C) Storage Temperature, °F (°C) 32 to 104 (0 to 40) 19 to 122 (-15 to 50) High ambient temperatures will reduce battery life. Relative Humidity Operating Elevation 0% to 95%, non-condensing Up to 10,000 ft. (3000m) at 104ºF (40ºC) without derating Storage Elevation 50,000 ft. (15000m) maximum Agency Safety UL 1778, c-UL Listed RFI/EMI Table 16 FCC Class A Surge Immunity IEC 62040-2 2nd Ed Transportation ISTA Procedure 1A Operating temperature parameters Ambient Temperature, °C (°F) Maximum Output Power Factor Derating @ Maximum Load Liebert® GXT4™ 25-30 (77-86) 30-35 (86-95) 35 - 40 (95-104) 100%-93% 93%-86% 86%-79% 46 Specifications Table 17 Battery run times Number of External Battery Cabinets Internal Battery Internal Battery + 1 External Battery Cabinet Internal Battery + 2 External Battery Cabinets Internal Battery + 3 External Battery Cabinets 208VAC RT Model 120VAC RT Models Load Percent of Capacity 500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA 10% 128 105 90 123 92 82 92 20% 82 61 37 52 38 38 39 30% 41 37 30 34 23 23 23 40% 38 32 23 23 16 16 16 50% 34 27 17 18 12 12 11 60% 31 22 14 14 9 9 9 70% 27 18 11 11 7 7 7 80% 23 15 9 9 5 5 5 90% 20 13 8 7 4 4 4 100% 17 11 7 6 3 3 3 10% 448 426 332 335 303 224 303 20% 329 302 165 162 140 137 139 30% 223 163 137 129 96 95 95 40% 166 144 108 96 66 66 65 50% 153 125 92 72 49 49 48 60% 139 106 74 54 38 41 41 70% 125 94 61 46 33 34 34 80% 108 78 49 38 28 27 27 90% 100 69 40 34 23 23 25 100% 92 60 38 31 20 21 21 10% 480 480 456 451 431 427 431 20% 454 433 331 318 207 202 205 30% 429 327 222 187 150 149 149 40% 333 265 166 151 124 124 123 50% 309 201 152 131 97 98 97 60% 225 164 137 107 75 76 75 70% 201 153 122 91 61 62 62 80% 166 142 105 74 50 50 50 90% 159 131 95 64 41 45 46 100% 151 120 79 53 38 41 41 10% 480 480 480 480 455 452 455 20% 480 461 441 426 326 323 325 30% 458 438 336 312 197 196 195 40% 442 344 305 198 155 155 154 50% 426 322 209 160 136 136 135 60% 338 300 167 145 111 112 112 70% 322 213 157 130 96 98 98 80% 305 189 146 111 78 79 79 90% 225 163 135 99 68 70 70 100% 209 155 124 83 56 60 60 47 Liebert® GXT4™ Specifications Table 17 Battery run times (continued) Number of External Battery Cabinets Internal Battery + 4 External Battery Cabinets Internal Battery + 5 External Battery Cabinets Internal Battery + 6 External Battery Cabinets 208VAC RT Model 120VAC RT Models Load Percent of Capacity 500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA 10% 480 480 480 480 480 466 480 20% 480 480 459 446 424 421 423 30% 480 457 435 341 308 307 307 40% 460 441 339 309 192 192 191 50% 448 424 316 204 157 158 157 60% 436 336 221 164 142 143 142 70% 424 318 199 153 126 128 128 80% 340 301 166 141 107 109 109 90% 327 213 158 130 95 97 98 100% 315 197 149 112 79 81 81 10% 480 480 480 480 480 480 480 20% 480 480 466 458 441 439 440 30% 480 464 446 432 333 332 331 40% 467 451 427 333 225 225 224 50% 457 438 341 306 188 190 188 60% 447 424 322 207 158 159 159 70% 438 343 303 167 145 147 147 80% 428 329 212 158 133 135 135 90% 390 315 193 148 120 122 122 100% 341 300 166 139 104 107 106 10% 480 480 480 480 480 480 480 20% 480 480 480 467 452 450 451 30% 480 480 458 445 422 421 421 40% 480 462 442 422 319 319 318 50% 467 451 426 327 216 218 216 60% 459 440 342 304 185 188 186 70% 451 428 326 208 159 160 160 80% 442 370 309 184 148 149 150 90% 434 336 221 161 137 139 139 100% 426 324 204 153 126 129 129 Run times in this table are approximate. Times can vary by ±5% due to manufacturing variances of the batteries. Times are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery cabinets. Liebert® GXT4™ 48 Specifications 9.1 Product Warranty Registration Registration is not required to activate the product warranty on a Liebert UPS. Registration is required to qualify for the Product Protection Promise. To register, visit the Emerson Network Power® Web site to fill out the online form at: www.emersonnetworkpower.com/en-US/Forms/Pages/LiebertProductWarrantyRegistration.aspx • To contact warranty support by e-mail: [email protected] 9.2 Technical Support Technical support contacts are listed on the back cover of this document. To contact Emerson Channel Product Support: Phone • NORTH AMERICA: 1-800-222-5877 • OUTSIDE NORTH AMERICA: 00-800-1155-4499 E-mail • TECHNICAL SUPPORT: [email protected] 49 Liebert® GXT4™ Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-23193_REV0_10-14 Emerson Network Power Liebert www.emerson.com United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572