ADAM-5056/D/S ADAM-5056SO ADAM-5057S ADAM-5056 ADAM-5056D ADAM-5056S RoHS 16-ch Digital Output Module 16-ch Source-type Isolated Digital Output Module with LED 32-ch Isolated Digital Output Module RoHS ADAM-5056SO COMPLIANT 2002/95/EC RoHS ADAM-5057S COMPLIANT 2002/95/EC COMPLIANT 2002/95/EC Specifications Specifications Specifications General General General Certification Connectors Certification Connectors ADAM-5056/5056D ADAM-5056S Enclosure LED Indicators ADAM-5056D ADAM-5056S Power Consumption CE, FCC class A (ADAM-5056S only) 1 x Plug-in screw terminal (# 14 ~ 22 AWG) 1 x Plug-in screw terminal (# 14 ~ 28 AWG) ABS+PC On: Output logic level 1 Off: Output logic level 0 On: Active Off: Inactive ADAM-5056:0.53 W (max.) ADAM-5056D: 0.84 W (max.) ADAM-5056S: 0.6 W (max.) Digital Output Channels Digital Output ADAM-5056/5056D ADAM-5056S Operating Voltage 16 Open collector to 30 V, 100 mA max. load Open collector to 40 V, 200 mA max. load (sink) ADAM-5056/5056D: 30 V max Power Dissipation 300 mW for each channel Protection (Only for ADAM-5056S) -Optical Isolation 2500 VDC -Overvoltage Protection 70 VDC -Power Dissipation 300 mW Ordering Information ADAM-5056 ADAM-5056D ADAM-5056S 16-ch Digital Output Module 16-ch Digital Output Module with LED 16-ch Sink Type Iso. DO Module w/ LED CE, FCC class A 1 x Plug-in screw terminal (# 14 ~ 28 AWG) Enclosure ABS+PC LED Indicator On: Active Off: Inactive Power Consumption 0.6 W (Max.) Digital Output Channels Digital Output Current Power Dissipation 16 10 ~ 35 VDC 200 mA max. (per channel) Channel : 1 W max. Total : 2.2 W Protection Optical Isolation Overvoltage Protection 2,500 VDC 70 VDC Ordering Information ADAM-5056SO 16-ch Source Type Iso. DO Module w/ LED Certification Connectors Enclosure LED Indicator CE, FCC class A 1 x 40 pin (wiring line) ABS+PC On: Active Off: Inactive Power Consumption 1W (Max.) Digital Output Channels Digital Output 32 Must connect with 2 units of ADAM-3920R Protection Optical Isolation Overvoltage Protection 2,500 VDC 70 VDC Relay Spec. of ADAM-3920R Contact Rating 10A @ 250 VAC 10A @ 30 VDC Contact Resistance 100 mΩ Operation Time 15 ms Relay Type SPST (Form A) Release Time 5 ms max Life Expectancy 1.7 x 105 at related load Insulation Resistance1GΩ @ 500 VDC Power Input +24 VDC Mounting DIN 35 rail, wall, rack (with mounting kit) Note: ADAM-5057S must connect with 2 units of ADAM-3920R via PCL-10220 Note: only for ADAM-5550 & 5560 Series Ordering Information ADAM-5057S ADAM-3920R PCL-10220 32-ch Digital Output Module 20-pin Flat Cable Wiring Relay Board 40-pin IDC to two 20-pin IDC cable, 1m Online Download www.advantech.com/products All product specifications are subject to change without notice Last updated : 28-Aug-2013