B86305L

EMC filters
3-phase line reactors for converters
4 A ... 390 A, 40 °C, 50/60 Hz
Series/Type:
B86305L
Date:
May 2014
© EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
Line reactors, output chokes and output filters
3-phase line reactors for converters
3-phase line reactors for converters
Rated voltage VR: 520 V AC
Rated current IR: 4 A to 390 A
Construction
3-phase line reactor
Natural cooling
Features
Easy to install
Low weight
Compact design
Design complies with IEC 60076-6
Degree of protection1):
IP20 (4 A ... 16 A)
IP10 (30 A ... 60 A)
IP00 (100 A ... 390 A)
Inductance constant up to 1.5 × IR
Inductance higher than 60% rated value at 3 × IR
UL approved insulation system
T-EIS-CF1
Typical applications
Frequency converters for motor drives, e.g.
elevators
pumps
traction systems
conveyor systems
HVAC systems (heating, ventilation and air
conditioning)
Power supplies
Terminals
Finger-safe terminal blocks (< 100 A)
Busbars from 100 A, cross section 20 × 3 mm
Marking
Marking on component:
Manufacturer's logo, ordering code, rated current, rated
frequency, inductance, approximate weight, date code
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
Page 2 of 11
B86305L
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
Technical data and measuring conditions
Rated voltage VR
Rated current IR
Test voltage Vtest
Relative voltage drop uk in %
Insulation class
Overload capability (thermal)
520 V AC (50/60 Hz)
Referred to 40 °C rated temperature
1100 V AC, 2 s (line/line)
2500 V AC, 2 s (lines/case)
At IR; 50 Hz and 400 V AC
F (155 °C)
3 IR, t < 3 s in 300 s
Climatic category (IEC 60068-1)
25/100/21 (25 °C/+100 °C/21 days damp heat test)
Approvals
Insulation system class 155 (F); T-EIS-CF1 UL 1446
Characteristics and ordering codes
IR*
A
uk
%
VR = 520 V AC
4
5.4
10
5.4
16
4.4
30
4.1
60
4.1
100
4.1
230
4.7
390
4.0
Rtyp1)
mΩ
LR2)
mH
PL3)
W
Approx. weight
kg
Ordering code
335.0
78.0
42.2
12.4
6.2
3.2
0.9
0.6
10.0
4.0
2.0
1.0
0.5
0.3
0.15
0.075
25
43
65
50
100
160
340
480
1.3
2.7
3.1
5.5
8.5
15.0
32.0
44.0
B86305L0004R000
B86305L0010R000
B86305L0016R000
B86305L0030R000
B86305L0060R000
B86305L0100S000
B86305L0230S000
B86305L0390S000
* Higher current values upon request
1) Typical value at 20 °C, tolerance ±10%
2) Tolerance 0%/+20%,
3) At IR , 50 Hz, 20 °C
Please read Cautions and warnings and
Important notes at the end of this document.
Page 3 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
Dimensional drawings
B86305L0004R000 ... B86305L0016R000 (4 A ... 16 A)
B
C
D1 × D2
E
G
G1
H
X
B86305L0004R000 100
135
60
6×9
80
40
60
42
40
B86305L0010R000 130
150
90
6 × 12
100
60
80.5
62
50
B86305L0016R000 130
150
90
6 × 12
100
60
80.5
62
50
Ordering code
A
General tolerances according to ISO 2768cL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 4 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
B86305L0030R000, B86305L0060R000 (30 A, 60 A)
Ordering code
A
B
C
E
F
G
G1
H
Q
MK
(mm2) (Nm)
PE D PE MP
(Nm)
B86305L0030R000 155 170 135 125 120 75
107 90
16
2.0-2.3 M4
1.2±0.1
B86305L0060R000 180 205 150 150 135 85
122 105 35
3.2-3.7 M6
3.0±0.15
General tolerances according to ISO 2768cL
Dimensions in mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 5 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
B86305L0100S000 ... B86305L0390S000 (100 A ... 390 A)
A1
B
C
∅D E
Ordering code
A
B86305L0100S000
270 270 210 180 6.5
180 145 105 181 100
240 M8
B86305L0230S000
320 300 290 235 8.5
200 185 190 230 142
270 M10 10±1
B86305L0390S0001) 320 300 290 265 8.5
F
G
G1
H
K
PE
M
6±0.3
200 215 190 230 168.5 270 M10 10±1
General tolerances according to ISO 2768cL
Dimensions in mm
1) Preliminary data: Size of Cu connectors 30 × 3 mm
Please read Cautions and warnings and
Important notes at the end of this document.
Page 6 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
Cautions and warnings
Please read all safety and warning notes carefully before installing the EMC filter and putting it
into operation (see ). The same applies to the warning signs on the filter. Please ensure that
the signs are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the
appropriate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in lowvoltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warning
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed
and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter or filter, such as with circuits able to cause resonances, impermissible voltages at higher frequencies etc. can lead to bodily injury and death as
well as cause substantial material damages (e.g. destruction of the filter housing).
EMC filters and filters must be protected in the application against impermissible exceeding of
the rated currents by overcurrent protective circuitry.
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the
required cross section before beginning of operation and save it against disconnecting. For
leakage currents IL1) <10 mA the PE conductor must have a KU value2) of 4.5 A3); for leakage
currents IL ≥10 mA the PE conductor must have a KU value of 6.4)
Output chokes and output filters must be protected in the application against impermissible
exceeding of the component temperature.
The converter output frequency must be within the specified range to avoid resonances and
uncontrolled warming of the output chokes and output filters.
1) IL = leakage current let-go
2) The KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
3) A value of KU = 4.5 with respect to interruptions is attained with: a) a permanently connected protective earth circuit ≥2.5 mm2
connected via shroud connectors (IEC 603092) and b) a protective earth circuit.
4) KU = 6 with respect to interruptions is achieved for fixedconnection lines ≥10 mm2 where the type of connection and line layout
correspond to the requirements for PEN conductors as specified in relevant standards.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 7 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
The table below summarizes the safety instructions that must be observed without fail. A detailed
description can be found in the relevant chapters of the databook.
Topic
Instructions
Selecting a filter
When selecting a filter, it is mandatory to observe the
rated data of the equipment (such as its rated input
current, rated voltage, harmonic content etc.) as well
as the derating instructions in Chapters 9 and 10.
Rated voltage
When power distribution systems deviating from the
Power distribution
symmetric TN-S system it is to check the suitability of systems,
the EMC filters and the allowed voltages including the 7
fault cases.
Protection from
residual voltages
Discharge resistors
Active parts must be discharged within 5 s to a
voltage of less than 60 V (or 50 µ C). If this limit
cannot be observed due to the operating mode, the
hazardous point must be permanently marked in a
clearly visible way.
Filters which are not permanently connected (e.g.
when the test voltage is applied to the filter at the
incoming goods inspection) must be discharged after
the voltage has been switched off.
Installing and
removing of EMC
filters
Installation
Reference chapter
(data book),
paragraph
Selection guide for
converter filters
Safety regulations,
6.1
Safety regulations,
6.2
When installing and removing our EMC filters, a Safety regulations,
voltage-free state must be set up and secured with 6.4
observance of the five safety rules described in
EN 50110-1.
Use in IT systems
The special features of the IT system ("first fault case" Power distribution
and other fault cases) shall be observed.
system (network
types), 7.6
Safety notes on
leakage currents
The filter leakage currents specified in the data book
are intended for user information only.The maximum
leakage current of the entire electrical equipment or
appliance has to be limited for safety reasons. Please
obtain the applicable limits for your application from
the relevant regulations, provisions and standards.
Leakage current,
8.4
Leakage current,
8.6
Voltage derating
If the permissible limits for the higher-frequency Voltage derating,
voltages at the filter are exceeded, the filter may be 9.8
Hazards caused by
overloading the filters damaged or destroyed.
Current derating at
elevated ambient
temperatures
Non-observance of the current derating may lead to Current derating,
overheating and consequently represents a fire 10.1
hazard.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 8 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
Topic
Protective earth
connection at
operating currents
>250 A
Instructions
Reference chapter
(data book),
paragraph
For operating currents greater than 250 A, we Mounting
recommend the PE connection to be set up between instructions, point
the feed (filter: line) and output (filter: load) not via the 2
PE terminal bolt in the filter housing.
Mounting position
Note the mounting position of the filters! It must Mounting
always be ensured that natural convection is not instructions, point
impaired.
13
Long motor cables
Long motor cables cause parasitic currents in the
installation. The cable lengths indicated for the output
chokes and output filters serve for orientation. The
user must check the technical parameters and
especially the choke temperatures for the respective
application.
Mounting
instructions, point
15
Display of ordering codes for EPCOS products
The ordering code for one and the same product can be represented differently in data sheets,
data books, other publications and the website of EPCOS, or in order-related documents such as
shipping notes, order confirmations and product labels. The varying representations of the
ordering codes are due to different processes employed and do not affect the specifications of the
respective products. Detailed information can be found on the Internet under
www.epcos.com/orderingcodes
Please read Cautions and warnings and
Important notes at the end of this document.
Page 9 of 11
Line reactors, output chokes and output filters
B86305L
3-phase line reactors for converters
Symbols and terms
Symbol
English
α
Insertion loss
CR
Rated capacitance
CX
Capacitance X capacitor
CY
Capacitance Y capacitor
∆V
Voltage drop (input to output)
dv/dt
Rate of voltage rise
f
Frequency
fM
Converter output frequency
fP
Pulse frequency
fR
Rated frequency
fres
Resonant frequency
IC
Current through capacitor
ILK
Filter leakage current
Imax
Maximum current
IN
Nominal current
Iop
Operating current (design current)
Ipk
Rated peak withstand current
Iq
Capacitive reactive current
IR
Rated current
IS
Interference current
L
Inductance
LR
Rated inductance
Lstray
Stray inductance
PL
Power loss
R
Resistance
Ris
Insulation resistance
Rtyp
DC resistance, typical value
TA
Ambient temperature
Tmax
Upper category temperature
Tmin
Lower category temperature
TR
Rated temperature
uk
Refered voltage drop in %
Veff
RMS voltage
VK
Voltage drop
VLE
Voltage line to earth; voltage line to ground
VN
Nominal voltage
VR
Rated voltage
Vpeak
Peak voltage
Vtest
Test voltage
VX
Voltage over X capacitor
VY
Voltage over Y capacitor
XL
Inductive reactance
Z
Impedance
|Z|
Impedance, absolute value
Please read Cautions and warnings and
Important notes at the end of this document.
Page 10 of 11
German
Einfügungsdämpfung
Bemessungskapazität
Kapazität X-Kondensator
Kapazität Y-Kondensator
Spannungsabfall im Filter
Spannungsanstiegsgeschwindigkeit
Frequenz
Motorfrequenz
Pulsfrequenz
Bemessungsfrequenz
Resonanzfrequenz
Strom durch Kondensator
Filter-Ableitstrom
Maximalstrom
Nennstrom
Betriebsstrom
Bemessungs-Stoßstromfestigkeit
Kapazitiver Blindstrom
Bemessungsstrom
Störstrom
Induktivität
Bemessungsinduktivität
Streuinduktivität
Verlustleistung
Widerstand
Isolationswiderstand
Gleichstromwiderstand, Richtwert
Umgebungstemperatur
Obere Kategorietemperatur
Untere Kategorietemperatur
Bemessungstemperatur
Bezogener Spannungsabfall in %
Effektivspannung
Spannungsabfall
Spannung Phase zu Erdpotential
Nennspannung
Bemessungsspannung
Spitzenspannung
Prüfspannung
Spannung über X-Kondensator
Spannung über Y-Kondensator
Induktiver Blindwiderstand
Scheinwidertand
Scheinwiderstand (Betragswert)
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar
with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of an electronic component could endanger human life or
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by
means of suitable design of the customer application or other action taken by the customer
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by
third parties in the event of malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order. We also
reserve the right to discontinue production and delivery of products. Consequently, we
cannot guarantee that all products named in this publication will always be available. The
aforementioned does not apply in the case of individual agreements deviating from the foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association
(ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CeraLink, CeraPlas, CSMP, CSSP,
CTVS, DeltaCap, DigiSiMic, DSSP, FilterCap, FormFit, MiniBlue, MiniCell, MKD, MKK,
MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI,
SIKOREL, SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV, SIP5D, SIP5K, TFAP,
ThermoFuse, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
Page 11 of 11