EPCOS B84142C1000S081

2−line filters
for converters and power electronics
preliminary data
1500 V DC, 180 ... 1600 A, 40 °C
Ordering code:
B84142C*S081
Date:
2009−10−09
Version:
51
 EPCOS AG 2008. Reproduction, publication and dissemination of this publication, enclosures
hereto and the information contained therein without EPCOS’ prior express consent is prohibited.
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Construction
2−line filter
Metal case
Features
Easy to install
Low weight
Reduced Y−capacitance
Design complies with
IEC 60939, UL 1283, CSA 22.2 No.8
Applications
Photovoltaic
Solar panels
Wind farms
Power supplies
Frequency converters for motor drives,
Terminals
Line side: bus bars
Load side: bus bars
Marking
Marking on component:
manufacturer’s logo, ordering code, rated voltage, rated current,
rated temperature, climatic category, date code
Minimum marking on packaging: maufacturer’s logo, ordering code,
date code, quantity
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 2 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Typical circuit diagram
Technical data and measuring conditions
Rated voltage
UR L−L
1500
V DC
Rated voltage
UR L−Gnd
1500
V DC
Test voltage line to line for 2 s
Utest
4200
V DC
Test voltage line to case for 2 s
Utest
4200
V DC
Rated temperature
TR
40
°C
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour
1.5 x IR
2.5 x IR
Climatic category (IEC 60068−1)
25/100/21
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 3 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Characteristics and ordering codes
IR
Terminal
cross
section
Rtyp
Approx.
weight
A
mm2
µΩ
kg
Ordering code
Approvals
180
20 x 3
110
4.9
B84142C0180S081
−
−
−
250
20 x 3
110
5.0
B84142C0250S081
−
−
−
320
25 x 5
51
7.8
B84142C0320S081
−
−
−
400
25 x 5
48
7.8
B84142C0400S081
−
−
−
600
30 x 5
43
7.9
B84142C0600S081
−
−
−
1000
40 x 8
29
19.9
B84142C1000S081
−
−
−
1600
50 x 10
22
24.5
B84142C1600S081
−
−
−
X = approval granted
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 4 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Dimensional drawings B84142A0180S081, B84142A0250S081 (180 A, 250 A)
Beschriftung
Marking
Beschriftung
Marking
Dimensional drawings B84142A0320S081, B84142A0400S081 (320 A, 400 A)
Beschriftung
Marking
Beschriftung
Marking
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 5 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Dimensional drawings B84142A0600S081 (600 A)
Beschriftung
Marking
Beschriftung
Marking
Dimensional drawings B84142A1000S081 (1000 A)
Beschriftung
Marking
Beschriftung
Marking
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 6 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Dimensional drawings B84142A1600S081 (1600 A)
Beschriftung
Marking
Beschriftung
Marking
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 7 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
100
dB
80
60
40
20
0
104
105
106
107
Hz
108
f
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 8 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Caution and warnings
Please note the advices in our data book “EMC Filters” (latest edition); attention should
be paid to the chapter “General safety notes”.
It shall be ensured that only qualified persons (electricity specialists) are engaged on work
such as planning, assembly, installation, operation, repair and maintenance. They must
be provided with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge.
Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is
installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective−earth connection must be observed.
Impermissible overloading of the EMC filter, such as with circuits able to cause resonances, impermissible voltages at higher frequencies etc. can lead to bodily injury and
death as well as cause substantial material damages (e.g. destruction of the filter housing).
EMC filters must be protected in the application against impermissible exceeding of the
rated currents by overcurrent protective.
In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with
the required cross section before beginning of operation and save it against disconnecting. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5;
for leakage currents IL 10 mA the PE conductor must have a KU value of 6.
3) The KU value (symbol KU) is a classification parameter of safety−referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
− with a permanently connected protective earth circuit 1.5 mm2
− with a protective earth circuit 2.5 mm2 connected via shroud connectors (IEC 60309−2).
KU = 6 with respect to interruptions is achieved for fixed−connection lines 10 mm2 where the type of connection and line layout correspond to the requirements for PEN conductors as specified in relevant standards.
4) IL = leakage current let−go
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 9 of 10
B84142−A180__A1600−S81−51−7659
2−line filters
B84142C*S081
for converters and power electronics
preliminary data
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products
for certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned.
We nevertheless expressly point out that such statement cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar
with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties
described in the product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before end of their usual service life time cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of a passive electronic component could endanger human
life or health (e.g. in accident prevention or life−saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the
customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is
sustained by third parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product−specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions
(e.g. because they are classed as hazardous). Useful information on this will be found in
our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any
more detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in
this publication may change from time to time. The same is true of the corresponding
product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. The aforementioned does not apply in the case of individual agreements deviating from
the foregoing for customer−specific products.
6. Unless otherwise agreed in individual contracts, all orders subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu−X, CeraDiode, CSSP, CTVS, DSSP, MiniBlue, MKK,
MLSC, MotorCAP, PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap,
SIMDAD, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are
trademarks registered or pending in Europe and in other countries. Further information
will be found on the Internet at www.epcos.com/trademarks.
1
Please read and Cautions and warnings and
Important notes at the end of this document.
Page 10 of 10
B84142−A180__A1600−S81−51−7659