FWX-(35-2500) - Cooper Industries

Bussmann
®
FWX 250V
Rated
Current
RMS-Amps
Type
†
35-2500A
Electrical Characteristics
I2t (A2 Sec)
Clearing
Pre-arc
at 250V
®
Ordering Information
Watts
Loss
Part
Number
Carton
Qty.
Carton
Weight
(lbs)
5
1.40
Dimensions
Curves
Figure
Number
BIF #
35
50
230
4.2
FWX-35A
_____________________________________________________________________________________
_
40
60
310
5.2
FWX-40A
____________________________________________________________________________________
__
45
80
390
5.7
FWX-45A
____________________________________________________________________________________
__
50
100
520
6.0
FWX-50A
____________________________________________________________________________________
__
60
140
740
8.1
FWX-60A
____________________________________________________________________________________________________________
_
70
330
1400
7.2
FWX-70A
____________________________________________________________________________________
__
80
430
1850
8.1
FWX-80A
____________________________________________________________________________________
__
90
570
2450
9.0
FWX-90A
____________________________________________________________________________________
__
100
740
3150
10.0
FWX-100A
____________________________________________________________________________________
__
0.32
125
1130
4850
12.5
FWX-125A
____________________________________________________________________________________
__
359
150
1620
6950
15.7
FWX-150A
____________________________________________________________________________________
__
175
2170
9300
18.5
FWX-175A
____________________________________________________________________________________
__
Fig. 1
200
2790
12000
22
FWX-200A
_____________________________________________________________________________________
_
______________
225
3210
14700
24
FWX-225A
____________________________________________________________________________________
__
250
3960
18100
27
FWX-250A
FWX ____________________________________________________________________________________
__
250V
275
4720
21600
31
FWX-275A
____________________________________________________________________________________
__
300
6000
27300
32
FWX-300A
____________________________________________________________________________________
__
350
10600
48600
39
FWX-350A
____________________________________________________________________________________
__
1
0.52
400
14500
66100
44
FWX-400A
____________________________________________________________________________________
__
450
22100
101000
49
FWX-450A
____________________________________________________________________________________
__
500
28000
128000
54
FWX-500A
____________________________________________________________________________________
__
600
41100
188000
62
FWX-600A
____________________________________________________________________________________
__
700
48800
190000
72
FWX-700A
____________________________________________________________________________________
__
800
59000
230000
84
FWX-800A
____________________________________________________________________________________
__
______________
0.90
1000
44000
360000
100
FWX-1000AH __
____________________________________________________________________________________
Fig. 2
1200
92000
750000
103
FWX-1200AH ___
___________________________________________________________________________________
1500
120000
880000
140
FWX-1500AH ___
___________________________________________________________________________________
1600
160000
1200000
140
FWX-1600AH ___
___________________________________________________________________________________
2000
320000
2300000
151
FWX-2000AH ___
___________________________________________________________________________________
2500
670000
4700000
163
† U.L. Recognition on 35 through 800 amperes only.
_____________
35785299
2.86
Fig. 3
FWX-2500AH
1 kg = 2.2 lbs
1 lb = 0.45 kg
n Interrupting rating 200kA RMS Symmetrical.
n Watts loss provided at rated current.
n (250 Vdc/Interrupting rating 20kA) U.L. Recognition on 35 through 800 amperes only.
7-11-01
SB01191
Form No. FWX 250
Page 1 of 2
BIF Doc #720005
Bussmann
®
†
35-2500A
FWX 250V
®
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as
a function of applied working voltage,
E g , (RMS).
Arc Voltage
This curve gives the peak arc voltage,
U L , which may appear across the fuse
during its operation as a function of the
applied working voltage, E g , (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, K p ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
1.5
1.4
1.2
1.0
Kp
0.8
K
UL
103
1.0
0.6
0.5
800
0.5
1)
600
500
2)
400
0.3
0.2
0.4
0.3
0.2
1)
300
Eg
0.15
75
125
200
250
2)
Eg
200
50
300
1) 35-800 Amp Range
2) 1000-2500 Amp Range
100
150
200
Ib
0.1
30 40 50
250
60
70
80 90 100%
1) 35-800 Amp Range
2) 1000-2500 Amp Range
Dimensions
Fig. 1: 35-800 Amp Range
Fig. 2: 1000-1200 Amp Range
Fig. 3: 1500-2500 Amp Range
J
A
A
A D E C
D
C
B
C
B
F
G
H
B
Order #
Fig.
A
B
C
D
E
F
G
H
J
Thread Depth
FWX-35A-60A
1
3.19
0.81
1.59
2.59
2.25
0.34
0.63
0.13
0.52
—
FWX-70A-200A
1
3.13
1.22
1.59
2.44
2.19
0.34
1.00
0.19
0.47
—
FWX-225A-600A
1
3.84
1.50
1.59
2.94
2.25
0.41
1.00
0.25
0.75
—
FWX-700A-800A
1
3.84
2.00
1.59
3.03
2.28
0.41
1.50
0.25
0.78
—
FWX-1000AH-1200AH
2
2.59
3.00
1.50
—
—
—
—
—
—
Tapped ‹Ω•∑-24 ≈ ⁄Ω™∑
FWX-1500AH-2500AH
3
2.59
3.50
1.50
1.50
—
—
—
—
—
Tapped ‹Ω•∑-24 ≈ ⁄Ω™∑
Dimension in inches.
1mm = 0.0394∑
1∑ = 25.4mm
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-11-01
SB01191
Form No.FWX 250
Page 2 of 2
BIF Doc #720005