ETC FWJ-175

Bussmann
®
FWJ 1000V
Rated
Current
RMS-Amps
Type
35-2000A
Electrical Characteristics
I2t (A2 Sec)
Clearing
Pre-arc
at 1000V
®
Ordering Information
Watts
Loss
Part
Number
Carton
Qty.
Carton
Weight
(lbs)
10
4.18
Dimensions
Curves
Figure
Number
See Page
or
(BIF #)
35
210
2000
7
FWJ-35A
__________________________________________________________________________
40
300
2500
8
FWJ-40A
__________________________________________________________________________
50
470
3500
10
FWJ-50A
__________________________________________________________________________
60
670
5000
11
FWJ-60A
__________________________________________________________________________
70
1100
6900
12
FWJ-70A
__________________________________________________________________________
80
1550
9700
13
FWJ-80A
__________________________________________________________________________
90
1900
12000
14
FWJ-90A
__________________________________________________________________________
100
2800
17500
15
FWJ-100A
_________________________________________________________________________________________________
125
4800
35000
16
FWJ-125A
__________________________________________________________________________
page 25
(35785303)
150
6300
45000
25
FWJ-150A
__________________________________________________________________________
4.40
175
7500
65000
30
FWJ-175A
__________________________________________________________________________
FWJ
200
11700
80000
32
FWJ-200A
__________________________________________________________________________
___________
1000V __________________________________________________________________________
250
16000
112000
50
FWJ-250A
300
23500
164000
56
FWJ-300A
__________________________________________________________________________
Fig. 1
350
33000
231000
62
FWJ-350A
__________________________________________________________________________
4.84
400
47000
330000
67
FWJ-400A
__________________________________________________________________________
500
39500
329000
95
FWJ-500A
__________________________________________________________________________
600
61000
520000
105
FWJ-600A
__________________________________________________________________________
1
___________
___________
5.28
page 26
(35785309)
800
87000
500000
182
FWJ-800A
__________________________________________________________________________
1000
190000
1100000
206
FWJ-1000A
__________________________________________________________________________
1200
370000
2100000
240
FWJ-1200A
__________________________________________________________________________
1400
470000
2700000
248
FWJ-1400A
__________________________________________________________________________
1600
700000
4000000
267
FWJ-1600A
__________________________________________________________________________
1800
925000
5300000
239
FWJ-1800A
__________________________________________________________________________
2000
n
n
n
n
1330000
7600000
Interrupting rating 200kA.
Watts loss provided at rated current.
800 Vdc U.L. Recognition on 40-200 and 500-600 amperes.
See accessories on page 20.
12-28-98
SB98107
Rev. A
244
FWJ-2000A
1 kg = 2.2 lbs
1 lb = 0.45 kg
Form No. FWJ 1000
Page 1 of 2
BIF Doc #720027
Bussmann
®
35-2000A
FWJ 1000V
®
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as
a function of applied working voltage,
E g , (RMS).
1.5
Arc Voltage
This curve gives the peak arc voltage,
U L , which may appear across the fuse
during its operation as a function of the
applied working voltage, E g , (RMS) at a
power factor of 15%.
1.0
Kp
0.8
2000
K
UL
1.0
0.6
0.5
1600
0.4
1200
0.5
0.3
800
0.3
0.2
0.15
200
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, K p ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
0.2
400
Eg
500
800
Eg
1000
200
600
Ib
0.1
30 40 50
1000 1400 1800
60
70
80 90 100%
Dimensions
Fig. 1: 35-2000 Amp Range
A
D
E
C
H
G F
B
J
Order #
Fig.
A
B
C
D
E
F
G
H
J
FWJ-35A-60A
1
5.000
0.940
3.110
4.235
4.180
0.352
0.750
0.125
0.380
FWJ-70A-100A
1
4.932
1.125
3.085
4.266
4.156
0.352
1.000
0.188
0.407
FWJ-125A-200A
1
5.685
1.526
3.261
4.803
4.055
0.445
1.000
0.250
0.819
FWJ-250A-400A
1
5.768
2.000
3.500
4.811
4.150
0.433
1.500
0.250
0.764
FWJ-500A-600A
1
7.201
2.500
3.465
5.984
4.706
0.562
2.000
0.375
1.201
FWJ-800A-2000A
1
6.811
3.500
3.312
5.472
4.962
0.625
2.750
0.500
0.880
Dimension in inches.
1mm = 0.0394∑
1∑ = 25.4mm
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
12-28-98
SB98107
Rev. A
Form No. FWJ 1000
Page 2 of 2
BIF Doc #720027