MEDIUM VOLTAGE DIN Fuse

MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
Standards/Approvals:
DIN 43625, VDE 0670 part 4,
IEC 60282-1 (2005)
Description:
Catalogue Symbol:
7.2TDLSJ(amp)
7.2TFLSJ(amp)
Class of Operation:
Back-up as IEC 60282-1 (2005)
Dimensional Data:
Fuse Reference
A
TDLSJ
C
292
TFLSJ
Packaging:
54
292
D
Weight (Kg)
76
3.1
51
80
1.63
A range of medium voltage DIN Fuses,
complete with striker, suitable for transformer
protection. The fuses can be used even
where there is no secondary LV protection,
provided they are used with fuse switches
fitted with instantaneous striker tripping.
All fuse-links are packed 3’s.
MOQ: 3
Packaging 100% recyclable
Technical Data:
DIN fuse-links
Rated voltage:
7.2kV
6.3A to 160A
Amps:
Rated breaking capacity: 40kA
Rated frequency:
50 - 60Hz
Suitable for outdoor and indoor use
RoHS compliant
Striker Diagram:
S = Spring Striker 50N to DIN 43625 and IEC 60282-1 designation “medium”
Force x Travel diagram for 50N Din striker
60
50
Force (N)
40
30
20
10
0
0
REV B - 10/4/2007
4
8
12
16
Travel (mm)
20
24
28
32
Form No. 7.2kV DIN
Page 1 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
Table of Ratings:
Standards/Approvals:
Rated Currents:
Part Number
Current Rating
In (A)
7.2TDLSJ6.3
6.3
7.2TDLSJ16
16
7.2TDLSJ10
7.2TDLSJ31.5
7.2TDLSJ40
7.2TFLSJ125
7.2TFLSJ160
40
Minimum
Breaking
Capacity
I3 (A)
20
40
31
40
49
40
25
49
40
31.5
40
80
40
100
40
143
40
50
7.2TDLSJ63
7.2TFLSJ100
I1 (kA)
20
7.2TDLSJ50
7.2TFLSJ80
Breaking
Capacity
10
7.2TDLSJ20
7.2TDLSJ25
DIN 43625, VDE 0670 part 4 and IEC 60282-1 (2005)
6.3, 10, 16, 20, 25, 31.5, 40, 50, 63, 80, 100, 125, 160 Amps
63
114
40
80
180
40
100
264
40
125
338
40
160
375
40
Cross-Reference
525
MESA
7.2TDLSJ6.3
7.2TDLSJ10
7.2TDLSJ16
7.2TDLSJ20
7.2TDLSJ25
7.2TDLSJ31.5
7.2TDLSJ40
7.2TDLSJ50
7.2TDLSJ63
7.2TFLSJ80
7.2TFLSJ100
7.2TFLSJ125
7.2TFLSJ160
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3009813
3009813
3009813
3009813
3009813
3009813
3009813
3009813
3009913
3009913
3009913
3009913
3010013
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CF-7,2/125
CF-7,2/160
Cold
Resistance &
Watts Loss in
Free Air
mΩ
205
99.7
65.1
48.9
32.6
26.0
16.0
12.9
8.14
6.01
4.65
3.60
2.73
Joule Integral (I2t)
W
Minimum PreArcing
19
2.5 X 102
11
23
5.5 X 102
8.2 X 103
292
51
1.63
45
8.0 X 102
3.2 X 102
5.0 X 103
9.1 X 103
64
1.5 X 104
79
3.0 X 104
97
80N Striker 50N Striker
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
kg
1.63
36
54
mm
51
2.0 X 102
46
mm
292
8.9 X102
36
Weight
6.5 X 103
5.7 X 102
28
Diameter
4.8 X 101
9.7 X 102
27
Maximum
Operating
Length
2.7 X 103
1.1 X 104
8.0 X 103
1.0 X 104
2.2 X 104
3.2 X 104
7.5 X 104
6.5 X 104
1.1 X 105
1.7 X 105
3.1 X 105
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
757352 BN
757352 BP
292
292
292
292
292
292
292
292
292
292
292
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
51
51
51
51
51
51
51
76
76
76
76
(type)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1.63
1.63
1.63
1.63
1.63
1.63
1.63
3.1
3.1
3.1
3.1
1YMB531034M0001
1YMB531034M0002
1YMB531034M0003
N/A
1YMB531034M0004
N/A
1YMB531034M0005
1YMB531034M0006
1YMB531034M0007
1YMB531034M0008
1YMB531034M0009
1YMB531034M0010
1YMB531034M0011
Watts Loss Comparison
Lowest Watts Loss
Part Number
7.2TDLSJ6.3
7.2TDLSJ10
7.2TDLSJ16
7.2TDLSJ20
7.2TDLSJ25
7.2TDLSJ31.5
7.2TDLSJ40
7.2TDLSJ50
7.2TDLSJ63
7.2TFLSJ80
7.2TFLSJ100
7.2TFLSJ125
7.2TFLSJ160
Watts Loss
11
19
23
27
28
36
36
46
45
54
64
79
97
Watts Loss
-
Watts Loss
8
13
11
13
16
21
27
30
34
47
64
98
103
MESA Watts
loss
-
88
87
Watts Loss
-
-
Watts Loss
-
88
87
Watts Loss
-
-
Watts Loss
-
-
Watts Loss
26
16
26
24
30
35
40
52
57
76
101
Form No. 7.2kV DIN
Page 2 of 10
Data sheet 720103
DATE
DRN
0.01
0.1
1
10
100
1000
10
APPD
DATE
DRN
DRN
MPJ
10/4/07
G
RE-DRAWN ON EXCEL. TDO & TFO REMOVED ECN11268
APPD
DATE
BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK.
TEL. 01509 882600 FAX 01509 882786
100
1000
10000
R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES
6.3A
10A
16A
20A
25A
31.5A
40A
50A
63A
80A
100A
125A
160A
CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT
FUSE TYPES: TDL / TFL
PF 1042
100000
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
APPD
VIRTUAL PRE-ARCING TIME IN SECONDS
10000
TIME- CURRENT CHARACTERISTIC
FOR 7.2kV FUSE-LINKS
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
Time Current Characteristics
Form No. 7.2kV DIN
Page 3 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
MV DIN
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
Cut-Off Curves
REF. No. PF 2042
100000
CUT-OFF CURRENT
CHARACTERISTIC
FOR 7.2kV FUSE-LINKS
FUSE TYPE
TDL/TFL
NOTES
1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2
AND 3 BELOW.
2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT.
FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN
ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE
DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF
PROSPECTIVE CURRENT.
3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE.
40A
50A
63A
80A
100A
125A
160A
PEAK CUT-OFF CURRENT IN AMPERE S
10000
1000
6.3A
100
100
DRN
DATE
APPD
10A
1000
16A
20A
25A
31.5A
10000
100000
R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
F
DRN
DATE
APPD
E
DRN MPJ
DATE 12/4/07
APPD
D
RE-DRAWN IN EXCEL
TFO & TDO REMOVED.
MPJ. ECN11268
PF2042
BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600
FAX +44 (0) 1509
Form No. 7.2kV DIN
Page 4 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SDLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 5 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SDLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 6 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SFLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 7 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SFLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 8 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SDLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 9 of 10
Data sheet 720103
MEDIUM VOLTAGE DIN Fuse-Links
7.2kV, Current Limiting Back-Up Fuse-Links, 6.3 to 160 Amps
MV DIN
KEMA Certificate
This certificate refers to SDLDJ 7.2kV fuse-links, which are electrically identical to the new T range, other than the fuses are sealed for outdoor use, have a brown
ceramic body and use a 50N striker.
Form No. 7.2kV DIN
Page 10 of 10
Data sheet 720103