TM MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 12TDLEJ(amp) 12THLEJ(amp) 12TKLEJ(amp) 12TXLEJ(amp) 12THMEJ (amp) 12TFMSJ(amp) Class of Operation: Description: A range of medium voltage DIN Fuses, complete with sealed striker, suitable for transformer protection. The fuses can be used even where there is no secondary LV protection, provided they are used with fuse switches fitted with instantaneous striker tripping. Packaging: All fuse-links are packed individually. MOQ: 3 Packaging 100% recyclable Back-up as IEC 60282-1 (2005) Dimensional Data: Fuse Reference A C D Weight (Kg) TDLEJ 292 54 51 1.7 THLEJ 292 67 64 2.6 TKLEJ 292 80 76 3.5 TXLEJ 292 88 88 3.7 THMEJ 442 67 64 3.7 TFMSJ 442 80 76 5.1 EJ Outline Technical Data: DIN fuse-links Rated voltage: 12kV Amps: 6.3A to 200A Rated breaking capacity: 50kA Rated frequency: 50 - 60Hz Suitable for outdoor and indoor use RoHS compliant SJ Outline Striker Diagrams: E = Spring Striker 80N to IEC 60282-1 designation “medium” S = Spring Striker 50N to DIN 43625 and IEC 60282-1 designation “medium” Force x Travel diagram for 50N DIN striker Force x Travel diagram for 80N DIN striker 60 100 90 50 80 70 40 Force (N) Force (N) 60 50 30 40 20 30 20 10 10 0 0 0 4 8 12 16 20 Travel (mm) 24 28 32 36 0 4 8 12 16 20 24 28 32 Travel (mm) Form No. 12kV DIN Page 1 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Table of Ratings: Standard Approvals: Technical Data: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) 6.3, 10, 16, 20. 25, 31.5, 40, 50, 63, 80, 100, 125, 160 and 200 Amps Minimum Breaking Capacity Breaking Capacity Current Rating Part Number In (A) I1 (kA) Cold Resistance & Watts Loss in Free Air I3 (A) mΩ W 12TDLEJ6.3 6.3 63 23 222 10 12TDLEJ10 10 63 35 131 16 12TDLEJ16 16 63 53 54.6 16 12TDLEJ20 20 63 73 39.1 18 12TDLEJ25 25 63 87 31.2 24 31.5 63 111 23.4 28 12TDLEJ40 40 63 143 17.2 36 12TDLEJ50 50 63 168 13.5 47 12TDLEJ63 63 63 235 10.6 60 12TDLEJ31.5 12THLEJ80 80 63 272 7.81 72 12THLEJ100 100 63 388 5.74 85 12TKLEJ125 125 63 687 3.99 93 12TXLEJ160* 160 63 560 4.30 217 12TXLEJ200* 200 63 610 3.80 333 12THMEJ100 100 63 272 5.74 85 12TFMSJ160 160 50 485 3.65 139 Joule Integral (I2t) Length Diameter Weight mm mm kg Minimum PreArcing Maximum Operating 9.8 X 101 2.8 X 102 1.0 X 103 2.3 X 103 292 51 1.7 292 51 1.7 2.6 X 102 5.2 X 102 3.9 X 103 5.4 X 103 292 51 1.7 292 51 1.7 8.1 X 102 1.4 X103 8.4 X 103 1.5 X 104 292 51 1.7 292 51 1.7 2.4 X 103 2.8 X 103 4.3 X 103 2.5 X 104 3.1 X 104 4.7 X 104 292 51 1.7 292 51 1.7 292 51 1.7 7.9 X 103 2.0 X 104 4.0 X 104 9.1 X 104 1.4 X 105 3.5 X 105 292 64 2.6 292 64 2.6 292 76 3.5 1.1 X 105 1.5 X 105 5.0 X 105 6.5 X 105 292 88 3.7 292 88 3.7 2.0 X 104 5.0 X 104 1.4 X 105 3.5 X 105 442 64 3.7 442 76 5.1 * Not compliant with VDE 0670 part 402 Cross-Reference MESA (80N Striker) (50N Striker) 12TDLEJ6.3 12TDLEJ10 12TDLEJ16 12TDLEJ20 12TDLEJ25 12TDLEJ31.5 12TDLEJ40 12TDLEJ50 12TDLEJ63 67120.0060 67120.0100 67120.0160 67120.0200 67120.0250 67120.0320 67120.0400 67120.0500 67120.0630 3000413 3000413 3000413 3000413 3000413 3000413 3000413 3000413 3001213 CF-12/6,3 CF-12/10 CF-12/16 CF-12/20 CF-12/25 CF-12/31,5 CF-12/40 CF-12/50 CF-12/63 4236005 4236006 4236007 4236008 4236009 4236010 4236011 4236012 4236013 4235005 4235006 4235007 4235008 4235009 4235010 4235011 4235012 4235013 51006 511 M0 51006 512 M0 51006 513 M0 51006 514 M0 51006 515 M0 51006 516 M0 51006 517 M0 51006 518 M0 51006 519 M0 ES 6509 006 ES 6509 010 ES 6509 016 ES 6509 020 ES 6509 025 ES 6509 030 ES 6509 040 ES 6509 050 ES 6509 063 IB-D1 IB-D1 IB-D1 IB-D1 IB-D1 & IB-D2 IB-D1 & IB-D2 IB-D1 & IB-D2 IB-D2 IB-D2 1YMB531042M0001 1YMB531042M0002 1YMB531042M0003 1YMB531042M0004 1YMB531002M0004 1YMB531002M0014 1YMB531002M0005 1YMB531002M0006 1YMB531002M0007 12THLEJ80 12THLEJ100 12TKLEJ125 67120.0800 67120.1000 67120.1250 3001213 3001213 3001213 CF-12/80 CF-12/100 N/A 4236014 4236015 4236016 42350014 42350015 42350016 51006 520 M0 51006 521 M0 N/A ES 6509 080 ES 6509 100 N/A IB-D3 IB-D3 N/A 1YMB531002M0021 1YMB531002M0022 1YMB531043M0010 12TXLEJ160 12TXLEJ200 67220.1600 67220.2000 3002013 3002014 N/A N/A 4236017 N/A 4235017 N/A N/A N/A N/A N/A N/A N/A N/A N/A Watts Loss Comparison Lowest Watts Loss Part Number Watts Loss Watts Loss Watts Loss MESA Watts loss Watts Loss Watts Loss Watts Loss Watts Loss Watts Loss 12TDLEJ6.3 12TDLEJ10 12TDLEJ16 12TDLEJ20 12TDLEJ25 12TDLEJ31.5 12TDLEJ40 12TDLEJ50 12TDLEJ63 10 16 16 18 24 28 36 47 60 19 29 21 25 31 39 46 62 60 14 23 28 23 29 38 50 56 63 16 18 37 42 52 59 74 70 82 15 10 19 23 33 46 56 44 65 16 18 37 42 52 59 74 70 82 19 18 35 36 38 41 56 74 89 12 19 27 28 29 36 50 52 64 46 25 34 38 47 41 52 70 78 12THLEJ80 12THLEJ100 12TKLEJ125 72 85 93 82 96 117 76 104 159 102 120 - 77 104 152 102 120 - 108 112 - 95 120 - 82 101 125 12TXLEJ160 12TXLEJ200 217 333 217 333 173 292* - 200 - - - - - * derating factor apply Form No. 12kV DIN Page 2 of 13 Data sheet 720104 200A 160A 10/4/07 DATE APPD DATE APPD RE-DRAWN ON EXCEL. ECN11268 MPJ DRN DRN BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK. TEL. 01509 882600 FAX 01509 882786 100 1000 10000 R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES B APPD 10 FUSE TYPES: TXL CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT DATE 0.01 0.1 1 10 100 1000 10000 DRN VIRTUAL PRE-ARCING TIME IN SECONDS TIME- CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS PF 1197 100000 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Time Current Characteristics Form No. 12kV DIN Page 3 of 13 Data sheet 720104 DATE DRN 26/3/07 MPJ 0.01 0.1 1 10 100 1000 10000 MBC added ECN11268 APPD VIRTUAL PRE-ARCING TIME IN SECONDS C 10 DATE DRN 26/3/07 MPJ Update ECN11237 APPD B 1000 HH 21/3/07 1st ISSUE ECN11220 APPD DATE A BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK. 10000 TEL. 01509 882600 FAX 01509 882786 R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES DRN 100 6.3A 10A 16A 20A 25A 31.5A 40A 50A 63A 80A 100A 125A CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT TIME- CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS PF 1275 100000 FUSE TYPES: TDL/THL/TKL MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Time Current Characteristics Form No. 12kV DIN Page 4 of 13 Data sheet 720104 1st ISSUE ECN11220 21/3/07 M LENGTH ONLY ECN11268 HH APPD DATE 16/4/07 APPD DRN MPJ DATE B 1000 100A (THM) 125A (TKM) 160A (TFM) A BURTON-ON-THE-WOLDS LEIC, LE12 5TH, UK. 10000 TEL. 01509 882600 FAX 01509 882768 R.M.S. SYMMETRICAL PROSPECTIVE CURENT IN AMPERES DRN 100 APPD 10 100000 FUSE TYPES: THM / TKM / TFM CURVES RELATE TO MEAN PRE_ARCING TIMES WITH A TOLERANCE OF ±10% ON CURRENT DATE 0.01 0.1 1 10 100 1000 10000 DRN VIRTUAL PRE-ARCING TIME IN SECONDS TIME- CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS PF 1280 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Time Current Characteristics Form No. 12kV DIN Page 5 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Cut-Off Curves CUT-OFF CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS REF. No. PF 2275 FUSE TYPE TDL/THL/TKL NOTES 1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2 AND 3 BELOW. 2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT. FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF PROSPECTIVE CURRENT. 3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE. 100000 PEAK CUT-OFF CURRENT IN AMPERE S 40A 50A 63A 80A 100A 20A 25A 125A 10000 1000 6.3A 100 100 10A 1000 16A 31.5A 10000 100000 R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES DRN DATE APPD C DRN DATE APPD B DRN MPJ DATE 21/3/07 APPD 1st ISSUE MPJ ECN11220 A PF2275 BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600 FAX +44 (0) 1509 882786 Form No. 12kV DIN Page 6 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Cut-Off Curves CUT-OFF CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS REF. No. PF 2280 FUSE TYPE THM TKM TFM NOTES 1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2 AND 3 BELOW. 2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT. FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF PROSPECTIVE CURRENT. 3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE. 100000 PEAK CUT-OFF CURRENT IN AMPERE S 100A (THM) 125A (TKM) 160A (TFM) 10000 1000 100 100 1000 10000 100000 R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES DRN DATE APPD C DRN MPJ DATE 16/4/07 APPD B M LENGTH ONLY MPJ ECN11268 DRN MPJ DATE 21/3/07 APPD 1st ISSUE MPJ ECN11220 A PF2280 BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600 FAX +44 (0) 1509 882786 Form No. 12kV DIN Page 7 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps Cut-Off Curves CUT-OFF CURRENT CHARACTERISTIC FOR 12kV FUSE-LINKS REF. No. PF 2197 FUSE TYPE TXL NOTES 1. CURVES SHOW EXTREME MAXIMUM VALUES WHICH WILL NOT BE EXCEEDED UNDER CONDITIONS STATED IN 2 AND 3 BELOW. 2. FOR HIGH VALUES OF PROSPECTIVE CURRENT A SYMMETRICAL FAULT GIVES THE HIGHEST CUT-OFFCURRENT. FOR LOW VALUES OF PROSPECTIVE CURRENT, WHERE THERE IS LITTLE OR NO CURRENT LIMITATION, AN ASYMMETRICAL FAULT PASSES THE HIGHEST PEAKCURRENT. THE CURVES ARE THEREFORE BASED ON THE DEGREE OF ASYMMETRY WHICH GIVES THE MAXIMUM CUT-OFF CURRENT AT ANY PARTICULAR VALUE OF PROSPECTIVE CURRENT. 3. CURVES RELATE TO FREQUENCY OF 50 Hz AND A RECOVERY VOLTAGE EQUAL TO THE FUSE RATED VOLTAGE. 100000 PEAK CUT-OFF CURRENT IN AMPERE S 160A 200A 10000 1000 100 100 1000 10000 100000 R.M.S. SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES DRN DATE APPD C DRN DATE APPD B DRN MPJ DATE 20/4/07 APPD 1st ISSUE MPJ ECN11268 A PF2197 BURTON-ON-THE-WOLDS, LEICS., LE12 5TH, U.K. TEL +44 (0) 1509 882600 FAX +44 (0) 1509 882786 Form No. 12kV DIN Page 8 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps ASTA Certificate Form No. 12kV DIN Page 9 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps KEMA Certificate Form No. 12kV DIN Page 10 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps KEMA Certificate Form No. 12kV DIN Page 11 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps KEMA Report This report of performance details 12kV DIN rated fuse-links tested in accordance with IEC60282-1:2005 to demonstrate correct operation on a 7.2kV system Form No. 12kV DIN Page 12 of 13 Data sheet 720104 MEDIUM VOLTAGE DIN Fuse-Links MV DIN 12kV, Current Limiting Back-Up Fuse-Links, 6.3 to 200 Amps KEMA Report This report of performance details tests to IEC60282-1:2005 clause 7.6.3 to demonstrate the fuse-links ability to withstand arcing for greater than 0.1 seconds Form No. 12kV DIN Page 13 of 13 Data sheet 720104