Bussmann Fuse Tables.indd

High Speed Fuses
Bussmann® fuses for Danfoss Drives
VLT® 4000 Series
200-240 V
Standard
Alternate
Model
HP
KW
E4273
RK1/JDDZ
E4273
J/JDDZ
E4273
T/ JDDZ
4006
5.0
4.0
KTN-R-25
JKS-25
JJN-25
4008
7.5
5.5
KTN-R-30
JKS-30
JJN-30
4011
10
7.5
KTN-R-50
JKS-50
JJN-50
4016
15
11
KTN-R-60
JKS-60
JJN-60
4022
20
15
KTN-R-80
JKS-80
JJN-80
4027
25
18.5
KTN-R-125
JKS-125
JJN-125
4032
30
22
KTN-R-125
JKS-125
JJN-125
4042
40
30
KTN-R-150
-
-
4052
50
37
KTN-R-200
-
-
4062
60
45
KTN-R-250
-
-
KTS fuses from Bussmann may be substituted for KTN for 240 V drives; JJS fuses from Bussmann may be substituted for JJN for 240 V drives.
Maximum allowable fuse ratings listed. Smaller fuses of same type can be substituted. For more information, visit Danfoss at www.namc.danfoss.com
High Speed Fuses
Bussmann® fuses for Danfoss Drives
VLT® 4000 Series
380-460 V
Standard
Alternate
Model
HP
KW
E4273
RK1/JDDZ
E56412/E91958
JFHR2
E4273
J/JDDZ
E4273
T/ JDDZ
E4273
H/JDDZ
E125085
JFHR2
4006
5.0
4.0
KTS-R-15
-
JKS-15
JJS-15
-
-
4008
7.5
5.5
KTS-R-20
-
JKS-20
JJS-20
-
-
4011
10
7.5
KTS-R-25
-
JKS-25
JJS-25
-
-
4016
15
11
KTS-R-30
-
JKS-30
JJS-30
-
-
4022
20
15
KTS-R-40
-
JKS-40
JJS-40
-
-
4027
25
18.5
KTS-R-50
-
JKS-50
JJS-50
-
-
4032
30
22
KTS-R-60
-
JKS-60
JJS-60
-
-
4042
40
30
KTS-R-80
-
JKS-80
JJS-80
-
-
4052
50
37
KTS-R-100
-
JKS-100
JJS-100
-
-
4062
60
45
KTS-R-125
-
JKS-125
JJS-125
-
-
4072
75
55
KTS-R-150
-
JKS-150
JJS-150
-
-
4075
75
55
-
FWH-150B
-
-
-
-
4100
100
75
-
FWH-200B
-
-
-
-
4102
100
75
-
FWH-200B
-
-
-
-
4122
125
90
-
FWH-250A
-
-
-
-
4125
125
90
-
FWH-250A
-
-
-
-
4150
150
110
-
FWH-300A
-
-
-
-
4152
150
110
-
FWH-300A
-
JJS-300
NOS-300
170M3017
4200
200
132
-
FWH-350A
-
-
-
-
4202
200
132
-
FWH-350A
-
JJS-350
NOS-350
170M3018
4250
250
160
-
FWH-400A
-
-
-
-
4252
250
160
-
FWH-400A
-
JJS-400
NOS-400
170M4012
4300
300
200
-
FWH-500A
-
-
-
-
4302
300
200
-
FWH-500A
-
JJS-500
NOS-500
170M4014
4350
350
250
-
FWH-600A
-
-
-
-
4352
350
250
-
FWH-600A
-
JJS-600
NOS-600
170M4016
4450
450
315
-
FWH-700A
-
-
-
-
4500
500
355
-
FWH-800A
-
-
-
-
4600
600
400
-
FWH-800A
-
-
-
-
FWP fuses from Bussmann may be substituted for FWH for 500V drives.
170M fuses from Bussmann shown use -/80 visual indicator. -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted.
Maximum allowable fuse ratings listed. Smaller fuses of same type can be substituted. For more information, visit Danfoss at www.namc.danfoss.com
High Speed Fuses
Bussmann® fuses for Danfoss Drives
VLT® 4000 Series
525-600 V (UL)
525-600 V
Standard
Alternate
Model
HP
KW
E4273
RK1/JDDZ
E56412
JFHR2
E125085
JFHR2
E4273
J/JDDZ
E4273
T/ JDDZ
4006
5.0
4.0
KTS-R-8
-
-
JKS-8
JJS-10
4008
7.5
5.5
KTS-R-10
-
-
JKS-10
JJS-10
4011
10
7.5
KTS-R-15
-
-
JKS-15
JJS-15
4016
15
11
KTS-R-20
-
-
JKS-20
JJS-20
4022
20
15
KTS-R-30
-
-
JKS-30
JJS-30
4027
25
18.5
KTS-R-35
-
-
JKS-35
JJS-35
4032
30
22
KTS-R-45
-
-
JKS-45
JJS-45
4042
40
30
KTS-R-60
-
-
JKS-60
JJS-60
4052
50
37
KTS-R-75
-
-
JKS-80
JJS-80
4062
60
45
KTS-R-90
-
-
JKS-90
JJS-90
4072
75
55
KTS-R-100
-
-
JKS-100
JJS-100
4100
100
75
-
FWP-125A
-
-
-
4125
125
90
-
FWP-175A
-
-
-
4150
150
110
-
FWP-200A
-
-
-
4200
200
132
-
FWP-250A
-
-
-
4250
250
160
-
FWP-350A
-
-
-
4300
300
200
-
FWP-400A
-
-
-
4102
100
75
-
-
170M3015
-
-
4122
125
90
-
-
170M3016
-
-
4152
150
110
-
-
170M3017
-
-
4202
200
132
-
-
170M3018
-
-
4252
250
160
-
-
170M4011
-
-
4302
300
200
-
-
170M4012
-
-
4352
350
250
-
-
170M4014
-
-
4402
400
300
-
-
170M5011
-
-
170M fuses from Bussmann shown use -/80 visual indicator. -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted.
170M fuses from Bussmann when provided in the 525-600 V (UL) drives are 170M3015 for VLT 4102, 170M3018 for VLT 4122-4202, and 170M5011 for
VLT 4252-4402.
Maximum allowable fuse ratings listed. Smaller fuses of same type can be substituted. For more information, visit Danfoss at www.namc.danfoss.com