COOPER 1329I

High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
The following data sheets contain information obtained directly from the
manufacturer’s installation instruction manuals. Within each application
there are specific requirements that detail how the Power Electronic
Equipment should be installed and the proper overcurrent protection that has
been tested and approved by certified testing agencies.
The part numbers shown in this guide were obtained from the latest available
published information from the manufacturer. It is recommended that each
installation be checked against the manufacturer’s installation guides to
determine if any additional requirements are needed. Bussmann is not
responsible for mis-application of our products.
For the latest, most up-to-date product specifications listed in this guide please
visit us at http://www.bussmann.com or by calling the Bussmann Information
Fax (BIF) at 636-527-1450.
This guide is intended to clearly represent product data and provide technical information that will help the end user with
design/installation applications. Bussmann reserves the right, without notice, to change design or construction of any products and to
discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any information
contained in this guide. Once a product has been selected, it should be checked and tested by the end user in all possible applications.
P.O. Box 14460
St. Louis, MO 63178-4460
(636) 394-2877
3/11/200
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1302 AC Drive (575 Volts)
Maximum Short Circuit Rating is 30kA
AC Input Line Fuse Selection Values
Model
Voltage
Number
V
1302–C001–AA
575
1302–C001–AF
575
1302–C002–AA
575
1302–C002–AF
575
1302–C003–AA
575
1302–C003–AF
575
1302–C004–AA
575
1302–C005–AA
575
1302–C005–AF
575
1302–C007–AF
575
1302–C010–AA
575
1302–C010–AF
575
Fuse Block
J60030-3CR or JP60030-3CR
HP
1
1
2
2
3
3
5
5
7.5
7.5
10
10
Input
Current
A
2
2
3.4
3.4
5.2
5.2
7.5
7.5
10.9
10.9
14.5
14.5
Fuse
Part Number
LPJ-4SP
LPJ-4SP
LPJ-7SP
LPJ-7SP
LPJ-10SP
LPJ-10SP
LPJ-15SP
LPJ-15SP
LPJ-20SP
LPJ-20SP
LPJ-25SP
LPJ-25SP
Disconnect Switch
CFD30J3
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1305 Adjustable Frequency AC Drive (Series C)
0.37 - 5kW (0.5 - 5 HP)
Catalog Number
1305-AA02A
1305-AA03A
1305-AA04A
1305-AA08A
1305-AA12A
1305-BA01A
1305-BA02A
1305-BA03A
1305-BA04A
1305-BA06A
1305-BA09A
KTK-R
LPJ
Voltage
V
200-230
200-230
200-230
200-230
200-230
380-460
380-460
380-460
380-460
380-460
380-460
(0 to 30)
(0 to 30)
Three Phase Input
HP
kW
0.5
0.37
0.75
0.55
1
0.75
2
1.5
3
2.2
0.5
0.37
0.75
0.55
1
0.75
2
1.5
3
2.2
5
4
Single Phase Input
HP
kW
0.25
0.19
0.5
0.37
0.75
0.55
1
0.75
2
1.5
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
Bussmann
Class CC
KTK-R-6
KTK-R-6
KTK-R-10
KTK-R-15
KTK-R-25
KTK-R-6
KTK-R-10
KTK-R-15
KTK-R-20
Bussmann
Class J
LPJ-6SP
LPJ-6SP
LPJ-10SP
LPJ-15SP
LPJ-25SP
LPJ-3SP
LPJ-3SP
LPJ-6SP
LPJ-10SP
LPJ-15SP
LPJ-20SP
Disconnect Switches
CFD30CC3
CFD30J3
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1329 Intergrated Drive/Motor (Series B)
1,0 to 5.0 HP
Maximum Short Circuit Rating is 10kA
Catalog Number
1329I-BJ001
1329I-BK001
1329I-BK002
1329I-BL001
1329I-BL002
1329I-BM001
1329I-BM002
1329I-BM003
1329I-BM005
KTK-R
LPJ
Single Phase Three Phase
Voltage
Voltage
115
230
230
230
230
460
460
460
460
(0 to 30)
(0 to 30)
HP
1
1
2
1
2
1
2
3
5
Input
Current
14
5.8
14
4.5
7.6
2.3
3.7
5.7
9
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
Bussmann
Class CC
KTK-R-20
KTK-R-9
KTK-R-20
KTK-R-7
KTK-R-12
KTK-R-3.5
KTK-R-6
KTK-R-9
KTK-R-15
Bussmann
Class J
LPJ-20SP
LPJ-9SP
LPJ-20SP
LPJ-7SP
LPJ-12SP
LPJ-3.5SP
LPJ-6SP
LPJ-9SP
LPJ-15SP
Disconnect Switches
CFD30CC3
CFD30J3
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1333 3/4 to 20HP (.55-15kW) Adjustable Frequency AC Drive
Series D
Catalog Number
1333-ZAA
1333-AAA
1333-YAA
1333-BAA
1333-CAA
1333-DAA
1333-EAA
1333-FAA
1333-GAA
1333-AAB
1333-YAB
1333-BAB
1333-CAB
Amperage
0 to 30
35 to 60
65 to 100
110 to 200
HP kW
0.75 0.55
1
0.75
2
1.5
3
2.2
5
4
7.5 5.5
10
7.5
15
11
20
15
1
0.75
2
1.5
3
2.2
5
4
Single Phase
Voltage
230
230
230
230
230
230
230
230
230
Three Phase
Voltage
230
230
230
230
230
230
230
230
230
460
460
460
460
Single Phase
Current
6.2
8.6
9.5
13
18.8
23.4
31.1
41.6
54.6
Three Phase
Current
4.1
6.5
9
14
22
27
37
47
62
3.3
4.5
8
13
Bussmann
Class RK5
FRS-R-15
FRS-R-15
FRS-R-15
FRS-R-30
FRS-R-40
FRS-R-70
FRS-R-80
FRS-R-100
FRS-R-125
FRS-R-15
FRS-R-15
FRS-R-15
FRS-R-20
Fuse Blocks
R60030-3CR
R60060-3CR
R60100-3CR
R60200-3CR
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336 FORCE Adjustable Frequncy AC Drive
0.75 - 485 kW (1 - 650 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line
Drive Catalog
Rating
Number
kW
1336T– _ _ F10
0.75
1336T– _ _ F30
2.2
1336T– _ _ F50
3.7
1336T– _ _ 001
0.75
1336T– _ _ 003
2.2
1336T– _ _ 007
5.5
1336T– _ _ 010
7.5
1336T– _ _ 015
11
1336T– _ _ 020
15
1336T– _ _ 025
18.5
1336T– _ _ 030
22
1336T– _ _ 040
30
1336T– _ _ 050
37
1336T– _ _ X060
45
1336T– _ _ 060
45
1336T– _ _ 075
56
1336T– _ _ 100
75
1336T– _ _ 125
93
1336T– _ _ X150
112
1336T– _ _ 150
112
1336T– _ _ 200
149
1336T– _ _ 250
187
1336T– _ _ X300
224
KTK-R
LPJ
JJS
Amps
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
Fuse Ratings (fuses are user supplied)
Use Bussmann LPJ, KTK-R or JJS Fuses
HP
200–240V
380–480V
500–600V
1
10
6
–
3
25
15
–
5
40
20
–
1
10
6
6
3
15
10
10
7.5
40
20
15
10
50
30
20
15
70
35
25
20
100
45
35
25
100
60
40
30
125
70
50
40
150
80
60
50
200
100
80
60
–
100
–
60
250
125
90
75
–
150
110
100
–
200
150
125
–
250
175
150
–
250
–
150
–
300
225
200
–
400
350
250
–
450
400
300
–
–
400
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
J60600-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C (Single pole blocks)
T60400-1C (Single pole blocks)
T60600-1C (Single pole blocks)
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
FD600J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
FD600J3/BDTA6
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
(cont.)
Model 1336 FORCE Adjustable Frequncy AC Drive
0.75 - 485 kW (1 - 650 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Use Bussmann Semiconductor Fuses
Drive Catalog
Rating
380–480V
Number
kW
HP
200–240V
500–600V
FWP-450A
1336T– _ _ X250
187
250
–
–
FWP-450A
1336E– _ _ P250
187
250
–
–
FWP-450A
1336T– _ _ 300T
224
300
–
FWP-400A
FWP-500A
1336E– _ _ 300
224
300
–
FWP-450A
FWP-500A
1336T– _ _ 350
261
350
–
FWP-450A
FWP-600A
1336E– _ _ 350
261
350
–
FWP-600A
1336T– _ _ 400
298
400
–
FWP-500A
FWP-600A
1336E– _ _ 400
298
400
–
FWP-800A
1336T– _ _ 450
336
450
–
FWP-600A
FWP-700A
1336E– _ _ 450
336
450
–
FWP-600A
FWP-800A
1336T– _ _ 500
373
500
–
FWP-800A
FWP-900A
1336T– _ _ 600
448
600
–
FWP-800A
–
1336T– _ _ 650
485
650
–
FWP-800A
1336T– _ _ 700C
522
700
–
FWP-600A{1}
FWP-700A{1}
1336T– _ _ 800C
597
800
–
FWP-700A{1}
FWP-700A{1}
{1} Two Fuses in parallel are required.
FWP
Amps
450 - 600
700
Fuse Blocks
1BS104
BH-3145
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336 IMPACT Adjustable Frequency AC Drive
0.37 - 597 kW (0.5 - 800 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Use Bussmann LPJ, KTK-R or JJS Fuses
Drive Catalog
Rating
Number
kW
HP
200–240V
380–480V
500–600V
1336E-_ _ F05
0.37
0.5
6
3
1336E-_ _ F07
0.56
0.75
6
3
1336E-_ _ F10
0.75
1
10
6
3
1336E-_ _ F15
1.2
1.5
15
6
1336E-_ _ F20
1.5
2
15
10
6
1336E-_ _ F30
2.2
3
25
15
10
1336E-_ _ F50
3.7
5
40
20
0.1
1336E-_ _ F75
5.5
7.5
20
15
1336E-_ _ F100
7.5
10
30
20
1336E-_ _ 007
5.5
7.5
40
20
15
1336E-_ _ 010
7.5
10
50
30
20
1336E-_ _ 015
11
15
70
35
25
1336E-_ _ 020
15
20
100
45
35
1336E-_ _ 025
18.5
25
100
60
40
1336E-_ _ 030
22
30
125
70
50
1336E-_ _ X040
30
40
150
80
60
1336E-_ _ 040
30
40
150
80
60
1336E-_ _ 050
37
50
200
100
80
1336E-_ _ X060
45
60
100
1336E-_ _ 060
45
60
250
125
90
1336E-_ _ 075
56
75
300
150
110
1336E-_ _ 100
75
100
400
200
150
1336E-_ _ 125
93
125
450
250
175
1336E-_ _ X150
112
150
250
1336E-_ _ 150
112
150
300
225
1336E-_ _ 200
149
200
400
350
1336E-_ _ 250
187
250
450
400
1336E-_ _ X300
224
300
400
KTK-R
LPJ
JJS
Amps
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
J60600-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C
(Single pole blocks)
T60400-1C
(Single pole blocks)
T60600-1C
(Single pole blocks)
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
FD600J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
FD600J3/BDTA6
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
(cont.)
Model 1336 IMPACT Adjustable Frequency AC Drive
0.37 - 597 kW (0.5 - 800 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Drive Catalog
Rating
Use Bussmann Semiconductor Fuses
Number
kW
HP
200–240V
380–480V
500–600V
1336E-_ _ 300
224
300
FWP-500A
FWP-400A
1336E-_ _ P300
224
300
FWP-500A
1336E-_ _ 350
224
300
FWP-600A
FWP-450A
1336E-_ _ P350
261
350
FWP-600A
1336E-_ _ 400
298
400
FWP-600A
FWP-500A
1336E-_ _ P400
298
400
FWP-600A
1336E-_ _ 450
336
450
FWP-800A
FWP-600A
1336E-_ _ P450
336
450
FWP-700A
1336E-_ _ 500
373
500
FWP-800A
FWP-800A
1336E-_ _ 600
448
600
FWP-900A
FWP-800A
1336E-_ _ 650
485
650
FWP-800A
1336E-_ _ 700C
522
700
FWP-600A{1}
FWP-700A{1}
1336E-_ _ 800C
597
800
FWP-700A{1}
FWP-700A{1}
{1} Two Fuses in parallel are required.
FWP
Amps
450 - 600
700
Fuse Blocks
1BS104
BH-3145
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336 PLUS Adjustable Frequency AC Drive
0.37 - 448 kW (0.5 - 600 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Use Bussmann LPJ, KTK-R or JJS Fuses
Drive Catalog
Rating
Number
kW
HP
200–240V
380–480V
500–600V
1336S-_ _ F05
0.37
0.5
6
3
1336S-_ _ F07
0.56
0.75
6
3
1336S-_ _ F10
0.75
1
10
6
6
1336S-_ _ F15
1.2
1.5
15
6
1336S-_ _ F20
1.5
2
15
10
10
1336S-_ _ F30
2.2
3
25
15
15
1336S-_ _ F50
3.7
5
40
20
20
1336S-_ _ F75
5.5
7.5
20
1336S-_ _ F100
7.5
10
30
1336S-_ _ 007
5.5
7.5
40
20
15
1336S-_ _ 010
7.5
10
50
30
20
1336S-_ _ 015
11
15
70
35
25
1336S-_ _ 020
15
20
100
45
35
1336S-_ _ 025
18.5
25
100
60
40
1336S-_ _ 030
22
30
125
70
50
1336S-_ _ 040
30
40
150
80
60
1336S-_ _ 050
37
50
200
100
80
1336S-_ _ X060
45
60
100
1336S-_ _ 060
45
60
250
125
90
1336S-_ _ 075
56
75
300
150
110
1336S-_ _ 100
75
100
400
200
150
1336S-_ _ 125
93
125
450
250
175
1336S-_ _ X150
112
150
250
1336S-_ _ 150
112
150
300
225
1336S-_ _ 200
149
200
400
350
1336S-_ _ 250
187
250
450
400
1336S-_ _ X300
224
300
400
KTK-R
LPJ
JJS
Amps
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
J60600-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C (Single pole blocks)
T60400-1C (Single pole blocks)
T60600-1C (Single pole blocks)
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
FD600J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
FD600J3/BDTA6
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
(cont.)
Model 1336 PLUS Adjustable Frequency AC Drive
0.37 - 448 kW (0.5 - 600 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Drive Catalog
Rating
Use Bussmann Semiconductor Fuses
Number
kW
HP
200–240V
380–480V
500–600V
1336S-_ _ P250
187
250
FWP-450A
1336S-_ _ X250
187
250
FWP-450A
1336S-_ _ 300
224
300
FWP-450A
FWP-400A
1336S-_ _ P300
224
300
FWP-500A
1336S-_ _ 350
261
350
FWP-500A
FWP-450A
1336S-_ _ P350
261
350
FWP-600A
1336S-_ _ 400
298
400
FWP-600A
FWP-500A
1336S-_ _ P400
298
400
FWP-600A
1336S-_ _ 450
336
450
FWP-800A
FWP-600A
1336S-_ _ P450
336
450
FWP-700A
1336S-_ _ 500
373
500
FWP-800A
FWP-800A
1336S-_ _ 600
448
600
FWP-900A
FWP-800A
FWP
Amps
450 - 600
700
Fuse Blocks
1BS104
BH-3145
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
M odel 1336 PLUS II Adjustable Frequency AC Drive
0.37 - 448 kW (0.5 - 600 HP)
M aximum Short Circuit Rating is 200kA
M aximum Recom mended AC Input Line Fuse Ratings (fuses are user supplied)
Use Bussm ann LPJ, KTK-R or JJS Fuses
Drive Catalog
Rating
Num ber
kW
HP
200–240V
380–480V
500–600V
1336F- _ _ F05
0.37
0.5
4
3
1336F- _ _ F05 Series A
0.37
0.5
6
3
1336F- _ _ F07
0.56
0.75
4
3
1336F- _ _ F07 Series A
0.56
0.75
6
3
1336F- _ _ F10
0.75
1
6
3
3
1336F- _ _ F10 Series A
0.75
1
10
6
6
1336F- _ _ F15
1.2
1.5
8
4
1336F- _ _ F15 Series A
1.2
1.5
15
6
1336F- _ _ F20
1.5
2
10
5
6
1336F- _ _ F20 Series A
1.5
2
15
10
10
1336F- _ _ F30
2.2
3
15
8
10
1336F- _ _ F30 Series A
2.2
3
25
15
15
1336F- _ _ F50
3.7
5
25
12
15
1336F- _ _ F50 Series A
3.7
5
40
20
20
1336F- _ _ F75
5.5
7.5
30
20
15
1336F- _ _ F100
7.5
10
30
20
1336F- _ _ F150
11
15
35
25
1336F- _ _ F200
15
20
35
30
1336F- _ _ 007
5.5
7.5
40
20
15
1336F- _ _ 010
7.5
10
50
30
20
1336F- _ _ 015
11
15
70
35
25
1336F- _ _ 020
15
20
100
45
35
1336F- _ _ 025
18.5
25
100
60
40
1336F- _ _ 030
22
30
125
70
50
1336F- _ _ 040/X040
30
40
150
80
60
1336F- _ _ 050
37
50
200
100
80
1336F- _ _ X060
45
60
100
1336F- _ _ 060
45
60
250
125
90
1336F- _ _ 075
56
75
300
150
110
1336F- _ _ 100
75
100
400
200
150
1336F- _ _ 125
93
125
450
250
175
1336F- _ _ X150
112
150
250
1336F- _ _ 150
112
150
300
225
1336F- _ _ 200
149
200
400
350
1336F- _ _ 250
187
250
450
400
1336F- _ _ X300
224
300
400
KTK-R
LPJ
JJS
Am ps
Fuse Blocks
Disconnect Switches
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
J60600-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C
(Single pole blocks)
T60400-1C
(Single pole blocks)
T60600-1C
(Single pole blocks)
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
FD600J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
FD600J3/BDTA6
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
(cont.)
Model 1336 PLUS II Adjustable Frequency AC Drive
0.37 - 448 kW (0.5 - 600 HP)
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Drive Catalog
Rating
Use Bussmann Semiconductor Fuses
Number
kW
HP
200–240V
380–480V
500–600V
1336F- _ _ BP/BPR250
187
250
FWP-450A
1336F- _ _ X250
187
250
FWP-450A
1336F- _ _ 300
224
300
FWP-450A
FWP-400A
1336F- _ _ BP/BPR300
224
300
FWP-500A
1336F- _ _ 350
261
350
FWP-500A
FWP-450A
1336F- _ _ BP/BPR350
261
350
FWP-600A
1336F- _ _ 400
298
400
FWP-600A
FWP-500A
1336F- _ _ BP/BPR400
298
400
FWP-600A
1336F- _ _ 450
336
450
FWP-800A
FWP-600A
1336F- _ _ BP/BPR450
336
450
FWP-700A
1336F- _ _ 500
373
500
FWP-800A
FWP-800A
1336F- _ _ 600
448
600
FWP-900A
FWP-800A
FWP
Amps
450 - 600
700
Fuse Blocks
1BS104
BH-3145
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336 SPIDER Adjustable Frequency Drive for the Fibers Industry
9.9A - 60A
Maximum Short Circuit Rating is 200kA
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Use Bussmann LPJ, KTK-R or JJS Fuses
Drive Catalog
Rating
Input
kW
Current
200–240V
380–480V
Number
1336Z- _ _ A022
1.8
7.6
30
1336Z- _ _ A036
3
12.5
30
1336Z- _ _ A060
5
24.6
50
1336Z- _ _ B010
1.6
8.7
20
1336Z- _ _ B017
2.7
11.4
20
1336Z- _ _ B033
5.5
19.8
40
KTK-R
LPJ
JJS
Amps
0 to 30
0 to 30
35 to 60
0 to 30
35 to 60
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
T60030-3CR
T60060-3CR
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
1336/1336VT/1336 PLUS/1336 PLUS II/FORCE/IMPACT
Series A Brake Chopper
Dynamic Brake Fuse
All brake modules are internally fused to protect brake components.
Dynamic Brake
Fuse
Rating
Recommended Fuse
1336-WA018
F1 & F2
30A, 600V FWC-30A10F
1336-WB009
F1 & F2
15A, 600V FWC-15A10F
1336-WC009
F1 & F2
15A, 600V FWC-15A10F
1336-WA070
F1 & F2
125A, 700V FWP-125A
1336-WB035
F1 & F2
60A, 700V FWP-60A
1336-WC035
F1 & F2
60A, 700V FWP-60A
1336-WA115
F1 & F2
200A, 700V FWP-200A
1336-WB110
F1 & F2
200A, 700V FWP-200A
1336-WC085
F1 & F2
200A, 700V FWP-200A
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336 Adjustable Frequency AC Drive
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Input
Input
Recommended Bussmann
Catalog Number
Current
Voltage
1336-B003
5.7
460
KTK-R-10
JJS-10
1336-B005
9.2
460
KTK-R-15
JJS-15
1336-B007
13.3
460
KTK-R-20
JJS-20
1336-B010
17
460
KTK-R-25
JJS-25
1336-B015
25
460
JJS-35
1336-B020
34
460
JJS-45
1336-B025
42
460
JJS-60
1336-B030
49
460
JJS-70
1336-B040
61
460
JJS-80
1336-B050
76
460
JJS-100
1336-B075
122
460
JJS-150
1336-B100
153
460
JJS-200
1336-B125
184
460
JJS-250
1336-B150
222
460
JJS-300
1336-B200
296
460
JJS-400
1336-C003
3.2
575
KTK-R-6
JJS-6
1336-C005
4.1
575
KTK-R-6
JJS-6
1336-C007
7.7
575
KTK-R-10
JJS-10
1336-C010
10.2
575
KTK-R-15
JJS-15
1336-C015
15
575
JJS-20
1336-C020
19
575
JJS-25
1336-C025
24
575
JJS-30
1336-C030
29
575
JJS-35
1336-C040
39
575
JJS-45
1336-C050
48
575
JJS-60
1336-C075
73
575
JJS-90
1336-C100
97
575
JJS-125
1336-C125
121
575
JJS-150
1336-C150
146
575
JJS-175
1336-C200
193
575
JJS-250
KTK-R
LPJ
JJS
Amps
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C
(Single pole blocks)
T60400-1C
(Single pole blocks)
Fuse
JKS-35
JKS-45
JKS-60
JKS-70
JKS-80
JKS-100
JKS-150
JKS-200
JKS-250
JKS-300
JKS-400
JKS-20
JKS-25
JKS-30
JKS-35
JKS-45
JKS-60
JKS-90
JKS-125
JKS-150
JKS-175
JKS-250
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Heavy Duty Dynamic Braking
for use with 1336/1336VT/1336 PLUS/1336 FORCE Drives
All brake modules are internally fused to protect brake components.
Dynamic Brake
Fuse
Rating
Recommended Fuse
1336-MOD-KA005
F1
10A, 500V FWH-10A14F
1336-MOD-KB005
F1
5A, 600V FWC-5A10F
1336-MOD-KC005
F1
5A, 700V FWP-5A14F
1336-MOD-KA010
F1
20A, 500V FWH-20A14F
1336-MOD-KB010
F1
10A, 600V FWC-10A10F
1336-MOD-KC010
F1
10A, 700V FWP-10A14F
1336-MOD-KA050
F1 & F2
50A, 500V FWH-50A
1336-MOD-KB050
F1 & F2
35A, 700V FWP-35A
1336-MOD-KC050
F1 & F2
35A, 700V FWP-35A
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1336VT Adjustable Frequency AC Drive
Catalog Number
1336VT-B003
1336VT-B005
1336VT-B007
1336VT-B010
1336VT-B015
1336VT-B020
1336VT-B025
1336VT-B030
1336VT-B040
1336VT-B050
1336VT-B060
1336VT-B075
1336VT-B100
1336VT-B125
1336VT-B150
1336VT-B200
1336VT-B250
KTK-R
LPJ
JJS
Input
Current
5.6
7.5
11.4
14.6
22
28
35
44
54
67
78
97
124
154
178
235
296
Amps
0 to 30
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
0 to 30
35 to 60
65 to 100
110 to 200
225 to 400
450 to 600
Input
Voltage
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
460
Recommended Bussmann Fuse
KTK-R-10
KTK-R-15
KTK-R-20
KTK-R-25
Fuse Blocks
BC6033B or OPM-NG-SC3
J60030-3CR or JP60030-3CR
J60060-3CR
J60100-3CR
J60200-3CR
J60400-3CR
J60600-3CR
T60030-3CR
T60060-3CR
T60100-3C
T60200-1C
(Single pole blocks)
T60400-1C
(Single pole blocks)
T60600-1C
(Single pole blocks)
JJS-35
JJS-45
JJS-60
JJS-70
JJS-80
JJS-100
JJS-110
JJS-150
JJS-200
JJS-250
JJS-300
JJS-400
JJS-500
JKS-30
JKS-45
JKS-60
JKS-60
JKS-80
JKS-100
JKS-110
JKS-150
JKS-200
JKS-250
JKS-300
JKS-400
JKS-500
Disconnect Switches
CFD30CC3
CFD30J3
CDF60J3
CFD100J3
FD200J3
FD400J3
FD600J3
CFD100J3/BDTA1
FD200J3/BDTA2
FD400J3/BDTA4
FD600J3/BDTA6
3/11/2002
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1391-DES Digital AC Servo Drive
Recommended fuse for transformer primary protection
XFMR
Catalog Number
KVA Rating
208
240
1391-T015
1.5
FRS-R-8
FRS-R-7
1391-T035
3.5
FRS-R-17-1/2 FRS-R-15
1391-T050
5
FRS-R-20
FRS-R-20
1391-T100
10
FRS-R-40
FRS-R-35
1391-T125
12.5
FRS-R-50
FRS-R-45
1391-T150
15
FRS-R-60
FRS-R-50
Voltage
380
415
FRS-R-4-1/2 FRS-R-4
FRS-R-9
FRS-R-8
FRS-R-12
FRS-R-12
FRS-R-25
FRS-R-20
FRS-R-30
FRS-R-25
FRS-R-35
FRS-R-30
480
FRS-R-3-1/2
FRS-R-7
FRS-R-10
FRS-R-17-1/2
FRS-R-25
FRS-R-30
Recommended fusing for shunt regulator.
Drive Rating
Fuse Location
Bussmann
15 Amps
Top Panel
KLM-10
22.5 Amps
Top Panel
FNM-6-1/4
22.5 Amps
External
KTK-15
45 Amps
External
KLM-20
3/11/2002
575
FRS-R-3
FRS-R-6
FRS-R-8
FRS-R-15
FRS-R-20
FRS-R-25
High Speed Fuses
Bussmann Fuses in Allen-Bradley Drives
TECHNICAL LITERATURE
Model 1394 Digital AC Multi-Axis Motion Control System
Maximum Short Circuit Rating of 100kA
Line Input Fusing
Catalog Number
1394-SJT05 Systems
1394C-SJT05 Systems
1394-SJT10 Systems
1394C-SJT10 Systems
1394x-SJT22 Systems
Shunt Module
Catalog Number
1394-SR9A
1394-SR9AF
1394-SR10A
1394-SR36A
1394-SR36AF
Series
Series A and B
Series C
Series A and B
Series C
Shunt has UL
FWP-50A14F
FWP-50A14F
FWP-40A14F
FWP-50A14F
FWP-50A14F
24 Volt Logic Input Power
24V logic input
voltage
19-28V AC
19-28V AC
18.75-31.25 DC
18.75-31.25 DC
Axis
1
2
3
4
Recommended Bussmann Fuses
FRS-R-20
KTK-R-20
LPJ-20SP
FRS-R-30
KTK-R-30
LPJ-30SP
FRS-R-35
LPS-RK-40SP
LPJ-45SP
Shunt has no UL
170N2013
FWP-50A22F
170N2013
FWP-50A22F
170N2013
170N2013
Current
3.5
4.4
5.2
6
FWP-50A22F
FWP-50A22F
Recommended
Fuse
MDA-15
MDA-15
MDA-15
MDA-15
3/11/2002