CERTIFICATE OF COMPLIANCE Issue Date 20120323-E305318 E305318-20060525 2012-March-23 Issued to: ALTECH CORP Certificate Number Report Reference 35 ROYAL RD FLEMINGTON, NJ 08822 USA This is to certify that representative samples of CIRCUIT BREAKERS, MOLDED CASE AND CIRCUIT-BREAKER ENCLOSURES XYURRL, DCXYURRL and XYURRL-HI X = 1, 2, 3 or 4 Y = B, C, K or D RR = 0.2A up to 63A Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: Additional Information: UL489 – The Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures C22.2 No.5-02 - The Standard for Molded-Case Circuit Breakers, MoldedCase Switches and Circuit-Breaker Enclosures See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Listing Mark for the US and Canada should be considered as being covered by UL's Listing and Follow-Up Service meeting the appropriate requirements for US and Canada. The UL Listing Mark for the US and Canada generally includes: the UL in a circle symbol with “C” and “US” identifiers: the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product. William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus Page 1 of 2 CERTIFICATE OF COMPLIANCE Certificate Number Report Reference Issue Date 20120323-E305318 E305318-20060525 2012-March-23 This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements. RATINGS Circuit breaker frame: Current: 63A 0.2A to max. 63A Voltage and Interrupting Rating as follows: Type AC DC Rated current Poles Voltage 0.2A – 32A 33A – 63A 0.2A – 32A 33A – 63A 0.2A – 20A (+) up to 63A up to 63A 1 1 2, 3, 4 2, 3, 4 1 1 2 277Vac 240Vac 480/277Vac 240Vac 277Vac 125Vdc 250Vdc High Interrupting current N/A 10kA N/A 10kA 14kA 10kA 10kA (+) – This is for the ‘C’ trip curve characteristic only (i.e. only for Models 1CU20L, 1CU20L-HI). William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus Page 2 of 2