$ 49 95 Va lue Based on the 2008 NEC® SPD - Selecting Protective Devices Section 4 - Industrial Control Panels, Pages 87 to 107 Introduction Selecting Protective Devices Handbook (SPD) Based on the 2008 NEC® Welcome to the Cooper Bussmann® Selecting Protective Devices Handbook (SPD). This is a comprehensive guide to electrical overcurrent protection and electrical design considerations. Information is presented on numerous applications as well as the requirements of codes and standards for a variety of electrical equipment and distribution systems. How to Use: The SPD is comprised of major sections which are arranged by topic. There are three methods for locating specific information contained within: 1. Table of Contents: The table of contents sequentially presents the major sections and their contents. New or revised sections are noted in red text. 2. Index: The index, found on page 265, is more detailed than the table of contents and is organized alphabetically by topic with corresponding page number references. 3. 2008 NEC® Section Index: The NEC® Section Index, found on page 264, makes it easy to find information associated with specific National Electrical Code® section references. For other technical resources and product information visit www.cooperbussmann.com. This handbook is intended to clearly present product data and technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit their distribution. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this handbook. Once a product has been selected, it should be tested by the user in all possible applications. Further, Cooper Bussmann takes no responsibility for errors or omissions contained in this handbook, or for mis-application of any Cooper Bussmann product. Extensive product and application information is available online at: www.cooperbussmann.com. National Electrical Code® is a trademark of the National Fire Protection Association, Inc., Batterymarch Park, Quincy, Massachusetts, for a triennial electrical publication. The term, National Electrical Code, as used herein means the triennial publication constituting the National Electrical Code and is used with permission of the National Fire Protection Association, Inc. ©2008 Cooper Bussmann 3 Cooper Bussmann Selecting Protective Devices Table of Contents (Red indicates NEW or significantly REVISED information) Industrial Control Panels . . . . . . . . . . .87 - 107 Short-Circuit Current Rating Marking Requirements . . . . . . . . . . . . . . . . . . .87-88 Determining Assembly SCCR: Two Sweep Method . . . . . . . . . . . . . . . . . . . .89 - 90 Umbrella Fuse Limits . . . . . . . . . . . . . . . . . . . .91 - 93 Determining Assembly SCCR: Example . . . .94 - 104 Increasing Assembly SCCR . . . . . . . . . . . . . .105-107 4 ©2008 Cooper Bussmann Industrial Control Panels - SCCR Short-Circuit Current Rating (SCCR) The 2008 NEC® has a new definition of “Short-Circuit Current Rating” (SCCR). Previously there was no definition of short-circuit current rating (sometimes referred to as “withstand rating”), although it was referenced in several sections on the marking and proper application of various types of equipment. Because the term is referenced in multiple locations of the Code, it was necessary to add a definition to Article 100 of the NEC®. Article 100 Definitions Short-Circuit Current Rating. The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria. Figure 2 What is Short-Circuit Current Rating? Short-Circuit Current Rating (SCCR) is the maximum short-circuit current a component or assembly can safely withstand when protected by a specific overcurrent protective device(s) or for a specified time. Adequate short-circuit current rating is required per NEC® 110.10. AWG Class J Fuse Wire Range Max. Amp 2-6 400A 2-14 200A 2-14 175A Resulting SCCR 200kA 50kA 100kA This power distribution block, protected with Class J fuses, is rated for use on a circuit capable of delivering no more than the SCCR kA shown (kA rms sym. or DC amps 600V maximum). Figure 1 Figure 1 illustrates a Power Distribution Block (PDB) that has a default SCCR of 10kA per UL 508A SB4 Table SB4.1. However, this PDB has been combination tested and UL Listed with higher SCCRs when in combination with specific types and maximum amp rating current-limiting fuses. The label is marked with a 200kA SCCR when protected by 400A or less Class J fuses and the conductors on the lineside and loadside are in the range of 2 to 6AWG. When analyzing assemblies for short-circuit current rating, the interrupting rating of overcurrent protective devices and the short-circuit current rating of all other components affect the overall equipment/assembly short-circuit current rating. For instance, the short-circuit current rating of an industrial control panel typically can not be greater than the lowest interrupting rating of any fuse or circuit breaker, or the lowest short-circuit current rating of all other components in the enclosure. Why is Short-Circuit Current Rating Important? Short-circuit current ratings provide the level of fault current that a component or piece of equipment can safely withstand (based on a shock hazard or a fire hazard external to the enclosure). Without knowing the available fault current and short-circuit current rating, it is impossible to determine if components or equipment can be safely installed. Specification and installation of new equipment with higher short-circuit current ratings, such as 200,000 amps, makes it easy to meet the requirements of the NEC®. In addition, when equipment is later moved within a facility or from plant to plant, equipment with the highest ratings can be moved without worrying about unsafe situations that might arise from placing the equipment in a new location where the available short-circuit current is higher than the old location and now above the rating of the equipment. “Short-circuit current rating” is not the same as “interrupting rating” and the two must not be confused. Interrupting rating is the maximum short-circuit current an overcurrent protective device can safely interrupt under standard test conditions; it does not ensure protection of the circuit components or equipment. Adequate interrupting rating is required per NEC® 110.9. The fuse in Figure 2 has a UL Listed interrupting rating of 300kA @ 600Vac or less. ©2008 Cooper Bussmann 87 Industrial Control Panels - SCCR SCCR Marking Requirements & Compliance What are the Short-Circuit Current Rating Marking Requirements? The NEC® has requirements for certain components and equipment to be marked with their short-circuit current rating. The important sections of the Code that require the marking of the short-circuit current rating include the following areas. Meter Disconnect Switches: 230.82(3) permits a meter disconnect switch (rated up to 600V) ahead of the service disconnecting means, provided the meter disconnect switch has a short-circuit current rating adequate for the available short-circuit current. Industrial Control Panels: 409.110 requires that an industrial control panel be marked with its short-circuit current rating (see Figure 3). Motor Controllers: 430.8 requires that motor controllers be marked with their short-circuit current rating. There are three exceptions: • For fractional horsepower motor controllers • Two horsepower or less general-purpose motor controllers, and • Where the short-circuit current rating is marked on the assembly How to Assure Compliance? To assure proper application, the designer, installer and inspector must assure that the marked short-circuit current rating of a component or equipment is not exceeded by the calculated available fault current. In order to assure compliance it is necessary to: 1. Determine the available short-circuit current or fault current at the point of installation of the component or equipment. 2. Assure the component or equipment marked short-circuit current rating (see Figure 3 for example) is equal to or greater than the available fault current. Figure 3 (Courtesy IAEI) Industrial Machinery Electrical Panel: 670.3(A) requires the nameplate on industrial machinery to include the short-circuit current rating of the machine industrial control panel. In previous editions of the NEC® (2002 Edition) and NFPA 79 (2002 Edition), the industrial machine nameplate was required to include only the interrupting rating of the machine overcurrent protective device, if furnished. This marking was misleading as it did not represent the short-circuit current rating of the machine industrial control panel, but could be misinterpreted as such. Figure 4 illustrates compliance of short-circuit ratings from a system perspective. Any installation where the component or equipment marked shortcircuit current rating is less than the available fault current is a lack of compliance, a safety hazard, and violation of 110.10. In these cases, the equipment cannot be installed until the component or equipment short-circuit current rating is sufficient or the fault current is reduced to an acceptable level. Interior of modern industrial machinery panel. Air Conditioning and Refrigeration Equipment with Multimotor and Combination Loads: 440.4(B) requires the nameplate of this equipment to be marked with its short-circuit current rating. There are three exceptions for which this requirement does not apply: • One and two family dwellings • Cord and attachment-plug connected equipment, or • Equipment on a 60A or less branch circuit So for most commercial and industrial applications, air conditioning and refrigeration equipment with multimotor and combination loads must have the short-circuit current rating marked on the nameplate. 88 Figure 4 (Courtesy NJATC) ©2008 Cooper Bussmann Industrial Control Panels - SCCR Determining Assembly SCCR: “Two Sweep” Method & Procedures How to Determine Assembly SCCR For components, the Short-Circuit Current Rating (SCCR) is typically determined by product testing. For assemblies, the marking can be determined through the equipment product listing standard or by an approved method. With the release of the UL 508A, UL Standard for Safety for Industrial Control Panels, an industry-approved method is now available. UL 508A, Supplement SB, provides an analytical method to determine the short-circuit current rating of an industrial control panel. This method is based upon the “weakest link” approach. In other words, the assembly marked short-circuit current rating is limited to the lowest rated component short-circuit current rating or the lowest rated overcurrent protective device interrupting rating. Since testing is not required with this method, it is typically the preferred method to use in determining the assembly SCCR. There are two basic concepts that must be understood and identified before analyzing the assembly SCCR per UL 508A, Supplement SB. The first is power circuit vs. control circuit. The second is branch circuit vs. feeder circuit. The differences and importance of these concepts are detailed below: • Per UL 508A: a power circuit is defined as the conductors and components of branch and feeder circuits. A branch and feeder circuit carries main line power current to loads such as motors, lighting, heating, appliances and general use receptacles. A control circuit is a circuit that carries the electric signals directing the performance of a controller, and which does not carry the main power current. Only devices in power circuits and overcurrent devices protecting control circuits affect the assembly SCCR. • Per UL 508A: a branch circuit is defined as the conductors and components following the final branch circuit overcurrent protective device protecting a load. A feeder circuit is the conductors and circuitry on the supply side of the branch circuit overcurrent protective device(s). In some cases, as will be discussed later; current-limiting devices in the feeder circuit can be used to increase the SCCR of branch circuit components. In addition, larger spacings are required for components used in feeder circuits versus when used in branch circuits. This is especially important for power distribution and terminal blocks, if used in feeder circuits. Using the “Two Sweep” Method Based on UL 508A After all the power circuit components and overcurrent devices protecting control circuits have been identified, the “Two Sweep” method based on UL 508A can be used to determine the assembly Short-Circuit Current Rating (SCCR). The purpose of performing two sweeps in this method is to assure that the overcurrent protective device interrupting rating (or SCCR for some devices) are never increased by an upstream overcurrent protective device. UL 508A requirements strictly prohibit any overcurrent protective device interrupting rating (or SCCR for some devices) from being raised beyond the marked interrupting rating by an upstream overcurrent protective device. Hence series rating of overcurrent devices is prohibited. Sweep 1: The Component Protection Sweep The first sweep reviews all components in the branch, feeder, sub-feeder and supply circuits, and determines the component with the lowest SCCR. Sweep 2: The Overcurrent Protection Sweep The second sweep reviews all overcurrent protection devices in the branch, feeder and supply circuits, and determines the lowest interrupting rating (or short-circuit current rating for some devices). ©2008 Cooper Bussmann The lowest rating from Sweep 1 and Sweep 2 identifies the assembly SCCR. Because this method determines the assembly SCCR, it may be referred to as the “FIND IT.” Note: It is necessary to complete both Sweeps and all Steps to determine an assembly’s SCCR marking. If an assembly SCCR marking is inadequate, then see the “FIX IT” portion at the end of this section for suggestions on how to increase an assembly’s marked SCCR. Procedures for the “Two Sweep” Method Each sweep of this method is broken down into steps. Sweep 1 has five steps and Sweep 2 has three steps. The following shows the procedure for completing the steps of both sweeps. Sweep 1: Verifying assembly component SCCRs Step 1: Determine the component SCCR for each branch circuit: • Identify all component short-circuit current ratings and any special conditions that exist to utilize the ratings by one of the following methods: 1. The SCCR based on the default ratings per UL 508A Table SB4.1 (see Table SCCR1 - Default SCCR Ratings). 2. The SCCR marked on the component or instruction sheet provided with the component. 3. The SCCR based on testing with a specific overcurrent protective device and/or combination of components in accordance with product standards and documented by the manufacturer. Example: a motor controller may have an SCCR of 100kA with a 30A Class J fuse, but only 5kA with a 30A circuit breaker. • Take and apply the lowest SCCR of any component used in a branch circuit as the SCCR for that branch circuit. Repeat this for each branch circuit in the assembly. • Note the lowest branch circuit SCCR for every branch circuit in the assembly or panel. Step 2: Determine the component SCCR for each feeder circuit (includes supply, feeders and sub-feeders): • Identify all component SCCRs and any special conditions that exist to utilize the ratings by one of the following methods: 1. The SCCR based on the default ratings per UL 508A Table SB4.1 (see Table SCCR1 - Default SCCR Ratings). 2. The SCCR marked on the component or instruction sheet provided with the component. 3. The SCCR based on testing with a specific overcurrent protective device and/or combination of components in accordance with product standards and documented by the manufacturer. Example: a power distribution block may have an SCCR of 100kA with a 200A Class J fuse, but only 10kA with a 200A circuit breaker. • Take and apply the lowest SCCR of any component used in the feeder circuit as the SCCR of the feeder circuit. • Note the lowest feeder circuit SCCR. 89 Industrial Control Panels - SCCR Determining Assembly SCCR “Two Sweep” Method Procedures Step 3: If using a 10kVA or less power transformer in a feeder circuit, modify the transformer circuit SCCR, if possible, as follows: • For 10kVA or less power transformers that are in a feeder circuit, determine if the SCCR of the downstream circuits can be increased by applying the following procedure: Step 5: Determine the assembly SCCR for Sweep 1 • Determine the Sweep 1 assembly SCCR by utilizing the lowest rated branch or feeder circuit SCCR. End of Sweep 1 1. On the transformer secondary, verify the SCCR of each component and the interrupting ratings of all overcurrent protective devices. 2. Identify the lowest component SCCR or overcurrent protective device interrupting rating. 3. If the lowest component SCCR or overcurrent protective device interrupting rating is 5kA or greater, apply the transformer’s primary overcurrent protective device interrupting rating to the entire transformer circuit. Otherwise apply the lowest downstream component SCCR or overcurrent protective device interrupting rating to the transformer circuit. • For 5kVA or less power transformers with 120V secondary in the feeder circuit, determine if the SCCR of the downstream circuits can be increased by applying the following: 1. On the transformer secondary, verify the SCCR of each component and the interrupting ratings of all overcurrent protective devices. 2. Identify the lowest component SCCR or overcurrent protective device interrupting rating. 3. If the lowest component SCCR or overcurrent protective device interrupting rating is 2kA or greater, apply the transformer’s primary overcurrent protective device interrupting rating to the entire transformer circuit. Otherwise apply the lowest downstream component SCCR or overcurrent protective device interrupting rating to the transformer circuit. Step 4: If using a current-limiting overcurrent protective device in the feeder circuit, modify branch circuit component SCCRs (other than branch circuit overcurrent protection devices such as fuses, circuit breakers, instantaneous trip circuit breakers or motor circuit protectors - MCPs - and self-protected combination starters), if possible, as follows: • If current-limiting overcurrent protective devices are used in the feeder circuit use the following procedure: 1. Determine the peak let-through value of the current-limiting overcurrent protective devices. a)If the overcurrent protective device is a current-limiting fuse, determine the peak let-through umbrella value dictated by the product standard for the fuse class and amp rating utilized at the level of fault current desired (50, 100, 200kA). See Table SCCR2 - UL Umbrella Limits at Rated Voltage (based on UL 508A Table SB4.2). b)If the overcurrent protective device is a current-limiting circuit breaker, manufacturer’s let-through curves can be used to determine the peak let-through value. A current-limiting circuit breaker must be listed and marked as current-limiting. It is important to note, that unlike the fuse industry, UL 489 for molded case circuit breakers does not have specific industry maximum short-circuit let-through limits established for each circuit breaker frame size and amp rating. So the degree of current limitation for the same frame size and amp rating circuit breaker can vary from one manufacturer to another. 2. Ensure that the peak let-through value is less than any of the SCCRs determined in Step 1. 3. If condition “2” above is met, apply a short-circuit current rating to branch circuits fed by the feeder based upon the value of fault current used to determine the peak let-through value of the current-limiting overcurrent protective device. 90 Sweep 2: Verify assembly overcurrent protective device interrupting rating (or SCCR for some devices). Step 1: Determine the interrupting ratings (or SCCR) of all the overcurrent protective devices used in feeder (includes supply, feeders and sub-feeders) and branch circuits, as well as those devices protecting control circuits. Step 2: Determine the lowest overcurrent protective device interrupting rating or SCCR. Step 3: Compare the lowest overcurrent protective device interrupting rating or SCCR with the component SCCRs from Sweep 1, Step 5. The lowest rating encountered is the assembly SCCR. This SCCR is then marked on the assembly. If this SCCR is not sufficiently high enough, there are “FIX IT” solutions at the end of this section that can be investigated to achieve a higher SCCR marking. End of Sweep 2 Table: SCCR1 - Default SCCR Ratings (UL 508A Table SB4.1) Component Bus bars Circuit breaker (including GFCI type) Current meters Current shunt Fuse holder Industrial control equipment a. Auxiliary devices (overload relay) b. Switches (other than mercury tube type) c. Mercury tube switches rated: • Over 60 amps or over 250 volts • 25 volts or less, 60 amps or less and over 5kVA • 250 volts or less and 2kVA or less Motor controller, rated in horsepower (kW) a. 0-50 (0-37.5) b. 51-200 (38-149) c. 201-400 (150-298) d. 401-600 (299-447) e. 601-900 (448-671) f. 901-1500 (672-1193) Meter socket base Miniature or miscellaneous fuse Receptacle (GFCI type) Receptacle (other than GFCI) Supplementary protector Switch unit Terminal block or power distribution block Default SCCR (kA) 10 5 * 10 10 5 5 5 3.5 1 5** 10** 18** 20** 42** 85** 10 10*** 2 10 0.2 5 10 * A SCCR is not required when connected via a current transformer or current shunt. A directly connected current meter shall have a marked SCCR. ** Standard fault current rating for motor controller rated within specified horsepower range. *** The use of a miniature fuse is limited to 125 volt circuits. ©2008 Cooper Bussmann Industrial Control Panels - SCCR Verify Assembly Assembly Overcurrent Protective Devices Table: SCCR2 - UL Umbrella Limits at Rated Voltage Fuse Amp Between threshold & 50kA 2 Fuse Type Rating I t x 10 Class CC 15 20 30 15 20 30 60 30 60 100 200 400 600 30 60 100 200 400 600 1 3 6 10 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600 700 800 1000 1200 2 2 7 — — — — 10 40 100 400 1200 3000 50 200 500 1600 5200 10000 – – – – – – – 3.5 – – – – 15 – – – 40 – – – – 150 – – – – 550 – – 1,000 – 1,500 – 3,500 Class G Class RK1 Class RK5 Class T 300V (UL 508A Table SB4.2) 3 100kA 3 2 Ip x 10 (kA) I t x 10 3 3 6 — — — — 6 10 14 18 33 45 11 20 22 32 50 65 – – – – – – – 5.0 – – – – 7 – – – 9 – – – – 13 – – – – 22 – – 29 – 37 – 50 2 3 7 3.8 5 7 25 10 40 100 400 1200 3000 50 200 500 1600 5000 10000 0.4 0.6 1 1.5 2 2.5 2.7 3.5 6 8.5 9 11 15 25 30 38 40 50 75 88 115 150 175 225 300 400 550 600 800 1,000 1,200 1,500 3,500 3,500 3 200kA 3 2 Ip x 10 (kA) I t x 103 Ip x 103 (kA) 3 4 7.5 4 5 7 10.5 10 12 16 22 35 50 11 21 25 40 60 80 0.8 1.3 2 3 4 4.5 5.5 7 7 7.2 7.6 8 9 10 11 12 12 12 13 14 15 16 21 22 24 27 28 32 37 37 45 50 65 65 3 3 7 — — — — 11 50 100 400 1600 4000 50 200 500 2000 6000 12000 – – – – – – – 3.5 – – – – 15 – – – 40 – – – – 150 – – – – 550 – – 1,000 – 1,500 – 4,000 4 5 12 — — — — 12 16 20 30 50 70 14 26 32 50 75 100 – – – – – – – 9 – – – – 12 – – – 15 – – – – 20 – – – – 35 – – 46 – 65 – 80 Note: These values are UL umbrella limits. Intermediate values shown in the 100kA column for Class J and T fuses are included per UL 248, but have not yet been added to UL 508A Supplement SB. ©2008 Cooper Bussmann 91 Industrial Control Panels - SCCR Verify Assembly Assembly Overcurrent Protective Devices Table: SCCR2 - UL Umbrella Limits at Rated Voltage Fuse Type Fuse Amp Rating Class T & J 600V 1 3 6 Class L (UL 508A Table SB4.2) (continued) Between threshold & 50kA I2t x 103 Ip x 103 (kA) – – – – – – 100kA I2t x 103 Ip x 103 (kA) 0.8 1 1.2 1.5 2 2.3 200kA I2t x 103 Ip x 103 (kA) – – – – – – 10 – – 3 3.3 – – 15 – – 4 4 – – 20 – – 5 5 – – 25 – – 5.5 6 – – 30 7 6 7 7.5 7 12 35 – – 12 7.5 – – 40 – – 17 8 – – 45 – – 18 8.5 – – 50 – – 22 9 – – 60 30 8 30 10 30 16 70 – – 50 12 – – 80 – – 60 13 – – 90 – – 75 14 – – 100 60 12 80 14 80 20 110 – – 100 15 – – 125 – – 150 16 – – 150 – – 175 17 – – 175 – – 225 19 – – 200 200 16 300 20 300 30 225 – – 350 23 – – 250 – – 450 24 – – 300 – – 600 26 – – 350 – – 800 29 – – 400 1,000 25 1,100 30 1,100 45 450 – – 1,500 36 – – 500 – – 2,000 42 – – 600 2,500 35 2,500 45 2,500 70 700* – – 3,500* 50* – – 800* 800 1200 1600 2000 2500 3000 4000 5000 6000 4,000* 10000 12000 22000 35000 — — — — — 50* 80 80 100 110 — — — — — 4,000* 10000 12000 22000 35000 75000 100000 150000 350000 350000 55* 80 80 100 120 165 175 220 — — 4,000* 10000 15000 30000 40000 75000 100000 150000 350000 500000 75* 80 120 150 165 180 200 250 300 350 *Value applies to Class T fuses Note: These values are UL umbrella limits. Intermediate values shown in the 100kA column for Class J and T fuses are included per UL 248, but have not yet been added to UL 508A Supplement SB. 92 ©2008 Cooper Bussmann Industrial Control Panels - SCCR About Umbrella Limits What is a Fuse Umbrella Limit? UL / CSA / ANCE Fuse Standards set maximum Ip and I2t let-through limits for short-circuit current performance of current-limiting fuses. The limits vary by fuse class, amp rating and available short-circuit current. To receive a listing, a commercially available current-limiting fuse must be tested and evaluated under short-circuit current tests per the applicable standard and witnessed by a National Recognized Testing Laboratory (NRTL). One evaluation criteria of the testing is that the fuse’s Ip and I2t let-through measured during the short-circuit tests can not exceed the Standard’s “umbrella limits” for Ip and I2t let-through established for that fuse class, amp rating, and available short-circuit current*. See Table: SCCR2 - UL Umbrella Limits at Rated Voltage on the preceding pages for the umbrella limits applicable to most of the current-limiting fuses. *NOTE: These tests are done at the fuse’s rated voltage, with only one fuse in the circuit and by controlled closing of the test circuit so that the fuse “starts to arc” between 60 and 90 degrees on the voltage wave. These test conditions are the most severe for fuse interruption. In addition, current-limiting fuses are required to have periodic NRTL witnessed follow-up testing in the same manner. The fuses for NRTL witnessed follow-up testing are pulled from inventory. Calculate Assembly SCCR with Ease & Confidence What is an umbrella fuse? An umbrella fuse is a special fuse that is designed to have short-circuit current Ip and I2t let-through that are at least equal to or greater than the UL / CSA / ANCE Fuse Standard limit. Umbrella fuses are not intended as commercially available fuses. UL has a specific standard for these devices, which is UL248-16 Test Limiters. UL uses the term “test limiters” for what we refer to as umbrella fuses. UL 248-16 states: “…test limiters are calibrated to specific limits of peak let-through current and clearing I2t at 250, 300, 480, or 600Vac. Test limiters are non-renewable and current-limiting, with test current ratings up to 200,000 A. They are calibrated to maximum peak let-through current and clearing I2t limits for the fuses specified in this Standard and are used for withstand testing of equipment designed to accept those fuses.” Umbrella fuses are used for test purposes in qualifying a combination short-circuit current rating with a specific component. For instance, a controller manufacturer wants the controller to be marked with a 100,000A SCCR at 600V when protected by 60A Class J fuses. The NRTL witnessed tests would be with 60A Class J umbrella fuses in combination with the controller on a test circuit of 100,000A at 600V. If the results satisfy the UL 508 Industrial Control Standard evaluation criteria, the controller can be labeled with a 100,000A, 600V SCCR when protected by Class J fuses 60A (or less). Another use of umbrella fuses is for series rated fuse/circuit breaker panelboard and switchboard combinations. For more information on series ratings see the section on Series Rating: Protecting Circuit Breakers. However, UL 508A Supplement SB4 does not permit series rated combinations for use in establishing the SCCR for industrial control panels. Therefore, the interrupting rating of overcurrent devices cannot be raised by another upstream overcurrent device. Enhanced Cooper Bussmann® OSCAR™ Software Speeds Code & Standards Compliance The new Cooper Bussmann® OSCAR™ Version 2.0 SCCR (Short-Circuit Current Rating) compliance software easily guides you through entering your electrical panel’s components and calculates an assembly SCCR. This award winning, online, essential design tool allows you to comply quickly and accurately with 2008 NEC® and UL 508A Supplement SB for assembly SCCR marking requirements: • Industrial Control Panels [409.110] • Industrial Machinery Electrical Panels [670.3(A)] • HVAC Equipment [440.4(B)] New Project Management Features: • • • • Simplify your panel design and project organization Save and edit existing panel designs Save multiple panels under a single project Copy existing panels to new projects New Intuitive Navigation: • • • • • Display your one-line diagram Select from pre-loaded circuit templates Identify the “weakest link” component automatically Print reports and one-line diagrams for required SCCR documentation Utilize mouse-over tips to enhance your design Design with Confidence: • • • • Logic updated to current UL requirements Extensive 55,000+ component database Search by partial part number or device rating Custom device option allows for entering specialized component rating information For more information, visit: www.cooperbussmann.com/OSCAR. ©2008 Cooper Bussmann 93 Industrial Control Panels - SCCR Example Using the “Two Sweep” Method: “FIND IT” “FIND IT” The following example will illustrate the procedures previously outlined for the two sweep method to determine the assembly SCCR. It may be helpful to periodically refer back to the procedures for the two sweep method while going through this example. The example is based on the industrial control panel shown in Figure 5 and 6. Figure 5 shows the graphical representation of the industrial control panel while Figure 6 is the one-line diagram for the industrial control panel. The ratings for each power circuit component are detailed in Figure 6. This example illustrates how each sweep and their steps are performed and documented in the tables. After both sweeps and all steps have been completed, the result identifies the assembly SCCR (“FIND IT”). Later, methods are outlined to increase the assembly SCCR (“FIX IT”). Figure 5 Industrial Control Panel Circuit and Device Descriptions Circuit Number 1 2 3 4 5 6 7 8 9 10 94 Device Descriptions Molded case circuit breaker protecting an IEC contactor Self-protected starter protecting an IEC contactor (additional components may be required) Instantaneous trip circuit breaker (MCP) protecting an IEC starter (special assembly conditions required) Molded case circuit breaker protecting an IEC starter Class CC fused switch protecting an IEC starter Class CC fused switch protecting variable frequency drive and contactor Molded case circuit breaker and GFCI receptacle Molded case circuit breaker protecting power transformer Power distribution block Class J fused switch ©2008 Cooper Bussmann Industrial Control Panels - SCCR Example Using the “Two Sweep” Method: “FIND IT” Note: It is important to record the voltage ratings for all components and overcurrent protective devices. The assembly is marked based upon the lowest or most restrictive device voltage rating. If there are devices with slash voltage ratings (such as 480/277V), these are more limiting than straight or full voltage ratings (such as 480V). Assemblies with 480/277V devices are suitable for only 480/277V solidly grounded wye systems. These assemblies cannot be applied on 480V ungrounded, resistance grounded or corner grounded systems. (See the section on Slash Voltage Ratings for more information.) Figure 6 – One-line Diagram of Industrial Control Panel Industrial Control Panel Circuit Descriptions and Ratings Circuit Number 1 Circuit Type Branch 2 Branch 3 Branch 4 Branch 5 Branch 6 Branch 7 Branch 8 Sub-Feeder 9 10 Feeder Supply ©2008 Cooper Bussmann • • • • • • • • • • • • • • • • • • • • • • Device Descriptions Molded case circuit breaker: IR = 14kA @ 480/277V IEC contactor: SCCR = 5kA @ 600V Self-protected starter with lineside terminal kit: SCCR = 65kA @ 480/277V IEC contactor: SCCR = 5kA @ 600V Instantaneous trip circuit breaker (MCP): unmarked IR IEC Starter: SCCR = 5kA @ 600V Molded case circuit breaker: IR = 14kA @ 480V IEC starter: SCCR = 5kA @ 600V Cooper Bussmann® Class CC Compact Circuit Protector (CCP): SCCR = 200kA @ 600V Cooper Bussmann® LP-CC Fuses: IR = 200kA @ 600V IEC starter: SCCR = 5kA @ 600V Cooper Bussmann Class CC Compact Circuit Protector (CCP): SCCR = 200kA @ 600V Cooper Bussmann LP-CC Fuses: IR = 200kA @ 600V Variable Frequency Drive: SCCR = 5kA @ 480V IEC contactor: SCCR = 5kA @ 600V Molded case circuit breaker: IR = 10kA @ 120V GFCI Receptacle: unmarked SCCR Molded case circuit breaker: IR = 14kA @ 480/277V 3kVA 480V-120V secondary power transformer (does not affect SCCR) Power distribution block: unmarked SCCR Cooper Bussmann® 100A Class J fused switch: SCCR = 200kA @ 600V Cooper Bussmann® 100A LPJ fuses: IR = 300kA @ 600V 95 Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 1 - Branch Circuit Components Sweep 1: Verifying assembly component SCCRs Step1: Determine lowest rated component in each branch circuit. Note: Determine SCCRs for components only. Interrupting rating or SCCR of overcurrent protective devices is ignored in this step. Branch Circuit 1 • IEC contactor: SCCR = 5kA @ 600V • Higher combination rating with a circuit breaker does not exist • SCCR = 5kA @ 600V Branch Circuit 2 • IEC contactor: SCCR = 5kA @ 600V • Combination rating with self-protected starter (only with same manufacturer) = 65kA @ 480/277V • SCCR = 65kA @ 480/277V 96 Branch Circuit 3 • IEC Starter: SCCR = 5kA @ 600V • Combination rating with MCP (only with same manufacturer) = 65kA @ 480V • SCCR = 65kA @ 480V Branch Circuit 4 • IEC starter: SCCR = 5kA @ 600V • Combination rating with circuit breaker (only with same manufacturer) = 25kA @ 480V • SCCR = 25kA @ 480V ©2008 Cooper Bussmann Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 1 - Branch Circuit Components Branch Circuit 5 • IEC starter: SCCR = 5kA @ 600V • Combination rating with Class CC fuses = 100kA @ 600V • SCCR = 100kA @ 600V Branch Circuit 7 • GFCI Receptacle: unmarked SCCR (2kA per Table SCCR1-Default SCCR Ratings) • Higher combination rating with circuit breaker does not exist • SCCR = 2kA @ 120V (does not affect panel voltage rating) Branch Circuit 6 • Variable Frequency Drive: SCCR = 5kA @ 480V • IEC contactor: SCCR = 5kA @ 600V • Combination rating with Class CC fuses: - 200kA @ 600V for variable frequency drive - 100kA @ 600V for IEC contactor • SCCR = 100kA @ 600V Sweep 1 - Step 1 Summary • Lowest SCCR of Step 1 is 2kA @ 480/277V Results of Sweep 1, Step 1: SCCR = 2kA @ 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V 65kA 480/277V 65kA 480V 25kA 480V 100kA 600V 100kA 600V 2kA – – – – – – – Sweep 1 Results Sweep 1-Step 5 SCCR Voltage Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage Note: Red cells in table denote limiting components and voltages for each step. ©2008 Cooper Bussmann 97 Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 2 - Feeder Circuit Components Sweep 1: Verifying assembly component SCCRs Step 2: Determine the component SCCR for each feeder, sub-feeder and supply circuit. Sub-Feeder Circuit 8 • This is a transformer circuit and is covered by Sweep 1, Step 3 Feeder Circuit 9 • Power distribution block (PDB): unmarked SCCR (10kA per Table SCCR1 - Default SCCR Ratings) • SCCR = 10kA @ 600V Note: PDB must have proper spacings for feeder application per UL 508A. Supply Circuit 10 • Cooper Bussmann® 100A Class J fused switch: SCCR = 200kA @ 600V • SCCR = 200kA @ 600V Sweep 1 - Step 2 Summary • Lowest SCCR of Step 2 is 10kA @ 600V • Lowest SCCR of Step 1 or Step 2 is 2kA @ 480/277V Results of Sweep 1, Step 2: SCCR = 2kA @ 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – 65kA 480/277V – – 65kA 480V – – 25kA 480V – – 100kA 600V – – 100kA 600V – – 2kA – – – – – – – – – 10kA 600V – – 200kA 600V Sweep 1 Results Sweep 1-Step 5 SCCR Voltage Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage Note: Red cells in table denote limiting components and voltages for each step. 98 ©2008 Cooper Bussmann Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 3 - Components/Transformers Sweep 1: Verifying assembly component SCCRs Step 3: Determine if 10kVA or smaller power transformers in the feeder, sub-feeder or supply circuit are able to raise branch circuit component SCCRs (circuit breaker and GFCI receptacle): SCCR Now 14kA Sub-Feeder Circuit 8 • Sub-feeder transformer is 3kVA with 120V secondary and can be used to raise the secondary components. Follow procedure for 5kVA or smaller transformers. • Since all secondary components have an interrupting rating/SCCR (circuit breaker IR = 10kA) or SCCR (GFCI receptacle SCCR = 2kA) of 2kA or higher, the interrupting rating rating of the transformer primary overcurrent protective device (Sub-Feeder Circuit 8) can be assigned to the entire Branch Circuit 7 (circuit breaker and GFCI receptacle). • Revised Branch Circuit 7 SCCR = 14kA Sweep 1 - Step 3 Summary • Branch Circuit 7 was raised to 14kA • However, Branch Circuit 1 is still the limiting SCCR factor Results of Sweep 1, Step 3: SCCR = 5kA @ 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – – 65kA 480/277V – – – 65kA 480V – – – 25kA 480V – – – 100kA 600V – – – 100kA 600V – – _ 2kA – – – 14kA – – – – – – – 10kA 600V – – – 200kA 600V – Sweep 1 Results Sweep 1-Step 5 SCCR Voltage Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage Note: Red cells in table denote limiting components and voltages for each step. ©2008 Cooper Bussmann 99 Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 4 - Current-Limiting Overcurrent Devices Sweep 1: Verifying assembly component SCCRs Step 4: Determine if current-limiting overcurrent protective devices (C-L OCPDs) are used in the feeder, sub-feeder or supply circuit that can raise branch circuit component ratings (other than devices that provide branch circuit overcurrent protection). 100A Class J Fuses Fault Current Peak Values of: Let-through = 50kA 12kA 100kA 14kA 200kA 20kA Note: Since the 100A Class J fuse peak let-through of 20kA at a fault current of 200kA is less than the SCCR of Step 1 for Branch Circuits 2 through 6, the SCCR is raised to 200kA. The SCCR of components in Feeder Circuit 9, Sub-Feeder Circuit 8 or Supply Circuit 10 cannot be raised per UL 508A. Supply Circuit 10 The 100A Class J fuse in Supply Circuit 10 is a current-limiting device. Use Table SCCR2 - UL Umbrella Limits at Rated Voltage to identify the peak let-through values: • Compare the peak let-through values with result of Step 1 and increase branch circuit component ratings where possible. Sweep 1 - Step 4 Summary • Branch Circuit 1 SCCR cannot be raised • Increased SCCR of Branch Circuits 2 through 6 to 200kA • Branch Circuit 7 SCCR cannot be raised in this step because it was raised by Step 3 Results of Sweep 1, Step 4: SCCR = 5kA @ 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – – – 65kA 480/277V – – – 200kA 65kA 480V – – – 200kA 25kA 480V – – – 200kA 100kA 600V – – – 200kA 100kA 600V – – _ 200kA 2kA – – – 14kA – – – – – – – – – 10kA 600V – – – – 200kA 600V – – Sweep 1 Results Sweep 1-Step 5 SCCR Voltage Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage Note: Red cells in table denote limiting components and voltages for each step. 100 ©2008 Cooper Bussmann Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 1, Step 5 - Results of Entire Sweep 1 Sweep 1: Verifying assembly component SCCRs Step 5: Determine the lowest branch or feeder circuit component SCCR based on all steps in Sweep 1 and retain for Sweep 2. • Lowest SCCR resulted from Branch Circuit 1 in Step 1 • Branch Circuit 2 limited voltage in Step 1 • Sweep 1 Lowest SCCR = 5kA @ 480/277V Note: Sweep 2 must still be completed to determine SCCR marking. Figure 7 – Results of Sweep 1, Steps 1 through 5 Sweep 1 - Step 5 Summary After completing all five steps in Sweep 1, the resulting SCCR based upon the components, remains at a low 5kA @ 480/277V because of the 5kA rated contactor in Branch Circuit 1 and the slash voltage rating of the contactor in Branch Circuit 2 (when protected by a slash voltage rated self protected motor starter). See figure 7. Results of Sweep 1, Step 5: SCCR = 5kA @ 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – – – 65kA 480/277V – – – 200kA 65kA 480V – – – 200kA 25kA 480V – – – 200kA 100kA 600V – – – 200kA 100kA 600V – – _ 200kA 2kA – – – 14kA – – – – – – – – – 10kA 600V – – – – 200kA 600V – – Sweep 1 Results Sweep 1-Step 5 SCCR 5kA 200kA 200kA 200kA 200kA 200kA 14kA – 10kA 200kA Voltage 600V 480/277V 480V 480V 600V 600V – – 600V 600V Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage Note: Red cells in table denote limiting components and voltages for each step ©2008 Cooper Bussmann 101 Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 2, Step 1 - Overcurrent Protective Device IR or SCCR Sweep 2: Verifying assembly SCCR based upon overcurrent protective device interrupting rating (or SCCR for some devices). Step 1: Determine overcurrent protective device interrupting rating or SCCR*: Branch Circuit 1 • Molded case circuit breaker • IR = 14kA @ 480/277V Branch Circuit 4 • Molded case circuit breaker • IR = 14kA @ 480V Branch Circuit 2 • Self-protected starter • SCCR = 65kA @ 480/277V *Note: Self-protected starters are not rated with an interrupting rating. So for this Step 1, its SCCR is used. Branch Circuit 5 • Cooper Bussmann® LP-CC fuses • Branch Circuit 3 • MCP – Combination rating with IEC Starter (same manufacturer) • SCCR = 65kA @ 480V *Note: Per UL 508A, in order to assure proper application in industrial control panels, the MCP must be procedure described to verify use as part of a listed combination motor controller and the corresponding SCCR. 102 IR = 200kA @ 600V Branch Circuit 6 • Cooper Bussmann® LP-CC fuses • IR = 200kA @ 600V ©2008 Cooper Bussmann Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 2, Step 2 - Lowest IR or SCCR Sweep 2: Verifying assembly overcurrent protective device interrupting rating or SCCR. Step 2: Determine lowest overcurrent protective device interrupting rating or SCCR. Feeder Circuit 9 • No overcurrent protective device in this circuit Branch Circuit 7 • Molded case circuit breaker analyzed in Sweep1, Step 3 • IR = 10kA, but raised to 14kA due to transformer and interrupting rating of Sub-Feeder Circuit 8 molded case circuit breaker Supply Circuit 10 • Cooper Bussmann® 100A LPJ fuses • IR = 300kA @ 600V Sub-Feeder Circuit 8 • Molded case circuit breaker • IR = 14kA @ 480/277V Sweep 2 - Step 1 & Step 2 Summary • The lowest interrupting rating or SCCR of this Step is 14kA @ 480/277V Figure 8 – Results of Sweep 2 – Steps 1 & 2 Results of Sweep 2, Steps 1 & 2: SCCR = 14kA @ 480/277V (Sweep 2, Step 2 Only) Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – – – 65kA 480/277V – – – 200kA 65kA 480V – – – 200kA 25kA 480V – – – 200kA 100kA 600V – – – 200kA 100kA 600V – – _ 200kA 2kA – – – 14kA – – – – – – – – – 10kA 600V – _ – – 200kA 600V – – Sweep 1 Results Sweep 1-Step 5 SCCR 5kA 200kA 200kA 200kA 200kA 200kA 14kA – 10kA 200kA Voltage 600V 480/277V 480V 480V 600V 600V – – 600V 600V Sweep 2-Steps 1& 2 (Overcurrent Device) IR/SCCR Voltage 14kA 480/277V 65kA 480/277V 65kA 480V 14kA 480V 200kA 600V 200kA 600V – – 14kA 480/277V – – 300kA 600V Note: Red cells in table denote limiting components and voltages for each step. ©2008 Cooper Bussmann 103 Industrial Control Panels - SCCR “Two Sweep” Method: Sweep 2, Step 3 - Final Assembly SCCR Sweep 2: Verifying assembly SCCRs based upon overcurrent protective device interrupting rating or SCCR. Step 3: Determine final assembly SCCR based upon results of Sweep 1 (component SCCR) and Sweep 2 (overcurrent protective device interrupting rating or SCCR). • Sweep 1 lowest SCCR = 5kA @ 480/277V • Sweep 2 lowest IR or SCCR = 14kA @ 480/277V • Resulting assembly SCCR = 5kA @ 480/277 (see Figure 9) P la s tic s P ro c e ss in g M ac h in e S N 23 5 6Y U P 7 7 S e ria l N um b er C urren t La rges t M oto r H .P . M ax O C P D evice V o lta ge P h ase & Freq .. 87 A m peres 25 H o rse p ow e r 1 00 A m p e re 48 0 /2 7 7 v olts 3 ph a se , 4 w ire, 6 0 H z S h o rt-C irc uit C u rren t R a tin g 5 ,0 0 0 A m p e re s R M S D ia gram N um b ers C M 12.1 T H R U C M 12.5 Q u a lity M ac h in e T o o l S o m ew h e re, U S A Example of assembly SCCR label marking based on the “2 Sweep” method. Figure 9 – Results of Sweep 2 – Step 3 Sweep 2 - Step 3 Summary • The lowest SCCR of both Sweep 1 and Sweep 2 is 5kA @ 480/277V • The 5kA SCCR is based on the contactor in Branch Circuit 1, analyzed in Sweep 1 - Step 1 • The 480/277 slash voltage rating is from multiple components in Sweep 1 - Steps 1 and 5, and Sweep 2, Steps 1, 2 and 3 • The Assembly SCCR is 5kA @ 480/277V Note: The assembly would have to be marked with 5kA SCCR and 480/277V. Assemblies with 480/277V devices are suitable for only 480/277V solidly grounded wye systems. These assemblies cannot be applied on 480V ungrounded, resistance grounded or corner grounded systems. See the section on Slash Voltage Ratings for more information.) Results of Sweep 2, Step 3: Assembly SCCR = 5kA, Voltage = 480/277V Branch Circuit 1 Branch Circuit 2 Branch Circuit 3 Branch Circuit 4 Branch Circuit 5 Branch Circuit 6 Branch Circuit 7 Sub-Feeder Circuit 8 Feeder Circuit 9 Supply Circuit 10 Assessment SCCR Revisions Sweep 1-Step 1 Sweep 1-Step 2 Sweep 1-Step 3 Sweep 1-Step 4 (Branch) (Feeder) (Trans) (C-L OCPDs) SCCR Voltage SCCR Voltage SCCR SCCR 5kA 600V – – – – 65kA 480/277V – – – 200kA 65kA 480V – – – 200kA 25kA 480V – – – 200kA 100kA 600V – – – 200kA 100kA 600V – – _ 200kA 2kA – – – 14kA – – – – – – – – – 10kA 600V – _ – – 200kA 600V – – Sweep 1 Results Sweep 1-Step 5 SCCR 5kA 200kA 200kA 200kA 200kA 200kA 14kA – 10kA 200kA Voltage 600V 480/277V 480V 480V 600V 600V – – 600V 600V Sweep 2 Final Sweep 2-Steps 1, 2 & 3 (Overcurrent Device) IR/SCCR Voltage 14kA 480/277V 65kA 480/277V 65kA 480V 14kA 480V 200kA 600V 200kA 600V – – 14kA 480/277V – – 300kA 600V Note: Red cells in table denote limiting components and voltages for each step. 104 ©2008 Cooper Bussmann Industrial Control Panels - SCCR Example: Increasing Assembly SCCR - “FIX IT” “FIX IT” What follows are methods to increase, or “FIX,” a low assembly SCCR using the appropriate overcurrent protective devices with higher interrupting ratings and components with higher SCCRs. To increase the assembly SCCR, identify the “weak links” and determine alternatives that can be used to increase the SCCR. While industrial control panels are only required to be marked with an SCCR, many OEMs and Industrials are finding that SCCR ratings of 65kA, 100kA, or higher with full voltage ratings (480V in lieu of 480/277V) are often needed to assure safety for the initial installation and flexibility for future changes to the system or moving the assembly to another location. The process to “FIX” these “weak links” is detailed below in order to meet the installation needs of OEMs and Industrials. “Weak Link” 1 Branch Circuit 1: SCCR = 5kA and Slash Voltage Rating “Weak Link” 2 Feeder Circuit 9: SCCR = 10kA The next “weak link” is the unmarked power distribution block. The easy solution to this is to find a power distribution block that has a high SCCR when protected by a specific overcurrent device upstream. Since the overcurrent device upstream is a Class J fuse, the solution would be to use a Cooper Bussmann® high SCCR power distribution block or terminal block. This is important to note, as most power distribution blocks and terminal blocks require a current-limiting fuse to achieve a SCCR higher than 10kA. In addition, since the power distribution block is in the feeder circuit, feeder circuit spacings are also required per UL 508A. The Cooper Bussmann PDB (open style) or PDBFS (enclosed style) Series of power distribution blocks are Listed to UL 1953 assuring compliance with feeder circuit spacing requirements in UL 508A and are UL Listed with high SCCR ratings with Class J fuses as shown in Figure 11. The first “weak link” from the previous “Two Sweep” example is the IEC contactor (5kA SCCR) and the slash rated circuit breaker (480/277V) from Branch Circuit 1. This can be a common issue where circuit breakers are used in branch circuits. As shown in Figure 10, not only does the circuit breaker have a low interrupting rating (14kA) and slash voltage rating (480/277V), but the other circuit components, such as the IEC contactor (5kA), can additionally limit the SCCR since higher combination ratings are not available. The “FIX IT” is to find a fully rated overcurrent device with a high interrupting rating and a high SCCR combination rating with the IEC contactor. A solution is to change the circuit breaker to the Cooper Bussmann® Compact Circuit Protector (CCP) with Class CC fuses. The Class CC CCP is rated 600V and 200kA. Since the Class CC CCP utilizes Class CC fuses, and since the IEC contactor in this example had a combination rating of 100kA with Class CC fuses, the SCCR is now 100kA. An additional benefit of the CCP can be space savings when compared to typical lighting and industrial style circuit breakers. Figure 11 High SCCR PDBs Often the power distribution block is the”weak link” holding assembly SCCR low. Using high SCCR PDBs protected with Class J fuses can deliver a higher combination SCCR. The following table shows the possible SCCRs. This power distribution block is rated for use on a circuit capable of delivering no more than the SCCR kA shown (kA rms sym. or DC amps 600V maximum). For other SCCR options, see Data Sheet 1049. AWG Class J Fuse Wire Range Max. Amp 2-6 400A 2-14 200A 2-14 175A Figure 10 Resulting SCCR 200kA 50kA 100kA Note: SCCR of the Cooper Bussmann® PDBFS is only 10kA with a circuit breaker. The Cooper Bussmann® CCP with Class CC fuses can easily increase SCCR by replacing low IR and slash rated molded case circuit breakers. Figure 12 ©2008 Cooper Bussmann 105 Industrial Control Panels - SCCR Example: Increasing Assembly SCCR - “FIX IT” “Weak Link” 3 Branch Circuit 4: SCCR = 14kA and Sub-Feeder Circuit 8 – SCCR = 14kA and Slash Voltage Rating The next “weak link” is the 14kA circuit breaker in Branch Circuit 4 and the 14kA slash rated (480/277V) circuit breaker in Sub-Feeder Circuit 8. There are two possible solutions for this, either increase the interrupting rating of both circuit breakers and change to a full or straight voltage rated circuit breaker in Sub-Feeder Circuit 8 (this will increase the cost and may require changing to a larger industrial style circuit breaker) or change to the Cooper Bussmann® CCP as shown in “Weak Link 1.” The most economical solution is to change the circuit breaker to the Cooper Bussmann CCP with Class CC fuses. In Branch Circuit 4, this change increases the interrupting rating to 200kA as well as increasing the rating of the IEC starter to 100kA through the use of Class CC fuses so that Branch Circuit 4 is now rated 100kA. The change to SubFeeder Circuit 8 not only increased the interrupting rating to 200kA, but also improved the voltage rating from 480/277V (limits the assembly) to 600V (not limited). “Weak Link” 5 Branch Circuit 2, 3 & 4: Manufacturer Limitation In motor circuits, when mechanical overcurrent protective devices are selected the assembly typically has SCCR or voltage rating limitations as shown previously. These devices can additionally lock the user into a single manufacturer. For instance, the self-protected starter and contactor in Branch Circuit 2 requires the same manufacturer to be selected if higher combination short-circuit current ratings are desired. The MCP and magnetic starter in Branch Circuit 3 must be from the same manufacturer to be a listed combination as required by the NEC®. The circuit breaker and magnetic starter in Branch Circuit 4 must be from the same manufacturer and a high interrupting rated circuit breaker must be selected to achieve a high combination short-circuit current rating. This greatly decreases flexibility for the user and can adversely increase component cost. In contrast, where fusible devices are used in motor circuits, high combination ratings with multiple manufacturers are possible increasing flexibility and reducing cost. Figure 13 Figure 15 “Weak Link” 4 Branch Circuit 2: Slash Voltage Ratings “FIX IT” Summary The next “weak link” is the slash voltage rating in Branch Circuit 2. While the self-protected starter is compact in size and has a relatively high SCCR (65kA), it typically comes with a slash voltage rating. The solution is to either add an overcurrent device with a high interrupting rating ahead of the selfprotected starter or change to the CCP with Class CC fuses and a magnetic starter. The most economical solution to achieve a high SCCR and full voltage rating is to change to the CCP with Class CC fuses and a magnetic starter. With this change the circuit is rated 100kA @ 600V. The Figure 16 shows how all the “weak links” have been changed and now the panel has a high assembly SCCR with a full voltage rating. P la s tic s P ro c e ss in g M ac h in e S e ria l N um b er C urren t La rges t M oto r H .P . M ax O C P D evice V o lta ge P h ase & Freq .. S h o rt-C irc uit C u rren t R a tin g D ia gram N um b ers S N 23 5 6Y U P 7 7 87 A m peres 25 H o rse p ow e r 1 00 A m p e re 600 Volts 3 ph a se , 4 w ire, 6 0 H z 100,0 0 0 A m p e re s R M S C M 12.1 T H R U C M 12.5 Q u a lity M ac h in e T o o l S o m ew h e re, U S A Figure 14 Figure 16 106 ©2008 Cooper Bussmann Industrial Control Panels - SCCR Increasing Assembly SCCR: “FIX IT” - Typical “Weak Links” Typical “Weak Links” and Improving SCCR The following table highlights the typical “weak links” in industrial control panels and provides Cooper Bussmann solutions, along with the added benefits that these solutions can provide for a design. “Weak Link” UL 1077 Supplementary Protectors Assembly Limiting Factor: • Some may have an interrupting rating of 5kA to 10kA. Default rating is 200A if unmarked. • Not permitted for feeder or branch circuit protection. UL 489 Instantaneous Trip Circuit Breaker Assembly Limiting Factor: • SCCR is dependent upon combination rating when used with a listed combination motor controller. Default rating can be as low as 5kA. Varies by manufacturer. Power Distribution Block in Feeder Circuit Assembly Limiting Factor: • If the power distribution block is not marked with a combination SCCR the default rating of 10kA must be used. • For feeder circuit applications, power distribution blocks must have feeder spacings per UL 508A. Molded Case Circuit Breakers with Low Interrupting Ratings Assembly Limiting Factor: • Typically have interrupting ratings of 10kA to 14kA. • Higher interrupting ratings are available at increased cost. Type E Self Protected Combination Starter Assembly Limiting Factor: • Slash voltage rating limits the application options for the assembly to only a solidly grounded wye system. • Line-to-ground interrupting capability is limited. • SCCR at 600/347V is typically limited. Additional Resources on SCCR Cooper Bussmann offers tools to assist with the proper application of short-circuit current ratings including: Simplified Guide to SCCR: basic understanding of short-circuit current ratings and tools to determine the “weakest link” for industrial control panels. OSCAR™: Online Short-Circuit Current per UL 508A Rating Compliance Software. Used to determine and document the shortcircuit current ratings of industrial control panels. Go online to www.cooperbussmann.com/oscar for more information. ©2008 Cooper Bussmann This is an example of how Cooper Bussmann can help “FIND” the “weakest link” and “FIX” the “weakest link.” Cooper Bussmann will provide the most versatile and reliable design for any overcurrent protection need. “FIX IT” Increase the Interrupting Rating: • Use Cooper Bussmann® current-limiting fuses and the CCP (Class CC or CUBEFuse®) or fuse holder to achieve higher SCCRs by replacing the low interrupting rated UL 1077 supplementary protector with modern current-limiting fuses with high IRs of up to 300kA. Increase the Interrupting Rating: • Use Cooper Bussmann current-limiting fuses and the CCP (Class CC or CUBEFuse) or fuse holder to achieve higher short-circuit current ratings by replacing the low SCCR combination rated instantaneous trip circuit breaker with modern current-limiting fuses with high interrupting ratings of up to 300kA. Use PDB and PDBFS Series of Power Distribution Blocks with High SCCR: • Cooper Bussmann has introduced a line of power distribution blocks Listed to UL 1953 with high SCCRs up to 200kA when protected by Class J fuses. By replacing a low rated power distribution block with the Cooper Bussmann® PDBs or PDBFS, a panel can achieve the high ratings and proper spacings needed. Increase the Interrupting Rating: • Use Cooper Bussmann current-limiting fuses and the CCP (Class CC or CUBEFuse) or fuse holder to achieve higher short-circuit current ratings by replacing the low interrupting rated circuit breaker with modern currentlimiting fuses with high interrupting ratings of up to 300kA. Use Device With Straight Voltage Rating: • Use Cooper Bussmann current-limiting fuses and the CCP (Class CC or CUBEFuse) or fuse holder with high SCCR combination and straight voltage rated motor starter to allow for installation on any type of system grounding. Short-Circuit Calculator Program: free software download to calculate the available fault current at different points within the electrical distribution system. For more information on the above, go to: www.cooperbussmann.com. 107