English

BL6501A
FEATURES
Single Phase Energy Meter IC
DESCRIPTION
High accuracy, less than 0.3% error over a
The BL6501A is a low cost, high accuracy, high
dynamic range of 500 : 1
stability, simple peripheral circuit electrical energy
meter IC. The meter based on the BL6501A is
Exactly measure the real power in the positive
orientation and negative orientation, calculate the
intended
energy in the same orientation
distribution systems. It can exactly measure the real
Two current monitors continuously monitor the
power in the positive orientation and negative
phase and neutral currents in two-wire distribution
orientation and calculate the energy in the same
systems. Uses the larger of two currents to bill, even
orientation.
during a Fault condition
for
using
in
single-phase,
two-wire
The BL6501A incorporates a novel
A PGA in the current channel allows using small
fault
detection scheme that both warns of fault conditions
value shunt and burden resistance
and allows the BL6501A to continue accurate billing
The low frequency outputs F1 and F2 can
during a fault event. The BL6501A does this by
directly drive electromechanical counters and two
continuously monitoring both the phase and neutral
phase stepper motors and the high frequency output
(return) currents. Fault condition is indicated by
CF, supplies instantaneous real power, is intended for
PIN19 (FAULT), when these currents differ by more
calibration and communications
than 12%. Billing is continued using the larger of the
two currents when the difference is greater than 14%.
Two logic outputs REVP and FAULT can be used
The BL6501A supplies average real power
to indicate a potential orientation or Fault condition
On-Chip power supply detector
information on the low frequency outputs F1 (Pin23)
On-Chip anti-creep protection
and F2 (Pin24). These logic outputs may be used to
On-Chip voltage reference of 2.44V ± 8%
directly drive an electromechanical counter and
(typical temperature coefficient of 30ppm/℃),with
two-phase stepper motors. The CF (Pin22) logic
external overdrive capability
output gives instantaneous real power information.
Single 5V supply
This output is intended to be used for calibration
Low static power (typical value of 15mW).
purposes or interface to an MCU.
The technology of SLiM (Smart–Low–current–
Management )
is used.
BL6501A thinks over the stability of reading
error in the process of calibration.. An internal no-load
threshold ensures that the BL6501A does not exhibit
Interrelated patents are pending
any creep when there is no load.
VREF
BLOCK DIAGRAM
AVDD
input
control
DVDD
1
24
F1
AC/DC
2
23
F2
AVDD
3
22
CF
V1A
4
21
DGND
V1B
5
20
REVP
V1N
6
V2N
7
19
FAULT
18
CLKOUT
V2P
8
17
CLKIN
9
16
RESET
G0
VREF 10
15
G1
AGND 11
14
S0
SCF 12
13
S1
BL6501A
DIP/SSOP 24
http://www.belling.com.cn
voltage
reference
V1A
V1B
V1N
current
sampling
V2P
V2N
voltage
sampling
analog
to
digital
high
pass
filte
r
analog
to
digital
high
pass
filte
r
power
detector
BL6501A
digital
multiplicat
ion
digital
to
frequency
and
output
low
pass
filte
r
logical control
G0
G1
-1Total 15 Pages
AC/DC
RESET
SCF
S0
S1
3/1/2007
FAULT
REVP
CF
F1
F2
BL6501A
Single Phase Energy Meter IC
PIN DESCRIPTIONS
Pin
Symbol
DESCRIPTIONS
1
DVDD
Digital Power Supply (+5V). Provides the supply voltage for the digital circuitry. It
should be maintained at 5 V±5% for specified operation.
2
AC/ DC
High-Pass Filter Select. This logic input is used to enable the high pass filter in the
current channel. Logic high on this pin enables the HPF.
3
AVDD
Analog Power Supply (+5V). Provides the supply voltage for the analog circuitry. It
should be maintained at 5 V±5% for specified operation.
4,5
V1A,V1B
Inputs for Current Channel. These inputs are fully differential voltage inputs with a
maximum signal level of ±660 mV with respect to pin6 (V1N) for specified
operation.
6
V1N
Negative Input Pin for Differential Voltage Inputs V1A and V1B.
7,8
V2N,V2P
Negative and Positive Inputs for Voltage Channel. These inputs provide a fully
differential input pair. The maximum differential input voltage is ±660 mV for
specified operation.
9
RESET
Reset Pin. Logic low on this pin will hold the ADCs and digital circuitry in a reset
condition and clear internal registers.
10
VREF
On-Chip Voltage Reference. The on-chip reference has a nominal value of 2.44V ±
8% and a typical temperature coefficient of 30ppm/℃. An external reference source
may also be connected at this pin.
11
AGND
Analog Ground Reference. Provides the ground reference for the analog circuitry.
12
SCF
Calibration Frequency Select. This logic input is used to select the frequency on the
calibration output CF.
13,14
S1,S0
Output Frequency Select. These logic inputs are used to select one of four possible
frequencies for the digital-to-frequency conversion. This offers the designer greater
flexibility when designing the energy meter.
15,16
G1,G0
Gain Select. These logic inputs are used to select one of four possible gains for current
channel. The possible gains are 1, 2, 8, and 16.
17
CLKIN
Clock In. An external clock can be provided at this logic input. Alternatively, a crystal
can be connected across this pin and pin18 (CLKOUT) to provide a clock source
18
CLKOUT
Clock Out. A crystal can be connected across this pin and pin17 (CLKIN) as described
above to provide a clock source.
FAULT
Fault Indication. Logic high indicates fault condition. Fault is defined as a condition
under which the signals on V1A and V1B differ by more than 12.5%. The logic output
will be reset to zero when fault condition is no longer detected.
19
Negative Indication. Logic high indicates negative power, i.e., when the phase angle
20
REVP
between the voltage and current signals is greater that 90°. This output is not latched
and will be reset when positive power is once again detected.
21
DGND
Digital Ground Reference. Provides the ground reference for the digital circuitry.
22
CF
Calibration Frequency. The CF logic output gives instantaneous real power
information. This output is intended to use for calibration purposes.
23,24
F1,F2
Low-Frequency. F1 and F2 supply average real power information. The logic outputs
http://www.belling.com.cn
-2Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
can be used to directly drive electromechanical counters and 2-phase stepper motors.
PACKAGE DIMENSIONS
24 PIN SSOP
ABSOLUTE MAXIMUM RATINGS
( T = 25 ℃ )
Parameter
Symbol
Value
Unit
Analog Power Voltage AVDD
AVDD
-0.3~+7(max)
V
Digital power Voltage DVDD
DVDD
-0.3~+7(max)
V
-0.3~+0.3
V
DVDD to AVDD
Analog Input Voltage of Channel 2 to AGND
V (V)
VSS+0.5≤V(v)≤VDD-0.5
V
Analog Input Voltage of Channel 1 to AGND
V (I)
VSS+0.5≤V(i)≤VDD-0.5
V
Operating Temperature Range
Topr
-40~+85
℃
Storage Temperature Range
Tstr
-55~+150
℃
15
mW
Power Dissipation(DIP24)
Electronic Characteristic Parameter
(T=25℃, AVDD=5V, DVDD= 5V, CLKIN=3.58MHz)
Parameter
Symbol
1 Analog Power Current
http://www.belling.com.cn
Test Condition
IAVDD
Measure
Pin
Pin1
-3Total 15 Pages
Min
Value
Typical
Value
Max
Value
Unit
2
3
mA
3/1/2007
BL6501A
2 Digital Power Current
IDVDD
Single Phase Energy Meter IC
Pin3
3 Logic Input Pins
G0, G1, SCF,S0,S1,
ACDC, /RESET
1
2
mA
Pin2,
9,12,13,14,
15,16
Input High Voltage
VIH
Input Low Voltage
VIL
Input Capacitance
CIN
AVDD=5V
DVDD=5V
2
V
1
10
4 Logic Output Pins
F1, F2
V
pF
Pin23, 24
Output High Voltage
VOH1
IH=10mA
Output Low Voltage
VOL1
IL=10mA
Output Current
4.4
V
0.5
IO1
10
5 Logic Output Pins
CF, REVP, FAULT
V
mA
Pin22,
20,19
Output High Voltage
VOH2
IH=10mA
Output Low Voltage
VOL2
IL=10mA
Output Current
4.4
0.5
IO2
6 On-chip Reference
Vref
V
10
AVDD=5V
7 Analog Input Pins
V1A, V1B, V1N, V2N, V2P
Pin10
2.245
2.44
V
mA
2.635
V
±1
V
Pin4, 5,6,
7,8
Maximum Input Voltage
VAIN
DC Input Impedance
330
Kohm
Input Capacitance
10
pF
8 Accuracy
Measurement Error on Channel
1 and 2
Gain=1
ENL1
Both Channels with
Full-Scale Signal
Pin22
0.1
0.3
%
Gain=2
ENL2
Pin22
0.1
0.3
%
Gain=8
ENL8
±660mV
Over a Dynamic
Range 500 to 1
Pin22
0.1
0.3
%
Gain=16
ENL16
Pin22
0.1
0.3
%
Channel 1 Lead 37°
(PF=0.8Capacitive)
Pin22
0.3
%
Channel 1 Lags
(PF=0.5Inductive)
Pin22
0.3
%
Phase Error between Channels
9 Start Current
ISTART
Ib=5A C=3200,
cosϕ=1
Voltage Channel
Pin5
0.2%I
b
A
Inputs ±110mV
Gain of Current
Channel 16
http://www.belling.com.cn
-4Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
10 Positive and Negative Real
Power Error (%)
ENP
Vv=±110mV,V(I)=
2mV, cosϕ=1
Vv=±110mV,V(I)=
2mV, cosϕ=-1
Pin22
1
%
11 Gain Error
Gain
error
External 2.5V
Reference,Gain=1,
V1=V2=500mV
DC
Pin22
±5
%
TERMINOLOGY
1) Nonlinear Error
The Nonlinear Error is defined by the following formula:
eNL%=[(Error at X-Error at Ib) / (1+Error at Ib )]*100%
When V(v)= ±110mV, cosϕ=1, over the arrange of 5%Ib to 800%Ib, the nonlinear error should be
less than 0.1%.
2) Start Current
When meter constant C=3200, Ib=5A, cosϕ=1, V(V)=±110mV, 5%Ib error in normal range, the
min AC current in current loop.
3) Positive And Negative Real Power Error
When the positive real power and the negative real power is equal, and V(v) =±110mV, the test
current is Ib, then the positive and negative real power error can be achieved by the following
formula:
eNP%=|[(eN%-eP%)/(1+eP%)]*100%|
Where: eP% is the Positive Real Power Error, eN% is the Negative Real Power Error.
4) Phase Error Between Channels
The HPF (High Pass Filter) in Channel 1 has a phase lead response. To offset this phase response
and equalize the phase response between channels, a phase correction network is also placed in
Channel 1. The phase correction network matches the phase to within ±0.1°over a range of 45
Hz to 65 Hz and ±0.2°over a range 40Hz to 1KHz.
5) Gain Error
The gain error of the BL6501A is defined as the difference between the measured output
frequency (minus the offset) and the ideal output frequency. It is measured with a gain of 1 in
channel V1. The difference is expressed as a percentage of the ideal frequency. The ideal
frequency is obtained from the BL6501A transfer function.
6) Gain Error Match
The gain error match is defined as the gain error (minus the offset) obtained when switching
between a gain of 1 and a gain of 2, 8, or 16. It is expressed as a percentage of the output
frequency obtained under a gain of 1. This gives the gain error observed when the gain selection is
changed from 1 to 2, 8 or 16.
http://www.belling.com.cn
-5Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
7) Power Supply Monitor
BL6501A has the on-chip Power Supply monitoring The BL6501A will remain in a reset
condition until the supply voltage on AVDD reaches 4 V. If the supply falls below 4 V, the
BL6501A will also be reset and no pulses will be issued on F1, F2 and CF.
TIMING CHARACTERISTIC
(AVDD=DVDD=5V, AGND=DGND=0V, On-Chip Reference, CLKIN=3.58MHz, Temperature
range: -40~+85°C)
Parameter
t1
Value
275ms
t2
Comments
F1 and F2 pulse-width (Logic Low). When the power is low, the
t1 is equal to 275ms; when the power is high, and the output
period exceeds 550ms, t1 equals to half of the output period.
F1 or F2 output pulse period.
t3
½ t2
Time between F1 falling edge and F2 falling edge.
t4
90ms
CF pulse-width (Logic high). When the power is low, the t4 is
equal to 90ms; when the power is high, and the output period
exceeds 180ms, t4 equals to half of the output period.
t5
t6
CF Pulse Period. See Transfer Function section.
CLKIN/4
Minimum Time Between F1 and F2.
Notes:
1) CF is not synchronous to F1 or F2 frequency outputs.
2) Sample tested during initial release and after any redesign or process change that may affect this
parameter.
THEORY OF OPERATION
Principle of Energy Measure
In energy measure, the power information varying with time is calculated by a direct
multiplication of the voltage signal and the current signal. Assume that the current signal and the
voltage signal are cosine functions; Umax, Imax are the peak values of the voltage signal and the
current signal; ωis the angle frequency of the input signals; the phase difference between the
current signal and the voltage signal is expressed asφ. Then the power is given as follows:
p (t ) = U max cos( wt ) × I max cos( wt + ϕ )
http://www.belling.com.cn
-6Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
If φ=0:
p (t ) =
U max I max
[1 + cos(2 wt )]
2
If φ≠0:
p (t ) = U max cos(ωt ) × I max cos(ωt + Φ )
= U max cos(ωt ) × [I max cos(ωt ) cos(Φ ) + I max sin(ωt ) sin(Φ )]
U max I max
[1 + cos(2ωt )] cos(Φ ) + U max I max cos(ωt ) sin(ωt ) sin(Φ )
2
U I
U I
= max max [1 + cos(2ωt )] cos(Φ ) + max max sin( 2ωt ) sin(Φ)
2
2
U I
U I
= max max cos(Φ) + max max [cos(2ωt ) cos(Φ ) + sin(2ωt ) sin(Φ)]
2
2
U I
U I
= max max cos(Φ) + max max cos(2ωt + Φ)
2
2
=
P(t) is called as the instantaneous power signal. The ideal p(t) consists of the dc component and ac
component whose frequency is 2ω. The dc component is called as the average active power, that
is:
P=
U max I max
cos(ϕ )
2
The average active power is related to the cosine value of the phase difference between the voltage
signal and the current signal. This cosine value is called as Power Factor (PF) of the two channel
signals.
Figure1.
The Effect of phase
When the signal phase difference between the voltage and current channels is more than 90°, the
average active power is negative. It indicates the user is using the electrical energy reversely.
Operation Process
In BL6501A, the two ADCs digitize the voltage signals from the current and voltage transducers.
These ADCs are 16-bit second order sigma-delta with an oversampling rate of 900 kHz. This
analog input structure greatly simplifies transducer interfacing by providing a wide dynamic range
for direct connection to the transducer and also simplifying the antialiasing filter design. A
programmable gain stage in the current channel further facilitates easy transducer interfacing. A
high pass filter in the current channel removes any dc component from the current signal. This
http://www.belling.com.cn
-7Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
eliminates any inaccuracies in the real power calculation due to offsets in the voltage or current
signals.
The real power calculation is derived from the instantaneous power signal. The instantaneous
power signal is generated by a direct multiplication of the current and voltage signals. In order to
extract the real power component (i.e., the dc component), the instantaneous power signal is
low-pass filtered. Figure 2 illustrates the instantaneous real power signal and shows how the real
power information can be extracted by low-pass filtering the instantaneous power signal. This
scheme correctly calculates real power for nonsinusoidal current and voltage waveforms at all
power factors. All signal processing is carried out in the digital domain for superior stability over
temperature and time.
current
sampling
I
voltage
sampling
V
analog to
digital
high pass
filter
analog to
digital
digital
multiplication
high pass
filter
CF
low pass
filter
digital to
frequency
F1
F2
instantaneous real
power signal
instantaneous
power signal p(t)
V*I
integral
p(t)=i(t)*v(t)
v(t)=V*cos(wt)
i(t)=I*cos(wt)
V*I
2
p(t)=
V*I
2
V*I
2
[1+cos(2wt)]
t
t
Figure 2.
Signal Processing Block Diagram
The low frequency output of the BL6501A is generated by accumulatingm this real power
information. This low frequency inherently means a long accumulation time between output
pulses. The output frequency is therefore proportional to the average real power. This average real
power information can, in turn, be accumulated (e.g., by a counter) to generate real energy
information. Because of its high output frequency and hence shorter integration time, the CF
output is proportional to the instantaneous real power. This is useful for system calibration
purposes that would take place under steady load conditions.
Offset Effect
The dc offsets come from the input signals and the forepart analog circuitry.
Assume that the input dc offsets on the voltage channel and the current channel are Uoffset and Ioffset,
and PF equals 1 (φ=0).
p (t ) = [U cos(ωt ) + U offset ] × [ I cos(ωt + Φ ) + I offset ]
=
UI
UI
+ I offsetU cos(ωt ) + U offset I cos(ωt ) +
cos(2ωt )
2
2
http://www.belling.com.cn
-8Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
Figure 3.
Effect of Offset
As can be seen, for each phase input, if there are simultaneous dc offsets on the voltage channel
and the current channel, these offsets contribute a dc component for the result of multiplication.
That is, the offsets bring the error of Uoffset×Ioffset to the final average real power. Additionally,
there exists the component of Uoffset×I+U×Ioffset at the frequency of ω. The dc error on the real
power will result in measure error, and the component brought to the frequency of ω will also
affect the output of the average active power when the next low-pass filter can’t restrain the ac
component very completely.
When the offset on the one of the voltage and the current channels is filtered, for instance, the
offset on the current channel is removed; the result of multiplication is improved greatly. There is
no dc error, and the additional component at the frequency of ω is also decreased.
When the offsets on the voltage channel and the current channel are filtered respectively by two
high-pass filters, the component at the frequency of ω (50Hz) is subdued, and the stability of the
output signal is advanced. Moreover, in this case, the phases of the voltage channel and the current
channel can be matched completely, and the performance when PF equal 0.5C or 0.5L is improved.
In BL6501A, this structure is selected. Though it is given in the system specification that the
ripple of the output signal is less than 0.1%, in real measure of BL6501A, the calibration output is
very stable, and the ripple of the typical output signal is less than 0.05%.
Additionally, this structure can ensure the frequency characteristic. When the input signal changes
from 45Hz to 65Hz, the complete machine error due to the frequency change is less than 0.1%. In
such, the meter designed for the 50Hz input signal can be used on the transmission-line system of
electric power whose frequency is 60Hz.
VOLTAGE CHANNEL INPUT
The output of the line voltage transducer is connected to the BL6501A at this analog input. As
Figure4 shows that channel V2 is a fully differential voltage input. The maximum peak differential
signal on Channel 2 is ±660mV. Figure4 illustrates the maximum signal levels that can be
connected to the BL6501A Voltage Channel.
http://www.belling.com.cn
-9Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
V1
+660mV
GAIN
V1A
Maximun input differential voltage
±660mV
+
V1
V2
V1N
-
V2
-660mV
GAIN
V1
Maximun input common-mode voltage
±100mV
V1B
+
AGND
Figure 4.
Voltage Channels
Voltage Channel must be driven from a common-mode voltage, i.e., the differential voltage signal
on the input must be referenced to a common mode (usually AGND). The analog inputs of the
BL6501A can be driven with common-mode voltages of up to 100 mV with respect to AGND.
However, best results are achieved using a common mode equal to AGND.
Figure5 shows two typical connections for Channel V2. The first option uses a PT (potential
transformer) to provide complete isolation from the mains voltage. In the second option, the
BL6501A is biased around the neutral wire and a resistor divider is used to provide a voltage
signal that is proportional to the line voltage. Adjusting the ratio of Ra and Rb is also a convenient
way of carrying out a gain calibration on the meter.
RF
CT
VAP
CF
+
±660mV
RF
AGND
VN
-
CF
AGND
Phase Neutral
AGND
CF
Ra
Rb
AGND
Rv
AGND
±660mV
VAP
Phase Neutral
RF
AGND
VN
Ra >> RF
Rb+Rv=RF
Figure 5.
+
-
CF
AGND
AGND
Typical Connections for Voltage Channels
CURRENT CHANNEL INPUT
The voltage outputs from the current transducers are connected to the BL6501A here. As Figure6
shows that channel V1 has two voltage inputs, namely V1A and V1B. These inputs are fully
differential with respect to V1N. However, at any one time, only one is selected to perform the
power calculation.
http://www.belling.com.cn
- 10 Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
V1
+660mV
V2P
Maximun input differential voltage
±660mV
+
V1
-
V2N
V2
V2
Maximun input common-mode voltage
±100mV
AGND
-660mV
Figure 6.
Current Channels
The analog inputs V1A, V1B and V1N have same maximum signal level restrictions as V2P and
V2N. However, Channel 1 has a programmable gain amplifier (PGA) with user-selectable gains of
1, 2, 8, or 16I. These gains facilitate easy transducer interfacing. Figure illustrates the maximum
signal levels on V1A, V1B, and V1N. The maximum differential voltage is ±660 mV divided by
the gain selection. Again, the differential voltage signal on the inputs must be referenced to a
common mode, e.g., AGND. The maximum common-mode signal is ±100 mV.
Figure7 shows a typical connection diagram for Channel V1. Here the analog inputs are being
used to monitor both the phase and neutral currents. Because of the large potential difference
between the phase and neutral, two CTs (current transformers) must be used to provide the
isolation. The CT turns ratio and burden resistor (Rb) are selected to give a peak differential
voltage of ±660 mV/gain.
RF
CT
V1A
Rb
IP
IN
±660mV
GAIN
+
CF
V1N
AGND
Rb
±660mV
GAIN
-
CF
V1B
CT
+
RF
Phase Neutral
CF
Ra
Rb
Rv
Ra >> RF
Rb+Rv=RF
AGND
±660mV
V1A
AGND
IP
+
-
V1N
IN
AGND
Rb
±660mV
GAIN
-
CF
V1B
CT
+
RF
Phase Neutral
Figure 7.
http://www.belling.com.cn
Typical Connections for Current Channels
- 11 Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
FAULT DETECTION
The BL6501A incorporates a novel fault detection scheme that warns of fault conditions and
allows the BL6501A to continue accurate billing during a fault event. The BL6501A does this by
continuously monitoring both the phase and neutral (return) currents. A fault is indicated when
these currents differ by more than 12.5%. However, even during a fault, the output pulse rate on
F1 and F2 is generated using the larger of the two currents. Because the BL6501A looks for a
difference between the signals on V1A and V1B, it is important that both current transducers are
closely matched. On power-up the output pulse rate of the BL6501A is proportional to the product
of the signals on Channel V1A and Voltage Channel. If there is a difference of greater than 12.5%
between V1A and V1B on power-up, the fault indicator (FAULT) will go active after about one
second. In addition, if V1B is greater than V1A the BL6501A will select V1B as the input. The
fault detection is automatically disabled when the voltage signal on Channel 1 is less than 0.5% of
the full-scale input range. This will eliminate false detection of a fault due to noise at light loads.
If V1A is the active current input (i.e., is being used for billing), and the signal on V1B (inactive
input) falls by more than 12.5% of V1A, the fault indicator will go active. Both analog inputs are
filtered and averaged to prevent false triggering of this logic output. As a consequence of the
filtering, there is a time delay of approximately one second on the logic output FAULT after the
fault event. The FAULT logic output is independent of any activity on outputs F1 or F2. Figure 8
illustrates one condition under which FAULT becomes active. Since V1A is the active input and it
is still greater than V1B, billing is maintained on VIA, i.e., no swap to the V1B input will occur.
V1A remains the active input.
V1A
V1B
V1A
V1B
0V
V1N
FAULT
current
sampling
to ADC
V1B < 87.5% V1A
Figure 8. Fault Conditions for Inactive Input Less than Active Input
Figure 9 illustrates another fault condition. If V1A is the active input (i.e., is being used for billing)
and the voltage signal on V1B (inactive input) becomes greater than 114% of V1A, the FAULT
indicator goes active, and there is also a swap over to the V1B input. The analog input V1B has
now become the active input. Again there is a time delay of about 1.2 seconds associated with this
swap. V1A will not swap back to being the active channel until V1A becomes greater than 114%
of V1B. However, the FAULT indicator will become inactive as soon as V1A is within 12.5% of
V1B. This threshold eliminates potential chatter between V1A and V1B.
http://www.belling.com.cn
- 12 Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
V1B
V1A
0V
V1A
V1B
V1N
FAULT
current
sampling
to ADC
V1A < 87.5% V1B
Figure 9. Fault Conditions for Inactive Input Greater than Active Input
Power Supply Monitor
The BL6501A contains an on-chip power supply monitor. If the supply is less than 4V±5% then
the BL6501A will go in an inactive state, i.e. no energy will be accumulated when the supply
voltage is below 4V. This is useful to ensure correct device operation at power up and during
power down. The power supply monitor has built-in hysteresis and filtering. This gives a high
degree of immunity to false triggering due to noisy supplies.
The trigger level is nominally set at 4V, and the tolerance on this trigger level is about ±5%. The
power supply and decoupling for the part should be such that the ripple at VDD does not exceed
5V±5% as specified for normal operation.
SLiM technology
The BL6501A adopts the technology of SLiM (Smart Low current Management) to decrease the
static power greatly. The static power of BL6501A is about 12mW. It is half of the previous
product BL0951 (about 25mW ).This technology also decreases the request for power supply
design.
BL65XX series products used 0.35um CMOS process. The reliability and consistency are
advanced.
OPERATION MODE
Transfer Function
The BL6501A calculates the product of two voltage signals (on Channel 1 and Channel 2) and
then low-pass filters this product to extract real power information. This real power information is
then converted to a frequency. The frequency information is output on F1 and F2 in the form of
active low pulses. The pulse rate at these outputs is relatively low. It means that the frequency at
these outputs is generated from real power information accumulated over a relatively long period
of time. The result is an output frequency that is proportional to the average real power. The
average of the real power signal is implicit to the digital-to-frequency conversion. The output
frequency or pulse rate is related to the input voltage signals by the following equation. (use
3.58MHz oscillator)
Freq =
5.74 × V (v) × V (i ) × gain × FZ
2
VREF
Freq——Output frequency on F1 and F2 (Hz)
V(v)——Differential rms voltage signal on Channel 1 (volts)
http://www.belling.com.cn
- 13 Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
V(i)——Differential rms voltage signal on Channel 2 (volts)
Gain——1, 2, 8 or 16, depending on the PGA gain selection, using logic inputs G0 and G1
Vref——The reference voltage (2.44 V±8%) (volts)
Fz——One of four possible frequencies selected by using the logic inputs S0 and S1.
S1
S0
Fz(Hz)
XTAL/CLKIN
0
0
1.7
CLKIN/2^21
0
1
3.4
CLKIN/2^20
1
0
6.8
CLKIN/2^19
1
1
13.6
CLKIN/2^18
Frequency Output CF
The pulse output CF (Calibration Frequency) is intended for use during calibration. The output
pulse rate on CF can be up to 128 times the pulse rate on F1 and F2. The following Table shows
how the two frequencies are related, depending on the states of the logic inputs S0, S1 and SCF.
Mode
SCF
S1
S0
CF/F1 (or F2)
1
1
0
0
128
2
0
0
0
64
3
1
0
1
64
4
0
0
1
32
5
1
1
0
32
6
0
1
0
16
7
1
1
1
16
8
0
1
1
8
Because of its relatively high pulse rate, the frequency at this logic output is proportional to the
instantaneous real power. As is the case with F1 and F2, the frequency is derived from the output
of the low-pass filter after multiplication. However, because the output frequency is high, this real
power information is accumulated over a much shorter time. Hence less averaging is carried out in
the digital-to-frequency conversion. With much less averaging of the real power signal, the CF
output is much more responsive to power fluctuations.
GAIN SELECTION
By select the digital input G0 and G1 voltage (5V or 0V), we can adjust the gain of current
channel. We can see that while increasing the gain, the input dynamic range is decreasing.
G1
G0
Gain
Maximum Differential
Signal
0
0
1
±660mV
0
1
2
±330mV
1
0
8
±82mV
1
1
16
±41mV
http://www.belling.com.cn
- 14 Total 15 Pages
3/1/2007
BL6501A
Single Phase Energy Meter IC
ANALOG INPUT RANGE
The maximum peak differential signal on Voltage Channel is ± 660 mV, and the common-mode
voltage is up to 100 mV with respect to AGND.
The analog inputs V1A, V1B, and V1N have the same maximum signal level restrictions as V2P
and V2N. However, The Current Channel has a programmable gain amplifier (PGA) with
user-selectable gains of 1, 2, 8, or 16. These gains facilitate easy transducer interfacing. The
maximum differential voltage is ±660 mV and the maximum common-mode signal is ±100
mV.
The corresponding Max Frequency of CF/F1/F2 is shown in the following table.
SCF
S1
S0
Fz
Max Frequency
of F1, F2 (Hz)
DC
CF Max Frequency (Hz)
AC
DC
AC
1
0
0
1.7
0.68
0.34
128×F1,F2=87.04
128×F1,F2=43.52
0
0
0
1.7
0.68
0.34
64×F1,F2=43.52
64×F1,F2=21.76
1
0
1
3.4
1.36
0.68
64×F1,F2=87.04
64×F1,F2=43.52
0
0
1
3.4
1.36
0.68
32×F1,F2=43.52
32×F1,F2=21.76
1
1
0
6.8
2.72
1.36
32×F1,F2=87.04
32×F1,F2=43.52
0
1
0
6.8
2.72
1.36
16×F1,F2=43.52
16×F1,F2=21.76
1
1
1
13.6
5.44
2.72
16×F1,F2=87.04
16×F1,F2=43.52
0
1
1
13.6
5.44
2.72
8×F1,F2=43.52
8×F1,F2=21.76
Notice: Sample tested during initial release and after any redesign or process change
that may affect parameter. Specification subject to change without notice. Please ask
for the newest product specification at any moment.
http://www.belling.com.cn
- 15 Total 15 Pages
3/1/2007