SE-330 IEC 61850 Interface Manual - New Revision

3714 Kinnear Place
Saskatoon, SK
Canada
S7P 0A6
Ph: (306) 373-5505
Fx: (306) 374-2245 www.littelfuse.com/relayscontrols
SE-330 SERIES (NEW REVISION) IEC 61850 INTERFACE
Revision 0-B-060914
Copyright  2014 Littelfuse Startco Ltd.
All rights reserved.
Document Number: PM-1206-EN
Printed in Canada.
SE-330 Series (New Revision) IEC 61850 Interface
This page intentionally left blank.
Page i
Rev. 0-B-060914
Page ii
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
TABLE OF CONTENTS
SECTION
LIST OF TABLES
PAGE
1
General ................................................................. 1
1.1 Configuration Software ......................................... 1
2
Network Configuration....................................... 1
2.1 Ethernet Ports ........................................................ 1
2.2 IP Settings ............................................................. 1
2.3 SNTP Settings ....................................................... 1
2.4 IEC 61850 Clients ................................................. 1
3
IEC 61850 Configuration ................................... 4
3.1 Server Configuration ............................................. 4
3.2 Report Control Blocks .......................................... 6
3.3 Data Sets ............................................................... 7
3.4 GOOSE Settings ................................................... 9
3.4.1 GOOSE Control Blocks ............................. 9
3.4.2 GOOSE Network Inputs ............................ 9
4
MMS Data Model .............................................. 12
4.1 Device Information LLN0................................... 12
4.1.1 Report Control Blocks ............................. 12
4.1.2 Default Datasets ....................................... 13
4.1.3 GOOSE Control Blocks ........................... 13
4.2 Physical Device LPHD ....................................... 13
4.3 Metering UIRMMXU1 ....................................... 14
4.4 Ground Fault GFPTOC1 ..................................... 15
4.5 Resistor Fault RFPTOV1 .................................... 16
4.6 Command CMDGGIO0 ...................................... 17
4.7 Event Record RECGGIO2 .................................. 18
5
Specifications ..................................................... 19
Appendix A SE-330 Series (New Revision)
IEC 61850 Interface Revision History ........................ 20
LIST OF FIGURES
FIGURE
1
2
3
4
5
6
7
8
9
PAGE
SE-MON330 Communications Settings ............... 2
Top View of SE-330 (SE-330-X6-XX) with
Dual RJ-45 Ethernet Network Communications ... 2
Top View of SE-330 (SE-330-X7-XX) with
Single Fiber SC and Single RJ-45
Ethernet Network Communications ...................... 3
Top View of SE-330 (SE-330-X8-XX)
with Dual Fiber SC Ethernet
Network Communications .................................... 3
SE-MON330 IEC 61850 Server Configuration
Tab ........................................................................ 4
SE-MON330 IEC 61850 Report Control
Block (RCB) Configuration Tab ........................... 5
SE-MON330 IEC 61850 Data Sets Tab ................ 7
SE-MON330 IEC 61850 Data Set
Properties Window ................................................ 8
SE-MON330 IEC 61850 GOOSE Tab................ 10
TABLE
1
2
3
4
5
6
7
8
9
10
11
12
PAGE
Default IP Settings .................................................1
Server Configuration Parameters ...........................4
RCB Report Conditions .........................................6
RCB Optional Fields..............................................6
GOOSE Network Input Status Values .................11
LLN0 – Logical Node Data .................................12
LPHD – Logical Node Data.................................13
Metering UIRMMXU1 ........................................14
Ground Fault GFPTOC1 ......................................15
Resistor Fault RFPTOV1 .....................................16
Command CMDGGIO0 .......................................17
Event Record RECGGIO2 ...................................18
DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a result
of incorrect application, incorrect adjustment, or a
malfunction.
SE-330 Series (New Revision) IEC 61850 Interface
This page intentionally left blank.
Page iii
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
Page 1
Rev. 0-B-060914
1. GENERAL
TABLE 1. DEFAULT IP SETTINGS
This manual describes the features of the SE-330,
SE-330AU, and SE-330HV IEC 61850 interface. Unless
otherwise indicated, “SE-330” refers to all three monitor
series in general. The optional IEC 61850 interface
includes Manufacturing Message Specification (MMS)
and Generic Object Oriented Substation Events (GOOSE)
elements. MMS Buffered and Unbuffered Report Control
Blocks are supported with user-definable Data Sets. Two
GOOSE Control Blocks and 16 GOOSE Network Inputs
are available to provide high speed peer-to-peer signaling.
Three hardware configuration options are available to
provide redundant network connections: Dual RJ45, Dual
Fiber SC, and Single RJ45/Single Fiber SC.
The IEC 61850 interface is configured using the
SE-MON330 configuration software (version 3.2 or later).
Modbus/TCP is included to support configuration of the
SE-330 over the network. For more information on the
Modbus/TCP interface, refer to the SE-330 Series
Modbus/TCP manual.
1.1 CONFIGURATION SOFTWARE
The IP, SNTP and IEC 61850 settings are configured
using SE-MON330 through the front-panel USB
interface.
To download SE-MON330, please visit
www.littelfuse.com/se-330. For information on how to
connect SE-MON330 to the SE-330, please refer to the
SE-MON330 help file found in the Help – Contents
menu.
2. NETWORK CONFIGURATION
IP and SNTP settings are configured on the
SE-MON330 Details Page tab as shown in Fig 1.
2.1 ETHERNET PORTS
Two Ethernet interface types are available for the
SE-330:
 10/100 BASE-Tx full/half duplex Auto-MDIX
RJ45
 100 Mbps fiber SC
Three combinations of these interface types are
available:
 Dual RJ45
 Dual Fiber SC
 Single RJ45 / Single Fiber SC
See Figs. 2, 3, and 4.
2.2 IP SETTINGS
When connected to the SE-330 with SE-MON330, the
IP settings can be found in the Details Page tab in the
Network Parameter section. The IP address, subnet mask
and gateway can be configured for each network
interface. Default values for these settings are listed in
Table 1.
INTERFACE 1
IP Address
Subnet Mask
Gateway
INTERFACE 2
IP Address
Subnet Mask
Gateway
192.168.1.100
255.255.255.0
0.0.0.0
192.168.2.100
255.255.255.0
0.0.0.0
For troubleshooting network connections, the SE-330
supports ICMP ping requests.
2.3 SNTP SETTINGS
When connected to the SE-330 with SE-MON330, the
SNTP Settings can be found in the Details Page tab in the
SNTP Parameter section. SNTP Enable, NTP Server IP
Address, Poll Period, and Timeout can be configured.
Enable the SNTP Client and set the NTP Server IP
Address to the address of the system NTP Server to
synchronize the SE-330 to the system time.
For
troubleshooting connection problems with the NTP
Server, monitor the SNTP Client status. The status
indicates problems such as NTP Server not found, NTP
Server not running, and timeout.
The Poll Period is the time between queries to the NTP
server. The default value is 60 s, which is typically
sufficient to maintain time synchronization to 1 ms
accuracy, but it can be configured for periods as low as
1 s.
The Timeout is the maximum time that the SNTP
Client will wait for a response from the NTP Server. The
default value is 5 s, and the minimum time is 1 s. If a
request fails, no change is made to the SE-330 internal
clock.
2.4 IEC 61850 CLIENTS
The SE-330 IEC 61850 interface supports a total of
four simultaneous client connections. Client connection
requests are accepted in the order they are received and
are available on either network interface.
SE-330 Series (New Revision) IEC 61850 Interface
FIGURE 1. SE-MON330 Communications Settings.
FIGURE 2. Top View of SE-330 (SE-330-X6-XX) with Dual RJ-45 Ethernet Network Communications.
Page 2
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
Page 3
Rev. 0-B-060914
FIGURE 3. Top View of SE-330 (SE-330-X7-XX) with Single Fiber SC and Single RJ-45 Ethernet Network
Communications.
FIGURE 4. Top View of SE-330 (SE-330-X8-XX) with Dual Fiber SC Ethernet Network Communications.
SE-330 Series (New Revision) IEC 61850 Interface
3. IEC 61850 CONFIGURATION
The SE-330 IEC 61850 interface can be configured
with SE-MON330. The configuration can be loaded from
an SE-330 or from an ICD configuration file that has been
generated in an IEC 61850 system design tool. When the
IEC 61850 configuration is ready in SE-MON330, it can
be written to the SE-330 or to an ICD file.
IEC 61850 settings are visible in the IEC 61850 tab of
SE-MON330 when it is connected to an SE-330 with the
optional IEC 61850 interface. When SE-MON330 is first
connected, the IEC 61850 fields are empty. The
configuration can be loaded from the SE-330 by clicking
“Load From SE330” or from an ICD file by clicking
“Load From ICD File”. The configuration can then be
Page 4
Rev. 0-B-060914
modified and written to the SE-330 by clicking “Write to
SE330”, or to an ICD file by clicking “Write to ICD
File”.
After writing the configuration to the SE-330, cycle
SE-330 control power for the settings to take effect.
3.1 SERVER CONFIGURATION
The IEC 61850 server settings are configured through
the IEC 61850 Server tab in SE-MON330 as shown in
Fig. 5.
The configuration includes the parameters listed in
Table 2.
FIGURE 5. SE-MON330 IEC 61850 Server Configuration Tab.
TABLE 2. SERVER CONFIGURATION PARAMETERS
PARAMETER
IED Name
Check Upper Addresses
AP ID
AE Qualifier
Presentation Selector
Session Selector
Transport Selector
Keep Alive
Two Access Points
DESCRIPTION
The user-definable name of the SE-330 on the IEC 61850 interface.
Check this option to use the upper addresses including AE Qualifier, Application ID,
Presentation Selector, Session Selector and Transport Selector in addition to IP Address
and TCP port for connection validation. If unchecked, only the IP Address and TCP port
will be used to validate the connection.
ACSE Application ID. Integer value between 0 and 65535.
OSI ACSE. AE Qualifier. Integer value between 0 and 65535.
OSI-PSEL. Presentation Selector. Integer value between 0 and 4294967295.
OSI-SSEL. Session Selector. Integer value between 0 and 65535.
OSI-TSEL. Transport Selector. Integer value between 0 and 65535.
The TCP Keep Alive period in seconds. The time it takes to detect a lost connection.
Check this option to record both network interfaces to the ICD file.
SE-330 Series (New Revision) IEC 61850 Interface
FIGURE 6. SE-MON330 IEC 61850 Report Control Block (RCB) Configuration Tab.
Page 5
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
3.2 REPORT CONTROL BLOCKS
The IEC 61850 interface includes four Buffered Report
Control Blocks (RCB) and four Unbuffered Report
Control Blocks. To configure the RCB’s, select the
IEC 61850 RCB tab in SE-MON330 as shown in Fig. 6.
RCB’s are used for data reporting to clients. Changes
made to the RCB configuration through SE-MON330
become the default settings. The RCB can be enabled or
disabled through the IEC 61850 interface.
The Data Set to be reported by the RCB is selected in
the Data Set field. Fixed or user-defined Data Sets can be
selected. See Section 3.3. The Report ID is a text
description of the RCB and has a maximum size of 64
characters.
Page 6
Rev. 0-B-060914
The Config Revision allows the user to maintain
control of the configuration revision. In a commissioned
system, if the RCB configuration changes, the Config
Revision should be incremented.
For buffered RCB’s, the Buffering Time can be
configured. The default time is 1,000 ms. The minimum
time is 0 ms, and the maximum is limited only by the
64 kB buffer memory.
The RCB can be configured to generate a report at
specific intervals by setting the Integrity Period to a value
other than 0 ms and enabling the Integrity Triggering
Option.
RCB’s can be configured to generate data reports under
the conditions listed in Table 3.
Optional report contents can be configured in the
“Option fields” section. The optional fields are listed in
Table 4.
TABLE 3. RCB REPORT CONDITIONS
CONDITION
Data Change
Quality Change
Data Update
Integrity
General Interrogation
DESCRIPTION
The report is sent when any of the Data Attributes of the Data Set associated with
the RCB have changed.
The report is sent when the Quality of any of the Data Attributes in the RCB’s Data
Set have changed.
The report is sent when any of the Data Attributes are updated. Data may not
change. Timestamp will be updated.
The report is sent at regular intervals.
The client can request the present data values at any time.
TABLE 4. RCB OPTIONAL FIELDS
FIELD
Sequence Number
Report Timestamp
Reason for Inclusion
Data Set Name
Data Reference
Buffer Overflow
Entry ID
Configuration Revision
DESCRIPTION
The integer sequence number. Incremented after each transmission of the report
starting with 0 for the first report sent after the RCB is enabled.
Timestamp of the report at the time of transmission. Not necessarily the same as
the timestamp of the data within the report.
The trigger condition that caused the report to be sent.
The name of the Data Set included in the report.
The data reference for the data included in the report.
Indicates a buffer overflow occurred. Only available in Buffered RCB’s.
The ID of the report. Only available in Buffered RCB’s.
The revision of the RCB configuration.
SE-330 Series (New Revision) IEC 61850 Interface
3.3 DATA SETS
Data Sets are used to group elements of the MMS data
model for use in RCB’s and GOOSE Control Blocks
(GCB).
Data Sets are viewed and edited using
SE-MON330 in the IEC 61850 Data Sets tab as shown in
Fig. 7.
The IEC 61850 interface includes three fixed Data Sets,
and 29 user-definable Data Sets. The three fixed Data
Sets are:
 LLN0$DS1_Measurement Data
 NGR Voltage
 NGR Impedance
 Ground-Fault Current Meter Values
 LLN0$DS2_Record Data
 Event Record Data for all events that are
recorded by the SE-330
 LLN0$DS3_GOOSE
 Ground-Fault Start
 Ground-Fault Operate
 Resistor-Fault Start
 Resistor-Fault Operate
 Remote Trip Status
FIGURE 7. SE-MON330 IEC 61850 Data Sets Tab.
Page 7
Rev. 0-B-060914
The GCB’s are configured to use the LLNO$DS3
GOOSE Data Set. Refer to Section 3.4.1 for more
information on the GCB’s. For a detailed description of
the fixed Data Sets, refer to Section 4.1.2.
User-defined Data Sets can be added through SEMON330. To add a Data Set open the Data Sets tab and
click the “+” button. This will open the Data Set
Properties window as shown in Fig. 8. In the Data Set
Properties window, assign the Data Set to a Logical Node,
give the Data Set a unique name and choose data elements
to include in the Data Set. Data elements are chosen from
the data-model tree on the left, and can be added to the
list on the right by clicking the arrow buttons. Up to 30
data elements can be added. Only data elements with a
functional constraint of ST or MX can be included in a
Data Set. When a data element has been added to the list
on the right, it can be moved up or down in the list with
the up and down arrow buttons, or removed from the list
with the “X” button.
SE-330 Series (New Revision) IEC 61850 Interface
FIGURE 8. SE-MON330 IEC 61850 Data Set Properties Window.
Page 8
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
3.4 GOOSE SETTINGS
IEC 61850 GOOSE is used to provide network trip and
alarm signaling in place of or in addition to traditional
relay connections. The GOOSE configuration is viewed
and edited in the IEC 61850 GOOSE tab as shown in
Fig. 9.
GCB’s are configured to publish GOOSE data on the
system network. GOOSE Network Inputs are configured
to subscribe to GOOSE data that is available on the
system network.
3.4.1 GOOSE CONTROL BLOCKS
To support the redundant network interfaces on the
SE-330, two GCB’s are available. The GCB’s can be
independently enabled and can be configured to transmit
on one or both network interfaces.
Both GCB’s transmit the LLN0$DS3_GOOSE Data
Set, which includes the Ground-Fault Start, Ground-Fault
Operate, Resistor-Fault Start, Resistor-Fault Operate and
Remote Trip status. These data elements support network
signaling of all SE-330 trip conditions.
The GCB’s are configured independently with options
for the Destination MAC address, VLAN settings,
Application ID, GOOSE ID, Test flag, and Network
Interface. The Configuration Revision is not configurable
and is fixed at 1.
The Destination MAC address, Application ID and
GOOSE ID are used to uniquely identify the source of the
GOOSE data. Each of these values is assigned by the
system designer in consideration of all GOOSE publishers
and subscribers on the network.
The 48-bit MAC address is typically marked as a
multicast address by setting the least significant bit of the
most significant byte to 1.
The Application ID can be any integer value between 1
and 4095.
The GOOSE ID is a user-definable text identifier. It
can contain alpha-numeric characters and underscores and
has a maximum length of 64 characters.
VLAN ID and VLAN Priority configure Virtual LAN
routing of GOOSE messages through the network.
VLAN parameters are assigned by the system designer in
consideration of all other traffic on the system network.
To disable VLAN support, set the VLAN ID and VLAN
Priority to 0.
The GCB can be configured to assert the Test flag
which informs subscribers to treat the GOOSE data as a
test. How test data is handled in the subscriber is
dependent on the specific device, but test data will
typically not be used in a trip decision.
The Network Interface can be set to Interface 1,
Interface 2 or Interface 1 and 2. When set to Interface 1
and 2, identical GOOSE messages are transmitted
simultaneously on both SE-330 network interfaces.
Page 9
Rev. 0-B-060914
The reception of duplicate GOOSE messages by a
subscriber can cause undefined behavior, so the redundant
network topology must be considered when configuring
the GCB’s.
When connected to a subscriber with redundant
network interfaces through a fully redundant network,
there is no danger of duplicate GOOSE messages being
received on either of the subscriber’s network interfaces.
In this case, a single GCB can be configured to transmit
messages on Interface 1 and 2. This configuration can be
supported in the subscriber by configuring two Network
Inputs, one for each network interface.
When connected to a subscriber with redundant
network interfaces through a network on which the
GOOSE messages can cross to either side of the network
and be received on both network interfaces of the
subscriber, the GCB configuration depends on the
behavior of the subscriber. In this case, two GCB’s can
be configured with unique GOOSE configurations to be
transmitted on different network interfaces.
3.4.2 GOOSE NETWORK INPUTS
Up to 16 GOOSE Network Inputs are supported. The
Network Inputs drive the Remote Trip function within the
SE-330.
Network Input parameters must be configured to match
the desired GOOSE message. The Destination MAC
address, Application ID, Config Revision, and GOOSE
ID must all match the corresponding fields in the GOOSE
message.
The Network Inputs require a Boolean data attribute.
The Boolean data attribute can be received as a single
Boolean value, or as a member of a Boolean bit-string.
Configure the Data Index to the index of the desired
Boolean value in the GOOSE message. The first data
element is index 0. If the value is a Boolean bit-string,
configure the Bit Index to the index of the desired bit
within the bit-string starting with index 0, otherwise set
Bit Index to 0.
The Boolean data can be inverted before it is used in
the trip decision by setting Inverted to Yes.
For troubleshooting Network Input configurations, the
status of each Network Input can be viewed in the
IEC 61850 GOOSE tab under NI Status. The Network
Input status values are listed in Table 5. The Network
Input is colored green when the received value will not
cause a Remote Trip, red when the received value will
cause a Remote Trip, and yellow when the received value
will be ignored due to the Network Input configuration.
SE-330 Series (New Revision) IEC 61850 Interface
Page 10
Rev. 0-B-060914
FIGURE 9. SE-MON330 IEC 61850 GOOSE Tab.
The Network Inputs are combined in a logical OR
operation to drive the Remote Trip function within the
SE-330. Disabled Network Inputs and Network Inputs
with a status other than OK are not included in the trip
decision. The Boolean equation for the trip status of each
Network Input is shown in Equation 3.1:
EQUATION 3.1:
Nx = Ex and [ (Tx xor Ix) and Rx]
Where:
Ex is the enabled state of network input x
(True = enabled)
Tx is the Boolean data value of network input x
Ix is the inverted setting of network input x
(True = inverted)
Rx is the state of the connection for network
input x (True = Status OK)
Nx is the final value for network input x
Equation 3.2 is the Boolean equation for the
combination of the Network Inputs in the Remote Trip
decision:
EQUATION 3.2:
Remote Trip = N0 or N1 or ... or N15
Where:
N0 through N15 are the Network Input values from
Equation 3.1
SE-330 Series (New Revision) IEC 61850 Interface
Page 11
Rev. 0-B-060914
TABLE 5. GOOSE NETWORK INPUT STATUS VALUES
STATUS
OK
No Data
Old
Bad Type
Test
Needs Commissioning
DESCRIPTION
The GOOSE messages are being received within the Time To Live period or the
Network Input is disabled.
No GOOSE messages matching the Network Input configuration are being
received.
GOOSE messages have been received in the past, but they are no longer being
received.
The Data Attribute specified in the Data Index field is not a Boolean bit-string
value.
The Test flag is set on the GOOSE messages.
The Needs Commissioning flag is set on the GOOSE messages.
SE-330 Series (New Revision) IEC 61850 Interface
4. MMS DATA MODEL
The SE-330 IEC 61850 interface includes a single
logical device that contains multiple logical nodes. The
logical nodes are described in this section.
4.1 DEVICE INFORMATION LLN0
The LLN0 Logical Node contains device information
as listed in Table 6.
Page 12
Rev. 0-B-060914
4.1.1 REPORT CONTROL BLOCKS
The LLN0 Logical Node contains four buffered and
four unbuffered RCB’s.
RCB’s can be configured with SE-MON330 or through
the IEC 61850 interface.
Buffered RCB’s are named brcb01, brcb02, brcb03,
and brcb04, and unbuffered RCB’s are named urcb01,
urcb02, urcb03, and urcb04.
TABLE 6. LLN0 – LOGICAL NODE DATA
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
Beh
INS
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
vendor
swRev
d
configRev
ldNS
VS255
VS255
VS255
VS255
VS255
DESCRIPTION
Mode for whole logical device (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Behaviour reflecting mode for whole logical device:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
The Health value reports the most severe error condition for all Logical
Nodes in the Logical Device:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in Safe Operation Mode
- SD Card Full
3 Alarm – Severe Problem, No Operation Possible
- ADC Error
- NVRAM Error
- FLASH Error
- Hardware Fault
- CT Error
- Calibration Error
- Firmware Fault
Vendor name: “Littelfuse Inc.”
Firmware Version
Description: “SE-330 Neutral Grounding Resistor Monitor”
Configuration Revision
Logical Device Name Space “IEC61850-7-4: 2003”
SE-330 Series (New Revision) IEC 61850 Interface
4.1.2 FIXED DATASETS
The LLN0 Logical Node contains two predefined Data
Sets with following contents:
Data Set DS1_Measurement
 UIRMMXU1.A (MX)
 UIRMMXU1.PhV (MX)
 UIRMMXU1.Z (MX)
Data Set DS2_Record
 GFPTOC1.Str (ST)
 GFPTOC1.Op (ST)
 RFPTOV1.Str (ST)
 RFPTOV1.Op (ST)
 RecGGIO2.AnIn1 (MX)
 RecGGIO2.AnIn2 (MX)
 RecGGIO2.AnIn3 (MX)
 RecGGIO2.Ind1 (ST)
 RecGGIO2.Ind2 (ST)
 RecGGIO2.Ind3 (ST)
 RecGGIO2.Ind4 (ST)
 RecGGIO2.Ind5 (ST)
 RecGGIO2.Ind6 (ST)
 RecGGIO2.Ind7 (ST)
 RecGGIO2.Ind8 (ST)
 RecGGIO2.Ind9 (ST)
 RecGGIO2.Ind10 (ST)
 RecGGIO2.Ind11 (ST)












Page 13
Rev. 0-B-060914
RecGGIO2.Ind12 (ST)
RecGGIO2.Ind13 (ST)
RecGGIO2.Ind14 (ST)
RecGGIO2.Ind15 (ST)
RecGGIO2.Ind16 (ST)
RecGGIO2.Ind17 (ST)
RecGGIO2.Ind18 (ST)
RecGGIO2.Ind19 (ST)
RecGGIO2.Ind18 (ST)
RecGGIO2.Ind19 (ST)
LLN0.Health (ST)
LPHD1.PhyHealth (ST)
Data Set DS3_GOOSE
 RFTPOV1.StrVal.general (ST)
 RFTPOV1.Op.general (ST)
 GFTPOC1.StrVal.general (ST)
 GFTPOC1.Op.general (ST)
 CMDGGIO1.SPCSO.stVal (ST)
4.1.3 GOOSE CONTROL BLOCKS
The LLN0 Logical Node contains two GCB’s: gcb1
and gcb2. The configuration for gcb1 and gcb2 includes
the DS3_GOOSE Data Set which cannot be changed.
4.2 PHYSICAL DEVICE LPHD
The LPHD Logical Node contains the physical device
information as listed in Table 7.
TABLE 7. LPHD – LOGICAL NODE DATA
DATA
OBJECT
NAME
PhyNam
DATA
OBJECT
TYPE
DPL
PhyHealth
Proxy
DATA
INS
ATTRIBUTE
NAME
vendor
hwRev
swRev
serNum
model
stVal
DATA
ATTRIBUTE
TYPE
VS255
VS255
VS255
VS255
VS255
INT8
SPS
stVal
BOOL
DESCRIPTION
Vendor Name: “Littelfuse Inc.”
The Hardware Revision
The Firmware Revision
The Unit Serial Number
“SE-330” or ”SE-330AU” or “SE-330HV”
Physical Device Health:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in Safe Operation Mode
3 Alarm – Severe Problem, No Operation Possible
TRUE = indicates that the LN is a proxy.
Page 14
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
4.3 METERING UIRMMXU1
The Metering Logical Node contains data objects for
the three metered values as listed in Table 8.
TABLE 8. METERING UIRMMXU1
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
DESCRIPTION
Beh
INS
ctlModel
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
PhV
WYE
VS255
VS255
VS255
FLOAT
A
WYE
FLOAT
Neutral grounding resistor current in amps.
Z
WYE
vendor
swRev
d
neut.cVal.ma
g.f
neut.cVal.ma
g.f
neut.cVal.ma
g.f
Mode for whole logical node (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Status-Only
Behaviour reflecting mode for whole logical node:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Logical Node Health:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in
Safe Operation Mode
3 Alarm – Severe Problem, No Operation Possible
Vendor Name: “Littelfuse Inc.”
Firmware Version
Description: “Neutral line measurements”
Neutral grounding resistor voltage in volts.
FLOAT
Neutral grounding resistor resistance in ohms.
SE-330 Series (New Revision) IEC 61850 Interface
Page 15
Rev. 0-B-060914
4.4 GROUND FAULT GFPTOC1
The Ground-Fault Logical Node contains data elements
that are associated with the ground-fault function of the
SE-330 as listed in Table 9.
TABLE 9. GROUND FAULT GFPTOC1
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
Beh
INS
ctlModel
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
Str
ACD
Op
StrVal
ACT
ASG
vendor
swRev
d
general
dirGeneral
general
setMag.f
VS255
VS255
VS255
BOOL
INT8
BOOL
FLOAT
OpDlTmms
ING
setVal
INT32
DESCRIPTION
Mode for whole logical node (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Status-Only
Behavior reflecting mode for whole logical node:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Logical Node Health:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in
Safe Operation Mode
3 Alarm – Severe Problem, No Operation Possible
Vendor Name: “Littelfuse Inc.”
Firmware Version
Description: “Io>”
Start. Ground Fault Condition Detected.
Unknown
Operate. Ground Fault tripped.
GF Trip Level [A] as configured through the front-panel GF Trip Level
dial.
Operate Delay Time [ms] as configured through the front-panel GF Trip
Time dial.
Page 16
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
4.5 RESISTOR FAULT RFPTOV1
The Resistor Fault Logical Node contains data
elements associated with the Neutral Grounding Resistor
(NGR) monitoring function of the SE-330. The data
elements are listed in Table 10.
TABLE 10. RESISTOR FAULT RFPTOV1
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
Beh
INS
ctlModel
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
Str
ACD
Op
StrVal
ACT
ASG
vendor
swRev
d
general
dirGeneral
general
setMag.f
VS255
VS255
VS255
BOOL
UINT8
BOOL
FLOAT
OpDlTmms
ING
setVal
INT32
DESCRIPTION
Mode for whole logical node (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Status Only
Behavior reflecting mode for whole logical node:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Logical Node Health:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in
Safe Operation Mode
3 Alarm – Severe Problem, No Operation Possible
Vendor Name: “Littelfuse Inc.”
Firmware Version
Description: “Uo>”
Start. Resistor Fault condition detected.
Unknown
Operate. Resistor Fault tripped.
Resistor Fault trip voltage [V] as configured through the front panel VN
Trip Level dial.
Operate Delay Time [ms]. Fixed at 12,000 ms.
Page 17
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
4.6 COMMAND CMDGGIO0
The CMDGGIO0 Logical Node is used to issue remote
trip and remote reset commands. The data elements
included in CMDGGIO0 are listed in Table 11.
TABLE 11. COMMAND CMDGGIO0
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
Beh
INS
ctlModel
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
SPCSO
SPC
vendor
swRev
d
stVal
Oper.ctlVal
ctlModel
VS255
VS255
VS255
BOOL
BOOL
DESCRIPTION
Mode for whole logical node (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Status-Only
Behavior reflecting mode for whole logical node:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Logical Node Health:
1 OK – No Problems, Normal Operation
2 Warning – Minor Problems, but in
Safe Operation Mode
3 Alarm – Severe Problem, No Operation Possible
Vendor Name: “Littelfuse Inc.”
Firmware Version
Description: “Remote Trip Command”
Remote Trip Status
Set to 1 to issue a remote trip command and to 0 to issue a remote reset
command (direct-with-normal-security).
Page 18
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
4.7 EVENT RECORD RECGGIO2
The RECGGIO1 Logical Node provides access to the
SE-330’s event record log. The data elements included in
the RECGGIO1 Logical Node are listed in Table 12.
Event records are readable from the RECGGIO1
Logical Node. A BRCB or URCB can be used to send
reports for new event records as they are generated. A
BRCB will also send reports for all event records
recorded since the last power cycle or since the report
buffer was last cleared. Event records that were added to
the SE-330’s internal event record list before the most
recent power cycle are not accessible through the IEC
61850 interface.
TABLE 12. EVENT RECORD RECGGIO2
DATA
OBJECT
NAME
Mod
DATA
OBJECT
TYPE
INC
DATA
ATTRIBUTE
NAME
stVal
DATA
ATTRIBUTE
TYPE
INT8
Beh
INS
ctlModel
stVal
INT8
Health
INS
stVal
INT8
NamPlt
LPL
AnIn1
MV
AnIn2
MV
AnIn3
MV
Ind1
SPS
vendor
swRev
d
mag.f
d
mag.f
d
mag.f
d
stVal
d
VS255
VS255
VS255
FLOAT
VS255
FLOAT
VS255
FLOAT
VS255
BOOL
VS255
Ind2
SPS
stVal
d
BOOL
VS255
Ind3
SPS
stVal
d
BOOL
VS255
Ind4
SPS
Ind5
SPS
stVal
d
stVal
d
BOOL
VS255
BOOL
VS255
Ind6
SPS
stVal
d
BOOL
VS255
Ind7
SPS
stVal
d
BOOL
VS255
Ind8
SPS
stVal
d
BOOL
VS255
DESCRIPTION
Mode for whole logical node (status only):
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Status-Only
Behavior reflecting mode for whole logical node:
1 ON
2 Blocked
3 Test
4 Test-blocked
5 OFF
Logical Node Health:
1 OK– No Problems, Normal Operation
2 Warning– Minor Problems, but in
Safe Operation Mode
3 Alarm– Severe Problem, No Operation Possible
Vendor Name: “Littelfuse Inc.”
Firmware Version
Description: “Recorded Values”
NGR voltage from event in volts.
Description: “Recorded NGR Voltage”
NGR current from event in amps.
Description: “Recorded NGR Current”
NGR resistance change from event in ohms.
Description: “Recorded NGR Resistance”
Ground Fault Tripped
Description: “Recorded value of Ground Fault Trip from trip field
status”
Resistor Fault Tripped
Description: “Recorded value of Resistor Fault Trip from trip field
status”
Calibration Error Tripped
Description: “Recorded value of Calibration Error Trip from trip field
status”
ADC Error Tripped
Description: “Recorded value of ADC Error from trip field status”
NGR Voltage Fault Tripped
Description: “Recorded value of NGR Voltage Fault Trip from trip field
status”
NVRam Error Tripped
Description: “Recorded value of NVRAM Error Trip from trip field
status”
Firmware Error Tripped
Description: “Recorded value of Firmware Error Trip from trip field
status”
Remote Tripped
Description: “Recorded value of Remote Trip from trip field status”
Page 19
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
DATA
OBJECT
NAME
Ind9
DATA
OBJECT
TYPE
SPS
DATA
ATTRIBUTE
NAME
stVal
d
DATA
ATTRIBUTE
TYPE
BOOL
VS255
Ind10
SPS
Ind11
SPS
Ind12
SPS
Ind13
SPS
Ind14
SPS
stVal
d
stVal
d
stVal
d
stVal
d
stVal
d
BOOL
VS255
BOOL
VS255
BOOL
VS255
BOOL
VS255
BOOL
VS255
Ind15
SPS
Ind16
SPS
Ind17
SPS
Ind18
SPS
Ind19
SPS
stVal
d
stVal
d
stVal
d
stVal
d
stVal
d
BOOL
VS255
BOOL
VS255
BOOL
VS255
BOOL
VS255
BOOL
VS255
DESCRIPTION
Hardware Error Tripped
Description: “Recorded value of Hardware Error Trip from trip field
status”
Ground Fault Exists
Description: “Recorded value of Ground Fault from setpoint status”
Resistor Fault Exists
Description: “Recorded value of Resistor Fault from setpoint status”
Calibration Exists
Description: “Recorded value of Calibration Error from setpoint status”
ADC Error Exists
Description: “Recorded value of ADC Error from setpoint status”
NGR Voltage Fault Exists
Description: “Recorded value of NGR Voltage Fault from setpoint
status”
NVRam Error Exists
Description: “Recorded value of NVRam Fault from setpoint status”
CT Error Exists
Description: “Recorded value of CT Error from setpoint status”
CT Error Tripped
Description: “Recorded value of CT Error Trip from setpoint status”
SD Card Full Error Exists
Description: “Recorded value of SD Card full from setpoint status”
Flash Memory Error Exists
Description: “Recorded value of Flash Memory Error from setpoint
status”
NOTES:
Data Attribute Types:
INT8
8-bit integer value (0-255).
VS255 Variable length ASCII string, maximum
255 characters.
FLOAT Floating point value, precision matches
IEEE-754 single.
BOOL
Boolean (TRUE or FALSE).
5. SPECIFICATIONS
Protocol ........................................IEC 61850
Ports .............................................2
IP Addresses ................................1 per port
Number of Connections ................ 4 total
Connectors ...................................Copper and/or fiber, refer
to Figs. 1, 2, and 3 and
ordering information in the
product manual
Copper:
Connector...............................RJ45
Cable ......................................CAT5
Length ....................................100 m (328’)
Interface .................................10BASE-T, 100BASE-Tx
Fiber:
Connector .............................. SC
Cable ...................................... SC Multimode
Length .................................... 2,000 m (6,561’) per
segment
Interface ................................. 100BASE-Fx
Page 20
Rev. 0-B-060914
SE-330 Series (New Revision) IEC 61850 Interface
APPENDIX A
SE-330 SERIES (NEW REVISION) IEC 61850 INTERFACE REVISION HISTORY
MANUAL RELEASE DATE
MANUAL REVISION
June 9, 2014
0-B-060914
March 4, 2014
0-A-030414
MANUAL REVISION HISTORY
REVISION 0-B-060914
SECTION 2
Updated Fig. 1.
SECTION 3
Updated Figs. 5, 6, 7, 8, and 9.
SECTION 4
Attribute “CtlModel” added.
Attribute “d” added.
APPENDIX A
Updated Revision History.
REVISION 0-A-030414
Initial release.