Littelfuse ProtectionRelays NGRM ENC Manual

3714 Kinnear Place
Saskatoon, SK
Canada
S7P 0A6
Ph: (306) 373-5505
Fx: (306) 374-2245 www.littelfuse.com/relayscontrols
NGRM-ENC MANUAL
ENCLOSED NEUTRAL-GROUNDING-RESISTOR MONITOR
Revision 0-B-030515
NGRM-ENC
CONTROL
POWER
PHASE
A
NGRM-ENC
PHASE
B
PHASE
C
PHASE
A
PHASE
B
PHASE
C
LITTELFUSE STARTCO
GROUND
FAULT
NEUTRAL-GROUNDING-RESISTOR
MONITOR
LEAKAGE
CURRENT
SE-330
LEAKAGE
CURRENT
RESISTOR
FAULT
GROUND
FAULT
DIAGNOSTIC
TRIP
TRIP
CALIBRATED
RESISTOR
FAULT
RELAY K1
8
6
10
20
40
60
80
POWER
RESET
0.4
0.3
0.2
0.1
ON
OFF
170
130
100
200
340
800
1200
60
1700
20
2000
VN TRIP LEVEL
4
100
2
MEM
GF TRIP LEVEL
(% CT RATING)
0.5 0.7 1.0
(S5
CAL
2.0
3.0
5.0
10.0
GF TRIP TIME (s)
20 K Ω
VN x 1
100 K Ω)
VN x 5
1.8 2.0 2.2
1.6
2.4
1.4
2.6
1.2
2.8
1.0
3.0
PULSE PERIOD (s)
ON
OFF
RESET
PULSE
ENABLE
PULSE
ENABLE
USB
Copyright © 2015 by Littelfuse Startco
All rights reserved.
Document Number: PM-1230-EN
Printed in Canada.
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
This page intentionally left blank.
Page i
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
TABLE OF CONTENTS
SECTION
DISCLAIMER
PAGE
1
General ................................................................. 1
1.1 SE-325 Models ..................................................... 1
1.2 SE-330 Models ..................................................... 1
2
Operation ............................................................. 1
2.1 Indication, Metering, and Reset ............................ 1
2.2 Configuration and Settings ................................... 1
3
Installation ........................................................... 2
3.1 Type 4X Enclosure ............................................... 2
3.2 Connections to the Neutral-Grounding-Resistor
and Current Transformer....................................... 2
3.2.1 SE-325 Models .......................................... 2
3.2.2 SE-330 Models .......................................... 2
3.3 Supply Voltage Connection .................................. 2
3.3.1 Supply by Field Connection ...................... 2
3.3.2 Control Power Transformer (CPT)
Models .................................................................. 2
3.4 Phase-Voltage Indication ...................................... 2
3.5 Relay-Output Connections .................................... 2
3.6 Network-Communications Connections ............... 2
3.7 Dielectric-Strength Testing ................................... 2
4
Technical Specifications ................................... 15
5
Ordering Information ....................................... 16
6
Warranty ........................................................... 16
Appendix A NGRM-ENC Revision History .............. 17
LIST OF FIGURES
FIGURE
1
2
3
4
5
6
7
8
9
10
11
12
Page ii
Rev. 0-B-030515
PAGE
NGRM-ENC Outline and Mounting Details ......... 3
SE-325 Typical Wiring Diagram........................... 4
SE-330 Typical Wiring Diagram........................... 5
SE-325 Model (NGRM-ENC-100-01)
Interior/Exterior Details .......................................... 6
SE-325 Model (NGRM-ENC-100-01)
Interior Details ........................................................ 7
SE-325 Model (NGRM-ENC-XX0-XX)
Wiring Label .......................................................... 8
SE-330 Surface-Mount Model
(NGRM-ENC-XX0-21) Interior/Exterior Details .... 9
SE-330 Surface-Mount Model
(NGRM-ENC-XX0-X1) Interior Details ............... 10
SE-330 Surface-Mount Model
(NGRM-ENC-XX0-XX) Wiring Label................. 11
SE-330 Panel-Mount Model
(NGRM-ENC-XX1-21) Interior/Exterior Details .. 12
SE-330 Panel-Mount Model
(NGRM-ENC-XX1-X1) Interior Details ............... 13
SE-330 Panel-Mount Model
(NGRM-ENC-XX1-XX) Wiring Label................. 14
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of incorrect application, incorrect adjustment, or a
malfunction.
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
This page intentionally left blank.
Page iii
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
1. GENERAL
The NGRM-ENC Enclosed Neutral-GroundingResistor (NGR) Monitor series is a Type 4X enclosure
housing a Littelfuse Startco SE-325 or SE-330 NeutralGrounding-Resistor Monitor and optional accessories that
include a 480/600-V control power transformer (CPT),
faulted-phase indication (FPI; implemented with an
EL3100 Ground-Fault & Phase-Voltage Indicator), earthleakage panel meter, pulse-enable control, and mounting
options. Appropriate fusing is included and field wiring
is to terminal blocks.
This manual supplements the relevant NGR-monitor
and EL3100 manuals.
1.1 SE-325 MODELS
NGRM-ENC models with an SE-325 NGR Monitor
include a surface-mounted NGR monitor, panel-mounted
indication and reset and have a Type 4X rating. Options
include a CPT and FPI. See Figs. 4 and 5.
1.2 SE-330 MODELS
NGRM-ENC models with an SE-330 NGR Monitor
include a panel- or surface-mounted NGR monitor which
can be optionally equipped with a network-communications
interface.
Panel-mounted models include an
SE-IP65CVR-G Hinged Transparent Cover and have an
IP65 rating. Surface-mounted models include panelmounted indication and reset, USB connector, and have a
Type 4X rating. Both mounting styles can optionally be
equipped with a CPT, FPI, earth-leakage panel meter, and
pulse-enable switch. See Figs. 7 and 10.
2. OPERATION
Refer to the SE-325, SE-330, and EL3100 manuals
included with the NGRM-ENC or at www.littelfuse.com/
relayscontrols, as required.
NOTE: For models equipped with an SE-330 NGR
Monitor and an optional pulse-enable switch, select Pulse
Enable to cause the SE-330 K1 contact to cycle at a rate
determined by the SE-330 front-panel Pulse Period
switch. Ensure that SE-330 configuration switch S1 is set
to K1=Pulse.
CAUTION: For models equipped with a CPT and/or FPI,
the maximum supply voltage is 600 Vac.
Page 1
Rev. 0-B-030515
2.1 INDICATION, METERING, AND RESET
Surface-mount models include red panel-mounted
Ground Fault and Resistor Fault LED’s that indicate the
NGR-monitor trip state, and a green Control Power LED.
Reset latched trips by pressing the Reset button when the
trip condition is no longer present. NGR-monitor frontpanel indication and reset is accessible when the door
panel is open.
Panel-mounted SE-330 face-plate indication is visible
through the hinged transparent cover. Open the hinged
transparent cover to access the SE-330 Reset button.
Models equipped with earth-leakage metering
continuously display earth-leakage current as a
percentage of the ground-fault-CT-primary rating when
the SE-330 is energized.
All SE-330 models have a USB interface through
which NGR-resistance-change, neutral-voltage and
current metering is accessible with a PC running
SE-MON330 software that is available at Littelfuse.com.
This data is also accessible through the optional networkcommunications interface.
2.2 CONFIGURATION AND SETTINGS
Factory configuration is per the SE-325 or SE-330
manual, except that SE-330 models equipped with a pulseenable switch have configuration switch S1 set to K1=Pulse.
Adjust settings as required – refer to the appropriate
manuals.
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
3. INSTALLATION
3.1 TYPE 4X ENCLOSURE
The 455 x 340 x 175 mm polyester enclosure has a
hinged front panel with dual lockable latches. For wall
mounting, attach the included mounting brackets to the
back of the enclosure with the enclosed fasteners, and
prepare the mounting surface using the dimensions as
shown in Fig. 1.
All models ship with no predrilled cable entry. An
appropriate hole or holes must be made in the enclosure
for the installation of all conductors. Space is allowed at
the bottom for cable entry. See Figs. 4, 7, and 10. Use
appropriate cable-entry fittings.
3.2 CONNECTIONS TO THE NEUTRAL-GROUNDINGRESISTOR AND CURRENT TRANSFORMER
For all models, connect NGRM-ENC terminal R to an
ER-series sensing resistor(1) terminal R. Follow SE-325 or
SE-330 manual guidelines for wire size selection. See
Figs. 2 and 3. All models connect to a current
The
transformer(1), which measures NGR current.
sensing resistor and CT are typically located in the NGR
enclosure.
3.2.1 SE-325 MODELS
Connect the CT200 current transformer(1) secondary to
NGRM-ENC terminals CT1 and CT2. Connections are
not polarity sensitive. Follow SE-325 manual guidelines
for wire size selection. See Fig. 2.
3.2.2 SE-330 MODELS
For sensitive EFCT- or SE-CS30-series current
sensors(1), connect to NGRM-ENC terminals S and C.
For 5-A-secondary CT’s connect to terminals 5 and C. A
field-wiring change is required for 1-A-secondary CT
connections. See Fig. 3. CT connections are not polarity
sensitive. Follow SE-330 manual guidelines for wire size
selection.
3.3 SUPPLY VOLTAGE CONNECTION
Appropriate supply-voltage fusing is provided for all
models. Connect terminal GND to system ground.
3.3.1 SUPPLY BY FIELD CONNECTION
For models requiring field-supply-voltage connections,
connect line and neutral to NGRM-ENC terminals L and
N. See Figs. 2 and 3. SE-325 and SE-330 models require
a 120-Vac supply. Consult the appropriate product
manual for power requirements.
Page 2
Rev. 0-B-030515
3.3.2 CONTROL POWER TRANSFORMER (CPT)
MODELS
Models equipped with a CPT are compatible with
480- and 600-V systems, and are factory-connected for a
600-V system. Field adjustment for a 480-V system is
required by moving the T1H3 connection on T1 to the H2
terminal of T1. Connect NGRM-ENC terminals ØA and
ØB to the 480- or 600-V bus using 14 to 6 AWG (2.08 to
13.3 mm2) wire. See Figs. 2 and 3.
3.4 PHASE-VOLTAGE INDICATION
For models equipped with phase-voltage and faultedphase indication, connect NGRM-ENC terminals ØA,
ØB, and ØC to the 480- or 600-V bus using 14 to 6 AWG
(2.08 to 13.3 mm2). See Figs. 2 and 3. These terminals
are shared by the CPT connections for models so
equipped.
3.5 RELAY-OUTPUT CONNECTIONS
For external alarm or trip indication and protection,
connect to SE-325 A-B relay output or SE-330 K1
relay output by connecting to NGRM-ENC terminals
301 and 302. A field-wiring change is required if a
supply-voltage connection is required to the relay
output(s) within the NGRM-ENC. Field wiring is
required if connection to SE-330 relay outputs K2, K3,
and K4 is required. See Figs. 2 and 3 and the
appropriate product manual.
NOTE: The SE-330 surface-mount options use relays K2
and K3 for panel-mounted ground-fault and resistor-fault
indication respectively.
3.6 NETWORK-COMMUNICATIONS CONNECTIONS
For SE-330 models equipped with a communications
option, connect directly to the SE-330 network
interface, referring to the appropriate product manual.
3.7 DIELECTRIC-STRENGTH TESTING
Remove the connections at the SE-325 and SE-330
L1 and L2 terminals, and remove the connection to the
EL3100 terminal 19 (if installed), before performing
dielectric-strength testing.
Ensure that all connections are reconnected and
securely fastened after any tests. See Figs. 2 and 3.
NOTES:
(1)
Not included with the NGRM-ENC.
Page 3
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
NGRM-ENC
PHASE
A
PHASE
B
PHASE
C
LITTELFUSE STARTCO
NEUTRAL-GROUNDING-RESISTOR
MONITOR
SE-330
LEAKAGE
CURRENT
RESISTOR
FAULT
GROUND
FAULT
DIAGNOSTIC
TRIP
TRIP
CALIBRATED
RELAY K1
8
6
10
20
40
60
80
POWER
453.8
(17.87)
100
2
MEM
GF TRIP LEVEL
(% CT RATING)
0.5 0.7 1.0
0.4
0.3
0.2
0.1
2.0
3.0
5.0
10.0
170
130
100
200
340
800
1200
60
1700
20
2000
VN TRIP LEVEL
4
(S5
CAL
GF TRIP TIME (s)
20 K Ω
VN x 1
100 K Ω)
VN x 5
1.8 2.0 2.2
1.6
2.4
1.4
2.6
1.2
2.8
1.0
3.0
ON
OFF
PULSE PERIOD (s)
RESET
PULSE
ENABLE
264.0
406.2
(10.40)
(16.00)
SIDE
FRONT
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
436.6
(17.19)
2. PANEL-MOUNTED SE-330 MODEL SHOWN.
330.5
(13.00)
REAR
(MOUNTING DETAIL)
FIGURE 1. NGRM-ENC Outline and Mounting Details.
Page 4
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
OPTIONAL
INCOMING 120V
BY CUSTOMER
L
N
OPTIONAL INCOMING
480V/600V
BY CUSTOMER
ØA
ØB
ØC
*F2
0.5 A
*F3
0.5 A
*F4
0.5 A
1
3
T1H3
T1H2
T1H1
5
600V
H1
480V
H2
19
H3
AH
BH
DB
CH
DA
G
*T1
600/480 120/240 150 VA
X1
120V
X2
DN
10
401
11
402
12
403
15
404
*PHASE C
DS4
GRN
DS3
*PHASE B
GRN
DS2
*PHASE A
GRN
*EL3100
X4
T1X2
T1X1
X3
120V
DC
F1
0.8 A
N
GND
X1
L
X2
GRN
LT1
CONTROL POWER
301 302
CT2
CT1
WHT
CT2
BLK
CT1
SHLD
CT1 CT2
SE-325 FACTORY SETTINGS
GF TRIP TIME: 0.1 SEC
GF TRIP LEVEL: 0.5 A
MODE: UV
RESISTOR: 20K
RESISTOR TRIP LEVEL: 20
ADJUST AS REQUIRED.
A
B
L1
L2
K1
SE-325
R
G
R
RI
304
+
305
GI
303
306
SW
LT3
RESISTOR FAULT
R
X1
NOTES:
1. RELAY CONTACTS SHOWN WITH
SE-325 DE-ENERGIZED.
2. DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
FIGURE 2. SE-325 Typical Wiring Diagram.
PB1
RESET
X2
RED
LT2
GROUND FAULT
X1
RED
X2
Page 5
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
OPTIONAL
INCOMING 120V
BY CUSTOMER
L
N
OPTIONAL INCOMING
480V/600V
BY CUSTOMER
ØA
ØB
*F2
0.5 A
ØC
*F3
0.5 A
*F4
0.5 A
1
3
T1H2
T1H3
T1H1
H1
600V
480V
H2
5
H3
AH
DC
BH
DB
120V
120V
X2
403
*PHASE B
GRN
DS2
404
*PHASE A
GRN
N
X1
5
WHT
S
BLK
C
8
9
S
6
BLK
RED
SHLD
X2
GRN
RED
C
DS3
LT1
NOTE 1
CONTROL POWER
WHT
S
DS4
*EL3100
L
5
402
GRN
X4
F1
0.8 A
GND
15
*PHASE C
401
T1X2
T1X1
X3
12
DN
G
*T1
600/480 120/240 150 VA
X1
11
DA
CH
19
10
5
C
1
10
11
R
R
7
G
1
301
SE-330 FACTORY SETTINGS
GF TRIP TIME: 0.5 SEC
GF TRIP LEVEL: 20%
VN TRIP LEVEL: 60 V
ADJUST AS REQUIRED.
K2 MODE: NON-FAIL-SAFE
K3 MODE: NON-FAIL-SAFE
L1
L2/N
K1
22
K2
26
GF
NOTE 1
X2
RED
LT3
RESISTOR FAULT
304
X1
NOTE 1
X2
RED
13
18
PB1
RESET
+
305
15
REMOTE
RESET
306
16
RESET
PULSE
ENABLE
307
17
PULSE ENABLE
-
3
5
0V
19
20
308
21
309
+
DS1
IDC
EARTH-LEAKAGE
CURRENT (OPTIONAL)
NOTES:
4
SPG
1. SURFACE-MOUNT MODELS ONLY.
SPGA
2. RELAY CONTACTS SHOWN WITH
SE-330 DE-ENERGIZED.
SE-330
FIGURE 3. SE-330 Typical Wiring Diagram.
X1
+24V
NC
(OPTIONAL)
303
LT2
GROUND FAULT
28
K4
14
NOTE 1
24
27
RF
12
302
25
K3
29
2
23
3. DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
Page 6
Rev. 0-B-030515
F2, F3, F4
SHLD
BLK
WHT
GND BLOCK
TB1
301
302
L
N
F1
CT1
CT2
A
B
L1
L2
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
FUSE
TB1
TB1
CTM
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
PB1
RESET
305
306
SE-325(SW)
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
DOOR WIRING
(REAR VIEW)
GND BLOCK
OPTIONAL INCOMING
120 VAC BY CUSTOMER
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
*T1X2
*T1X1
ØA
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
SE-325
TRIP
NGR
NOTES:
1.T1 IS SET FOR 600V INCOMING. FOR 480V ENCLOSURE
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
2.DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
ØB
ØC
*F2 - 0.5 A
*F3 - 0.5 A
9
8
7
6
5
4
3
2
1
400
RES TRIP
LEVEL (VAC)
POWER
SE-325
SW GI
*F2
RI
NGR MONITOR
R
G
9
8
C
B
208/240
BL
CL
7
A
AL
6
5
4
3
2
200
20
G F MODE RES
4.0 A SH
2.0 A
0.5 A UV 20K
*F4
*F3
DISPLAY
15 14 13 12 11 10
RE SI STO R
FAULT
16
2.0
GF TRIP
TIME (s)
CH
RESET
1.0
0.1
1
SE-325(RI)
RED
SE-325(+)
GROUND
FAULT
480/600
BH
*NOTE 1
F3
AH
X2 304
17
F3
SE-325(CT1)
SE-325(G)
*EL3100(19)
*T1X2
SE-325(GND)
TB1
X1
DN DR DG DA DB DC
F2
18
T1H2
T1H3
SE-325(GI)
L2
SH
T1H1
GND BLOCK
X2 303
LT3
RESISTOR
FAULT
L1
G
LT2
GROUND
FAULT
RED
B
19
*T1
150 VA
T1X1
TB1
GRN
X1
A
FAULT
R
G
GND
5W
GI
+
RI
F1
L
CT1 CT2
EL3100 SERIES
X1
X2
GND BLOCK
PB1
GND BLOCK
TB1 T1X2
LT1
CONTROL
POWER
TB1 N
F1
306
LT2 303
305
LT3 304
TB1 R
GND BLOCK
*DS4
*DS2
*DS3
401
403
402
*EL3100(10)
*EL3100(11)
*EL3100(12)
*EL3100(15)
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
SE-325
404
LT1(X1)
SE-325(L1)
SE-325(L2)
LT1(X2)
*EL3100(1)
*T1H1
*T1H3 *EL3100(3)
*F4 - 0.5 A
GND GRN
GND
GND
301
302
WHT
CT2
CT1 BLK
SHLD
R
*EL3100(5)
L(F1)
0.8 A
600V
GND BLOCK
CTM
SE-325(A)
SE-325(B)
SE-325(CT2)
SE-325(CT1)
ØA(F2)
0.5 A
600V
SE-325(R)
TB1
ØB(F3)
0.5 A
600V
ØC(F4)
0.5 A
600V
GND
GND
GND
301
302
CT2
CT1
SHLD
R
T1
150 VA
INTERIOR
NGRM-ENC
CONTROL
POWER
PHASE
A
GROUND
FAULT
RESISTOR
FAULT
RESET
SIDE
FRONT
NOTE:
1. SHOWN WITH ALL OPTIONS AVAILABLE.
FIGURE 4. SE-325 Model (NGRM-ENC-100-01) Interior/Exterior Details.
PHASE
B
PHASE
C
18
SH
RES TRIP
LEVEL (VAC)
POWER
SE-325
SW GI
RI
NGR MONITOR
R
G
L(F1)
0.8 A
600V
ØA(F2)
0.5 A
600V
ØB(F3)
0.5 A
600V
ØC(F4)
0.5 A
600V
GND
GND
GND
301
302
CT2
CT1
SHLD
R
T1
150 VA
FIGURE 5. SE-325 Model (NGRM-ENC-100-01) Interior Details.
8
9
208/240
BL
CL
7
B
A
AL
6
5
CH
4
3
480/600
BH
2
16
400
17
20
G F MODE RES
4.0 A SH
2.0 A
0.5 A UV 20K
G
2.0
GF TRIP
TIME (s)
19
0.1
1
200
AH
RE SI STO R
FAULT
1.0
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
RESET
L2
DISPLAY
L1
15 14 13 12 11 10
B
EL3100 SERIES
GROUND
FAULT
A
DN DR DG DA DB DC
CT1 CT2
FAULT
F1
C
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
Page 7
Rev. 0-B-030515
F2, F3, F4
WHT
GND BLOCK
TB1
301
302
L
N
SHLD
BLK
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
F1
CT1
CT2
A
B
L1
L2
FUSE
TB1
TB1
CTM
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
*EL3100(10)
GND BLOCK
TB1 T1X2
LT1
CONTROL
POWER
TB1 N
306
LT2 303
PB1
305
LT3 304
R
TB1
GND BLOCK
*DS4
5W
GI
+
RI
*EL3100(15)
401
402
*EL3100(11)
*EL3100(12)
403
*DS2
*DS3
404
X1
X2
F1
L
R
G
GND
SE-325
*T1
150 VA
T1X1
GND BLOCK
T1H1
T1H2
T1H3
TB1
F2
F3
*NOTE 1
F3
GRN
LT2
GROUND
FAULT
X2 303
X1
SE-325(CT1)
SE-325(G)
*EL3100(19)
*T1X2
SE-325(GND)
TB1
GND BLOCK
SE-325(GI)
RED
LT3
RESISTOR
FAULT
X1
X2 304
SE-325(RI)
RED
PB1
RESET
SE-325(+)
305
306
SE-325(SW)
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
DOOR WIRING
(REAR VIEW)
GND BLOCK
OPTIONAL INCOMING
120 VAC BY CUSTOMER
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
*T1X2
*T1X1
ØA
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
SE-325
TRIP
NGR
NOTES:
1.T1 IS SET FOR 600V INCOMING. FOR 480V ENCLOSURE
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
2.DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
ØB
ØC
*F2 - 0.5 A
*F3 - 0.5 A
9
8
7
6
5
4
3
2
1
FIGURE 6. SE-325 Model (NGRM-ENC-XX0-XX) Wiring Label.
*F3
*F2
LT1(X1)
SE-325(L1)
SE-325(L2)
LT1(X2)
*EL3100(1)
*T1H1
*T1H3 *EL3100(3)
*F4 - 0.5 A
GND GRN
GND
GND
301
302
WHT
CT2
CT1 BLK
SHLD
R
TB1
*F4
*EL3100(5)
GND BLOCK
CTM
SE-325(A)
SE-325(B)
SE-325(CT2)
SE-325(CT1)
SE-325(R)
Page 8
Rev. 0-B-030515
Page 9
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
LT1
CONTROL
POWER
*DS4
*EL3100(15)
X1
X2
TB1 N
L
401
GRN
TB1
LT2
GROUND
FAULT
*EL3100(10)
*EL3100(11)
*EL3100(12)
403
402
*DS2
*DS3
404
SE-330(20)
X2
N
*DS1
- 309
308 +
Idc
X1 303
RED
SE-330(24)
LT3
RESISTOR
FAULT
SE-330(21)
X2
X1 304
SE-330(27)
RED
PB1
RESET
*S1
PULSE
SE-330(17)
307
SE-330(15)
306
305
SE-330(16)
*EL3100(19)
*T1X2
TB1
SE-330(11)
SE-330(7)
SE-330(3)
OPTIONAL INCOMING
120 VAC BY CUSTOMER
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
GND BLOCK
LT1(X1)
SE-330(1)
*T1X2
*T1X1
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
NOTES:
SE-330
1.T1 IS SET FOR 600V INCOMING. FOR 480V
TRIP
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
NGR
2.DESIGNATORS WITH LEADING “*” ARE
ENCLOSURE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
16
17
18
19
9
8
7
6
5
4
3
2
1
8
6
*F4
*F3
*F2
SE-330(29)
L
L
SE-330(26)
L
SE-330(2)
N
LT1(X2)
N
F1 - 0.8 A
ØA *F2 - 0.5 A *T1H1 *EL3100(1)
*EL3100(3)
ØB
*F3 - 0.5 A *T1H3
ØC
*EL3100(5)
*F4 - 0.5 A
GND GRN
GND
GND BLOCK
GND
SE-330(22)
301
302 RED
SE-330(23)
5
SE-330(10)
WHT
S
SE-330(8)
BLK
C
SE-330(11)
CTM
SHLD
R
SE-330(6)
10
20
40
60
80
4
100
2
MEM
GF TRIP LEVEL
(% CT RATING)
0.5 0.7 1.0
0.4
0.3
0.2
0.1
2.0
3.0
5.0
10.0
POWER
170
130
100
200
340
800
1200
60
1700
20
2000
VN TRIP LEVEL
(S5
CAL
GF TRIP TIME (s)
20 K Ω
VN x 1
9
8
C
B
208/240
BL
CL
7
A
AL
6
5
CH
4
3
2
16
RELAY K1
*NOTE 1
F3
1
DISPLAY
15 14 13 12 11 10
DN DR DG DA DB DC
TRIP
CALIBRATED
17
F3
FAULT
DIAGNOSTIC
TRIP
TB1
F2
AH
T1H2
18
T1H1
SH
*T1
150 VA
T1X1
T1H3
GND BLOCK
SE-330
RESISTOR
FAULT
GROUND
FAULT
CTM
WHT
8
9 RED
10 BLK
11 SHLD
GRN GND BLOCK
GND BLOCK
TB2 T1X2
F1
NEUTRAL-GROUNDING-RESISTOR
MONITOR
TB1
480/600
BH
R
6
GND
GND BLOCK
7
LT2 303 24
25
L
TB1
26
LT3 304 27
L 28
TB1
29
G
F2, F3, F4
LITTELFUSE STARTCO
19
F1
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
TB1
SE-330
301
22
302
23
TB1
FUSE
L
1
2 N
3 GND GND BLOCK
4
5
EL3100 SERIES
12
13
14
305
15
PB1 306 16
*S1 307 17
18
19
*DS1(+) 308 20
309
*DS1(-)
21
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
DOOR WIRING (REAR VIEW)
100 K Ω)
VN x 5
1.8 2.0 2.2
1.6
2.4
1.4
2.6
1.2
2.8
1.0
3.0
PULSE PERIOD (s)
RESET
L(F1)
0.8 A
600V
ØA(F2)
0.5 A
600V
ØB(F3)
0.5 A
600V
TB1
ØC(F4)
0.5 A
600V
T1
150 VA
GND
GND
GND
301
302
5
S
C
SHLD
R
INTERIOR
NGRM-ENC
CONTROL
POWER
PHASE
A
GROUND
FAULT
PHASE
B
PHASE
C
LEAKAGE
CURRENT
RESISTOR
FAULT
RESET
ON
OFF
PULSE
ENABLE
USB
SIDE
FRONT
NOTE:
1. SHOWN WITH ALL OPTIONS AVAILABLE.
FIGURE 7. SE-330 Surface-Mount Model (NGRM-ENC-XX0-21) Interior/Exterior Details.
60
80
POWER
0.4
0.3
0.2
0.1
2.0
3.0
5.0
10.0
200
340
800
1200
60
1700
20
2000
VN TRIP LEVEL
4
100
2
MEM
GF TRIP LEVEL
(% CT RATING)
0.5 0.7 1.0
170
130
100
18
40
G
10
19
8
6
SH
(S5
CAL
GF TRIP TIME (s)
20 K Ω
VN x 1
100 K Ω)
VN x 5
1.8 2.0 2.2
1.6
2.4
1.4
2.6
1.2
2.8
1.0
3.0
PULSE PERIOD (s)
L(F1)
0.8 A
600V
RESET
ØA(F2)
0.5 A
600V
ØB(F3)
0.5 A
600V
ØC(F4)
0.5 A
600V
T1
150 VA
GND
GND
GND
301
302
5
S
C
SHLD
R
FIGURE 8. SE-330 Surface-Mount Model (NGRM-ENC-XX0-X1) Interior Details.
8
9
208/240
BL
CL
7
B
A
AL
6
5
CH
4
3
480/600
BH
2
RELAY K1
20
1
17
16
CALIBRATED
AH
TRIP
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
DIAGNOSTIC
TRIP
EL3100 SERIES
RESISTOR
FAULT
GROUND
FAULT
DISPLAY
15 14 13 12 11 10
SE-330
FAULT
NEUTRAL-GROUNDING-RESISTOR
MONITOR
DN DR DG DA DB DC
LITTELFUSE STARTCO
C
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
Page 10
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
LT1
CONTROL
POWER
*DS4
*EL3100(15)
SE-330(20)
X1
X2
TB1 N
L
401
GRN
TB1
LT2
GROUND
FAULT
*EL3100(10)
*EL3100(11)
*EL3100(12)
403
402
*DS2
*DS3
404
X2
N
*DS1
- 309
308 +
Idc
X1 303
RED
SE-330(24)
LT3
RESISTOR
FAULT
SE-330(21)
X2
X1 304
SE-330(27)
RED
PB1
RESET
*S1
PULSE
SE-330(17)
307
SE-330(15)
306
305
SE-330(16)
DOOR WIRING (REAR VIEW)
305
PB1 306
*S1 307
*DS1(+) 308
309
*DS1(-)
F1
F2, F3, F4
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
L
1
2 N
3 GND GND BLOCK
4
5
R
6
GND
GND BLOCK
7
LT2 303 24
25
L
TB1
26
LT3 304 27
L 28
TB1
29
*T1
150 VA
T1X1
T1H1
T1H2
T1H3
*EL3100(19)
*T1X2
TB1
SE-330(11)
SE-330(7)
SE-330(3)
GND BLOCK
OPTIONAL INCOMING
120 VAC BY CUSTOMER
TB1
CTM
WHT
8
9 RED
10 BLK
11 SHLD
GRN GND BLOCK
GND BLOCK
TB2 T1X2
F1
TB1
SE-330
301
22
302
23
TB1
FUSE
12
13
14
15
16
17
18
19
20
21
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
GND BLOCK
LT1(X1)
SE-330(1)
*T1X2
*T1X1
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
NOTES:
SE-330
1.T1 IS SET FOR 600V INCOMING. FOR 480V
TRIP
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
NGR
2.DESIGNATORS WITH LEADING “*” ARE
ENCLOSURE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
TB1
F2
F3
*NOTE 1
F3
9
8
7
6
5
4
3
2
1
*F4
*F3
*F2
SE-330(29)
SE-330(26)
SE-330(2)
LT1(X2)
ØA *F2 - 0.5 A *T1H1 *EL3100(1)
*EL3100(3)
ØB
*F3 - 0.5 A *T1H3
ØC
*EL3100(5)
*F4 - 0.5 A
GND GRN
GND
GND BLOCK
GND
SE-330(22)
301
302 RED
SE-330(23)
5
SE-330(10)
WHT
S
SE-330(8)
BLK
C
SE-330(11)
CTM
SHLD
R
SE-330(6)
TB1
FIGURE 9. SE-330 Surface-Mount Model (NGRM-ENC-XX0-XX) Wiring Label.
Page 11
Rev. 0-B-030515
Page 12
Rev. 0-B-030515
SE-330(21)
SE-330(16)
GND BLOCK
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
SE-330(1)
OPTIONAL INCOMING
120 VAC BY CUSTOMER
*T1X2
*T1X1
ØA
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
NOTES:
1.T1 IS SET FOR 600V INCOMING. FOR 480V
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
2.DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
SE-330
TRIP
NGR
ENCLOSURE
ØB
ØC
*F2 - 0.5 A
*F3 - 0.5 A
9
8
C
208/240
BL
CL
7
AL
6
5
*F4
*F3
*F2
L(F1)
0.8 A
600V
SE-330(2)
*EL3100(1)
*T1H1
*T1H3 *EL3100(3)
*F4 - 0.5 A
GND GRN
GND
GND
301
302 RED
5
WHT
S
BLK
C
SHLD
R
CH
B
G
19
9
8
7
6
5
4
3
2
1
4
A
18
SH
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
DOOR WIRING
(REAR VIEW)
3
DISPLAY
17
306
*EL3100(19)
*T1X2
TB1
SE-330(11)
SE-330(7)
SE-330(3)
*DS1
- 309
308 +
Idc
*S1
PULSE
307
2
*NOTE 1
GND BLOCK
1
F3
F3
*DS4
*DS3
*DS2
F2
401
402
403
T1H2
T1H3
*EL3100(10)
*EL3100(11)
*EL3100(12)
SE-330(20)
SE-330(17)
T1H1
*T1
150 VA
T1X1
*EL3100(15)
AH
F1
15 14 13 12 11 10
WHT
8
RED 9
BLK 10
SHLD 11
GND BLOCK GRN
GND BLOCK
TB2 T1X2
404
TB1
24
25
26
27
28
29
CTM
TB1
DN DR DG DA DB DC
301
22
302
23
R
6
GND BLOCK GND 7
TB1
12
13
14
15
306
16
17 307 *S1
18
19
308 *DS1(+)
20
309
*DS1(-)
21
FAULT
SE-330
16
F2, F3, F4
480/600
BH
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
F1
EL3100 SERIES
L
1
N 2
GND BLOCK GND 3
4
5
TB1
FUSE
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
ØA(F2)
0.5 A
600V
*EL3100(5)
GND BLOCK
CTM
SE-330(22)
SE-330(23)
SE-330(10)
SE-330(8)
SE-330(11)
ØB(F3)
0.5 A
600V
SE-330(6)
ØC(F4)
0.5 A
600V
TB1
GND
GND
GND
301
302
5
S
C
SHLD
R
T1
150 VA
INTERIOR
NGRM-ENC
PHASE
A
PHASE
B
PHASE
C
LITTELFUSE STARTCO
NEUTRAL-GROUNDING-RESISTOR
MONITOR
SE-330
LEAKAGE
CURRENT
RESISTOR
FAULT
GROUND
FAULT
DIAGNOSTIC
TRIP
TRIP
CALIBRATED
RELAY K1
8
6
10
20
40
60
80
4
100
2
MEM
GF TRIP LEVEL
(% CT RATING)
0.5 0.7 1.0
0.4
0.3
0.2
0.1
2.0
3.0
5.0
10.0
POWER
170
130
100
200
340
800
1200
60
1700
20
2000
VN TRIP LEVEL
(S5
CAL
GF TRIP TIME (s)
20 K Ω
VN x 1
100 K Ω)
VN x 5
1.8 2.0 2.2
1.6
2.4
1.4
2.6
1.2
2.8
1.0
3.0
PULSE PERIOD (s)
ON
OFF
RESET
PULSE
ENABLE
SIDE
FRONT
NOTE:
1. SHOWN WITH ALL OPTIONS AVAILABLE.
FIGURE 10. SE-330 Panel-Mount Model (NGRM-ENC-XX1-21) Interior/Exterior Details.
17
306
SE-330(21)
SE-330(16)
18
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
DOOR WIRING
(REAR VIEW)
GND BLOCK
LT1(X1)
SE-330(1)
OPTIONAL INCOMING
120 VAC BY CUSTOMER
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
*T1X2
*T1X1
ØA
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
NOTES:
1.T1 IS SET FOR 600V INCOMING. FOR 480V
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
2.DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
G
19
*EL3100(19)
*T1X2
TB1
SE-330(11)
SE-330(7)
SE-330(3)
*DS1
- 309
308 +
Idc
*S1
PULSE
307
SH
*EL3100(12)
*EL3100(11)
SE-330(20)
GND BLOCK
SE-330
TRIP
NGR
ENCLOSURE
ØB
ØC
*F2 - 0.5 A
*F3 - 0.5 A
*F4
*F3
*F2
SE-330(2)
*EL3100(1)
*T1H1
*T1H3 *EL3100(3)
*F4 - 0.5 A
GND GRN
GND
GND
301
302 RED
5
WHT
S
BLK
C
SHLD
R
TB1
T1
150 VA
9
8
7
6
5
4
3
2
1
*EL3100(5)
GND BLOCK
CTM
SE-330(22)
SE-330(23)
SE-330(10)
SE-330(8)
SE-330(11)
SE-330(6)
L(F1)
0.8 A
600V
ØA(F2)
0.5 A
600V
ØB(F3)
0.5 A
600V
ØC(F4)
0.5 A
600V
GND
GND
GND
301
302
5
S
C
SHLD
R
FIGURE 11. SE-330 Panel-Mount Model (NGRM-ENC-XX1-X1) Interior Details.
9
8
C
B
208/240
BL
CL
7
AL
6
5
CH
4
3
*NOTE 1
480/600
BH
*DS3
F3
*EL3100(15)
*DS2
*DS4
F2
F3
403
402
*EL3100(10)
401
T1H2
T1H3
404
SE-330(17)
T1H1
*T1
150 VA
T1X1
2
F1
1
GND BLOCK
TB2 T1X2
AH
WHT
8
RED 9
BLK 10
SHLD 11
GND BLOCK GRN
TB1
TB1
24
25
26
27
28
29
CTM
A
301
22
302
23
R
6
GND BLOCK GND 7
TB1
EL3100 SERIES
SE-330
DISPLAY
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
FAULT
F2, F3, F4
15 14 13 12 11 10
F1
16
FUSE
12
13
14
15
306
16
17 307 *S1
18
19
308 *DS1(+)
20
309
*DS1(-)
21
DN DR DG DA DB DC
L
1
N 2
GND BLOCK GND 3
4
5
TB1
GROUND-FAULT & PHASE-VOLTAGE INDICATOR
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
Page 13
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
L
1
N 2
GND BLOCK GND 3
4
5
TB1
FUSE
RATING
0.8 A, 600 VAC
LITTELFUSE KLDR.800TXP
0.5 A, 600 VAC
LITTELFUSE KLK.500
F1
F2, F3, F4
SE-330
WHT
8
RED 9
BLK 10
SHLD 11
GND BLOCK GRN
GND BLOCK
TB2 T1X2
F1
TB1
F2
F3
*NOTE 1
F3
*EL3100(15)
*DS2
*DS3
GND BLOCK
*DS1
- 309
308 +
Idc
SE-330(21)
*S1
PULSE
307
306
*EL3100(19)
*T1X2
TB1
SE-330(11)
SE-330(7)
SE-330(3)
SE-330(20)
*EL3100(12)
*EL3100(11)
403
402
*DS4
401
*EL3100(10)
T1H2
T1H3
404
SE-330(17)
T1H1
*T1
150 VA
T1X1
308 *DS1(+)
309
*DS1(-)
24
25
26
27
28
29
CTM
TB1
306
307 *S1
301
22
302
23
R
6
GND
GND BLOCK
7
TB1
12
13
14
15
16
17
18
19
20
21
SE-330(16)
*DS4 401 10
*DS3 402 11
403 12
*DS2
13
404 14 *EL3100
*DS2
15
DOOR WIRING
(REAR VIEW)
GND BLOCK
LT1(X1)
SE-330(1)
OPTIONAL INCOMING
120 VAC BY CUSTOMER
16
17
18
19
L
L
L
N
N
F1 - 0.8 A
*T1X2
*T1X1
ØA
OPTIONAL INCOMING
480 / 600 V BY CUSTOMER
NOTES:
1.T1 IS SET FOR 600V INCOMING. FOR 480V
INCOMING, MOVE F3-TO-T1 CONNECTION
FROM T1H3 TO T1H2.
2.DESIGNATORS WITH LEADING “*” ARE
OPTIONAL.
3.MINIMUM SUPPLY CONDUCTOR RATING
90ºC.
4.DASHED LINES INDICATE FIELD WIRING.
SE-330
TRIP
NGR
ENCLOSURE
ØB
ØC
*F2 - 0.5 A
*F3 - 0.5 A
9
8
7
6
5
4
3
2
1
*F4
*F3
*F2
SE-330(2)
*EL3100(1)
*T1H1
*T1H3 *EL3100(3)
*F4 - 0.5 A
GND GRN
GND
GND
301
302 RED
5
WHT
S
BLK
C
SHLD
R
*EL3100(5)
GND BLOCK
CTM
SE-330(22)
SE-330(23)
SE-330(10)
SE-330(8)
SE-330(11)
SE-330(6)
TB1
FIGURE 12. SE-330 Panel-Mount Model (NGRM-ENC-XX1-XX) Wiring Label.
Page 14
Rev. 0-B-030515
Page 15
Rev. 0-B-030515
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
4. TECHNICAL SPECIFICATIONS
Supply:
NGRM-ENC-000-00 ............12 VA, 120 Vac
(+10, -45%), 60 Hz
NGRM-ENC-100-00
EL3100 ...............................2 mA, 480/600 Vac,
60 Hz,
3-phase, 3-wire (no
neutral)
Monitor ...............................12 VA, 120 Vac
(+10, -45%), 60 Hz
NGRM-ENC-000-01,
NGRM-ENC-100-01 ............14 VA, 480/600 Vac,
60 Hz,
3-phase, 3-wire (no
neutral)
NGRM-ENC-2XX-X0,
NGRM-ENC-4XX-X0,
NGRM-ENC-6XX-X0,
NGRM-ENC-8XX-X0..........32 VA, 120 Vac
(+10, -45%), 60 Hz
NGRM-ENC-3XX-X0,
NGRM-ENC-5XX-X0,
NGRM-ENC-7XX-X0,
NGRM-ENC-9XX-X0
EL3100 ...............................2 mA, 480/600 Vac,
60 Hz,
3-phase, 3-wire (no
neutral)
Monitor ...............................32 VA, 120 Vac
(+10, -45%), 60 Hz
NGRM-ENC-2XX-X1,
NGRM-ENC-3XX-X1,
NGRM-ENC-4XX-X1,
NGRM-ENC-5XX-X1,
NGRM-ENC-6XX-X1,
NGRM-ENC-7XX-X1,
NGRM-ENC-8XX-X1,
NGRM-ENC-9XX-X1..........34 VA, 480/600 Vac,
60 Hz
3-phase, 3-wire (no
neutral)
Wiring Requirements:
Terminals Blocks:
Conductor Size................. 20 to 10 AWG
(0.52 to 5.26 mm2)
Fuseholders:
Conductor Size................. 14 to 6 AWG
(2.08 to 13.29 mm2)
Fuse Requirements:
F1:
Fuse Rating ...................... 0.8 A, 600 Vac,
Class CC
Fuse Part Number ............ Littelfuse KLDR.800T or
KLDR.800TXP (RoHS)
F2 to F4 (see order options):
Fuse Rating ...................... 0.5 A, 600 Vac,
Fuse Part Number ............ Littelfuse KLK.500
Dimensions:
Height ................................. 454 mm (17.9”)
Width .................................. 406 mm (16.0”)
Maximum Depth (with
SE-IP65CVR-G installed) .. 264 mm (10.4”)
Clearance required to open
SE-IP65CVR-G .................. 112 mm (4.4”)
Shipping Dimensions:
NGRM-ENC-XXX-XX:
Height .............................. 516 mm (20.3”)
Width ............................... 465 mm (18.3”)
Depth ............................... 309 mm (12.2”)
Shipping Weight:
NGRM-ENC-XXX-XX ........ 13.6 kg (30 lb) maximum
Enclosure ................................. Polyester, Lockable
Ratings:
SE-325 Order Options ..... Type 4X
SE-330 Surface-Mount
Order Options .................. Type 4X
SE-330 Panel-Mount
Order Options .................. IP65
Environment:
Operating Temperature ......... -40 to 60°C (-40 to
140°F)
Storage Temperature ............. -55 to 80°C (-67 to
176°F)
Humidity................................ 85% Non-Condensing
Certification ................................. CSA, Canada and USA
R
C
LR 53428
US
To: CSA C22.2 No. 144 Ground Fault Circuit
Interrupters
CSA C22.2 No. 94 Special Purpose Enclosures
UL 1053 Ground Fault Sensing and Relaying
Equipment
UL 50 Enclosures for Electrical Equipment
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
Page 16
Rev. 0-B-030515
5. ORDERING INFORMATION
6. WARRANTY
NGRM-ENC-
The NGRM-ENC Enclosed Neutral-GroundingResistor Monitor is warranted to be free from defects in
material and workmanship for a period of one year from
the date of purchase.
Littelfuse Startco will (at Littelfuse Startco’s option)
repair, replace, or refund the original purchase price of an
NGRM-ENC that is determined by Littelfuse Startco to
be defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products
repaired or modified by non-Littelfuse Startco personnel.
-
Control-Power Transformer
Option
0 No CPT
1 480/600-V CPT(1)
Ammeter & Pulse Control
Option
0 No ammeter
1 Earth-leakage panel meter(2)
2 Earth-leakage panel meter &
pulse-enable switch(3)
NGR Monitor Mounting Option
0 Surface-mounted NGR
monitor(4)
1 Panel-mounted NGR monitor(5)
Network Communications
Option
0 No network communications
1 DeviceNet(2)
3 Ethernet, dual RJ45(2)
4 Ethernet, 1 RJ45 & 1 fiber(2)
5 Ethernet, dual fiber(2)
6 IEC 61850, dual RJ45(2)
7 IEC 61850, 1 RJ45 & 1 fiber(2)
8 IEC 61850, dual fiber(2)
Protection Relay Option
0 SE-325
1 SE-325 & voltage indication(1)
2 SE-330 (N.O. K4)
3 SE-330 (N.O. K4) & voltage
indication(1)
4 SE-330 (N.C. K4)
5 SE-330 (N.C. K4) & voltage
indication(1)
6 SE-330HV (N.O. K4)
7 SE-330HV (N.O. K4) & voltage
indication(1)
8 SE-330HV (N.C. K4)
9 SE-330HV (N.C. K4) & voltage
indication(1)
NOTES:
Includes fuses.
(2)
SE-330 models only.
(3)
SE-330 models only, excluding SE-330HV models.
(4)
Includes panel-mounted indication & reset, and USB
connector for SE-330 models.
(5)
SE-330 models only; includes IP65 hinged transparent
cover.
(1)
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
MANUAL
RELEASE DATE
APPENDIX A
NGRM-ENC REVISION HISTORY
MANUAL
PRODUCT REVISION
REVISION
(REVISION NUMBER ON PRODUCT LABEL)
March 5, 2015
0-B-030515
April 25, 2014
0-A-042514
MANUAL REVISION HISTORY
REVISION 0-B-030515
SECTION 1
Added enclosure ratings.
SECTION 3
Updated Figs. 2, 3, 7, 11, and 12.
SECTION 4
Added enclosure ratings and CSA certification.
APPENDIX A
Updated revision history.
REVISION 0-A-042514
Initial release.
PRODUCT REVISION HISTORY
REVISION 00
Initial release.
Page 17
Rev. 0-B-030515
00
NGRM-ENC Enclosed Neutral-Grounding-Resistor Monitor
This page intentionally left blank.
Page 18
Rev. 0-B-030515