Touch DIM PD LI 2P WOS
Motion sensor w/o sensor head
General
Safety information
• This product may only be installed by qualified personnel who have been appropriately
trained and who have the relevant authority. The installation personnel must be familiar with
the operating instructions. Power must be switched off before any work is undertaken on
the unit.
• The relevant safety and accident prevention regulations must be observed.
•
This product is designed exclusively for control of electronic ballasts from OSRAM type
QUICKTRONIC INTELLIGENT DALI (QTi DALI...DIM) or HALOTRONIC INTELLIGENT DALI
(HTi DALI..DIM). Other usage may destroy this and other connected products.
• No other control components may be connected.
•
Max. number of ballasts and max. wire length has to be observed.
•
Connection to other voltage levels will destroy the device.
•
The product has to be supplied by an AC voltage (no DC allowed). This has to be respected
especially when a UPS system is used.
• ATTENTION!: The motion sensor element is connected to mains, a sufficient isolation
and protection against contact has to be guaranteed. The sensor cable and the PIR sensor
socket apply to low voltage installation regulations of 230V AC. If isolation parts or the
plastic cab of the motion sensor element is damaged, the device has to be put out of
operation.
OSRAM GmbH
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg, Germany
www.osram.com
www.osram.de
Tel. : (+49) 1803 / 677 - 200 (charges apply)
Fax.: (+49) 1803 / 677 - 202
Page 1
OSRAM - operating instructions: TOUCH DIM PD LI 2P WOS
Wiring diagram
L
N
PE
~
~
DA
Push button
(manual
control)
1
ECG QTi DALI
DA
L N S
~
~
DA
~
~
DA
3
4
Lamp
1
ECG QTi DALI
DA
TOUCH DIM
Sensor
2
2
3
4
Lamp
1
ECG QTi DALI
DA
2
3
4
max. 4
QTi ECG
or HTi
transform
ers
Lamp
signal wire length max. 10m
Push button and sensor have to be
connected to the same mains phase!
~
~
DA
DA
1
ECG QTi DALI
2
3
4
Lamp
Mounting hints
The sensor is connected to a 3 wire cable which is admitted for mains voltage. Parallel connection of
several sensors is not allowed. The sensor is typically installed in luminaires, ceiling installation is
possible by use of a flush device box and an adequate cover.
Following sensor heads are approved to be used with the Touch DIM PD LI 2P WOS sensor:
(-> sensor head not included in delivery)
PANASONIC NaPiOn sensors (passiv infrared)
Digital version
- Standard type
(5m range)
Standard
Economy
- Type for small movements
Standard
Economy
- Spot type
Standard
Economy
- 10m type
Standard
Economy
anthracite
white
anthrazit
white
AMN11111
AMN11112
AMN31111
AMN31112
anthracite
white
anthracite
white
AMN12111
AMN12112
AMN32111
AMN32112
anthracite
white
anthracite
white
AMN13111
AMN13112
AMN33111
AMN33112
anthracite
white
anthracite
white
AMN14111
AMN14112
AMN34111
AMN34112
When adding a sensor head to the sensor, please note the following:
• The entire workplace must lie within the monitoring cone of the sensor.
• The sensor must not be exposed to drafts (e.g. near air vents). A draft could be misinterpreted as
the presence of a person in the room.
Page 2
OSRAM - operating instructions: TOUCH DIM PD LI 2P WOS
Technical data
Designation:
Operating voltage:
Connections :
Interface :
overall length of signal connection:
Power consumption :
Operating temperature:
CE requirement:
Protection class:
Protection type:
Touch DIM PD LI 2P WOS
Motion sensor w/o sensor head
220 – 240V / 50-60Hz (no DC operation)
L, N, S (signal)
OSRAM specific, max. 4 QTi DALI ECG or. 4 HTi transformers
connectable
10m
< 0.5 W
0C°...+ 50C°
EMC according to EN 61547
II
IP 20
OSRAM GmbH
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg, Germany
www.osram.com
www.osram.de
Tel. : (+49) 1803 / 677 - 200 (charges apply)
Fax.: (+49) 1803 / 677 - 202
ZNN2587707-000-00_B
Page 3
OSRAM - operating instructions: TOUCH DIM PD LI 2P WOS