pdf

Description
Function and application
The TOUCH DIM LS/PD LI sensor regulates the brightness
at the workplace and in office areas to increase the working
comfort and to save energy.
TOUCH DIM LS/PD LI
The sensor can be installed in luminaires (e.g. floor standing
luminaires) or in false ceilings.
Function
The sensor measures the brightness in the area to be regulated
and keeps this to an adjustable set value by introducing artificial
light according to the amount of daylight available.
A B
The sensor also detects the movements of people.
C
As daylight increases the artificial light is reduced . The sensor
no longer detects any motions, it switches the luminaires off.
Construction
The sensor is made up of the following components:
• Light sensor (A)
• Motion sensor (B)
• Housing (C)
• Connections (D) for signal line, zero line and phase
D
Light and motion sensor
Fitting instructions
Installation
Safety instructions
The sensor must only be installed and put into operation by
a qualified electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the sensor when it is deenergized.
• Disconnect the sensor or luminaire from the
power supply if the housing or plastic lens is
damaged.
CAUTION!
Destruction of the sensor and other devices
through incorrect mounting!
• Only use electronic OSRAM ballast coils of the
type QUICKTRONIC INTELLIGENT DALI (QTi
DALI…DIM), HALOTRONIC INTELLIGENT
DALI (HTi DALI…DIM) or OPTOTRONIC
INTELLIGENT DALI (OT…DIM).
• Do not operate any other other control units on
the control line.
• Do not exceed the maximum number of
ballast coils and maximum overall cable ­length
between the operating button, sensor and
ballast coil.
• Do not connect control line with external
voltage.
• Only supply sensor with an AC operating voltage, especially in networks with UPS systems.
L
N
PE
Connecting the sensor
F
~
~
E
DA
L N S
1
EVG QTi DALI
2
3
DA
4
~
~
1
DA
DA
EVG QTi DALI
2
E Operating pushbutton: Same phase as sensor.
F Electronic ballast coil (EVG): Connect max. 4 ballast coils.
G Signal line: Max. 10 m.
H Sensor: Cable connection via 3-wires permitted for mains
voltage. Do not switch the sensors in parallel.
3
4
H
Touch DIM
Sensor
G
Continued on the back page!
Fitting (cont.)
Selecting the installation location
I Surveillance cone: entire workplace; not on window surfaces
K Avoid direct light irradiation
L Avoid drafts (e.g. from ventilators or fans)
M Place centrally.
Optimum installation location
Possible installation location
80° – 100°
80° – 100°
I
K
L
M
Appendix
Technical data
Operating voltage
220-240 V / 50-60 Hz (no DC
operation)
Connections
L, N, S (signal)
Interface
Osram-specific, maximum
4 QTi DALI coil ballast
or 4 HTi transformers or
4 OTi LED dimmers can be
connected
Maximum overall length of
the signal line
10 m
Power consumption
approx. 0.5 W
Operating temperature
0 °C ... +50 °C
Adjustable light value
approx. 0-300 lx measured
on the sensor (corresponds
to approx. 10-1200 lx on the
work surface)
Motion detection area
conical, approx. 80° ... 100°
aperture angle
Pollution severity
2 (dry, not conductive to
IEC 664)
Dimensions
63 x 29 x 21 mm
(L x W x H)
Protection class
II
Protection type
IP 20
VII 2008
TouchDIM-LSPD-LI_ma0807en_we1.02.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
The EMC requirements to EN 61547 are fulfilled.
www.osram.com
www.osram.de
40083210230250
4008321023025
Conformity with the relevant EU directives is
confirmed by the CE symbol.