Tenderspecification RadiPac 630-900 EN~1

Text for invitation to tender for
EC centrifugal fan modules – RadiPac
EC centrifugal fans – RadiPac
Sizes 630 to 900
Direct-drive single inlet centrifugal fans with backwards-curved high-performance centrifugal impellers with
radial diffusers, mounted on a GreenTech EC external rotor motor with integrated control electronics.
Impeller made of aluminum, with 7 backwards-curved, continuously welded blades; flow-optimized inlet ring made
of galvanized sheet steel with pressure test nipple.
Motor impeller statically and dynamically balanced on two planes to balancing grade G 6.3 (motor size 200 to
balancing grade G 4.0) in accordance with DIN ISO 1940. GreenTech EC external rotor motor surpasses efficiency
class IE4, magnets with no rare earths, maintenance-free ball bearings with long-term lubrication, theoretical nominal
service life of at least 40,000 hours of operation. Soft start, integrated current limitation, extended voltage input
3~380-480 V, 50/60 Hz. Fan can be used with all standard power supply networks with unaltered air performance.
Integrated electronics, low-noise commutation logic; 100 % open-loop speed control; all fans have an
RS485/MODBUS RTU interface, and do not need to be installed with shielded cables.
Terminal box made of aluminum with easily accessible connection area with spring-loaded terminals, environmentresistant cable glands.
Any work required for isolation from structure-borne noise to be performed by the customer.
Fan satisfies the applicable EMC guidelines and requirements with regard to circuit feedback (for specific information,
see the respective data sheet).
Documentation and marking conform to the applicable EU Directives.
Reliable performance data, air performance measurements on intake-side chamber test rig according to ISO 5801
and DIN 24163, noise measurements in anechoic rooms according to DIN EN ISO 3745.
Integrated protective devices:
-
Alarm relay with zero-potential change-over contacts (250 V AC/2 A, cos φ = 1)
Locked-rotor protection
Phase failure detection
Soft start of motors
Mains under-voltage detection
Thermal overload protection for electronics and motor
Short circuit protection
Optional:
-
Other and specific requirements on request
Subject to change / As at 2016/03/15
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 7938 81-0 ·Fax: +49 7938 81-110 ·www.ebmpapst.com ·[email protected]
Text for invitation to tender for
EC centrifugal fan modules – RadiPac
Technical data:
Fan types
Air flow
Stat. pressure increase
Stat. overall efficiency
Operating speed
Motor type
Type of control
Motor efficiency class
Total power consumption
Specific fan power
Nominal voltage range
Mains frequency
Nominal current
Safety class
Sound power level
Sound pressure level (at 1 m)
Perm. ambient temperature
Fan weight
qV
pfs
ηes
n
Ped
SFP
UN
f
IN
LW A(A, in)
LpA(A, in)
T
m
K3G ________ - ________ - _____
= ___________________________
= ___________________________
= ___________________________
= ___________________________
= EC motor
= 0-100% speed control
= IE4
= ___________________________
= ___________________________
= ___________________________
= 50 / 60
= ___________________________
= IP54
= _______ / LWA(A, out) = _______
= _______ / LpA(A, out) = _______
= ____________ to ____________
= ___________________________
m3/h, cfm
Pa, in wg
%
rpm
kW
kW/(m³/s)
V
Hz
A
dB(A)
dB(A)
°C
kg