EC centrifugal fans – RadiPac version 2014-06 RadiPac: Now even more efficient The line of radial plug fans with GreenTech EC motor technology already All RadiPacs listed in the catalogue exceed the tougher new minimum established in the market has been expanded further. Our new product efficiency requirements of the ErP Directive for Fans, effective as of 2015. line: RadiPac. The motor efficiency of the GreenTech EC motors is significantly above those specified in efficiency class IE4. And this is achieved without even RadiPac is to denote medium pressure radial fans and is meant to be an having to resort to any of the rare earth magnets, the procurement of independent line positioned to complement the low pressure line RadiCal. which we are critical of. The “Pac” in RadiPac is short for “packaged”, as all required functions are packed into one fan and are on board. The welded impellers with their 7 backward curved blades are deliberate- The RadiPac line is available in drive capacities of up to 12 kW and sizes and maximises durability with high circumferential velocity. The position of 250mm to 1250mm in outer diameter. As a standard, all fans with their the impellers on the EC external-rotor motors has been optimised in terms rated input exceeding 500 Watts can be controlled by MODBUS and of aerodynamic and installation requirements. ly made of aluminium as this minimises the bearing load of the motors 0-10V. With the new release of our selection programme “Product selector”, the What is new is their mechanical design. All sizes can now also be ordered complete RadiPac line is available. This tool allows fans to be selected as versions which can be directly mounted on the floor. As of size 400, the according to the specified duty points, and this selection to be compared mechanical structure is executed in the form of a cube. The proven sup- and documented. Using a DLL file, the RadiPacs can be integrated in your port bracket is available up to size 560. specific programme for fan selection. All this allows them to be used in a wide variety of applications, going beyond the mere ventilation and air-conditioning industry. Generally, the RadiPacs are intended for use without scroll housing. 2 Table of contents RadiPac: Everything packed in compact form 2 GreenTech: The Green Company 4 Product overview: RadiPac 6 Overview of characteristic curves - RadiPac 8 Text for tenders 10 Size 250 - Z50 12 Size 280 - 450 (compact design) 78 Accessories 82 Electrical connections 88 Technical parameters & scope 94 ebm-papst representatives & subsidiaries 98 3 Sustainability is at the centre of our thoughts and actions. Out of conviction! Eco-friendliness and sustainability have always been at the core of our thoughts and actions. For decades, we have worked according to the simple but strict creed of our co-founder Gerhard Sturm: “Each new product we develop has to be better than the last one in terms of economy and ecology.” GreenTech is the ultimate expression of our corporate philosophy. GreenTech is pro-active development. GreenTech is eco-friendly production. Even in the design phase, the materials and processes we use are op- GreenTech also stands for maximum energy efficiency in our pro- timised for the greatest possible eco-friendliness, energy balance and duction processes. There, the intelligent use of industrial waste heat – wherever possible – recyclability. We continually improve the materi- and groundwater cooling, photovoltaics and, of course, our own al and performance of our products, as well as the flow and noise cha- cooling and ventilation technology are of the utmost importance. Our racteristics. At the same time, we significantly reduce energy conump- most modern plant, for instance, consumes 91% less energy than tion. Close co-operation with universities and scientific institutes and currently specified and required. In this way, our products contribute the professorship we endow in the area of power engineering and re- to protecting the environment, from their origin to their recyclable generative energies allows us to profit from the latest research finings packaging. in these fields – and at the same time ensure highly qualified young academics. GreenTech follows a firm philosophy. GreenTech is pro-active development. GreenTech pays off for our customers. GreenTech is eco-friendly production. GreenTech is acknowledged and certified. 4 GreenTech is acknowledged and certified. Our customers profit from this every day. Every step in our chain of production meets the stringent standards of The heart of GreenTech is future-oriented EC technology from ebm- environmental specialists and the public. papst. The EC technology at the core of our most efficient motors This supports our position as Germany‘s most sustainable company and fans allows efficiency of up to 90%, saves energy at a very high 2013, as does the DEKRA Award 2012 we received in the category level, significantly extends service life and makes our products “Umwelt – Herausforderung Energiewende / Environment – Challen- maintenance-free. These values pay off not only for the environ- ge: Transition to more sustainable energy systems”, to name only a ment, but every cent also pays off for the user! All ebm-papst pro- few of a large number of examples. The environmental advantage gai- ducts – even those for which GreenTech EC technology does not ned in the performance of the products developed from our Green- (yet) make sense from an application viewpoint – feature the grea- Tech philosophy can also be measured in the fulfillment of the most test possible connection of economy and ecology. stringent energy and environmental standards. In many instances, our products are already well below the thresholds energy legislation will impose a few years from now – several times over. 5 Product overview: RadiPac RadiPac: Overview of types Baugröße Size Nominal voltage range VAC Max. input power W M3G 084-DF 1~ 200-277 450 R3G250-AT39-71 K3G250-AT39-72 M3G 084-FA 1~ 200-277 700 R3G250-AV29-B1 K3G250-AV29-B2 M3G 084-GF 3~ 380-480 820 R3G250-AY11-C1 K3G250-AY11-C2 M3G 084-FA 1~ 200-277 415 R3G280-AT04-71 K3G280-AT04-72 M3G 084-GF 1~ 200-277 715 R3G280-AU06-B1 K3G280-AU06-B2 M3G 084-GF 3~ 380-480 1000 R3G280-AU11-C1 K3G280-AU11-C2 M3G 112-EA 3~ 380-480 1000 R3G310-AX52-90 K3G310-AX52-90 M3G 112-EA 1~ 200-277 1270 R3G310-AX54-21 K3G310-AX54-22 M3G 112-GA 3~ 380-480 1650 R3G310-BB49-01 K3G310-BB49-02 M3G 112-IA 3~ 380-480 3240 R3G310-AZ88-01 K3G310-AZ88-02 M3G 112-EA 3~ 380-480 1000 R3G355-AX56-90 K3G355-AX56-90 M3G 112-GA 1~ 200-277 1400 R3G355-AY43-21 K3G355-AY43-22 M3G 112-GA 3~ 380-480 1700 R3G355-AY40-01 K3G355-AY40-02 M3G 112-IA 3~ 380-480 2250 R3G355-BC92-01 K3G355-BC92-02 M3G 112-IA 3~ 380-480 1850 R3G400-AY87-01 K3G400-AY87-02 M3G 150-FF 3~ 380-480 3000 R3G400-AQ23-01 K3G400-AQ23-01 M3G 150-FF 3~ 380-480 3380 R3G400-AQ23-68 K3G400-AQ23-68 M3G 112-IA 3~ 380-480 1650 R3G450-AY86-01 K3G450-AY86-02 M3G 150-FF 3~ 380-480 2640 R3G450-AQ25-68 K3G450-AQ25-68 M3G 150-IF 3~ 380-480 5250 R3G450-AZ24-68 K3G450-AZ24-68 M3G 150-FF 3~ 380-480 2825 R3G500-AP25-01 K3G500-AP25-01 M3G 150-FF 3~ 380-480 3540 R3G500-AP25-68 K3G500-AP25-68 M3G 150-IF 3~ 380-480 5400 R3G500-AQ31-68 K3G500-AQ31-68 M3G 150-IF 3~ 380-480 3530 R3G560-AP21-68 K3G560-AP21-68 M3G 150-NA 3~ 380-480 4600 R3G560-AQ08-68 K3G560-AQ08-68 M3G 150-NA 3~ 380-480 2900 R3G630-AP01-01 K3G630-AP01-01 M3G 200-HF 3~ 380-480 6750 --- --- M3G 200-QA 3~ 380-480 11000 --- --- M3G 150-NA 3~ 380-480 2800 R3G710-AP02-01 K3G710-AP02-01 M3G 200-LA 3~ 380-480 7860 --- --- M3G 200-QA 3~ 380-480 11800 --- --- M3G 200-QA 3~ 380-480 7530 --- --- M3G 200-QA 3~ 380-480 11600 --- --- M3G 200-QA 3~ 380-480 7520 --- --- M3G 200-QA 3~ 380-480 8700 --- --- M3G 200-QA 3~ 380-480 3560 --- --- Baugröße Size Motor Nominal voltage range VAC Max. input power W Centrifugal fan 280 M3G 084-GF 3~ 380-480 985 R3G280-AJ14-C1 310 M3G 112-GA 3~ 380-480 1650 R3G310-BC38-01 355 M3G 112-GA 3~ 380-480 1730 R3G355-BD43-01 400 M3G 150-FF 3~ 380-480 2840 R3G400-AS23-01 450 M3G 150-FF 3~ 380-480 2380 R3G450-AS24-01 250 250 280 310 355 355 400 400 450 500 500 560 630 710 800 900 Z50 Centrifugal fan Standard RadiPac in compact design 6 Centrifugal module with support bracket Standard Motor Centrifugal module with support bracket Increased corrosion protection (1) Centrifugal module with support bracket Hygiene devices (2) Centrifugal module with support- (3), cube design (4) K3G250-AT39-74 K3G250-AT39-56 K3G250-AT39-89 (3) K3G250-AV29-B4 K3G250-AV29-B6 K3G250-AV29-B9 (3) K3G250-AY11-C4 --- K3G250-AY11-C9 (3) K3G280-AT04-74 K3G280-AT04-56 K3G280-AT04-89 (3) K3G280-AU06-B4 K3G280-AU06-B6 K3G280-AU06-B3 (3) K3G280-AU11-C4 K3G280-AU11-C6 K3G280-AU11-C9 (3) K3G310-AX52-96 (3) K3G310-AX52-91 K3G310-AX52-35 K3G310-AX54-52 --- K3G310-AX54-98 (3) K3G310-BB49-32 --- K3G310-BB49-96 (3) K3G310-AZ88-32 K3G310-AZ88-35 K3G310-AZ88-96 (3) K3G355-AX56-91 --- K3G355-AX56-96 (3) K3G355-AY43-52 --- K3G355-AY43-98 (3) K3G355-AY40-32 K3G355-AY40-35 K3G355-AY40-96 (3) K3G355-BC92-32 --- K3G355-BC92-96 (3) K3G400-AY87-32 --- K3G400-AY87-96 (3) K3G400-AQ23-31 K3G400-AQ23-35 K3G400-AQ23-02 (4) --- --- --- K3G450-AY86-32 --- K3G450-AY86-96 (4) --- --- --- --- --- --- K3G500-AP25-31 --- K3G500-AP25-02 (4) --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- K3G630-AR02-01 (4) --- --- K3G630-AS05-01 (4) --- --- --- --- --- K3G710-AR03-01 (4) --- --- K3G710-AS06-01 (4) --- --- K3G800-AR08-01 (4) --- --- K3G800-AS07-01 (4) --- --- K3G900-AR10-01 (4) --- --- K3G900-AS08-01 (4) --- --- K3GZ50-AQ11-01 (4) Legend: (1) Increased corrosion protection: - Support bracket coated in black - Support plate and impeller coated in black - Motor coated in black (2) Design of hygiene devices: - Support bracket coated in black - Support plate and impeller coated in white - Motor coated in black - Mounting elements made of stainless steel For technical data and dimensions – see standard type. (3) Support (4) Cube design design 7 Pa Overview of characteristic curves: RadiPac 3000 Ø 310 2000 Ø 450 Ø 500 Ø 630 Ø 710 Ø 800 Ø 400 Ø 355 Ø 900 Ø 560 Ø 250 Ø 280 1000 900 800 700 600 500 400 Ø Z50 300 pfs 200 100 500 qV 8 1000 2000 3000 4000 5000 10000 20000 30000 40000 50000 m3/h RadiPac in the Product Selector Additionaly, and for selecting the correct fan, you can take advan- Additionally, the life cycle costs for the selected fans can be calculated. tage of the ebm-papst software "Product Selector" with integrated You can make your selection based on the operating point or on the type “Black-Box" module for integration in system configuration pro- designation. grammes on the customer side. The data sheets, which can be created in PDF format, show not only the The new selection program gives you the ability to select plug fans based nominal data of the fan, but also the performance data in the specified on the operating point. If multiple fans are in the specified power range, operating point with the inlet and outlet side sound power levels across the aerodynamic and acoustic data displayed can be used to select and the octave band. document the most suitable fan. For more detailed information, simply ask your ebm-papst contact! 9 EC centrifugal fans – RadiPac K3G 250 to K3G 560 Text for tender for radial fan modules: Protective features: Single inlet; direct drive; high-performance radial impeller with circumfe- - Alarm relay with zero-potential change-over contacts rential diffuser mounted on an electronically commutated external-rotor motor with integrated control electronics; radial impeller made of alumi- (250 V AC/2 A, cos ϕ = 1) - Locked-rotor protection nium with backward curved, continuously welded blades; aerodynamical- - Phase failure detection ly optimised inlet nozzle with bleeder connection for pressure relief made - Soft start of motors of zinc-coated sheet steel; complete unit statically and dynamically balan- - Mains under-voltage detection ced in two planes as per DIN / ISO 1940 to balancing grade G 6.3; EC - Over-temperature protection of electronics and motor external-rotor motor, efficiency class IE4 without “rare earth” magnets - Short-circuit protection being used, with maintenance-free ball bearings and permanent lubrication; nominal lifetime 40,000 operating hours; wide voltage input 1~200- Technical data: 277 V, 50/60 respectively 3~380-480 V, 50/60 Hz; unit can be operated - Air flow qV on all standard Electricity Board networks at identical air performance; - Static pressure pfs = __________Pa optimised motor technology; soft start; integrated current limitation; con- - Nominal voltage range U = V nection via brought-out variable cable connector (motor size 084) or easy- - Frequency f = Hz to-mount and robust integrated terminal box made of aluminium with - Fan speed n = __________rpm spring-loaded terminals (motor sizes 112, 150 and 200); extremely com- - Input power Ped = __________kW pact electronics; with adjustable PID controller (motor sizes 112, 150 and - Current draw I = __________A 200); meets all relevant EMC directives and all requirements as to circuit - Noise level Lp = __________dBA feedbacks; requires no complicated installation with shielded cables; very - Perm. ambient temperature T low-noise commutation logic; 100 % speed-controllable. Motors with an - Mass Fan output of 750W or higher have an RS485/MODBUS RTU interface. Any potentially necessary constructional measures for structure-borne sound insulation have to be provided by customers. Optional: Modules with increased corrosion protection. For technical data, dimensions and connections – see data sheet. 10 Fan type: K3G ..... Product: ebm-papst = __________m3/h = °C = __________kg EC centrifugal fans – RadiPac K3G 400 to K3G Z50 Text for tender for radial fan modules: Protective features: Single inlet; direct drive; high-performance radial impeller with circumfe- - Alarm relay with zero-potential change-over contacts rential diffuser mounted on an electronically commutated external-rotor (250 V AC/2 A, cos ϕ = 1) motor with integrated control electronics; radial impeller made of alumi- - Locked-rotor protection nium with backward curved, continuously welded blades; aerodynamical- - Phase failure detection ly optimised inlet nozzle made of zinc-coated sheet steel; complete unit - Soft start of motors statically and dynamically balanced in two planes as per DIN / ISO 1940 - Mains under-voltage detection to balancing grade G 6.3; EC external-rotor motor, efficiency class IE4 - Over-temperature protection of electronics and motor without “rare earth” magnets being used, with maintenance-free ball bea- - Short-circuit protection rings and permanent lubrication; nominal lifetime 40,000 operating hours; wide voltage input 3~380-480 V, 50/60 Hz; unit can be operated on all Technische Daten: standard Electricity Board networks at identical air performance; optimi- - Air flow qV sed motor technology; soft start; integrated current limitation; connection - Static pressure pfs = __________Pa via easy-to-mount and robust integrated terminal box made of aluminium - Nominal voltage range U = V with spring-loaded terminals; extremely compact electronics; with adju- - Frequency f = Hz stable PID controller; meets all relevant EMC directives and all require- - Fan speed n = __________rpm ments as to circuit feedbacks; requires no complicated installation with - Input power Ped = __________kW shielded cables; very low-noise commutation logic; 100 % speed-control- - Current draw I = __________A lable. All fans have an RS485/MODBUS RTU interface. Any potentially - Noise level Lp = __________dBA necessary constructional measures for structure-borne sound insulation - Perm. ambient temerature T = have to be provided by customers. - Mass Fan = __________kg - Direction of rotation Impeller = Clockwise, seen on rotor For technical data, dimensions and connections – see data sheet. = __________m3/h °C Fan type: K3G ..... Product: ebm-papst 11 EC centrifugal fans – RadiPac backward curved, Ø 250 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 1~ 200-277 50/60 3000 448 2,80 -25..+40 p. 88 / K1) B 1~ 200-277 50/60 3450 750 3,30 -25..+40 p. 91 / L7) C 3~ 380-480 50/60 3580 790 1,50 -25..+60 p. 93 / P2) Curve Nominal data Type Motor *3G 250 M3G 084-DF A *3G 250 M3G 084-FA *3G 250 M3G 084-GF Curves Pa (1) Nominal data in operating point with maximum load and 230 or 400 VAC in H2O subject to alterations Technical features and electr. connection – Material: Support bracket: Steel, coated in black Support plate and inlet nozzle: Sheet steel, galvanised Impeller: Sheet aluminium Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings C ηmax. = 4,8 1200 3 4,0 1000 4 800 3,2 3 A 4 600 2,4 3 3 400 1,6 2 2 pfs 200 0,8 2 0 qV 400 400 800 800 1200 1 1600 1200 1600 2000 2400 2800 1 cfm m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 12 Ped W I A LWA dB(A) A 1 3175 380 2,48 84 A 2 3045 436 2,72 80 A 3 3000 448 2,80 76 A 4 3020 436 2,72 80 B 1 3450 581 2,58 85 B 2 3450 673 2,98 82 B 3 3450 750 3,30 79 B 4 3450 691 3,07 86 C 1 3655 642 1,25 87 C 2 3605 735 1,40 84 C 3 3580 790 1,50 80 C 4 3635 709 1,38 88 4 B n rpm Mass of centrifugal module with support design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 88 ff. – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Cable exit: A Variable – Terminal box design: B C Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for Centrifugal fan kg Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module w. support design kg R3G 250-AT39 -71 4,4 25075-2-4013 K3G 250-AT39 -72 8,4 K3G 250-AT39 -74 8,4 K3G 250-AT39 -89 10,4 R3G 250-AV29 -B1 5,6 25075-2-4013 K3G 250-AV29 -B2 10,1 K3G 250-AV29 -B4 10,1 K3G 250-AV29 -B9 12,1 R3G 250-AY11 -C1 6,7 25075-2-4013 K3G 250-AY11 -C2 11,1 K3G 250-AY11 -C4 11,1 K3G 250-AY11 -C9 13,1 (2) Centrifugal module with higher protection against corrosion Drawings p. 14 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 88 ff. 13 EC centrifugal fans – RadiPac backward curved, Ø 250 R3G 250-AT39-71 (Centrifugal fan) 4x90° 201,5±3 153,5 ±2 30° 45° 43 4xØ4.5 48 Depth of screw max. 10 mm 80 112 Core-end sleeves 4x90° 600+20 85 Ø260 Ø290 Ø166.2 Ø178 Ø150±0.25 Ø100 Ø176 +1 Ø284 M6 6 1,5 Ø164±0.35 Accessory part: Inlet nozzle 25075-2-4013 not included in the standard scope of delivery (k-value: 70) Connection line AWG 22, 3x crimped core-end sleeves Connection line AWG 18, 5x crimped core-end sleeves K3G 250-AT39-72 / -74 (Centrifugal module with support bracket) 235±3 187±1 o400 o298 2 4xØ11 10 85 60 ± 0 +2 0 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 70) K3G 250-AT39-89 (Centrifugal module with support design) 235 ±3 187 ±2 400 350 298 2 404 4xØ11 Pressure tap (k-value: 70) 20 0+ 60 4 10 ± 85 8 110 M4 15 32.5 160 14 280 325 351 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 250-AV29-B1 (Centrifugal fan) 223.9±3 167.4±2 4x Ø4.5 56.5 5x 72 ° 43 Depth of screw max. 16 mm Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø260 Ø290 Ø166.2 Ø176 +1 Ø284 Ø197 Ø165±0.25 Ø130 M6 (5x) 1.5 Ø186±0,5 Tightening torque 3.5±0.5 Nm 80 112 6 Accessory part: Inlet nozzle 25075-2-4013 not included in the standard scope of delivery (k-value: 70) K3G 250-AV29-B2 / -B4 (Centrifugal module with support bracket) 257.5±3 201±1 o400 o298 2 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 70) K3G 250-AV29-B9 (Centrifugal module with support design) 257.5 ±3 201 ±1 400 350 298 Observe the correct mounting position! Install the support struts only as shown in the view! 4 404 4xØ11 2 Pressure tap (k-value: 70) 125 M4 15 32.5 175 280 325 351 Ø9 15 EC centrifugal fans – RadiPac backward curved, Ø 250 R3G 250-AY11-C1 (Centrifugal fan) 223.9±3 167.4±2 4x Ø4.5 56.5 5x 72 43 ° Depth of screw max. 16 mm Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø260 Ø290 Ø166.2 Ø176 +1 Ø284 Ø197 Ø165±0.25 Ø130 M6 (5x) 1.5 Ø186±0,5 Tightening torque 3.5±0.5 Nm 80 112 6 Accessory part: Inlet nozzle 25075-2-4013 not included in the standard scope of delivery (k-value: 70) K3G 250-AY11-C2 / -C4 (Centrifugal module with support bracket) 257.5±3 201±1 o400 o298 2 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 70) K3G 250-AY11-C9 (Centrifugal module with support design) 257.5 ±3 201 ±1 400 350 298 4 404 4xØ11 2 Pressure tap (k-value: 70) 16 125 M4 15 32.5 175 280 325 351 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! 17 EC centrifugal fans – RadiPac backward curved, Ø 280 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 1~ 200-277 50/60 2400 415 2,70 -25..+40 p. 88 / K1) B 1~ 200-277 50/60 2800 715 3,10 -25..+40 p. 91 / L7) C 3~ 380-480 50/60 3100 1000 1,60 -25..+60 p. 93 / P2) Curve Nominal data Type Motor *3G 280 M3G 084-FA A *3G 280 M3G 084-GF *3G 280 M3G 084-GF Curves Pa (1) Nominal data in operating point with maximum load and 230 or 400 VAC in H2O subject to alterations 3 C ηmax. = 4 4,0 1000 B 4 3,2 800 3 A 3 600 2,4 4 400 1,6 3 2 2 0,8 2 200 pfs 1 0 qV 500 500 1000 1000 1500 1500 2000 2500 1 2000 3000 3500 1 cfm m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 18 Technical features and electr. connection – Material: Support bracket: Steel, coated in black Support plate and inlet nozzle: Sheet steel, galvanised Impeller: Sheet aluminium Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings n rpm Ped W I A LWA dB(A) A 1 2530 335 2,19 80 A 2 2415 392 2,57 75 A 3 2400 415 2,70 71 A 4 2405 405 2,66 75 B 1 2800 479 2,11 83 B 2 2800 655 2,88 79 B 3 2800 715 3,10 76 B 4 2800 650 2,85 82 C 1 3100 645 1,04 86 C 2 3100 852 1,35 83 C 3 3100 1000 1,60 80 C 4 3100 921 1,46 83 Mass of centrifugal module with support design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 88 ff. – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Cable exit: A Variable – Terminal box design: B C Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: VDE, UL, CSA, CCC, GOST are applied for Centrifugal fan kg Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module w. support design kg R3G 280-AT04 -71 5,4 28075-2-4013 K3G 280-AT04 -72 9,7 K3G 280-AT04 -74 9,7 K3G 280-AT04 -89 11,7 R3G 280-AU06 -B1 6,8 28075-2-4013 K3G 280-AU06 -B2 11,5 K3G 280-AU06 -B4 11,5 K3G 280-AU06 -B3 13,5 R3G 280-AU11 -C1 7,1 28075-2-4013 K3G 280-AU11 -C2 11,7 K3G 280-AU11 -C4 11,7 K3G 280-AU11 -C9 13,7 (2) Centrifugal module with higher protection against corrosion Drawings p. 20 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 88 ff. 19 EC centrifugal fans – RadiPac backward curved, Ø 280 R3G 280-AT04-71 (Centrifugal fan) 30° 53 4xØ4.5 48 4x90° 227±3 179 ±2 Depth of screw max. 10 mm 45° 90 132 Core-end sleeves 4x90° 600+20 85 Ø280 Ø325 Ø187.2 Ø178 Ø150±0.25 Ø100 Ø197.4 +1.8 Ø319 M6 10 1.5 Ø164±0.35 Accessory part: Inlet nozzle 28075-2-4013 not included in the standard scope of delivery (k-value: 93) Connection line AWG 18, 5x crimped core-end sleeves Connection line AWG 22, 3x crimped core-end sleeves K3G 280-AT04-72 / -74 (Centrifugal module with support bracket) 268±3 218±1 o400±1.2 o298 2 4xØ11 10 6 85 00+ ± 2 0 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 93) K3G 280-AT04-89 (Centrifugal module with support design) 268 ±3 218 ±1 400 350 298 2 404 4xØ11 Pressure tap (k-value: 93) 20 0+ 60 4 10 ± 85 8 140 M4 15 32.5 190 20 280 325 351 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 280-AU06-B1 (Centrifugal fan) 252.4±3 196±2 4x Ø4.5 56.5 5x Depth of screw max. 16 mm 72 ° 53 Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø280 Ø325 Ø187.2 Ø197 Ø165±0.25 Ø130 Ø197.4 +1.8 Ø319 M6 (5x) Tightening torque 3.5±0.5 Nm Ø186±0,5 1.5 90 132 Accessory part: Inlet nozzle 28075-2-4013 not included in the standard scope of delivery (k-value: 93) 10 K3G 280-AU06-B2 / -B4 (Centrifugal module with support bracket) 291.5±3 235±1 o400 o298 2 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 93) (Centrifugal module with support design) 291.5 ±3 235 ±1 400 350 298 404 4xØ11 2 Observe the correct mounting position! Install the support struts only as shown in the view! 4 K3G 280-AU06-B3 Pressure tap (k-value: 93) 155 M4 15 32.5 205 280 325 351 Ø9 21 EC centrifugal fans – RadiPac backward curved, Ø 280 R3G 280-AU11-C1 (Centrifugal fan) 252.4±3 196±2 4x Ø4.5 56.5 Depth of screw max. 16 mm 5x 72 ° 53 Ø280 Ø325 Ø187.2 Ø197 Ø165±0.25 Ø130 Ø197.4 +1.8 Ø319 M6 (5x) Tightening torque 3.5±0.5 Nm Ø186±0,5 1.5 Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm 90 132 Accessory part: Inlet nozzle 28075-2-4013 not included in the standard scope of delivery (k-value: 93) 10 K3G 280-AU11-C2 / -C4 (Centrifugal module with support bracket) 291.5±3 235±1 o400 o298 2 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! o350 Pressure tap (k-value: 93) K3G 280-AU11-C9 (Centrifugal module with support design) 291.5 ±3 235 ±1 400 350 298 4 404 4xØ11 2 Pressure tap (k-value: 93) 155 32.5 205 22 M4 15 280 325 351 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! 23 EC centrifugal fans – RadiPac backward curved, Ø 310 Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 2580 1000 1,63 -25..+55 p. 90 / L6) B 1~ 200-277 50/60 2850 1270 5,60 -25..+60 p. 92 / L9) M3G 112-GA C 3~ 380-480 50/60 3140 1650 2,50 -25..+60 p. 89 / M3) M3G 112-IA D 3~ 380-480 50/60 4100 3240 4,90 -25..+40 p. 89 / M3) Curve Nominal voltage range Technical features and electr. connection – Material: Support bracket: Steel, coated in black Support plate and inlet nozzle: Sheet steel, galvanised Impeller: Sheet aluminium Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Nominal data Type Motor *3G 310 M3G 112-EA A *3G 310 M3G 112-EA *3G 310 *3G 310 Curves Pa (1) Nominal data in operating point with maximum load and 230 or 400 VAC in H2O subject to alterations 1600 ηmax. = 8,0 6,4 2000 3 4 D 4,8 1200 4 A 3 800 3,2 4 2 3 2580 669 1,17 88 2 2580 862 1,46 81 A 3 2580 1000 1,63 77 A 4 2580 907 1,53 79 B 1 2930 946 4,14 88 B 2 2895 1147 5,01 83 B 3 2850 1270 5,60 79 B 4 2850 1237 5,41 83 C 1 3140 1158 1,79 90 C 2 3140 1440 2,21 86 C 3 3140 1650 2,50 83 C 4 3140 1559 2,39 87 1,6 2 D 1 4100 2244 3,35 99 D 2 4100 2767 4,12 94 D 3 4100 3240 4,90 91 D 4 4100 3018 4,49 95 2 2 pfs 1 0 qV 500 1000 1000 2000 1500 2000 3000 2500 4000 1 1 3000 5000 1 3500 cfm 6000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 24 LWA dB(A) 1 3 400 I A A 4 B Ped W A 3 C n rpm Mass of centrifugal module with support design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 ff. – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: B GOST A C D VDE, GOST Centrifugal fan kg Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module w. support design kg R3G 310-AX52 -90 8,8 31575-2-4013 K3G 310-AX52 -90 16,7 K3G 310-AX52 -91 16,7 K3G 310-AX52 -96 19,0 R3G 310-AX54 -21 11,0 31575-2-4013 K3G 310-AX54 -22 19,4 K3G 310-AX54 -52 19,4 K3G 310-AX54 -98 22,2 R3G 310-BB49 -01 12,6 31575-2-4013 K3G 310-BB49 -02 21,0 K3G 310-BB49 -32 21,0 K3G 310-BB49 -96 24,1 R3G 310-AZ88 -01 15,0 31575-2-4013 K3G 310-AZ88 -02 24,2 K3G 310-AZ88 -32 24,2 K3G 310-AZ88 -96 26,2 (2) Centrifugal module with higher protection against corrosion Drawings p. 26 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 25 EC centrifugal fans – RadiPac backward curved, Ø 310 R3G 310-AX52-90 (Centrifugal fan) 253,7±3 197,2±2 4xØ4,5 56,5 5xM6 55 Depth of screw max. 16 mm ° 72 Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø325 Ø350 Ø222 Ø360 Ø211,7 5x Ø165 Ø186±0,5 100 147 10 Tightening torque 3.5±0.5 Nm Accessory part: Inlet nozzle 31575-2-4013 not included in the standard scope of delivery (k-value: 116) K3G 310-AX52-90 / -91 (Centrifugal module with support bracket) 294±3 237.5±2.5 o500 o372 15 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! M16x1.5(3x) o450 Pressure tap (k-value: 116) K3G 310-AX52-96 (Centrifugal module with support design) 500 450 372 15 4xØ11 294 ±3 237.5±2.5 4.3 Pressure tap (k-value: 116) 150 200 26 15 M6 32.5 350 395 422 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 310-AX54-21 (Centrifugal fan) 4xØ4.5 72 269.2 ±3 197.2 ±2 Accessory part: Inlet nozzle 31575-2-4013 not included in the standard scope of delivery (k-value: 116) 55 Depth of screw max. 20 mm 6xM10 6x6 Ø325 Ø350 Ø 222 Ø 360 Ø211.7 0° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 100 147 Tightening torque 3.5±0.5 Nm Ø 252±0.5 10 K3G 310-AX54-22 / -52 (Centrifugal module with support bracket) 309.5±3 237.5±2,5 o500 o375 15 Ø11 (4x) Observe the correct mounting position! Install the support struts only as shown in the view! M o450 Pressure tap (k-value: 116) K3G 310-AX54-98 ) x 5(3 1. 20x (Centrifugal module with support design) 500 450 375 15 Observe the correct mounting position! Install the support struts only as shown in the view! 4.3 4xØ11 309.5 ±3 237.5 ±2.5 Pressure tap (k-value: 116) 150 200 15 M6 32.5 350 395 422 Ø9 27 EC centrifugal fans – RadiPac backward curved, Ø 310 R3G 310-BB49-01 (Centrifugal fan) 289.2 ±3 217.2 ±2 4xØ4.5 72 Accessory part: Inlet nozzle 31575-2-4013 not included in the standard scope of delivery (k-value: 116) 55 Depth of screw max. 20 mm 6xM10 6x6 Ø325 Ø350 Ø 222 Ø 360 Ø211.7 0° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 100 147 Ø 252±0.5 10 Tightening torque 3.5±0.5 Nm K3G 310-BB49-02 / -32 (Centrifugal module with support bracket) 317.5±3 257.5±2 o500 o375 15 Ø11 (4x) Observe the correct mounting position! Install the support struts only as shown in the view! .5 0x1 M2 o450 Pressure tap (k-value: 116) K3G 310-BB49-96 ) (3x (Centrifugal module with support design) 500 450 375 15 4xØ11 317.5 ±3 257.5 ±2.5 4.3 Pressure tap (k-value: 116) 170 220 28 15 M6 32.5 350 395 422 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 310-AZ88-01 (Centrifugal fan) 289.2 ±3 217.2 ±2 Accessory part: Inlet nozzle 31575-2-4013 not included in the standard scope of delivery (k-value: 116) 4xØ4.5 72 55 Depth of screw max. 20 mm 6xM10 0 6x6 Ø325 Ø350 Ø 222 Ø 360 Ø211.7 ° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 80 127 Tightening torque 3.5±0.5 Nm Ø 252±0.5 10 K3G 310-AZ88-02 / -32 (Centrifugal module with support bracket) 329.5±3 257.5±2.5 o500 o375 15 Ø11 (4x) Observe the correct mounting position! Install the support struts only as shown in the view! .5 0x1 M2 o450 Pressure tap (k-value: 116) (Centrifugal module with support design) 500 450 375 15 4xØ11 329.5 ±3 257.5 ±2.5 Observe the correct mounting position! Install the support struts only as shown in the view! 4.3 K3G 310-AZ88-96 ) (3x Pressure tap (k-value: 116) 170 220 15 M6 32.5 350 395 422 Ø9 29 EC centrifugal fans – RadiPac backward curved, Ø 355 Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 2140 1000 1,65 -25..+60 p. 90 / L6) B 1~ 200-277 50/60 2450 1400 6,00 -25..+50 p. 92 / L9) M3G 112-GA C 3~ 380-480 50/60 2600 1700 2,60 -25..+40 p. 89 / M3) M3G 112-IA D 3~ 380-480 50/60 2800 2250 3,50 -25..+55 p. 89 / M3) Curve Nominal voltage range Technical features and electr. connection – Material: Support bracket: Steel, coated in black Support plate and inlet nozzle: Sheet steel, galvanised Impeller: Sheet aluminium Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Nominal data Type Motor *3G 355 M3G 112-EA A *3G 355 M3G 112-GA *3G 355 *3G 355 Curves Pa (1) Nominal data in operating point with maximum load and 230 or 400 VAC 1400 5,6 in H2O subject to alterations D 3 ηmax. = n rpm Ped W I A LWA dB(A) 4 4,8 1200 A 1 2140 656 1,14 87 A 2 2140 893 1,50 77 A 3 2140 1000 1,65 75 A 4 2140 918 1,54 78 B 1 2450 998 4,33 86 B 2 2440 1232 5,35 82 B 3 2450 1400 6,00 79 B 4 2410 1344 5,94 82 C 1 2600 1140 1,74 92 C 2 2600 1510 2,30 83 C 3 2600 1700 2,60 79 C 4 2600 1594 2,42 83 D 1 2800 1463 2,33 90 D 2 2800 1916 2,99 86 D 3 2800 2250 3,50 85 D 4 2800 2134 3,29 88 C 4 3 4,0 1000 B 4 3 800 3,2 A 4 3 600 2,4 3 2 pfs 200 2 2 0,8 400 1,6 2 0 qV 500 1000 1000 2000 1500 2000 3000 2500 4000 1 3000 5000 1 3500 6000 1 4000 cfm 7000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 30 Mass of centrifugal module with support design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 ff. – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: B GOST A C D VDE, GOST Centrifugal fan kg Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module w. support design kg R3G 355-AX56 -90 9,4 35675-2-4013 K3G 355-AX56 -90 17,4 K3G 355-AX56 -91 17,4 K3G 355-AX56 -96 19,4 R3G 355-AY43 -21 14,0 35675-2-4013 K3G 355-AY43 -22 22,4 K3G 355-AY43 -52 22,4 K3G 355-AY43 -98 25,5 R3G 355-AY40 -01 13,1 35675-2-4013 K3G 355-AY40 -02 23,4 K3G 355-AY40 -32 23,4 K3G 355-AY40 -96 25,0 R3G 355-BC92 -01 15,2 35675-2-4013 K3G 355-BC92 -02 25,8 K3G 355-BC92 -32 25,8 K3G 355-BC92 -96 27,8 (2) Centrifugal module with higher protection against corrosion Drawings p. 32 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 31 EC centrifugal fans – RadiPac backward curved, Ø 355 R3G 355-AX56-90 (Centrifugal fan) 270.7±3 214.2±2 4xØ4.5 56.5 Depth of screw max. 16 mm 5xM6 64.5 ° 72 Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø345 Ø370 Ø239 Ø405 Ø250.3 Ø404 5x Ø165 Ø186±0.5 112 164 12 Tightening torque 3.5±0.5 Nm Accessory part: Inlet nozzle 35675-2-4013 not included in the standard scope of delivery (k-value: 148) K3G 355-AX56-90 / -91 (Centrifugal module with support bracket) 319.5±3 263±2.5 o500 o372 15 M16x1.5(3x) 4xØ11 Observe the correct mounting position! Install the support struts only as shown in the view! o450 Pressure tap (k-value: 148) K3G 355-AX56-96 (Centrifugal module with support design) 500 450 372 15 4xØ11 319,5 ±3 263 ±2.5 4.3 Pressure tap (k-value: 148) 175 225 32 15 M6 32.5 350 395 422 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 355-AY43-21 (Centrifugal fan) 306.2 ±3 234.2±2 4xØ4.5 72 Accessory part: Inlet nozzle 35675-2-4013 not included in the standard scope of delivery (k-value: 148) 64.4 Depth of screw max. 20 mm 6xM10 Ø345 Ø370 Ø 405 Ø 250.3 Ø 404 Ø239 0° 6x6 Ø 232 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 112 164 Ø 252±0.5 12 Tightening torque 3.5±0.5 Nm K3G 355-AY43-22 / -52 (Centrifugal module with support bracket) 354.5±3 282.5±2,5 o500 o375 15 Ø11 (4x) Ø405 Observe the correct mounting position! Install the support struts only as shown in the view! ) 3x 5( 1. 20x M o450 Pressure tap (k-value: 148) K3G 355-AY43-98 (Centrifugal module with support design) 500 450 375 15 Observe the correct mounting position! Install the support struts only as shown in the view! 4.3 4xØ11 354.5 ±3 282.5 ±2.5 Pressure tap (k-value: 148) 195 245 15 M6 32.5 350 395 422 Ø9 33 EC centrifugal fans – RadiPac backward curved, Ø 355 R3G 355-AY40-01 (Centrifugal fan) 4xØ4.5 72 306.2±3 234.2±2 Accessory part: Inlet nozzle 35675-2-4013 not included in the standard scope of delivery (k-value: 148) 64.4 Depth of screw max. 20 mm 6xM10 6x6 Ø345 Ø370 Ø 405 Ø 250.3 Ø 404 Ø239 0° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 112 164 Ø 252±0.5 12 Tightening torque 3.5±0.5 Nm K3G 355-AY40-02 / -32 (Centrifugal module with support bracket) 354.5±3 282.5±2.5 o500 o375 15 Ø11 (4x) Ø405 Observe the correct mounting position! Install the support struts only as shown in the view! 3x) 5( 1. 20x M o450 Pressure tap (k-value: 148) K3G 355-AY40-96 (Centrifugal module with support design) 500 450 375 15 4xØ11 343±3 282.5 ±2.5 4.3 Pressure tap (k-value: 148) 195 245 34 15 M6 32.5 350 395 422 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 355-BC92-01 (Centrifugal fan) 4xØ4.5 326.2±3 254.2±2 72 Accessory part: Inlet nozzle 35675-2-4013 not included in the standard scope of delivery (k-value: 148) 64.4 Depth of screw max. 20 mm 6xM10 6x6 Ø345 Ø370 Ø 405 Ø 250.3 Ø 405 Ø239 0° Ø 232 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 112 164 Ø 252±0.5 12 Tightening torque 3.5±0.5 Nm K3G 355-BC92-02 / -32 (Centrifugal module with support bracket) 374.5±3 302.5±2.5 o500 o375 15 Ø11 (4x) Ø405 Observe the correct mounting position! Install the support struts only as shown in the view! M 3x) .5( 1 20x o450 Pressure tap (k-value: 148) K3G 355-BC92-96 (Centrifugal module with support design) 500 450 375 15 Observe the correct mounting position! Install the support struts only as shown in the view! 4.3 4xØ11 374.5 ±3 302.5 ±2.5 Pressure tap (k-value: 148) 215 265 15 M6 32.5 350 395 422 Ø9 35 EC centrifugal fans – RadiPac backward curved, Ø 400 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 2180 1850 2,90 -25..+50 p. 89 / M3) B 3~ 380-480 50/60 2550 3000 4,60 -25..+60 p. 89 / M3) C 3~ 380-480 50/60 2680 3380 5,15 -25..+40 p. 89 / M3) Curve Nominal data Type Motor *3G 400 M3G 112-IA A *3G 400 M3G 150-FF *3G 400 M3G 150-FF Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC 1600 in H2O subject to alterations Technical features and electr. connection – Material: Support bracket: Steel, coated in black; Support plate and inlet nozzle: Sheet steel, galvanised; Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: A "B"; B C "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings 3 4 n rpm ηmax. = Ped W I A LWA dB(A) 5,6 C 1400 A 1 2180 1178 1,81 89 A 2 2180 1748 2,66 82 A 3 2180 1850 2,90 81 A 4 2180 1638 2,49 84 B 1 2550 1989 3,03 93 B 2 2550 2578 3,92 87 B 3 2550 3000 4,60 85 B 4 2550 2890 4,41 87 C 1 2680 2384 3,65 93 C 2 2680 3069 1,69 88 C 3 2680 3380 5,15 85 C 4 2680 3140 4,77 91 B 1200 4,8 4 3 3 1000 4,0 A 4 3,2 400 1,6 600 200 0,8 800 2,4 3 2 2 2 pfs 1 0 qV 1000 2000 3000 2000 4000 4000 6000 1 5000 8000 1 6000 cfm 10000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 36 Centrifugal fan kg R3G 400-AY87 -01 15,6 Mass of centrifugal module with supportcube design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A VDE, GOST; B UL, CSA, GOST; C GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module with support-(3) cube design(4) 40075-2-4013 K3G 400-AY87 -02 26,0 K3G 400-AY87 -32 26,0 K3G 400-AY87 -96 (3) 28,0 K3G 400-AQ23 -02 (4) 47,0 R3G 400-AQ23 -01 21,7 40075-2-4013 K3G 400-AQ23 -01 32,3 K3G 400-AQ23 -31 32,3 R3G 400-AQ23 -68 21,7 40075-2-4013 K3G 400-AQ23 -68 32,3 --- --- --- kg --- (2) Centrifugal module with higher protection against corrosion (3) Support design (4) Cube design Drawings p. 38 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 37 EC centrifugal fans – RadiPac backward curved, Ø 400 R3G 400-AY87-01 (Centrifugal fan) Accessory part: Inlet nozzle 40075-2-4013 not included in the standard scope of delivery (k-value: 188) 72 6xØ9 345 ±3 273 ±2 68 Depth of screw max. 20 mm 6xM10 6x6 Ø390 Ø413 Ø 282 Ø 455 Ø270.9 0° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 125 182 Tightening torque 3.5±0.5 Nm Ø 252±0.5 9 K3G 400-AY87-02 / -32 (Centrifugal module with support bracket) 399±3 327±2.5 o500 o375 15 Ø11 (4x) Ø455 Observe the correct mounting position! Install the support struts only as shown in the view! .5 1 20x M ) (3x o450 Pressure tap (k-value: 188) K3G 400-AY87-96 (Centrifugal module with support design) 387±3 327±2.5 500 450 375 4xØ11 15 4.3 Pressure tap (k-value: 188) 240 290 38 15 M6 32.5 350 395 422 Ø9 Observe the correct mounting position! Install the support struts only as shown in the view! R3G 400-AQ23-01 (Centrifugal fan) Accessory part: Inlet nozzle 40075-2-4013 not included in the standard scope of delivery (k-value: 188) 68 6xØ9 335.6 ±3 265.6 ±2 70 Depth of screw max. 25 mm 6xM10 220.5±1 Ø390 Ø413 Ø270.9 Ø455 Ø282 Ø188 0° 6x6 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 9 125 182 Ø252±0,3 Ø275 Tightening torque 3.5±0.5 Nm K3G 400-AQ23-01 / -31 (Centrifugal module with support bracket) 390±3 320±2 o500-1 o375 15 M 20 x (3 1.5 x) Ø11 (4x) Ø455 Observe the correct mounting position! Install the support struts only as shown in the view! o450 Pressure tap (k-value: 188) K3G 400-AQ23-02 (Centrifugal module with cube design) Inlet nozzle with pressure tap (k-value: 188) 431 323 15 4xØ9 *435 *93 *298 500 * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. 39 EC centrifugal fans – RadiPac backward curved, Ø 400 R3G 400-AQ23-68 (Centrifugal fan) 6xØ9 335.6 ±3 265.6 ±2 70 Accessory part: Inlet nozzle 40075-2-4013 not included in the standard scope of delivery (k-value: 188) 68 Depth of screw max. 25 mm 6xM10 220.5±1 Ø390 Ø413 Ø270.9 Ø455 Ø282 Ø188 0° 6x6 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 9 125 182 Ø252±0,3 Ø275 Tightening torque 3.5±0.5 Nm K3G 400-AQ23-68 (Centrifugal module with support bracket) 390±3 320±2 15 o500-1 o375 20 x (3 1.5 x) M Ø11 (4x) Ø455 Observe the correct mounting position! Install the support struts only as shown in the view! o450 Pressure tap (k-value: 188) 40 41 EC centrifugal fans – RadiPac backward curved, Ø 450 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 1750 1615 2,50 -25..+50 p. 89 / M3) B 3~ 380-480 50/60 2040 2640 4,00 -25..+60 p. 89 / M3) C 3~ 380-480 50/60 2750 5250 7,95 -25..+40 p. 89 / M3) Curve Nominal data Type Motor *3G 450 M3G 112-IA A *3G 450 M3G 150-FF *3G 450 M3G 150-IF 1600 1200 C 3 4 6,4 2000 n rpm ηmax. = 3,2 3 2 4 3 2 2 1,6 400 pfs 1 0 qV 1000 2000 2000 4000 3000 4000 6000 5000 8000 1 6000 10000 1 7000 cfm 12000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 42 LWA dB(A) 1 1750 1036 1,61 87 2 1750 1457 2,25 80 A 3 1750 1615 2,50 77 A 4 1750 1524 2,33 80 B 1 2040 1795 2,73 92 B 2 2040 2309 3,45 86 B 3 2040 2640 4,00 82 B 4 2040 2401 3,58 87 C 1 2750 3356 5,11 101 C 2 2750 4565 6,91 94 C 3 2750 5250 7,95 90 C 4 2750 4642 7,03 97 B A I A A 4 800 Ped W A 3 4,8 Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC 8,0 in H2O subject to alterations Technical features and electr. connection – Material: Support bracket: Steel, coated in black; Support plate and inlet nozzle: Sheet steel, galvanised; Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: A "B"; B C "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Mass of centrifugal module with cube design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A VDE, GOST; B C GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module with cube design kg 16,4 45075-2-4013 K3G 450-AY86 -02 31,9 K3G 450-AY86 -32 31,9 K3G 450-AY86 -96 46,0 R3G 450-AQ25 -68 22,5 45075-2-4013 K3G 450-AQ25 -68 38,2 --- --- --- --- R3G 450-AZ24 -68 31,1 45075-2-4013 K3G 450-AZ24 -68 52,7 --- --- --- --- Centrifugal fan kg R3G 450-AY86 -01 (2) Centrifugal module with higher protection against corrosion Drawings p. 44 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 43 EC centrifugal fans – RadiPac backward curved, Ø 450 R3G 450-AY86-01 (Centrifugal fan) Accessory part: Inlet nozzle 45075-2-4013 not included in the standard scope of delivery (k-value: 240) 6xØ9 367 ±3 295 ±2 72 76 Depth of screw max. 20 mm 6xM10 6x6 Ø430 Ø480 Ø 317 Ø 505 Ø303.4 0° Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 140 204 Tightening torque 3.5±0.5 Nm Ø 252±0.5 9 K3G 450-AY86-02 / -32 (Centrifugal module with support bracket) 429±3 357±2.5 o630 o551 15 Ø11 (4x) Ø505 Observe the correct mounting position! Install the support struts only as shown in the view! 3x) 5( 1. 20x M o580 Pressure tap (k-value: 240) K3G 450-AY86-96 (Centrifugal module with cube design) Inlet nozzle with pressure tap (k-value: 240) *565 463.5 356 15 *61.5 *361.5 4xØ9 630 * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. 44 R3G 450-AQ25-68 (Centrifugal fan) Accessory part: Inlet nozzle 45075-2-4013 not included in the standard scope of delivery (k-value: 240) 76 6xØ9 357 ±3 287.2 ±2 70 Depth of screw max. 25 mm 6xM10 220.5±1 Ø430 Ø480 Ø505 Ø303.4 Ø317 Ø188 0° 6x6 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø252±0,3 Ø275 9 140 204 Tightening torque 3.5±0.5 Nm K3G 450-AQ25-68 (Centrifugal module with support bracket) 419±3 349±2 15 o630-1 o551 Pressure tap (k-value: 240) 20 x1 (3 .5 x) M Ø11 (8x) Ø566 Observe the correct mounting position! Install the support struts only as shown in the view! o580 45 EC centrifugal fans – RadiPac backward curved, Ø 450 R3G 450-AZ24-68 (Centrifugal fan) 406.5±3 293.5±2 Accessory part: Inlet nozzle 45075-2-4013 not included in the standard scope of delivery (k-value: 240) 6xØ9 113 Depth of screw max. 20 mm 76 6xM10 Ø430 Ø480 Ø303.4 Ø317 Ø505 Ø188 0° 6x6 Ø280-2 Cable gland M20x1,5(2x) Cable gland M25x1,5(1x) 112 176 Ø304±0.5 9 K3G 450-AZ24-68 (Centrifugal module with support bracket) 15 o630-1 o520.5 Ø11(8x) 469±3 355.5±2 o580 Pressure tap (k-value: 240) 46 Tightening torque 3.5±0.5 Nm Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 47 EC centrifugal fans – RadiPac backward curved, Ø 500 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 1780 2825 4,30 -25..+60 p. 89 / M3) B 3~ 380-480 50/60 1910 3540 5,40 -25..+45 p. 89 / M3) C 3~ 380-480 50/60 2200 5400 8,10 -25..+45 p. 89 / M3) Curve Nominal data Type Motor *3G 500 M3G 150-FF A *3G 500 M3G 150-FF *3G 500 M3G 150-IF Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC in H2O subject to alterations 1400 4 C 4,8 B 1200 n rpm ηmax. = 5,6 1600 6,4 3 3 800 4,0 2,4 1,6 200 0,8 2 400 2 pfs 1 0 qV 2000 2000 LWA dB(A) 1 1780 1985 3,09 94 A 2 1780 2530 3,90 89 A 3 1780 2825 4,30 83 A 4 1780 2692 4,14 85 B 1 1910 2365 3,53 95 B 2 1910 3044 4,57 89 B 3 1910 3540 5,40 82 B 4 1910 3202 4,81 87 C 1 2200 3614 5,39 98 C 2 2200 4630 6,95 93 C 3 2200 5400 8,10 87 C 4 2200 4937 7,41 92 3 2 600 I A A 3 3,2 1000 Ped W 4 A 4 4000 4000 6000 6000 8000 10000 12000 1 8000 1 14000 m3/h cfm Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 48 Technical features and electr. connection – Material: Support bracket: Steel, coated in black; Support plate and inlet nozzle: Sheet steel, galvanised; Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Mass of centrifugal module with cube design Mass of centrifugal module with support bracket Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A UL, CSA, GOST; B C GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg Centrifugal module w. supp. bracket (2) kg Centrifugal module with cube design kg 24,6 64025-2-4013 K3G 500-AP25 -01 40,2 K3G 500-AP25 -31 40,2 K3G 500-AP25 -02 58,5 R3G 500-AP25 -68 24,6 64025-2-4013 K3G 500-AP25 -68 40,2 --- --- --- --- R3G 500-AQ31 -68 21,7 64025-2-4013 K3G 500-AQ31 -68 32,3 --- --- --- --- Centrifugal fan kg R3G 500-AP25 -01 (2) Centrifugal module with higher protection against corrosion Drawings p. 50 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 49 EC centrifugal fans – RadiPac backward curved, Ø 500 R3G 500-AP25-01 (Centrifugal fan) Accessory part: Inlet nozzle 64025-2-4013 not included in the standard scope of delivery (k-value: 281) 75 6xØ9 373.5 ±3 303.5 ±2 70 Depth of screw max. 25 mm 6xM10 220.5±1 6x6 Ø445 Ø470 Ø337.2 Ø566 Ø352.5 Ø188 0° Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø252±0,3 Ø275 12 150 220 Tightening torque 3.5±0.5 Nm K3G 500-AP25-01 / -31 (Centrifugal module with support bracket) 431.5±3 361.5±2 o630-1 o551 15 M 20 x (3 1.5 x) Ø11 (8x) Ø566 Observe the correct mounting position! Install the support struts only as shown in the view! o580 Pressure tap (k-value: 281) K3G 500-AP25-02 (Centrifugal module with cube design) Inlet nozzle with pressure tap (k-value: 281) *565 364 15 *96 473 4xØ9 *336 630 * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. 50 R3G 500-AP25-68 (Centrifugal fan) 6xØ9 373.5 ±3 303.5 ±2 70 Accessory part: Inlet nozzle 64025-2-4013 not included in the standard scope of delivery (k-value: 281) 75 Depth of screw max. 25 mm 6xM10 220.5±1 6x6 Ø445 Ø470 Ø337.2 Ø566 Ø352.5 Ø188 0° Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø252±0,3 Ø275 12 150 220 Tightening torque 3.5±0.5 Nm K3G 500-AP25-68 (Centrifugal module with support bracket) 431.5±3 361.5±2 o630-1 o551 15 20 x (3 1.5 x) M Ø11 (8x) Ø566 Observe the correct mounting position! Install the support struts only as shown in the view! o580 Pressure tap (k-value: 281) 51 EC centrifugal fans – RadiPac backward curved, Ø 500 R3G 500-AQ31-68 (Centrifugal fan) 450.5±3 337.5±2 6xØ9 113 Accessory part: Inlet nozzle 64025-2-4013 not included in the standard scope of delivery (k-value: 281) 75 6xM10 298.5±1 Depth of screw max. 20 mm Ø445 Ø470 Ø337 Ø352.5 Ø566 Ø188 0° 6x6 Tightening torque 3.5±0.5 Nm Ø280-2 Cable gland M20x1,5(2x) Cable gland M25x1,5(1x) 150 220.5 12 Ø304±0.5 K3G 500-AQ31-68 (Centrifugal module with support bracket) 15 o630-1 o520.5 Ø11(8x) 510 ±3 396.5 ±2 o580 Pressure tap (k-value: 281) 52 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 53 EC centrifugal fans – RadiPac backward curved, Ø 560 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. VAC Hz rpm W A °C 3~ 380-480 50/60 1610 3530 5,40 -25..+40 p. 89 / M3) 3~ 380-480 50/60 1750 4600 7,10 -25..+40 p. 89 / M3) Curve Nominal data Type Motor *3G 560 M3G 150-IF A *3G 560 M3G 150-NA B Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC 1400 in H2O subject to alterations Technical features and electr. connection – Material: Support bracket: Steel, coated in black; Support plate and inlet nozzle: Sheet steel, galvanised; Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings B 3 ηmax. = 4,8 4,0 A 1000 3,2 2,4 3 600 1,6 2 400 0,8 2 200 pfs 1 0 qV 2000 4000 4000 6000 8000 12000 1 cfm 8000 16000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 54 I A LWA dB(A) 1 1610 2247 3,48 94 A 2 1610 2951 4,55 88 A 3 1610 3530 5,40 82 A 4 1610 3241 4,97 86 B 1 1750 2938 4,47 95 B 2 1750 3704 5,59 89 B 3 1750 4600 7,10 84 B 4 1750 4271 6,42 87 3 4 800 Ped W A 4 1200 n rpm Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg 30,5 64030-2-4013 K3G 560-AP21 -68 56,1 40,0 64030-2-4013 K3G 560-AQ08 -68 69,7 Centrifugal fan kg R3G 560-AP21 -68 R3G 560-AQ08 -68 Drawings p. 56 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 ff. 55 EC centrifugal fans – RadiPac backward curved, Ø 560 R3G 560-AP21-68 (Centrifugal fan) 82 6xØ9 422 ±3 352 ±2 70 Accessory part: Inlet nozzle 64030-2-4013 not included in the standard scope of delivery (k-value: 348) Depth of screw max. 25 mm 6xM10 250.5±1 6x6 Ø490 Ø515 Ø385 Ø636 Ø395 Ø188 0° Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø252±0,3 Ø275 16 160 239 Tightening torque 3.5±0.5 Nm K3G 560-AP21-68 (Centrifugal module with support bracket) 483±3 413±2 o800-1 o555 15 20 x (3 1.5 x) M Ø11 (8x) Ø566 Observe the correct mounting position! Install the support struts only as shown in the view! o750 Pressure tap (k-value: 348) 56 R3G 560-AQ08-68 (Centrifugal fan) Accessory part: Inlet nozzle 64030-2-4013 not included in the standard scope of delivery (k-value: 348) 6xØ9 505±3 392±2 113 Depth of screw max. 20 mm 82 333±1 6xM10 Tightening torque 3.5±0.5 Nm 6x6 Ø490 Ø515 Ø385 Ø395 Ø636 Ø188 0° Ø280-2 Cable gland M20x1,5(2x) Cable gland M25x1,5(1x) 160 239 16 Ø304±0.5 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm K3G 560-AQ08-68 (Centrifugal module with support bracket) 15 o800-1 o570 Ø11(8x) 566 ±3 453 ±2 o750 Pressure tap (k-value: 348) 57 EC centrifugal fans – RadiPac backward curved, Ø 630 Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium Number of blades: 7 Direction of rotation: Clockwise, seen on rotor Type of protection: IP 54 (acc. to EN 60529) Insulation class: "F" Mounting position: Shaft horizontal ( B C for floor installation only) or rotor on bottom; rotor on top on request Condensate discharges: Rotor-side Mode of operation: Continuous operation (S1) Bearings: Maintenance-free ball bearings – – – – – Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. Mass VAC Hz rpm W A °C kg 3~ 380-480 50/60 1130 2900 4,50 -25..+55 40 p. 89 / M3) B 3~ 380-480 50/60 1500 6750 10,30 -25..+50 125 p. 89 / M3) C 3~ 380-480 50/60 1850 11000 17,00 -25..+40 160 p. 89 / M3) Curve Nominal data Type Motor *3G 630 M3G 150-NA A *3G 630 M3G 200-HF *3G 630 M3G 200-QA 1600 7,2 1800 3 C 4 ηmax. = 6,4 Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC in H2O subject to alterations C Nominal voltage range – – – B 5,6 1200 1000 B 4 4,0 1400 4,8 3 800 3,2 3 A 2 3 2 1,6 400 2,4 4 600 200 0,8 2 pfs 1 0 qV 2000 4000 5000 6000 10000 8000 15000 10000 12000 20000 1 14000 1 25000 cfm m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 58 Technical features and electr. connection – Material: n rpm Ped W I A LWA dB(A) A 1 1130 2155 3,26 88 A 2 1130 2834 4,30 81 A 3 1130 2900 4,50 78 A 4 1130 2461 3,73 79 B 1 1500 4523 7,00 97 B 2 1500 5763 8,87 92 B 3 1500 6750 10,30 88 B 4 1500 6333 9,69 88 C 1 1850 7459 11,55 101 C 2 1850 10040 15,39 96 C 3 1850 11000 17,00 91 C 4 1850 9894 15,15 92 Mass of centrifugal module with cube design Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: A Interference emission acc. to EN 61000-6-3 A Interference immunity acc. to EN 61000-6-2 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A UL, CSA, GOST; B C GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg 40,0 64070-2-4013 K3G 630-AP01 -01 77,5 --- --- --- --- --- --- --- K3G 630-AR02 -01 125,0 --- --- --- --- --- K3G 630-AS05 -01 160,0 Centrifugal fan kg R3G 630-AP01 -01 Drawings p. 60 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Centrifugal module with cube design Rubber mounting p. 85 kg Guard grille p. 86 Electr. connection p. 89 59 EC centrifugal fans – RadiPac backward curved, Ø 630 70 6xØ10.5 R3G 630-AP01-01 (Centrifugal fan) 359 ±2 Depth of screw max. 25 mm 98.5 6xM10 250.5±1 Ø600 Ø634 Ø433 Ø427 Ø716 Ø444 ±3.6 Ø188 0° 6x6 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 6 224 318.3 2 Ø252±0,3 Ø275 Tightening torque 3.5±0.5 Nm Accessory part: Inlet nozzle 63070-2-4013 not included in the standard scope of delivery (k-value: 438) Cable gland M20x1,5(3x) K3G 630-AP01-01 (Centrifugal module with support bracket) 508 ±3 439 ±2.5 o 800 o 652 20 Ø11 (8x) Observe the correct mounting position! Install the support struts only as shown in the view! M20x1.5(3x) o 750±1 Pressure tap (k-value: 438) 60 K3G 630-AR02-01 (Centrifugal module with cube design) 506 652.5 511.5 8xØ11 666 20 4xØ11 *674 4xØ11 *159 660 760 *451 Inlet nozzle with pressure tap (k-value: 438) Tightening torque 3,5±0.5 Nm * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm M25x1.5 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm K3G 630-AS05-01 (Centrifugal module with cube design) 506 8xØ11 666 20 711 570 4xØ11 4xØ11 *674 *169 660 760 *500 Inlet nozzle with pressure tap (k-value: 438) Tightening torque 3,5±0.5 Nm * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 6±0.6 Nm M25x1.5 Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6±0.6 Nm 61 EC centrifugal fans – RadiPac backward curved, Ø 710 Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium Number of blades: 7 Direction of rotation: Clockwise, seen on rotor Type of protection: IP 54 (acc. to EN 60529) Insulation class: "F" Mounting position: Shaft horizontal ( B C for floor installation only) or rotor on bottom; rotor on top on request Condensate discharges: Rotor-side Mode of operation: Continuous operation (S1) Bearings: Maintenance-free ball bearings – – – – – Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. Mass VAC Hz rpm W A °C kg 3~ 380-480 50/60 920 2800 4,30 -25..+40 44 p. 89 / M3) B 3~ 380-480 50/60 1300 7860 12,00 -25..+40 163 p. 89 / M3) C 3~ 380-480 50/60 1550 11800 18,00 -25..+40 194 p. 89 / M3) Curve Nominal data Type Motor *3G 710 M3G 150-NA A *3G 710 M3G 200-LA *3G 710 M3G 200-QA Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC in H2O subject to alterations C Nominal voltage range – – – B Technical features and electr. connection – Material: 1400 C 1 920 1824 2,72 84 A 2 920 2522 3,77 80 A 3 920 2800 4,30 78 A 4 920 2566 3,82 78 B 1 1300 5116 7,87 96 B 2 1300 6911 10,63 91 B 3 1300 7860 12,00 86 B 4 1300 7367 11,21 87 C 1 1550 7632 11,88 101 C 2 1550 10356 16,00 94 C 3 1550 11800 18,00 88 C 4 1550 11144 17,09 91 A 2,4 2 600 4 2 1,6 3 400 0,8 2 200 pfs 1 0 qV 5000 5000 10000 10000 15000 1 20000 25000 1 cfm 15000 30000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 62 LWA dB(A) 4,8 4,0 3,2 3 800 I A A 3 4 1000 Ped W 4 B 1200 n rpm ηmax. = 5,6 1600 6,4 3 Mass of centrifugal module with cube design Mass of centrifugal fan Mass of centrifugal module with support bracket – Technical features: See electrical connections p. 89 – EMC: A Interference emission acc. to EN 61000-6-3 A Interference immunity acc. to EN 61000-6-2 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A UL, CSA, GOST; B C GOST Inlet nozzle with one pressure tap Centrifugal module w. support bracket kg 44,0 64070-2-4013 K3G 710-AP02 -01 92,0 --- --- --- --- --- --- --- K3G 710-AR03 -01 163,0 --- --- --- --- --- K3G 710-AS06 -01 194,0 Centrifugal fan kg R3G 710-AP02 -01 Drawings p. 64 ff. Inlet nozzle p. 82 ff. Spring elements p. 84 Centrifugal module with cube design Rubber mounting p. 85 kg Guard grille p. 86 Electr. connection p. 89 63 EC centrifugal fans – RadiPac backward curved, Ø 710 R3G 710-AP02-01 (Centrifugal fan) 70 Depth of screw max. 25 mm 117 6xØ9 394 ±2 6xM10 250.5±1 Ø700 Ø720 Ø488 Ø470.3 Ø806 Ø501+4.6 Ø188 0° 6x6 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 15 250 354 2.5 Ø252±0,3 Ø275 Tightening torque 3.5±0.5 Nm Accessory part: Inlet nozzle 71075-2-4013 not included in the standard scope of delivery (k-value: 545) Cable gland M20x1,5(3x) K3G 710-AP02-01 (Centrifugal module with support bracket) 559 ±3 490 ±2.5 o 960 o 783 25 Ø11 (12x) Observe the correct mounting position! Install the support struts only as shown in the view! M20x1.5(3x) 600 ±1 o 880 ±1 Pressure tap (k-value: 545) 64 K3G 710-AR03-01 (Centrifugal module with cube design) 712.5 579.5 700 20xØ11 864 25 4xØ11 4xØ11 600 750 880 960 *337 *234 *884 Inlet nozzle with pressure tap (k-value: 545) Tightening torque 3,5±0.5 Nm * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. M20x1.5 (2x) M25x1.5 Cable diameter min. 4 mm, max. 10 mm, tightening torque4±0.6 Nm Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm K3G 710-AS06-01 (Centrifugal module with cube design) 700 20xØ11 864 25 759 621 4xØ11 *252.5 *884 *405 4xØ11 600 750 880 960 Inlet nozzle with pressure tap (k-value: 545) Tightening torque 3,5±0.5 Nm * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 6±0.6 Nm M25x1.5 Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6±0.6 Nm 65 EC centrifugal fans – RadiPac backward curved, Ø 800 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. Mass VAC Hz rpm W A °C kg 3~ 380-480 50/60 1050 7530 11,60 -25..+40 189 p. 89 / M3) 3~ 380-480 50/60 1370 11600 17,80 -25..+40 196 p. 89 / M3) Curve Nominal data Type Motor K3G 800-AR08 -01 M3G 200-QA A K3G 800-AS07 -01 M3G 200-QA B Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC in H2O subject to alterations 1200 ηmax. = 4,0 3,2 4 800 2,4 1,6 200 pfs 400 0,8 3 600 2 2 5000 0 qV Ped W I A LWA dB(A) A 1 1050 4907 7,58 94 A 2 1050 6555 10,10 88 A 3 1050 7530 11,60 85 A 4 1050 7183 11,02 85 B 1 1370 6755 10,53 106 B 2 1370 9619 14,77 98 B 3 1370 11600 17,80 90 B 4 1370 10690 16,37 93 3 A 1000 n rpm 4 5,6 1400 B 4,8 1600 6,4 3 5000 10000 15000 1 1 20000 15000 10000 20000 25000 30000 35000 cfm m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 66 Technical features and electr. connection – Material: Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal (for floor installation only) or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings – – – – – – Technical features: See electrical connections p. 89 Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) Terminal box design: Electrical connection via terminal strip Protection class: I (if customer has provided connection for protective earth) Product conforming to standards: EN 61800-5-1, CE Approvals: GOST Drawings p. 68 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 67 EC centrifugal fans – RadiPac backward curved, Ø 800 K3G 800-AR08-01 (Centrifugal module with cube design) 783 650 700 20xØ11 864 25 4xØ11 600 750 880 960 4xØ11 *884 Inlet nozzle with pressure tap (k-value: 695) * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. *251.5 *430 Tightening torque 3,5±0.5 Nm M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 68 M25x1.5 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm K3G 800-AS07-01 (Centrifugal module with cube design) 700 20xØ11 864 25 759 621 4xØ11 *884 *252.5 *405 4xØ11 600 750 880 960 Inlet nozzle with pressure tap (k-value: 695) * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. Tightening torque 3,5±0.5 Nm M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 6±0.6 Nm M25x1.5 Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6±0.6 Nm 69 EC centrifugal fans – RadiPac backward curved, Ø 900 Nominal voltage range Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. Mass VAC Hz rpm W A °C kg 3~ 380-480 50/60 860 7520 11,50 -25..+40 222 p. 89 / M3) 3~ 380-480 50/60 1050 8700 13,50 -25..+40 232 p. 89 / M3) Curve Nominal data Type Motor K3G 900-AR10 -01 M3G 200-QA A K3G 900-AS08 -01 M3G 200-QA B Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC 1200 4,8 in H2O subject to alterations Technical features and electr. connection – Material: Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal (for floor installation only) or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings 3 B 3 3,2 4 2,4 3 600 1,6 2 400 pfs 0,8 2 200 5000 0 qV 5000 10000 15000 1 20000 15000 10000 20000 25000 30000 35000 1 cfm m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 70 I A LWA dB(A) A 1 860 5028 7,72 92 A 2 860 6750 10,33 87 A 3 860 7520 11,50 82 A 4 860 7015 10,72 81 B 1 1050 5036 8,03 99 B 2 1050 7329 11,42 91 B 3 1050 8700 13,50 86 B 4 1050 7744 12,03 87 A 800 Ped W 4 4,0 1000 n rpm ηmax. = – – – – – – Technical features: See electrical connections p. 89 Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) Terminal box design: Electrical connection via terminal strip Protection class: I (if customer has provided connection for protective earth) Product conforming to standards: EN 61800-5-1, CE Approvals: GOST Drawings p. 72 ff. Spring elements p. 84 Rubber mounting p. 85 Guard grille p. 86 Electr. connection p. 89 71 EC centrifugal fans – RadiPac backward curved, Ø 900 K3G 900-AR10-01 (Centrifugal module with cube design) 930 24xØ11 1084 30 745 612 4xØ11 *1104 Inlet nozzle with pressure tap (k-value: 900) * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. *203.5 4xØ11 Tightening torque 3,5±0.5 Nm M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 72 400 800 950 1100 1180 *440 M25x1.5 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm K3G 900-AS08-01 (Centrifugal module with cube design) 930 24xØ11 1084 30 657 519 4xØ11 *1104 Inlet nozzle with pressure tap (k-value: 900) * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. *181 *375 4xØ11 400 800 950 1100 1180 Tightening torque 3,5±0.5 Nm M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 6±0.6 Nm M25x1.5 Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6±0.6 Nm 73 EC centrifugal fans – RadiPac backward curved, Ø Z50 Hz rpm W A °C kg 50/60 380 3560 5,40 -25..+40 350 3~ 380-480 A p. 89 / M3) Pa (1) Nominal data in operating point with maximum load and 400 VAC Curves A 250 n rpm ηmax. = 1,2 3 4 1,0 300 200 0,8 150 0,6 3 0,4 50 pfs 100 0,2 2 0 qV 5000 10000 10000 20000 15000 20000 30000 25000 40000 1 30000 cfm 50000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 74 Technical features and electr. connection Mass VAC in H2O subject to alterations Perm. amb. temp. M3G 200-QA Max. current draw(1) K3G Z50-AQ11 -01 Max. input power(1) Motor Speed/rpm(1) Type Frequency Nominal data Nominal voltage range Curve – Material: Cube design with inlet nozzle: Sheet steel, galvanised and plastic-coated in light grey (RAL 7035) Impeller: Sheet aluminium Rotor: Coated in black; Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "F" – Mounting position: Shaft horizontal (for floor installation only) or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Ped W I A LWA dB(A) A 1 380 2250 3,40 81 A 2 380 3180 4,60 74 A 3 380 3560 5,40 73 A 4 380 3340 4,90 73 – – – – – – Technical features: See electrical connections p. 89 Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) Terminal box design: Electrical connection via terminal strip Protection class: I (if customer has provided connection for protective earth) Product conforming to standards: EN 61800-5-1, CE Approvals: GOST Drawings p. 76 Electr. connection p. 89 75 EC centrifugal fans – RadiPac backward curved, Ø Z50 K3G Z50-AQ11-01 (Centrifugal module with cube design) 974.3 797.3 30 *1424 *277.3 *566 24xØ11 4xØ11 1500 Tightening torque 3,5±0.5 Nm Inlet nozzle with pressure tap (k-value: 1730) * Screw-on position for rubber mounting respectively spring elements; with horizontal shaft position, only direct installation on the floor possible and permitted. 76 M20x1.5 (2x) Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm M25x1.5 Cable diameter min. 9 mm, max. 16 mm, tightening torque 6±0.9 Nm 77 EC centrifugal fans – RadiPac backward curved, Ø 280 - 450 (compact design) Frequency Speed/rpm(1) Max. input power(1) Max. current draw(1) Perm. amb. temp. Mass VAC Hz rpm W A °C kg 3~ 380-480 50/60 3260 985 1,60 -25..+60 7,1 p. 90 / L6) B 3~ 380-480 50/60 3170 1650 2,50 -25..+50 12,1 p. 89 / M3) M3G 112-GA C 3~ 380-480 50/60 2650 1730 2,60 -25..+60 12,6 p. 89 / M3) R3G 400-AS23 -01 M3G 150-FF D 3~ 380-480 50/60 2550 2840 4,20 -25..+60 21,3 p. 89 / M3) R3G 450-AS24 -01 M3G 150-FF E 3~ 380-480 50/60 2040 2380 3,60 -25..+60 22,0 p. 89 / M3) Curve Nominal voltage range Technical features and electr. connection – Material: Impeller: Sheet aluminium Rotor: Coated in black Electronics enclosure: Die-cast aluminium – Number of blades: 7 – Direction of rotation: Clockwise, seen on rotor – Type of protection: IP 54 (acc. to EN 60529) – Insulation class: "B" – Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request – Condensate discharges: Rotor-side – Mode of operation: Continuous operation (S1) – Bearings: Maintenance-free ball bearings Nominal data Type Motor R3G 280-AJ14 -C1 M3G 084-GF A R3G 310-BC38 -01 M3G 112-GA R3G 355-BD43 -01 Curves Pa (1) Nominal data in operating point with maximum load and 400 VAC 1400 5,6 in H2O subject to alterations ηmax. = 3 4,8 4 1000 4,0 4 4 3 3,2 3 3 C 2,4 B 1 3260 703 1,31 89 2 3260 877 1,57 86 A 3 3260 985 1,60 84 A 4 3260 873 1,57 85 B 1 3170 1230 1,83 90 B 2 3170 1523 2,27 88 B 3 3170 1650 2,50 85 B 4 3170 1540 2,30 88 C 1 2650 1248 1,86 90 C 2 2650 1561 2,33 86 C 3 2650 1730 2,60 84 C 4 2650 1629 2,42 86 D 1 2550 2095 3,13 92 D 2 2550 2594 3,84 89 D 3 2550 2840 4,20 86 D 4 2550 2675 3,95 89 E 1 2040 1641 2,48 90 E 2 2040 2156 3,23 85 E 3 2040 2380 3,60 82 E 4 2040 2171 3,24 86 E D A 2 2 2 2 0,8 pfs 200 1,6 2 400 0 qV 500 1000 1000 2000 1500 1 2000 3000 1 2500 4000 3000 5000 1 3500 6000 1 4000 7000 4500 8000 5000 1 5500 cfm 9000 m3/h Air performance measured as per: ISO 5801, Installation category A, with ebm-papst inlet nozzle without protection against accidental contact. Suction-side noise levels: LWA as per ISO 13347, LpA measured at 1 m distance to fan axis. The acoustic values given are only valid under the measurment conditions listed and may vary depending on the installation situation. With any deviation to the standard setup, the specific values have to be checked and reviewed once installed or fitted! For detailed information see page 94 ff. 78 LWA dB(A) A 3 600 I A 3 4 800 Ped W A 4 1200 n rpm – Technical features: See electrical connections p. 89 – EMC: Interference emission acc. to EN 61000-6-3 Interference immunity acc. to EN 61000-6-2 Harmonics acc. to EN 61000-3-2/3 – Touch current: : < 3,5 mA acc. to IEC 60990 (test circuit, illustration 4) – Terminal box design: Electrical connection via terminal strip – Protection class: I (if customer has provided connection for protective earth) – Product conforming to standards: EN 61800-5-1, CE – Approvals: A VDE, UL, CSA, CCC, GOST are applied for; B C VDE, GOST; D E UL, CSA, GOST Drawings p. 80 ff. Inlet nozzle p. 82 ff. Guard grille p. 86 Electr. connection p. 89 ff. 79 EC centrifugal fans – RadiPac backward curved, Ø 280 - 450 (compact design) 56.5 4x Ø4.5 R3G 280-AJ14-C1 (Centrifugal fan) 152.4±2 5x 72 53 ° Depth of screw 12-16 mm Cable gland M16x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 2.5±0.4 Nm Ø280 Ø325 Ø187.2 Ø197.4 0 Ø284 Ø197 Ø165±0.25 Ø130 +1.8 Ø5.5 Tightening torque 3.5±0.5 Nm Ø186±0,5 90 126 Accessory part: Inlet nozzle 28075-2-4013 not included in the standard scope of delivery (k-value: 93) 6 60 170.2 ±2 4xØ4.5 R3G 310-BC38-01 (Centrifugal fan) Accessory part: Inlet nozzle 31575-2-4013 not included in the standard scope of delivery (k-value: 116) 55 Depth of screw max. 20 mm 6xM10 Ø325 Ø350 Ø 222 +2 Ø 319 Ø211.7 0° 6x6 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 100 147 Tightening torque 3.5±0.5 Nm Ø 252±0.5 6 60 187.2 ±2 4xØ4.5 R3G 355-BD43-01 (Centrifugal fan) Accessory part: Inlet nozzle 35675-2-4013 not included in the standard scope of delivery (k-value: 148) 64.4 Depth of screw max. 20 mm 6xM10 Ø345 Ø370 Ø 250.3 +2.3 Ø 360 Ø239 0° 6x6 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø 232 112 164 80 6 Ø 252±0.5 Tightening torque 3.5±0.5 Nm R3G 400-AS23-01 (Centrifugal fan) 6xØ9 289.5 ±3 228.5 ±2 70 Accessory part: Inlet nozzle 40075-2-4013 not included in the standard scope of delivery (k-value: 188) 68 Depth of screw max. 25 mm 14xM10 45 8x 220.5±1 6x60 ° Ø390 Ø413 Ø404 Ø270.9 22.5° Ø282 ° Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm Ø252±0,3 Ø275 9 125 182 Tightening torque 3.5±0.5 Nm R3G 450-AS24-01 (Centrifugal fan) 320.2 ±3 250.2 ±2 6xØ9 70 Accessory part: Inlet nozzle 45075-2-4013 not included in the standard scope of delivery (k-value: 240) 76 Depth of screw max. 25 mm 14xM10 6x60 ° Ø430 Ø480 Ø303.4 Ø455 22.5° Ø317 ° 45 8x 220.5±1 Ø232-2 Cable gland M20x1,5 (3x): Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm 140 204 9 Ø252±0,3 Ø275 Tightening torque 3.5±0.5 Nm 81 Inlet nozzles Vers. 1 - Material: galvanised sheet steel Vers. 2 6x6 0° ° 90 4x Inlet nozzles without measuring device for backward curved centrifugal fans Part no. Size Vers. For dimensions, see 25070-2-4013 250 1 page 14 28070-2-4013 280 1 page 20 31570-2-4013 310 1 page 26 35670-2-4013 355 1 page 32 40070-2-4013 400 2 page 38 45070-2-4013 450 2 page 44 63072-2-4013 500 2 page 50 63071-2-4013 560 2 page 56 63070-2-4013 630 2 page 60 71070-2-4013 710 2 page 64 subject to alterations Effects of installation space Curve: might be reduced. 1,00 When mounting our product in a rectangular box, air performance 0,99 B Formula: dh = 2 x B x H / (B + H) B = Width of box H = Height of box D = Outer diameter of the fan 82 0,96 0,95 0,94 0,93 0,92 Correction factor for air flow dh = Hydraulic diameter D D 0,5xD H 0,97 0,98 D 1,4 1,6 1,8 Hydraulic diameter dh/D 2,0 2,2 2,4 2,6 2,8 Inlet nozzles with measuring device Vers. 3 (with one pressure tap) - Material: galvanised sheet steel Vers. 4 (with piezometer ring) Inlet nozzles with measuring device to determine air flow for backward curved centrifugal fans Part no. Part no. Size Vers. For dimensions, see (4) 250 3/4 page 14 (4) 280 3/4 page 20 31575-2-4013(3) / 31580-2-4013(4) 310 3/4 page 26 35675-2-4013(3) / 35680-2-4013(4) 355 3/4 page 32 (4) 400 3/4 page 38 45075-2-4013(3) / 45080-2-4013(4) 450 3/4 page 44 64025-2-4013(3) / 64002-2-4013(4) 500 3/4 page 50 (4) 560 3/4 page 56 64040-2-4013(3) / 64000-2-4013(4) 630 3/4 page 60 71075-2-4013(3) / 71080-2-4013(4) 710 3/4 page 64 (3) 25075-2-4013 (3) 28075-2-4013 (3) 40075-2-4013 (3) 64030-2-4013 subject to alterations / 25080-2-4013 / 28080-2-4013 / 40080-2-4013 / 64001-2-4013 (3) with one pressure tap (4) with piezometer ring (4 pressure taps connected by tubing) Air flow determination qV = k . Δp 0,5xD D The differential pressure approach compares the static pressure before the inlet nozzle with the static pressure inside the inlet nozzle. Air flow can be calculated on the basis of the differential pressure (difference in pressure of the static pressures) in keeping with the following equation: qV in [m3/h] und Δp in [Pa] k takes into account the specific nozzle characteristics. Differences in static pressure are measured in 1/4 measuring point(s) along the circumference of the inlet nozzle. Connection on the customer side is acomplished via a pre-mounted T tube connector. This tube connector is suited for pneumatic hoses with an internal diameter of 4 mm. Δp If constant air flow is to be controlled to, then the nozzle pressure has to be kept constant: Δp = qV2 : k2 k-values: (for RadiPac inlet nozzles) Size 250 280 310 355 400 450 500 k-value 70 93 116 148 188 240 281 Size 560 630 710 800 900 Z50 k-value 348 438 545 695 900 1730 83 Spring elements - Packaging: part numbers refer to one set consisting of 4 x spring elements. Vers. 2 *94 *57 Vers. 1 Delivered in cardboard box. Ø70 Ø52 M8 M10 * unloaded Spring elements Order no. (set) Type 11001-4-5142 K3G 250-AT39-89 1 360 rpm 14,1 mm 11001-4-5142 K3G 250-AV29-B9 1 340 rpm 16,0 mm 11001-4-5142 K3G 280-AT04-89 1 340 rpm 16,4 mm 11001-4-5142 K3G 280-AU06-B3 1 330 rpm 16,5 mm 11001-4-5142 K3G 280-AU11-C9 1 320 rpm 18,2 mm 11003-4-5142 K3G 310-AX52-96 1 420 rpm 10,3 mm 11003-4-5142 K3G 310-AX54-98 1 390 rpm 12,2 mm 11003-4-5142 K3G 310-BB49-96 1 380 rpm 13,1 mm 11003-4-5142 K3G 310-AZ88-96 1 360 rpm 14,2 mm 11003-4-5142 K3G 355-AX56-96 1 420 rpm 10,5 mm 11003-4-5142 K3G 355-AY43-98 1 370 rpm 13,8 mm 11003-4-5142 K3G 355-AY40-96 1 370 rpm 13,6 mm 11003-4-5142 K3G 400-AY87-96 1 350 rpm 15,2 mm 11005-4-5142 K3G 450-AY86-96 1 470 rpm 8,1 mm 11005-4-5142 K3G 400-AQ23-02 1 430 rpm 10,1 mm 11005-4-5142 K3G 450-AQ24-02 1 390 rpm 12,1 mm 11005-4-5142 K3G 500-AP25-02 1 380 rpm 12,5 mm 11012-4-5142 K3G 630-AR02-01 2 270 rpm 25,7 mm 11013-4-5142 K3G 630-AS05-01 2 330 rpm 17,3 mm 11013-4-5142 K3G 710-AR03-01 2 310 rpm 19,5 mm 11013-4-5142 K3G 710-AS06-01 2 300 rpm 20,3 mm 11013-4-5142 K3G 800-AR08-01 2 280 rpm 23,1 mm 11013-4-5142 K3G 800-AS07-01 2 280 rpm 23,1 mm 11014-4-5142 K3G 900-AR10-01 2 320 rpm 17,8 mm 11014-4-5142 K3G 900-AS08-01 2 320 rpm 17,8 mm subject to alterations 84 Vers. Minimum speed Spring deflection Rubber mounting - Packaging: Part numbers refer to one set consisting of 4 x rubber stops, washers and nuts. L G T H Delivered in plastig bag. G D Rubber mounting Order no. (set) Type Minimum speed 10001-4-5164 K3G 250-AT39-89 1250 rpm 10001-4-5164 K3G 250-AV29-B9 10001-4-5164 K3G 280-AT04-89 10001-4-5164 Spring deflection D G H L T 0,9 mm 15 M4 25 10 5 1170 rpm 1,0 mm 15 M4 25 10 5 1160 rpm 1,0 mm 15 M4 25 10 5 K3G 280-AU06-B3 1150 rpm 1,0 mm 15 M4 25 10 5 10001-4-5164 K3G 280-AU11-C9 1100 rpm 1,1 mm 15 M4 25 10 5 10002-4-5164 K3G 310-AX52-96 1390 rpm 0,7 mm 20 M6 25 18 6 10002-4-5164 K3G 310-AX54-98 1270 rpm 0,9 mm 20 M6 25 18 6 10002-4-5164 K3G 310-BB49-96 1230 rpm 0,9 mm 20 M6 25 18 6 10002-4-5164 K3G 310-AZ88-96 1180 rpm 1,0 mm 20 M6 25 18 6 10002-4-5164 K3G 355-AX56-96 1370 rpm 0,7 mm 20 M6 25 18 6 10002-4-5164 K3G 355-AY43-98 1190 rpm 1,0 mm 20 M6 25 18 6 10002-4-5164 K3G 355-AY40-96 1210 rpm 0,9 mm 20 M6 25 18 6 10002-4-5164 K3G 400-AY87-96 1140 rpm 1,1 mm 20 M6 25 18 6 10002-4-5164 K3G 450-AY86-96 980 rpm 1,4 mm 20 M6 25 18 6 10003-4-5164 K3G 400-AQ23-02 950 rpm 1,5 mm 25 M8 25 20 8 10003-4-5164 K3G 450-AQ24-02 870 rpm 1,8 mm 25 M8 25 20 8 10003-4-5164 K3G 500-AP25-02 860 rpm 1,8 mm 25 M8 25 20 8 10005-4-5164 K3G 630-AR02-01 680 rpm 2,9 mm 40 M10 40 28 10 10006-4-5164 K3G 630-AS05-01 740 rpm 2,4 mm 50 M10 50 28 10 10005-4-5164 K3G 710-AR03-01 620 rpm 3,5 mm 40 M10 40 28 10 10006-4-5164 K3G 710-AS06-01 680 rpm 2,9 mm 50 M10 50 28 10 10005-4-5164 K3G 800-AR08-01 570 rpm 4,1 mm 40 M10 40 28 10 10006-4-5164 K3G 800-AS07-01 640 rpm 3,3 mm 50 M10 50 28 10 10005-4-5164 K3G 900-AR10-01 520 rpm 5,0 mm 40 M10 40 28 10 10006-4-5164 K3G 900-AS08-01 580 rpm 3,9 mm 50 M10 50 28 10 subject to alterations 85 Air intake guard grilles Vers. 1 Vers. 2 b a a Ød Ød Ød a e - Material: steel wire, plastic coated Vers. 3 e b e b Air intake guard grilles for backward curved centrifugal fans (according to EN ISO 13857) Part no. Size Vers. a b d e Strut pitch 78129-2-4039 250 1 260 4,5 210 2,8 4 x 90° 78130-2-4039 280 1 280 4,5 230 2,8 4 x 90° 78131-2-4039 310 1 325 4,5 250 2,8 4 x 90° 78132-2-4039 355 1 345 4,5 310 2,8 4 x 90° 78133-2-4039 400 2 390 8,5 350 3,8 3 x 120° 78134-2-4039 450 2 430 8,5 410 3,8 3 x 120° 78139-2-4039 500 2 445 8,5 410 3,8 3 x 120° 78137-2-4039 560 3 490 8,5 430 3,8 6 x 60° 78138-2-4039 630 2 600 8,5 490 3,8 3 x 120° 78141-2-4039 710 3 700 8,5 598 4,8 6 x 60° 78141-2-4039 800 3 700 8,5 598 4,8 6 x 60° 78142-2-4039 900 3 850 8,5 680 4,8 6 x 60° subject to alterations 86 87 Electrical connections EC K1) Technical features: • PFC (passive) • Control input 0-10 VDC / PWM • Output 10 VDC max. 1,1 mA • Alarm relay • Over-temperature protected electronics / motor Notes on various control possibilities and their applications Umin = 15 V Imax = 10 mA Mains 50/60 Hz L black N blue PE green/yellow + - NC white1 + white2 Voltage output red +10 V max. 1.1 mA U PWM - 10 K 12 V Alarm relay: Break for failure (2 A, 250 VAC, AC1) Lin/PWM control input yellow 0-10 VDC / PWM 1 μF GND blue Speed setting PWM 1 - 10 kHz Speed setting with variable resistance Speed setting Full speed 1 V - 10 V 10 V -> n=max approx. 1 V -> n=min < 1 V -> n=0 100% PWM -> n=max approx. 10% PWM -> n=min < 10% PWM -> n=0 start up at > 1.4 V start up at > 14 % Customer circuit Connection +10 V 0-10 V PWM GND green/yellow white1 COM blue Line 2 NC N black PE L Line 1 Fan white2 red yellow blue Line Connection Colour Assignment / function Line Connection Colour Assignment / function 1 L black Mains 50/60 Hz, phase 2 +10 V N blue Mains 50/60 Hz, neutral 0-10 V / PWM yellow Control input (Impedance 100 kΩ) PE NC green/yel white1 Protective earth GND GND COM white2 88 Status relay, floating status contact, break with error Status relay, floating status contact, changeover contact, common connection (2 A, 250 V, min. 10 mA, AC1) red blue Voltage output +10 V max. 1.1 mA Electrical connections EC M3) Motor current limitation, Alarm relay Line undervoltage / phase failure detection Over-temperature protected electronics / motor Reverse polarity and locked-rotor protection, Soft start External 24 V input (programming) External release input Operation and alarm display Control interface with SELV potential safely disconnected from the mains KL3 KL2 KL1 Ain2 I Aout Ain1 I Din1 NO COM NC 2 3 4 5 6 7 1 2 3 L3 +20 V +10 V 1 L2 Ain2 U Ain1 U 14 GND 13 GND 12 Din3 11 RS B 10 Din2 9 RS A 8 L1 • • • • • • • • PE Technical features: • PFC (passive) • integrated PID controller • Control input 0-10 VDC / PWM • Input for sensor 0-10 V or 4-20 mA • Slave output 0-10 V max. 5 mA • Output 20 VDC (±20 %) max. 50 mA • Output 10 VDC (+10 %) max. 10 mA • RS485 MODBUS-RTU 1 2 3 Connector Pin Connection Assignment / function KL1 1 L1 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz 2 L2 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz 3 L3 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz PE Earth connection, PE connection 1 NO Status relay, floating status contact, close with error 2 COM Status relay, floating status contact, changeover contact, common connection (2 A, 250 V, min. 10 mA, AC1) 3 NC Status relay, floating status contact, break with error 1 RSA Bus connection RS485; RSA; MODBUS RTU 2 RSB Bus connection RS485; RSB; MODBUS RTU 3/10 GND Signal ground for control interface 4 Ain1 U Analogue input 1 (set value); 0-10 V; Ri= 100 kΩ; parametrisable curves; only usable as alternative to input Ain1 I 5 +10 V Fixed voltage output 10 VDC; +10 V ±3 %; max. 10 mA; short circuit proof; power supply for ext. devices (e.g. potentiometer) 6 7 Ain1 I Din1 Analogue input 1 (set value); 4-20 mA; Ri= 100 Ω; parametrisable curve; only usable as alternative to input Ain1 U PE KL2 KL3 Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridge to GND or applied voltage < 1 VDC; reset function: triggers software reset after a level change to < 1V 8 Din2 Digital input 2: parameter set switch 1/2; according to EEPROM setting, thr valid/used parameter set is selectable per BUS or per digital input Din2. Parameter set 1: open oin or applied voltage 5 to 50 VDC; parameter set 2: bridge to GND or applied voltage < 1 VDC 9 Din3 Digital input 3: Control characteristic of the integrated controller; according to EEPROM setting, the control characteristic of the integrated controller is normally/inversely selectable per BUS or per digital input; normal: open pin or applied voltage 5 to 50 VDC (control deviation = actual sensor value - set value); inverse: bridge to GND or applied voltage < 1 VDC control deviation = set value - actual sensor value) 11 Ain2 U Analogue input 2; actual sensor value 0-10 V; Ri= 100 kΩ; parametrisable curve; only usable as alternative to input Ain2 I 12 +20 V Fixed voltage output 20 VDC; +20 V +25/-10 %; max. 50 mA; short circuit proof; power supply for ext. devices (e.g. sensors) 13 14 Ain2 I Aout Analogue input 2; actual sensor value 4-20 mA; Ri= 100 Ω; parametrisable curve; only usable as alternative to input Ain2 U Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/of the actual motor speed; function selectable per BUS; parametrisable curve 89 Electrical connections EC L6) Alarm relay Line undervoltage / phase failure detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start L1 PE KL1 NC COM NO OUT GND +10 V 0-10 V PWM +20 V KL2 4-20 mA GND 0-10 V PWM RS B RS A RS B RS A KL3 L3 • • • • • • L2 Technical features: • PFC (passive) • Integrated PID controller • Control input 0-10 VDC / PWM • Input for sensor 0-10 V or 4-20 mA • Slave output 0-10 V max. 3 mA • Output 20 VDC (±20 %) max. 50 mA • Output 10 VDC (+10 %) max. 10 mA • RS485 MODBUS Connector Connection Assignment / function Connector Connection Assignment / function PE KL1 KL3 KL2 PE Protective earth OUT Master output 0-10 V max. 5 mA L3 Mains; L3 GND GND L2 Mains; L2 L1 NC Mains; L1 Status relay, floating status contact, break with error 0-10 V / PWM Control / Actual value input (Impedance 100 kΩ) +10 V Supply for external potentiometer, COM Status relay, floating status contact, changeover contact, common connection (2 A, 250 V, min. 10 mA, AC1) +20 V NO Status relay, floating status contact, close with error 4-20 mA 10 VDC (±3 %), max. 10 mA Supply for external sensor, 20 VDC (+25 % / -10 %), max. 50 mA Control / Actual value input 0-10 V / PWM Control / Actual value input (Impedance 100 kΩ) 90 GND GND RSB RS485 interface for MODBUS RTU; RSB RSA RS485 interface for MODBUS RTU; RSA RSB RS485 interface for MODBUS RTU; RSB RSA RS485 interface for MODBUS RTU; RSA Electrical connections EC L7) Alarm relay Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start KL1 L NC COM NO OUT GND +10 V 0-10 V PWM +20 V KL2 4-20 mA GND 0-10 V PWM RS B RS A RS B RS A KL3 PE • • • • • • N Technical features: • PFC (active) • Integrated PID controller • Control input 0-10 VDC / PWM • Input for sensor 0-10 V or 4-20 mA • Slave output 0-10 V max. 3 mA • Output 20 VDC (±20 %) max. 50 mA • Output 10 VDC (+10 %) max. 10 mA • RS485 MODBUS Connector Connection Assignment / function Connector Connection Assignment / function PE KL1 KL3 KL2 PE Protective earth OUT Master output 0-10 V max. 3 mA N Mains 50/60 Hz. neutral GND GND L NC Mains 50/60 Hz, phase Status relay, floating status contact, break with error 0-10 V / PWM Control / Actual value input (Impedance 100 kΩ) COM Status relay, floating status contact, changeover contact, common connection (2 A, 250 V, min. 10 mA, AC1) NO +10 V Supply for external potentiometer, 10 VDC (+10 %) max. 10 mA +20 V Status relay, floating status contact, close with error Supply for external sensor, 20 VDC (±20 %) max. 50 mA 4-20 mA Control / Actual value input 0-10 V / PWM Control / Actual value input (Impedance 100 kΩ) GND GND RSB RS485 interface for MODBUS RTU; RSB RSA RS485 interface for MODBUS RTU; RSA RSB RS485 interface for MODBUS RTU; RSB RSA RS485 interface for MODBUS RTU; RSA 91 Electrical connections EC L9) Alarm relay Line undervoltage detection Motor current limitation Over-temperature protected electronics / motor Locked-rotor protection Soft start +20 V Ain2 I Aout +10 V Ain1 I Din1 N Ain2 U Ain1 U L1 GND GND KL1 PE Din3 RS B NO Din2 KL2 RS A KL3 NC • • • • • • COM Technical features: • PFC (active) • Integrated PID controller • Control input 0-10 VDC / PWM • Input for sensor 0-10 V or 4-20 mA • Slave output 0-10 V max. 3 mA • Output 20 VDC (±20 %) max. 50 mA • Output 10 VDC (+10 %) max. 10 mA • RS485 MODBUS Connector Connection Assignment / function Connector Connection Assignment / function KL1 KL3 PE KL2 Din1 N Mains; neutral L1 Mains; L1 PE NC Protective earth Status relay, floating status contact, break with error Ain1 I Analogue set value input, 4-20 mA (impedance 100 Ω), COM Status relay, floating status contact, changeover contact, common connection (2 A, 250 V, min. 10 mA, AC1) +10 V Supply for external potentiometer, NO Digital input 1 (enabling / disabling of electronics), Enabling: Pin open or applied voltage 5 to 50 VDC Disabling: Bridge to GND or applied voltage < 1 VDC only to be used as alternative to terminal Ain1 U Status relay, floating status contact, close with error 10 VDC (±3 %) max. 10 mA Ain1U Analogue set value input, 0-10 V (impedance 100 kΩ), GND GND RSB RS485 interface for MODBUS RTU; RSB RSA Aout RS485 interface for MODBUS RTU; RSA only to be used as alternative to terminal Ain1 I Analogue output 0-10 V max. 5 mA, reading of current motor speed / current motor control factor Ain2 I Analog. actual value input, 4-20mA (impedance 100Ω), +20 V Supply for external sensor, only to be used as alternative to terminal Ain2 U 20 VDC (+25 % / -10%) max. 40 mA Ain2 U Analog. actual value input, 0-10 V (impedance 100 kΩ), GND Din3 GND only to be used as alternative to terminal Ain2 I Digital input 3 (switch Normal / Inverse), The preset effective direction of the integrated controller can be selected via BUS or via digital input Normal/Inverse. Normal: Pin open or applied voltage 5 to 50 VDC Inverse: Bridge to GND or applied voltage < 1 VDC Din2 Digital input 2 (switch Day / Night), The preset set of parameters can be selected via BUS or via digital input Day/Night. Day: Pin open or applied voltage 5 to 50 VDC Night: Bridge to GND or applied voltage < 1 VDC 92 Electrical connections EC P2) Motor current limitation, Alarm relay Line undervoltage / phase failure detection Over-temperature protected electronics / motor Locked-rotor protection, Soft start Control interface with SELV potential safely disconnected from the mains 11 10 1-10V 2 3 10V -> n = max 1V -> n = min <1V -> n = 0 9 8 7 6 5 4 3 2 Speed setting with potentiometer Set value e.g. for pressure 5 10K 4-20mA 1 4 3 3/7 2 2 6 1 3 2 1 RSB RSA RSA RSB RSB GND 0-10V/PWM IN 47K I 4-20mA 1 O +20V/50mA 20V +10V/10mA 10V 33 0-10V/PWM 100 GND 47K 2.2μF OUT KL2 NO OUT GND A2 12 3/7 4 KL3 RSA COM NC A1 Speed setting 14 12 Full Speed • • • • • 11 Technical features: • PFC (passive) • integrated PID controller • Control input 0-10 VDC / PWM • Input for sensor 0-10 V or 4-20 mA • Slave output 0-10 V max. 5 mA • Output 20 VDC (±25 % / -10 %) max. 50 mA • Output 10 VDC (+3 %) max. 10 mA • External 24 V input (programming) • RS485 MODBUS RTU KL1 L1 P L2 N L3 PE PE Customer circuit PE Connection Fan Connector Pin Connection Assignment / function PE PE Earth connection, PE connection 1/2/3 L1, L2, L3 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz 1 NC Status relay, floating status contact; option 1: break with error; option 2: break with error for run monitor error message 2 COM Status relay, floating status contact; changeover contact; common connection (2 A, 250 V, min. 10 mA, AC1) 3 1 NO OUT Status relay, floating status contact; option 1: close with error; option 2: close with run monitor error message 2/8 GND Signal ground for control interface KL3; SELV 3/7 0-10 V Control input 0-10 VDC, impedance 100 kΩ; only usable as alternative to 4-20 mA input, SELV 4 +10 V Fixed voltage output 10 VDC (±3 %), max. 10 mA; power supply for ext. devices (e.g. potentiometer), SELV 5 +20 V Fixed voltage output 20 VDC (+25 % / -10 %), max. 50 mA; power supply for ext. devices (e.g. sensors), SELV 6 4-20 mA Control input 4-20 mA, impedance 100 Ω; only usable as alternative to 0-10 V input, SELV 9/11 RSB RS485 interface for MODBUS RTU; RSB 10/12 RSA RS485 interface for MODBUS RTU; RSA KL1 KL2 KL3 Analogue output 0-10 V; max. 5 mA, SELV, output of the actual motor duty cycle (PWM): 1 V corresponds to 10 % PWM, 10 V corresponds to 100 % PWM 93 Technical parameters & scope High standards for all ebm-papst products Here at ebm-papst, we constantly strive to further improve our products in order to be able to offer you the best possible product for your application. Careful monitoring of the market ensures that technical innovations are reflected in the improvements of our products. Based on the technical parameters listed below and the ambience you want our product to operate in, we here at ebm-papst can always work out the best solution for your specific application.. General performance parameters The majority of our products use maintenance-free ball bearings for Any deviations from the technical data and parameters described here any mounting position possible. As an option, sleeve bearings can be are listed on the product-specific data sheet. used, which is indicated on the product-specific data sheet wherever Type of protection The type of protection is specified in the product-specific data sheets. applicable. The service life L10 of the ball bearings can be taken as approx. 40,000 operating hours at an ambient temperature of 40 °C, yet this estimate Insulation class can vary according to the actual ambient conditions. The insulation class is specified in the product-specific data sheets. We will gladly provide you with a lifetime calculation taking into account your specific operating conditions. Mounting position The mounting position is specified in the product-specific data sheets. Motor protection / thermal protection Information on motor protection and thermal protection is provided in the Condensate discharge holes product-specific data sheets. Information on the condensate discharge holes is provided in the Depending on motor type and field of application, the following protective product-specific data sheets. features are realised: Mode of operation – Thermal overload protection (TOP), either in-circuit or external The mode of operation is specified in the product-specific data sheets. – PTC with electronic diagnostics – Impedance protection Protection class – Thermal overload protection (TOP) with electronic diagnostics The protection class is specified in the product-specific data sheets. – Current limitation via electronics Service life The service life of ebm-papst products depends on two major factors: – The service life of the insulation system – The service life of the bearing system If an external TOP is connected, the customer has to make sure to connect a conventional trigger device for switching it off. Products without fitted TOP and without protection against improper use, a motor protection complying with the valid standards has to be installed. The service life of the insulation system mainly depends on voltage level, Mechanical strain / performance parameters temperature and ambient conditions, such as humidity and condensation. All ebm-papst products are subjected to comprehensive tests complying The service life of the bearing system depends mainly on the thermal load with the normative specifications. In addition to this, the tests also reflect on the bearing. the vast experience and expertise of ebm-papst. 94 Vibration test Standards Vibration tests are carried out in compliance with Information on standards is provided in the product-specific data sheets. – Vibration test in operation according to DIN IEC 68, parts 2-6 – Vibration test at standstill according to DIN IEC 68, parts 2-6 EMC Information on EMC standards is provided in the product-specific data Shock load sheets. Shock load tests are carried out in compliance with Complying with the EMC standards has to be established on the final – Shock load according to DIN IEC 68, parts 2-27 appliance, as different mounting situations can result in changed EMC Balancing quality properties. Testing the balancing quality is carried out in compliance with Leakage current – Residual imbalance according to DIN ISO 1940 Information on the leakage current is provided in the product-specific – Standard balancing quality level G 6.3 data sheets. Should you require a higher balancing quality level for your specific Measuring is according to IEC 60990. application, please let us know and specify this when ordering your product. Approvals In case you require a specific approval for your ebm-papst product Chemo-physical strain / performance parameters (VDE, UL, GOST, CCC, CSA, etc.) please let us know. Should you have questions about chemo-physical strain, please direct Most of our products can be supplied with the relevant approval. them to your ebm-papst contact. Information on existing approvals is provided in the product-specific Fields of application, industries and applications data sheets. Our products are used in various industries and applications: Air performance measurements Ventilation, air-conditioning and refrigeration technology, clean room All air performance measurements are carried out on suction side and on technology, automotive and rail technology, medical and laboratory tech- chamber test beds conforming to the specifications as per ISO 5801 and nology, electronics, computer and office technology, telecommunications, DIN 24163. The fans under test are installed in the measuring chamber at household appliances, heating, machines and plants, drive engineering. free air intake and exhaust (installation category A) and are operated at Our products are not designed for use in the aviation and aerospace nominal voltage, with AC also at nominal frequency, and without any industry! additional components such as guard grilles. Legal and normative directives The products described in this catalogue are designed, developed and As required by the standard, the air performance curves correspond to an air density of 1.2 kg/m3. produced in keeping with the standards in place for the relevant product and, if known, the conditions governing the relevant fields of application. 95 Technical parameters & scope Measurement conditions for air and noise measurement Sound pressure level and sound level ebm-papst products are measured under the following conditions: All acoustic values are established according to ISO 13347, DIN 45635 – Axial and diagonal fans in direction of rotation “V” in full nozzle and and ISO 3744/3745 to accuracy class 2 and given in A-rated form. without guard grille When the sound pressure level (Lp) is measured, the microphone is on – Backward curved centrifugal fans, free-running and with inlet nozzle the intake side of the fan being tested, usually at a distance of 1 m on – Forward curved single and dual inlet centrifugal fans with housing the fan axis. Noise measurements All noise measurements are carried out in low-reflective test rooms with reverberant floor. Thus the ebm-papst acoustic test chambers meet the requirements of precision class 1 according to DIN EN ISO 3745. For noise measurement, the fans being tested are placed in a reverberant wall and operated at nominal voltage (for AC, also at nominal frequency) without additional attachments such as the guard grille. To measure the sound power level (Lw), 10 microphones are distributed over an enveloping surface on the intake side of the fan being tested (see graphic). The sound power level measured can be roughly calculated from the sound pressure level by adding 7 dB. Measuring configuration as per ISO 13347-3 respectively DIN 45635-38: 10 measuring points d≥D h = 1,5d ... 4,5d D 1,5d Measurement area S = 6d2 + 7d (h + 1,5d) h 3d 2d 96 9 dB. Thus the overall sound level of the installation can be expected to be 84 dB(A). 15 10 9 Example: 8 A3G800 axial fans are on a condenser. According to the data sheet, the sound pressure level of a fan is approximately 75 dB(A). The level increase measured from the diagram is 5 the noise values specified in the data sheet. This is shown in the diagram opposite. 0 The noise characteristics of multiple identical fans can be determined in advance based on [dB] [dB(A)] Adding 2 noise sources with the same level results in a level increase of approx. 3 dB. Increase in sound pressure / sound power level Combined level of multiple same-level sound sources 1 2 3 4 5 6 7 8 9 10 15 20 25 point and an axial fan A3G710 with 71 dB(A) in a ventilation unit. The level difference is 4 dB. The level increase can now be read in the diagram as approx. 1.5 dB. This means that the overall sound level of the unit can be expected to be 76.5 dB(A). 3 2 1,5 Example: There is an axial fan A3G800 with a sound pressure level of 75 dB(A) at the operating 1 levels given in the data sheet. This is shown in the diagram opposite. 0 The acoustic performance of two different fans can be predetermined based on the sound Increase in sound pressure / sound power level Combined level of two different-level sound sources [dB] [dB(A)] Number of sources of sound with identical level 0 4 8 12 16 20 Sound power level is independent of distance to the sound source. In contrast to this, sound -10 pressure level decreases the further away the noise source is. The adjacent diagram shows the 0 [dB] [dB(A)] Distance laws 24 [dB] [dB(A)] Difference in level with two sources of sound decrease in level under far sound field conditions. Far sound field conditions apply whenever the ably smaller. The following example only applies to far sound field conditions and can vary strongly depending on the installation effects: With an axial fan A3G300, a sound pressure level of 65 dB(A) was measured at a distance of 1 m. According to the adjacent diagram, at a distance of 20 m we would get a reduction by -20 -26 -30 In the near field of the fan, other correlations apply and the decrease in levels can be consider- -40 this complex topic. Per doubling of distance, the level in the far sound field decreases by 6 dB. Decrease in sound pressure level distance between microphone and fan is big when compared to fan diameter and wavelength to be considered. For more information on far sound field, please consult the relevant literature on 1 Distance 2 5 10 20 50 100 [m] 26 dB, i.e. a sound pressure level of 39 dB(A). 97 ebm-papst in Germany ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 74673 Mulfingen GERMANY Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected] 98 ebm-papst St. Georgen GmbH & Co. KG Hermann-Papst-Straße 1 78112 St. Georgen GERMANY Phone +49 7724 81-0 Fax +49 7724 81-1309 [email protected] Berlin Dipl.-Ing. (TH) Jens Duchow Händelstraße 7 16341 Panketal GERMANY Phone +49 30 944149-62 Fax +49 30 944149-63 [email protected] Heilbronn / Heidelberg Dipl.-Ing. Mark Gartner Gehrweg 12 74199 Unterheinriet GERMANY Phone +49 7130 404569-1 Fax +49 7130 404569-2 [email protected] Bielefeld Dipl.-Ing. (FH) Wolf-Jürgen Weber Niehausweg 13 33739 Bielefeld GERMANY Phone +49 5206 91732-31 Fax +49 5206 91732-35 [email protected] Kassel Dipl.-Ing. (FH) Ralph Brück Hoherainstraße 3 b 35075 Gladenbach GERMANY Phone +49 6462 4071-10 Fax +49 6462 4071-11 [email protected] Dortmund Dipl.-Ing. (FH) Hans-Joachim Pundt Auf den Steinern 3 59519 Möhnesee-Völlinghausen GERMANY Phone +49 2925 800-407 Fax +49 2925 800-408 [email protected] Koblenz Winfried Schaefer Hinter der Kirch 10 56767 Uersfeld GERMANY Phone +49 2657 16-96 Fax +49 2657 16-76 [email protected] Frankfurt Dipl.-Ing. Christian Kleffmann Dr.-Hermann-Krause-Straße 23 63452 Hanau GERMANY Phone +49 6181 1898-12 Fax +49 6181 1898-13 [email protected] Munich Dipl.-Wirt.-Ing. (FH) Jens Peter Landsbergerstraße 14 86932 Pürgen GERMANY Phone +49 8196 99877-54 Fax +49 8196 99877-55 [email protected] Halle Dipl.-Ing. (TU) Michael Hanning Lercheneck 4 06198 Salzatal / OT Lieskau GERMANY Phone +49 345 55124-56 Fax +49 345 55124-57 [email protected] Nuremberg Dipl.-Wirt.-Ing. (FH) Axel Resch Dr.-August-Koch-Str. 1 91639 Wolframs-Eschenbach GERMANY Phone +49 9875 9783-170 Fax +49 9875 9783-171 [email protected] Hamburg Ingenieurbüro Breuell GmbH Ing. Dirk Kahl Elektroingenieur Grützmühlenweg 48 22339 Hamburg GERMANY Phone +49 40 538092-19 Fax +49 40 538092-84 [email protected] Offenburg Dipl.-Ing. (FH) Ralf Braun Hubeneck 21 77704 Oberkirch GERMANY Phone +49 7802 9822-52 Fax +49 7802 9822-53 [email protected] fan agent Stuttgart Dipl.-Ing. (FH) Rudi Weinmann Hindenburgstraße 100/1 73207 Plochingen GERMANY Phone +49 7153 9289-80 Fax +49 7153 9289-81 [email protected] compact fan agent motor specialist ebm-papst Landshut GmbH Hofmark-Aich-Straße 25 84030 Landshut GERMANY Phone +49 871 707-0 Fax +49 871 707-465 [email protected] Ulm M.Sc. Reinhard Sommerreißer Am Germanenring 13 86674 Baar / Schwaben GERMANY Phone +49 8276 5899-775 Fax +49 8276 5899-776 [email protected] Distributoren Frankfurt R.E.D. Handelsgesellschaft mbH Gutenbergstraße 3 63110 Rodgau - Jügesheim GERMANY Phone +49 6106 841-0 Fax +49 6106 841-111 [email protected] www.red-elektromechanik.de Hamburg Breuell + Hilgenfeldt GmbH Grützmühlenweg 48 22339 Hamburg GERMANY Phone +49 40 538092-20 Fax +49 40 538092-84 [email protected] Munich A. Schweiger GmbH Ohmstraße 1 82054 Sauerlach GERMANY Phone +49 8104 897-0 Fax +49 8104 897-90 [email protected] www.schweiger-gmbh.com (1 to 5 pieces) North Breuell + Hilgenfeldt GmbH Grützmühlenweg 48 22339 Hamburg GERMANY Phone +49 40 538092-20 Fax +49 40 538092-84 [email protected] South HDS Ventilatoren Vertriebs GmbH Glaswiesenstraße 1 74677 Dörzbach GERMANY Phone +49 7937 80355-20 Fax +49 7937 80355-25 [email protected] www.hds-gmbh.net motor agent ebm-papst in Europe Europe Austria ebm-papst Motoren & Ventilatoren GmbH Straubingstraße 17 4030 Linz AUSTRIA Phone +43 732 321150-0 Fax +43 732 321150-20 [email protected] www.ebmpapst.at Belarus ebm-papst Bel AgmbH Lipkovskaya Gasse 34 Office No.6, Room 106,107 223010 Minsk BELARUS Phone +375 17 3851556 Fax +375 17 3851556 [email protected] www.ebmpapst.by Belgium ebm-papst Benelux B.V. Sales office Belgium-Luxemburg Romeinsestraat 6/0101 Research Park Haasrode 3001 Heverlee-Leuven BELGIUM Phone +32 16 396-200 Fax +32 16 396-220 [email protected] www.ebmpapst.be Bulgaria ebm-papst Romania S.R.L. Str. Tarnavei No. 20 500327 Brasov ROMANIA Phone +40 268 331859 Fax +40 268 312805 [email protected] Croatia ebm-papst Industries Kft. Ezred u. 2. 1044 Budapest HUNGARY Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] Czech Republic / Slovakia ebm-papst CZ s.r.o. Kaštanová 34a 620 00 Brno CZECH REPUBLIC Phone +420 544 502-411 Fax +420 547 232-622 [email protected] www.ebmpapst.cz Denmark ebm-papst Denmark ApS Vallensbækvej 21 2605 Brøndby DENMARK Phone +45 43 631111 Fax +45 43 630505 [email protected] www.ebmpapst.dk Estonia ebm-papst Oy, Eesti Filiaal Kesk tee 13 Aaviku küla, Jüri Tehnopark 75301 Rae Vald, Harjumaa ESTONIA Phone +372 65569-78 Fax +372 65569-79 www.ebmpapst.ee Finland ebm-papst Oy Puistotie 1 02760 Espoo FINLAND Phone +358 9 887022-0 Fax +358 9 887022-13 [email protected] www.ebmpapst.fi France ebm-papst sarl ZI Nord - rue A. Mohler BP 62 67212 Obernai Cedex FRANCE Phone +33 820 326266 Fax +33 3 88673883 [email protected] www.ebmpapst.fr Greece Helcoma Th. Rotas & Co OE Davaki 65 17672 Kallithea-Attiki GREECE Phone +30 210 9513-705 Fax +30 210 9513-490 [email protected] www.helcoma.gr Hungary ebm-papst Industries Kft. Ezred u. 2. 1044 Budapest HUNGARY Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] Iceland RJ Engineers Stangarhyl 1a 110 Reykjavik ICELAND Phone +354 567 8030 Fax +354 567 8015 [email protected] www.rj.is Ireland ebm-papst UK Ltd. Chelmsford Business Park Chelmsford Essex CM2 5EZ UNITED KINGDOM Phone +44 1245 468555 Fax +44 1245 466336 [email protected] www.ebmpapst.co.uk AuBren Limited Portlaoise Business & Technology Park Mountrath Road Portlaoise, Co. Laois IRELAND Phone +353 57 8664343 Fax +353 57 8664346 [email protected] www.aubren.com Italy ebm-papst Srl Via Cornaggia 108 22076 Mozzate (Co) ITALY Phone +39 0331 836201 Fax +39 0331 821510 [email protected] www.ebmpapst.it Macedonia ebm-papst Industries Kft. Ezred u. 2. 1044 Budapest HUNGARY Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] 99 ebm-papst in Europe Netherlands ebm-papst Benelux B.V. Engelseweg 127 5705 AC Helmond NETHERLANDS Phone +31 492 502-900 Fax +31 492 502-950 [email protected] www.ebmpapst.nl Russia ebm-papst Ural GmbH Posadskaja-Strasse, 23(E), 3 620102 Ekaterinburg RUSSIA Phone +7 343 2338000 Fax +7 343 2337788 [email protected] www.ebmpapst.ur.ru Switzerland ebm-papst AG Rütisbergstrasse 1 8156 Oberhasli SWITZERLAND Phone +41 44 73220-70 Fax +41 44 73220-77 [email protected] www.ebmpapst.ch Norway ebm-papst AS P.B. 173 Holmlia 1203 Oslo NORWAY Phone +47 22 763340 Fax +47 22 619173 [email protected] www.ebmpapst.no ebm-papst Rus GmbH proezd 4529, vladenie 5, stroenie 1 141000 Mytistschi, Oblast Moskau RUSSIA Phone +7 495 9807524 Fax +7 495 5140924 [email protected] www.ebmpapst.ru Turkey Akantel Elektronik San. Tic. LTD. Sti. Atatürk Organize Sanayi Bölgesi 10007 SK. No.:6 35620 Cigli-Izmir TURKEY Phone +90 232 3282090 Fax +90 232 3280270 [email protected] www.ebmpapst.com.tr Poland ebm-papst Polska Sp. z o.o. ul. Annopol 4A 03236 Warszawa POLAND Phone +48 22 6757819 Fax +48 22 6769587 [email protected] www.ebmpapst.pl Portugal ebm-papst (Portugal), Lda. Centro Empresarial de Alverca Rua de Adarse, Vale D’Ervas Corpo D / Fracção 3 2615-178 Alverca do Ribatejo PORTUGAL Phone +351 218 394 880 Fax +351 218 394 759 [email protected] www.ebmpapst.pt Romania ebm-papst Romania S.R.L. Str. Tarnavei Nr. 20 500327 Brasov ROMANIA Phone +40 268 331859 Fax +40 268 312805 [email protected] 100 fan agent Serbia & Montenegro ebm-papst Industries Kft. Ezred u. 2. 1044 Budapest HUNGARY Phone +36 1 8722-190 Fax +36 1 8722-194 [email protected] Spain ebm-papst Ibérica S.L. Avda. del Sistema Solar, 29 28830 San Fernando de Henares (Madrid) SPAIN Phone +34 91 6780894 Fax +34 91 6781530 [email protected] www.ebmpapst.es Sweden ebm-papst AB Äggelundavägen 2 17562 Järfälla SWEDEN Phone +46 10 4544400 Fax +46 8 362306 [email protected] www.ebmpapst.se compact fan agent Ukraine ebm-papst Ukraine LLC Lepse Boulevard, 4, Building 21 03067 Kiev UKRAINE Phone +38 044 2063091 Fax +38 044 2063091 [email protected] www.ebmpapst.ua United Kingdom ebm-papst UK Ltd. Chelmsford Business Park Chelmsford Essex CM2 5EZ UNITED KINGDOM Phone +44 1245 468555 Fax +44 1245 466336 [email protected] www.ebmpapst.co.uk ebm-papst Automotive & Drives (UK) Ltd. The Smithy Fidlers Lane East Ilsley, Berkshire RG20 7LG UNITED KINGDOM Phone +44 1635 2811-11 Fax +44 1635 2811-61 A&[email protected] www.ebmpapst-ad.com motor specialist motor agent ebm-papst in America and Africa America Argentina ebm-papst de Argentina S.A. Hernandarias 148 Lomas del Mirador Pcia. de Buenos Aires (1752) ARGENTINA Phone +54 11 46576135 Fax +54 11 46572092 [email protected] www.ebmpapst.com.ar Brasil ebm-papst Motores Ventiladores Ltda. Av. José Giorgi, 301 Galpões B6+B7 Condominio Logical Center 06707-100 Cotia - São Paulo BRAZIL Phone +55 11 4613-8700 Fax +55 11 4777-1456 [email protected] www.ebmpapst.com.br USA ebm-papst Inc. P.O. Box 4009 100 Hyde Road Farmington, CT 06034 UNITED STATES Phone +1 860 674-1515 Fax +1 860 674-8536 [email protected] www.ebmpapst.us ebm-papst Automotive & Drives, Inc. 3200 Greenfield, Suite 255 Dearborn, MI 48120 UNITED STATES Phone +1 313 406-8080 Fax +1 313 406-8081 [email protected] www.ebmpapst-automotive.us Africa South Africa ebm-papst South Africa (Pty) Ltd. P.O. Box 3124 1119 Yacht Avenue 2040 Honeydew SOUTH AFRICA Phone +27 11 794-3434 Fax +27 11 794-5020 [email protected] www.ebmpapst.co.za Canada ebm-papst Canada Inc. 1800 Ironstone Manor, Unit 2 Pickering, Ontario, L1W3J9 CANADA Phone +1 905 420-3533 Fax +1 905 420-3772 [email protected] www.ebmpapst.ca Mexico ebm Industrial S. de R.L. de C.V. Paseo de Tamarindos 400-A-5to Piso Col. Bosques de las Lomas Mexico 05120, D.F. MEXICO Phone +52 55 3300-5144 Fax +52 55 3300-5243 [email protected] www.ebmpapst.com.mx 101 ebm-papst in Asia and Australia Asia China ebm-papst Ventilator (Shanghai) Co., Ltd. No. 418, Huajing Road WaiGaoQiao Free Trade Zone No. 2001, Yang Gao (N) Road 200131 Shanghai P.R. of CHINA Phone +86 21 5046-0183 Fax +86 21 5046-1119 [email protected] www.ebmpapst.com.cn Hong Kong ebm-papst Hong Kong Ltd. Room 17E, MG Tower 133 Hoi Bun Road, Kwun Tong Hong Kong P.R. of CHINA Phone +852 2145-8678 Fax +852 2145-7678 [email protected] India ebm-papst India Pvt. Ltd. 26/3, G.N.T. Road, Erukkencherry Chennai-600118 INDIA Phone +91 44 25372556 Fax +91 44 25371149 [email protected] www.ebmpapst.in Indonesia ebm-papst Indonesia Representative Office German Centre, 4th Floor, Suite 4470 Jl. Kapt. Subijono Dj. Bumi Serpong Damai 15321 Tangerang INDONESIA Phone +62 21 5376250 Fax +62 21 5388305 [email protected] Israel Polak Bros. Import Agencies Ltd. 9 Hamefalsim Street Kiryat Arie, Petach-Tikva 49514 ISRAEL Phone +972 3 9100300 Fax +972 3 5796679 [email protected] www.polak.co.il 102 fan agent Japan ebm-papst Japan K.K. Attend on Tower 13F Shinyokohama 2-8-12, Kohoku-ku 222-0033 Yokohama-City, Kanagawa JAPAN Phone +81 45 47057-51 Fax +81 45 47057-52 [email protected] www.ebmpapst.jp Thailand ebm-papst Thailand Co., Ltd. 99/9 Moo 2, Central Chaengwattana Tower 14th Floor, Room 1402 Chaengwattana Road Bangtarad, Pakkret 11120 Nonthaburi THAILAND Phone +66 2 8353785-7 Fax +66 2 8353788 [email protected] Korea ebm-papst Korea Co. Ltd. 6F, Trutec Bldg. 12, WorldCupbuk-ro 56-gil Mapo-Gu Seoul 121-835 KOREA Phone +82 2 366213-24 Fax +82 2 366213-26 [email protected] www.ebmpapst.co.kr United Arab Emirates ebm-papst Middle East FZE PO Box 17755 Jebel Ali Free Zone / FZS1 / AP05 Dubai UNITED ARAB EMIRATES Phone +971 4 88608-26 Fax +971 4 88608-27 [email protected] www.ebmpapst.ae Malaysia ebm-papst Malaysia Representative Office Unit 12-2, Jalan USJ Sentral 3 Persiaran Subang, Selangor Darul Ehsan 47600 Subang Jaya MALAYSIA Phone +60 3 8024-1680 Fax +60 3 8024-8718 [email protected] Singapore ebm-papst SEA Pte. Ltd. No. 23 Ubi Road 4 #06-00 Olympia Industrial Building Singapore 408620 SINGAPORE Phone +65 65513789 Fax +65 68428439 [email protected] Taiwan ETECO Engineering & Trading Corp. 10F-I, No. 92, Teh-Wei Str. Tsow-Inn District, Kaohsiung TAIWAN Phone +886 7 557-4268 Fax +886 7 557-2788 [email protected] www.ebmpapst.com.tw compact fan agent motor specialist Vietnam ebm-papst Vietnam Representative Office Room #102, 25 Nguyen Van Thu Street District 1 Ho Chi Minh City VIETNAM Phone +84 8 39104099 Fax +84 8 39103970 [email protected] Australia Australia ebm-papst A&NZ Pty Ltd. 10 Oxford Road Laverton North, Victoria, 3026 AUSTRALIA Phone +61 3 9360-6400 Fax +61 3 9360-6464 [email protected] www.ebmpapst.com.au New Zealand ebm-papst A&NZ Pty Ltd. 61 Hugo Johnston Drive, Unit H Penrose 1061, Auckland NEW ZEALAND PO Box 112278, Penrose 1642, Auckland Phone +64 9 525-0245 Fax +64 9 525-0246 [email protected] www.ebmpapst.com.au motor agent 103 www.ebmpapst.com 37797-7-8811 37903-7-8811 · 2014-06 · 2013-11 · KH-3’ Printed in Germany ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 74673 Mulfingen Germany Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]