MAG - Magnetics in Switched-Mode Power Supplies

Magnetics in
Switched-Mode Power Supplies
Agenda
•
•
•
•
•
2
Block Diagram of a Typical AC-DC Power Supply
Key Magnetic Elements in a Power Supply
Review of Magnetic Concepts
Magnetic Materials
Inductors and Transformers
Block Diagram of an
AC-DC Power Supply
AC
Input
3
Input
Filter
Rectifier
PFC
Power
Stage
Transformer
Output
Circuits
DC
Outputs
(to loads)
Functional Block Diagram
Input Filter
Rectifier
PFC
L
+ Bus
G
PFC
Control
+ Bus
Return
N
Power Stage
Xfmr
Output Circuits
+
12 V, 3 A
+
+ Bus
5 V, 10 A
PWM
Control
+
3.3 V, 5 A
-
+ Bus
Return
Mag
Amp
Reset
4
Transformer
Xfmr
CR2
L3a
+
CR3
12 V, 3 A
-
C5
CR4
L3b
+
+ Bus
Q2
CR5
5 V, 10 A
-
C6
+ Bus
Return
•
•
In forward converters, as in most topologies, the transformer simply
transmits energy from primary to secondary, with no intent of energy
storage.
Core area must support the flux, and window area must accommodate
the current. => Area product.
⎛
PO
AP = Aw Ae = ⎜⎜
⎝ K ⋅ ΔB ⋅
5
4
3
⎞
⎟⎟ cm 4
f⎠
Output Circuits
•
Popular configuration for these
voltages---two secondaries, with
From 12 V
a lower voltage output derived secondary
from the 5 V output using a mag
amp postregulator.
From 5 V
CR2
L3a
+
CR3
CR4
C5
L3b
+
secondary
CR5
CR6
C6
CR8
+
CR7
C7
Mag
Amp
Reset
6
5 V, 10 A
-
L4
SR1
•
12 V, 3 A
-
Feedback to primary PWM is usually from the 5 V output,
leaving the +12 V output quasi-regulated.
3.3 V, 5 A
-
Transformer (cont’d)
•
Note the polarity dots.
Xfmr
– Outputs conduct while Q2 is on.
– Secondary Vpeaks = +Bus • Ns/Np
•
Note the coupled output choke, L3.
– Windings must have same turns ratios
as transformer, which is the same as
output voltages plus diode drops of
CR3 and CR5.
•
•
7
CR2
L3a
+
CR3
12 V, 3 A
-
C5
CR4
L3b
+
+ Bus
Q2
CR5
C6
5 V, 10 A
-
+ Bus
Return
With output chokes in continuous conduction, each output voltage
is the average of its secondary voltage (neglecting diode drops).
Therefore, each output voltage is its secondary peak voltage times
the duty ratio of the primary bus voltage, +Bus, (neglecting diode
drops and Q2’s ON voltage).
Review of Some Magnetic Concepts
•
•
•
•
8
Units used in the design of magnetic components
Current and magnetic flux
Characteristics of magnetic materials
Faraday’s Law (the “transformer equation”)
Units and Their Symbols
Symbol
•
•
9
Description
SI Units
H
B
μ
F
field strength
flux density
permeability
magnetomotive force
A-t/m
tesla (T)
T-m/A-t2
A-t
φ
R
P
I
L
N
flux
reluctance
permeance
current
inductance
winding turns
weber/t (Wb/t)
A-t2/Wb
henry/t2
ampere (A)
henry (H)
turn (t)
Units named for famous people are not capitalized (ampere,
henry, volt), but their symbols are (A, H, V).
Always separate the value from the unit symbol (10 uH, not
10uH)---it’s not an option.
Right-Hand Rule
Flux Direction as a Result of Current Flow
•
10
Wrap one’s right hand around a conductor with thumb pointing in the
direction of current flow. Fingers point in the direction of flux lines.
Material Characteristics
B
flux density in tesla (1 tesla = 10,000 gauss)
Slope = B/H = μ
= permeability
Air
μ(relative) = 1
H
magnetic field strength in ampere turns / meter
•
•
Bulk property of the material
H = NI/le = ampere ⋅ turns per meter
– Classic definition is amperes per meter (assumes only one turn)
– le = magnetic path length
•
11
µ = permeability, usually relative to air (µair = 4⋅π ⋅10-7 H/m)
Core Characteristics
φ = B Ae
flux in webers (1 weber = 1 tesla square meter)
Slope = φ /F = P = permeance
"Inductance Factor" in H / t2
F = H le
magnetomotive force in ampere turns
• Core with no winding.
• Material characteristics, with Ae and le added.
– Ae = core area, le = effective magnetic path length
– Common unit for the slope is “Inductance Factor,” usually given in nH / t2
12
Wound Coil Characteristics
Νφ
flux turns in weber turns = volt seconds
Slope = L = inductance (henries)
I
current in amperes
•
13
Using volt-seconds and amperes, the wound component can be
analyzed easily by circuit engineers using time-domain analysis.
The “Transformer Equation”
(Faraday’s Law)
E
= 4 B ⋅ Ae ⋅ f
N
•
B in tesla, Ae in m2, f in Hz
– Modern SI units
•
14
The saturation flux density, Bmax, determines the
maximum volts per turn that can be applied to a given
transformer or inductor winding at a given frequency.
Watch closely, now:
Transformer Equation from Faraday’s Law
ΔΦ
E=N
Δt
Φ = B ⋅ Ae
B
ΔB
ΔΦ = ΔB ⋅ Ae = 2 B ⋅ Ae
1
1 1
Δt = T = ⋅
2
2 f
E ΔΦ
1
=
= 2 B ⋅ Ae ⋅ 1 = 4 B ⋅ Ae ⋅ f
N
Δt
2f
•
15
Note: This applies to square waves (where Δt = half of the period).
An Extremely Important Fact
E ΔΦ
=
= 4 B ⋅ Ae ⋅ f
N
Δt
•
•
•
•
•
16
Unless the flux is changing, there will be no voltage.
If the flux swings back and forth, so will the voltage.
In order for there to be a net dc voltage, the flux must be continually
increasing.
Therefore, our chances of inventing a magnetic rectifier are ZERO.
The average voltage (dc) across a winding (neglecting winding
resistance) is ALWAYS ZERO. This is one of the most useful facts
in our bag of tools.
Popular Materials
Material
•
17
Permeability Bsat
(relative)
(tesla)
Loss @ 0.1 T,
100 kHz
(mW/cm3)
Usage
Ferrite
(Mag. Inc. P)
2500
0.5
80
Power Transformers
Filter Inductors (gapped)
PFC Inductors (gapped)
Ferrite
(Mag. Inc. W)
10,000
0.42
250
EMI Filters
(common-mode only)
Molypermalloy
(Mag. Inc. MPP)
60
0.75
340
Filter Inductors
PFC Inductors
Sendust
(Mag. Inc. Kool-Mu)
60
1
850
Filter Inductors
PFC Inductors
Powdered iron
(Micrometals 52)
75
1.4
3200
Filter Inductors
PFC Inductors
80% Cobalt tape
(Honeywell 2714A)
100,000
0.55
90
Mag. Amps
Note the wide range of permeability and power loss.
Inductors and Transformers
• Inductor operation (example: buck regulator)
• Conduction modes
– Continuous mode
– Critical conduction mode
– Discontinuous mode
• The boost regulator
• Transformer operation
– Flyback converter
– Forward converter
18
Buck Regulator
(Continuous Conduction)
•
Inductor current is continuous.
– Vout is the average of the voltage at
its input (V1).
– Output voltage is the input voltage
times the duty ratio (D) of the
switch.
– When switch in on, inductor current
flows from the battery.
– When switch is off, it flows through
the diode.
– Neglecting losses in the switches
and inductor, D is independent of
load current.
•
A characteristic of buck regulators
and its derivatives:
– Input current is discontinuous
(chopped), and output current is
continuous (smooth).
19
i3
i1
v1
Vin =
15 V
Vout = 5 V
Load
(R)
i2
v1 0
i1 0
i2 0
i3
0
time
Buck Regulator
(Critical Conduction)
i3
i1
•
Inductor current is still
continuous, but just
“touches” zero as the
switch turns on again.
– This is called “critical
conduction.”
•
Output voltage is still equal
to the input voltage times
D.
v1
Vin =
15 V
Load
(R)
i2
v1 0
i1
i2
i3
0
time
20
Vout = 5 V
Buck Regulator
(Discontinuous Conduction)
•
•
•
•
In this case, the current in the
inductor is zero during part of
each period.
Output voltage is still (as
always) the average of v1.
Output voltage is NOT the input
voltage times the duty ratio (D)
of the switch.
While the load current is below
the critical value, D varies with
load current (while Vout
remains constant).
i3
i1
i2
i1
Vin =
15 V
v1
Load
(R)
i2
v1
0
i1
i2
i3
time
21
Vout = 5 V
Boost Regulator
•
Output voltage is always greater
than (or equal to) the input
voltage.
Input current is continuous, and
output current is discontinuous
(the opposite of a buck
regulator).
Relationship of the output
voltage to the duty ratio, D, is not
as simple as in the buck
regulator. In the continuousconduction case, it is:
•
•
⎛ 1 ⎞
Vo = Vin ⎜
⎟
⎝1− D ⎠
•
22
In this example, Vin = 5,
Vout = 15, and D = 2/3.
i1
i3
Vout = 15 V
v1
Vin =
5V
i2
Load
(R)
Vout = 15 V
Vin = 5 V
v1 0
i1
0
i2
0
i3
0
time
Transformer (No Energy Storage)
IN
ΔΦ
OUT
•
Ampere-turns of all windings sum to zero.
– Right-hand rule applies to the applied current and the resulting flux.
The opposite occurs on the output winding.
23
Transformer (Energy Storage)
•
•
•
•
24
This is a conventional flyback transformer.
Energy is delivered to the magnetic core during the pulse applied to the primary.
Energy is transferred from the core to the load during the remaining portion of the cycle.
Ampere-turns of all windings do not sum to zero over each cycle when in continuousconduction mode. This is consistent with energy storage ( 1/2 L I2 ).
Transformer Operation
Including Effect of Primary Inductance
v
0
time
i
i
turns ratio:
1:2
i1
i2
i sec.
v sec.
Load (R)
0
v sec. 0
•
•
25
i1
0
i2
0
i sec. 0
This is an example of a “step-up” transformer (secondary voltage is
higher than the primary voltage).
Transformer is shown as an ideal transformer, with its primary
(magnetizing) inductance as an inductor in parallel with the primary.
Flyback Transformer
Really a Multi-Winding Inductor
turns ratio:
i pri.
1:2
i sec.
Vout
Vin
v pri.
v pri. 0
v sec.
Load (R)
Vout
v drain
0
v sec. 0
i pri. 0
time
•
•
26
i sec. 0
Here, the primary inductance is intentionally low, to determine the
peak current and hence the stored energy. When the primary
switch is turned off, the energy is delivered to the secondary.
Discontinuous conduction mode is shown in this example.
Forward Converter Transformer
turns ratio:
1:2
i pri.
Vin
v pri. 0
i1
i2
i3
i sec.
Vout
Load (R)
v sec.
iRESET
v drain
1
0
v sec. 0
i pri. 0
i1
Vout
0
iRESET 0
v node 0
0
i sec. 0
i2
time
i3
•
•
27
0
Primary inductance is high, as there is no need for energy storage.
Magnetizing current (i1) flows in the “magnetizing inductance” and causes
core reset (voltage reversal) after primary switch turns off.
Power Factor Correction
•
•
Power Factor (PF) is a term describing the input characteristic of an
electrical appliance that is powered by alternating current (ac).
It is the ratio of “real power” to “apparent power” or:
Preal
(v ⋅ i )averaged over one cycle
PF =
=
Papparent
Vrms ⋅ Irms
•
•
28
Where v and i are instantaneous values of voltage and current, and rms
indicates the root-mean-squared value of the voltage or current. The
apparent power (Vrms x Irms), in effect, limits the available output
power.
The boost regulator is the most popular topology chosen to shape the
input current to match the input voltage (usually a sine wave).
Boost Regulator
•
•
•
Output voltage is always greater
than (or equal to) the input
voltage.
Input current is continuous, and
output current is discontinuous
(the opposite of a buck
regulator).
Relationship of the output
voltage to the duty ratio, D, is not
as simple as in the buck
regulator. In the continuousconduction case, it is:
⎛ 1 ⎞
Vo = Vin ⎜
⎟
⎝1− D ⎠
•
29
In this example, Vin = 5,
Vout = 15, and D = 2/3.
i1
i3
Vout = 15 V
v1
Vin =
5V
i2
Load
(R)
Vout = 15 V
Vin = 5 V
v1 0
i1
0
i2
0
i3
0
time
Design of the PFC Inductor
•
•
•
•
•
Input: 90 – 264 Vac; Output: 400 Vdc
Pout = 120 W (into the output converter)
Choose: Ripple current = 0.5 A pp when input is 50% of the output
voltage.
Switching frequency f = 130 kHz.
Inductance required:
– Note: Use V = 200, since this represents the input at 200 V and the output
at 400 V.
1
200 ⋅
V ⋅t
2 ⋅130,000
L=
= 1.54 mH
=
i pp
0.5
30
Winding Losses in High-Frequency Magnetics
•
Power loss in switched-mode magnetic components are significant and
sometimes difficult to predict.
– Analytically, they amount to three-dimensional field problems.
– Winding losses are usually more troublesome than core losses.
•
•
•
•
31
The skin effect --- current crowding in conductors at high frequencies --is well-known, but is not the worst part of the problem.
Proximity effects --- due to fields induced by nearby conductors --- are
much more significant, AND more difficult to predict.
Early work, using sine waves, is inadequate to explain the losses with
typical waveshapes in switched-mode power supplies.
A knowledge of the basic principles is essential in HF magnetics design.
Eddy Currents
•
Skin effect is cause by eddy currents induced in a conductor by the
current in that conductor.
•
Proximity effect is caused by eddy currents induced in a conductor by
the current in an adjacent conductor.
EDDY CURRENT
SKIN EFFECT
32
PROXIMITY EFFECT
Eddy Currents (cont’d)
•
•
33
As in the earlier two-winding transformer
example, magnetic field is induced by the
current per the right-hand rule (dotted lines
of flux).
The flux causes eddy currents, analogous to
the secondary current in the transformer.
Skin Depth in Copper
•
34
Example: At 100 kHz, skin depth is 0.2 mm = radius of #26 wire.
Rac/Rdc vs. Diameter
•
Example: If the diameter is 7 skin depths, Rac = 2 Rdc.
– At 100 kHz, this corresponds to # 15 wire (1.4 mm dia.).
35
Proximity Effect
Note Opposing Currents
CURRENTS IN OPPOSITE DIRECTIONS
•
At 100 kHz, with rectangular waveforms (high harmonic content),
the proximity effect is MUCH more important than skin effect.
36
Proximity Effect
Multiple Parallel Wires
•
37
This occurs when using copper wires in parallel in transformers and
inductors.
MMF Diagrams
•
•
•
•
•
•
•
38
Eddy current loss and energy stored in a field are proportional to |H|2
To design HF windings you must know what the field intensity (H) is.
The mmf diagram is a very useful tool for determining H within a
winding.
F = NI = H le
In the following examples we assume le = 1 so that F = H
Even when not used for computation, the mmf diagram is powerful tool
for arranging the winding structure to minimize loss and leakage
inductance because it allows one to visualize the effect of different
winding arrangements on the fields within a winding structure
For simplicity, in the following examples solenoidal fields will be
assumed
H Diagram for a Single-Layer Coil
E-E Core
H = NI/le
0
•
39
H goes from 0 at outside to NI/le inside, then back to 0 outside.
Inductor with 4-Layer Winding
4I
3I
2I
I
0
•
•
40
H increases with each layer, remains at 4 I within the coil, then
decreases with each layer and returns to 0 outside.
Remember: Power loss is proportional to H2.
Design of the Main Transformer
•
•
•
•
•
•
41
Most important: Determine the range of input voltage.
In PFC-input power supplies, the max. is usually 400 V.
The minimum input voltage to the transformer is usually a matter of
how much holdup time is required---the time that the power supply
can continue to operate after an interruption of the input power.
In ac-input power supplies, with or without PFC, there is an energystorage capacitor at the input of the converter.
The design of this holdup feature requires the choice of the
capacitor value and the operating voltage range of the converter.
The converter’s operating range sets the transformer design.
Holdup Time vs. Bus Voltage
•
•
How much holdup time is achieved by allowing the bus voltage to
decay to a given fraction of its initial value?
Energy U extracted from the
bus capacitor is
1
1
U = C ⋅ (V0 2 − V12 )
2
Let V1 = k ⋅ V0
1
Then U = C ⋅ V0 2 ⋅ (1 − k 2 )
2
•
42
0.8
0.6
U( k )
0.4
0.2
0
0.4
0.5
0.6
0.7
k
0.8
0.9
Note that half of the available energy has been extracted when the
voltage had decayed to 70.7% of its initial value.
1
Example
•
•
•
•
43
Pick 400 V for the nominal bus voltage.
Use a 450 V bus capacitor, 500 V FETs in a two-transistor forward,
half-bridge or full-bridge converter, or 900 V to 1000 V FETs in a
single-ended forward converter.
Design for a final voltage of 60% (240 Vdc). Given a max. duty
ratio of 45%, the nominal duty ratio will be 27%.
This results in a minimum capacitor value of 0.4 uF per watt of
output power into the output power converter, for a holdup time of
20 ms.
Details
k=
V final
V0
(
1
2
2
U = P ⋅ t = C ⋅ V0 1 − k
2
k = 0.6
V0 = 400
t = .02
C=
)
2⋅ P ⋅t
Vo 2 (1 − k 2 )
And the answer is...
C = 0.4 uF per watt (into the final power stage)
44
Main Transformer Design
•
High-frequency transformers are a challenge.
– Core losses are usually not negligible.
– Winding losses are almost always significant.
– Winding losses are usually much more difficult to deal with in transformers
than in inductors, as the high-frequency components of winding currents are
large, compared to the average values of currents.
– The high-frequency winding losses are very dependent on the winding
structure.
• Layers, wire sizes, interleaving techniques are all important, and some
of the tradeoffs are counterintuitive.
45
Transformer Requirements
Power Stage
Xfmr
Output Circuits
+
12 V, 3 A
+
+ Bus
5 V, 10 A
PWM
Control
+
3.3 V, 5 A
+ Bus
Return
Mag
Amp
Reset
• Per the earlier discussion, design for a final voltage of 60%
(240 Vdc). Given a max. duty ratio of 45%, the nominal duty
ratio will be 27% (with 400 Vdc bus).
• Duty ratio in the 3.3 V output will be approx. 3.3/5 of these.
46
Essential Specifications
•
•
•
•
•
•
•
•
47
Vin range
Output 1
Output 2
Output 3
Frequency
Max. temp. rise
Cooling
Duty ratio
240 – 400 V
5 V, 10 A
3.3 V, 5 A
12 V, 3 A
100 kHz
40 oC
Natural convection
27% to 45%
Output Voltages and Turns Ratios
•
•
•
•
•
•
Assume the 5 V rectifier is a Schottky, with .4 V drop
Assume the 12 V rectifier has a .8 V drop
These are perhaps generous, but include IR drops in wdgs.
Output voltages are then 5.4 V and 12.8 V
– We’re losing a diode drop both during the pulse and during the rest
of the cycle, so simply add the diode drop to the output voltage.
Turns ratio between output windings:
12.8/5.4 = 2.37. Use 2 t and 5 t ? 12 V output will be 5/2 x 5.4 – 0.8 =
12.7 V. If 3 t and 7 t, it will be 11.8 V. Go for the 2 t and 5 t , if these
result in a reasonable flux density.
N p = N s1 ⋅
•
48
Vp
V s1
400
= 2⋅
= 40 turns.
20
Peak voltage on the 5 V secondary is 5.4 V / (d = .27) = 20 V.
Core Selection
•
Select size by manufacturer’s recommendation, based on power and
frequency, or by area product.
⎛
PO
AP = Aw Ae = ⎜⎜
⎝ K ⋅ ΔB ⋅
•
•
•
•
•
•
49
4
3
⎞
⎟⎟ cm 4
f⎠
Where K = 0.014 for forward converters
Choose ΔB for a core loss of 100 mW/cm3 (ΔB is twice the B shown
on the core loss curves).
The above formula is based on a current density (J) of 420 A/cm2 and
a window utilization of 40% copper.
For Magnetics P material, B = 0.12 T ΔB = 0.24 T
For 120 W, 100 kHz: AP = 0.253 cm4 T
Choose a PQ 2620 core (approx. 26 mm sq. footprint; 20 mm high).
A Handy Table
Sorted by WaAe (Area Product)
Core
Mfr.
Ae
cm2
Wa WaAe Ve
cm2 cm4 cm3
PQ2020
TDK
0.62
0.36
0.22
2.8
TDK
23
23
18
5.3
10.7
3.4
Without clamp
EFD25
Thomson 0.58
0.4
0.23
3.3
B&B
26
25
13
6.5
16.7
2.4
Horiz. mount
ETD24
TDK
0.56
0.45
0.25
3.5
TDK
34
29
22
9.7
17.2
2.6
Horiz. mount
LP22/13
TDK
0.68
0.46
0.31
3.3
TDK
32
26
19
8.4
13.4
3.4
Horiz. mount
PQ2620
TDK
1.19
0.31
0.37
5.5
TDK
29
27
22
7.8
9.2
3.4
Without clam p
EFD30
Thomson 0.69
0.54
0.37
4.3
B&B
31
30
13
9.3
20.4
2.6
Horiz. mount
RM10
Siemens
0.98
0.42
0.41
4.3
Siemens 39
25
23
9.7
10.3
4.1
Pow er bobbin
RM10
Siemens
0.98
0.42
0.41
4.3
Siemens 25
25
19
6.1
10.5
4.0
Regular bobbin
LP32/13
TDK
0.7
0.72
0.50
4.5
26
19
10.5
21.1
3.4
Type
•
50
Bobbin
Mfr.
TDK
Overall (mm)
L
W H
41
Floor
Winding (mm) Notes
2
Area, cm Width Height
1 Horiz. mount
List the standard cores your company uses, with the parameters
you’ll use in your designs. With this in an Excel spreadsheet, you
can sort by AP, floor area, height, as needed.
Determine the Core’s Thermal Resistance
•
51
PQ2620 core has thermal resistance of 24 oC/W (computed by
calculating the slope, 60 oC / 2.5 W = 24 oC/W ).
Determine Allowable Power Loss & B
•
•
Plim = oCrise/RT = 40 / 24 = 1.63 watts
Apportioning half to core loss, half to wire loss:
– Pcore = 0.8 W max.
– Pwire = 0.8 W max.
•
•
•
52
Core volume is 5.5 cm3
Therefore, core material loss is 0.8 W / 5.5 cm3, or 145 mW/cm3.
This corresponds to a flux density of 0.12 T in Magnetics P material.
Calculate the Number of Turns
•
Flux density is determined by volt-seconds per turn, so it can be
calculated from any winding. Using the primary,
d
VP ⋅
VP ⋅ t
dΦ
f
=
Since V = N
, we can write N P =
dt
ΔB ⋅ Ae 2 B ⋅ Ae
0.27
400 ⋅
100,000
NP =
= 37.8 turns
−4
2 ⋅ 0.12 ⋅1.19 ⋅10
•
•
53
This corresponds to the desired core loss of 0.8 W. Raising or
lowering it will simply move the core loss down or up
(respectively). Loss is proportional to B2.86 at 100 kHz in “P”
material. 5% less turns will cause 15% more loss.
Our previous calculation resulted in 40 turns on the primary,
which will simply result in less core loss.
Designing the Winding Structure
•
•
•
•
•
54
This is perhaps the most interesting and creative part of transformer
design.
Adjust the secondary turns to match the desired output voltages (5 V
and 12 V)
Adjust the primary turns to optimize the layer structure.
In both cases, adjust conductor sizes and shapes to minimize fractional
layers and take advantage of the available space.
A popular way to minimize winding losses is to split the primary winding,
winding half of the turns, then the secondary turns, and finally, the other
half of the primary turns.
Winding Structure
1/2 Primary
3 layers of
tape
12 V Sec.
tape
5, 3.3 V Sec.
3 layers of
tape
1/2 Primary
BOBBIN
•
Analysis of build height:
–
–
–
–
•
55
Primary layers: 2 x 0.374 mm
5 V sec: 0.887 mm
12 V sec: 0.714 mm
7 layers tape @ .127 mm.
Grand total: 3.283 mm. Bobbin height is 3.4 mm, so we’re IN.
Flyback
•
Transformer stores energy
– Designed like an inductor
– Causes it to be larger
– Really an “integrated magnetic,”
because it combines the transformer
and inductor functions in one core
+ Bus
Q2
PWM
Control
Bus
Return
56
Flyback
•
For discontinuous mode, design the
transformer so that the duty ratio (D) just
approaches maximum at max. load and min.
input voltage.
–
•
Vin = 12 V
Vout = 12 V
In this example, max. D is 0.5, and min. Vin is
12 V.
I pri.
–
–
–
•
Ipri. rises to the necessary peak value in less
time, so primary pulse is narrower, as shown in
this example.
Volt-seconds on any winding must average to
zero, so with 18 V in, the pulse width decreases
by 12/18.
Load is constant, so secondary pulse width is
same as before.
Peak current simply transfers from primary to
secondary when the switch turns off. In this
example, turns ratio is 1:1.
Transformer size is determined by the power
and frequency.
Design can be modified for different secondary
voltage(s) by changing secondary turns
and wire size, and primary operating
conditions stay the same.
57
12
0
I sec.
As Vin rises to 18 V, the slope of the input
current rises by di/dt = V / L.
–
24
Vin = 12 to 18 V
I pri.
I sec.
Vin = 18 V
•
Inductance is chosen to provide
the required energy during each
pulse.
Energy = power x time.
•
U = Pin • t = Po • t / efficiency
Li 2 = Vin • Iin • t
L=
Vin • Iin
f
30
18
0
I pri.
I sec.
For More Information
•
View the extensive portfolio of power management products from ON
Semiconductor at www.onsemi.com
•
View reference designs, design notes, and other material supporting
the design of highly efficient power supplies at
www.onsemi.com/powersupplies
58