Standby Power Reduction Techniques TND324/D Rev.1 – September 2007 Agenda • Regulatory requirements • Sources for standby power losses • Methods to lower the standby power consumption • Measured results versus calculated results • Conclusion 2 TND324/D Rev.1 – September 2007 Agenda • Regulatory requirements • Sources for standby power losses • Methods to lower the standby power consumption • Measured results versus calculated results • Conclusion 3 TND324/D Rev.1 – September 2007 Regulatory challenges • Standby Power Reduction • 25% of total energy consumption is in low power/sleep/standby mode • Concerted effort by CECP, Energy Star, IEA and other international agencies to limit standby power • Active Mode Efficiency Improvement • 75% of total energy consumption is in active mode • Changing efficiency from 60% to 75% can result in 15% energy savings • Next focus area for agencies • Power Factor Correction (or Harmonic Reduction) • Applicable with IEC 1000-3-2 (Europe, Japan) • Some efficiency specifications also require >0.9 PF 4 TND324/D Rev.1 – September 2007 Standby certification programs Code 5 (external power supplies) Region/Country & Timing No Load Power Consumption CUC1 CECP (China) & Energy Star (US) From January, 2005 (Tier 1) ≤ 0.50 W for 0-<10 W ≤ 0.75 W for ≥10-250 W CUC2 CECP and Energy Star From July 1, 2006 (Tier 2) ≤ 0.30 W for 0-<10 W ≤ 0.50 W for ≥10-250 W CE1 Europe (EC Code of Conduct) From January 1, 2005 ≤ 0.30 W for <15 W ≤ 0.50 W for 15-50 W ≤ 0.75 W for 50-60 W ≤ 1.00 W for 60-150 W CE2 Europe (EC Code of Conduct) From January 1, 2007 ≤ 0.30 W for non-PFC ≤ 0.50 W for PFC CA1 Australia (High Efficiency) From April, 2006 ≤ 0.50 W For 0-180 W TND324/D Rev.1 – September 2007 Standby mandatory programs Code Region/Country & Timing No Load Power Consumption MU0 US – FEMP DOE (Final 2011) ≤ 1.00 W for most applications ? MC1 China GB (Guo Biao) Standards (From January, 2005) ≤ 0.75 W for 0-10 W ≤ 1.00 W for 10-250 W MC2 China GB (Guo Biao) Standards (From October, 2007) ≤ 0.50 W for 0-10 W ≤ 0.75 W for 10-250 W MA1 Australia (MEPS) From April, 2006 ≤ 0.75 W for 0-180 W MA2 Australia (MEPS) From 2008/9 ≤ 0.50 W for 0-180 W 6 TND324/D Rev.1 – September 2007 Agenda • Regulatory requirements • Sources for standby power losses • Methods to lower the standby power consumption • Measured results versus calculated results • Conclusion 7 TND324/D Rev.1 – September 2007 Application overview • • One application was selected. Notebook adaptor operating in a flyback topology. • • • • • Standby power losses calculations • • • 8 Start-up resistors 70 Vac, or 100 Vdc Standby power calculations 230 Vac (required) Standby power measured data • • • Universal input 85 -265 Vac Vout 19 Vdc @ 90 W Frequency 65 kHz No power factor correction pre-regulation stage. Measured data 230 Vac, or 325 Vdc Goal to have a standby power < 0.5 W minimum Desired < 0.3 W TND324/D Rev.1 – September 2007 What are the sources for standby power losses? • • • • • 9 Switching losses Gate charge losses Start-up circuits Bias circuits Snubbers TND324/D Rev.1 – September 2007 Switching losses • Switching losses are associated with the controller turning on the power MOSFET each oscillator cycle 1 P = • C 2 1 P = • 390 2 OSS • V 2 DS pF • 325 V • Freq 2 • 65 kHz = 1 . 33 W Where: Operating frequency = 65 kHz 230 Vac • 1.414 = 325 V MOSFET Characteristics VDS = 650 V ID = 11 A COSS = 390 pF Q = Gate Charge = 45 nC 10 TND324/D Rev.1 – September 2007 Gate charge loss • The loss due to the controller charging and discharging the power MOSFET’s gate P = Vg • Q • Fsw = 13 V • 45 nC • 65 kHz = 38 mW Q = Gate Charge = 45 nC Lower gate charge devices are available, but they typically have a higher RDSON, decreasing the active efficiency of the SMPS at full load 11 TND324/D Rev.1 – September 2007 Start-up circuits • Start-up circuits are used in SMPS to start the controller when the input power is first applied to the power supply . The start-up time is 5 s CVcc 39 µF, Vccon 12 V 50 µA is the start-up current of the controller •The start-up current: dV ITOTAL = ISTART-UP Controller + C dt ITOTAL = 50 µA + 94 µA > 144 µA (Use 150 µA) Where: dV = 12 V the controller turn-on threshold (VCCON) dt = 5 s (the start-up time) C = CVcc = 39 µF 12 TND324/D Rev.1 – September 2007 Start-up circuits continued R START R START P START − UP − − UP UP Vdc min = I Total 100 Vdc = 150 μ A = 667 2 2 = VBulk = 325 667 k Ω R START − UP kΩ = 160 mW PSTART_UP is calculated at 230 Vac 13 TND324/D Rev.1 – September 2007 Start-up time vs. standby power Changing the start-up time to 500 ms CVcc 39 µF, Vccon 12 V IVcc =50 µA is the start-up current of the controller I VCC =C VCC T VCC start ON − up 12 V = 39 μ F = 936 μ A 500 ms ITotal = IVCC + Icontroller = 936 μA + 50 μA = 986 μA R START P START 14 − UP − UP = min Vdc = VBulk R START I Total 2 − UP = 100 Vdc 986 μ A 325 V 2 = =1.04 W 101 . 4 k =100.4 k To increase the start-up time, Rstart-up must be lowered increasing the standby power TND324/D Rev.1 – September 2007 Half-wave connection Rstart − up = 100 Vpk = 212 k Ω 150 μ A • π Vin 2 230 Vac 2 Pstart − up = = = 125 mW 2 • Rstart − up 2 • 212 kΩ Pstart-up@ 230 Vac = 125 mW, a 22% reduction 15 TND324/D Rev.1 – September 2007 Integrated high voltage start-up MOSFETs • The high voltage MOSFET is used as a current source that charges up the controllers Vcc capacitor when the input ac power is applied to the Power Supply. Controller with a High Voltage Start-Up FET Typical Isource 4 mA The Start-Up time is 118 ms Typical ILeakage 30 µA Pd = ILeakge • VBulk = 30μA • 325Vdc = 9.75mW Advantages: • Can reduce the standby power consumption by approximately 150 mW (compared to a SMPS with the start-up resistors connected to the bulk capacitor) down to 9.75 mW • Faster start-up time. 16 TND324/D Rev.1 – September 2007 Bias currents • In any power supply there are a number of circuits that, if not carefully selected, can consume a significant amount of standby power. • TL431 Shunt Regulator (TL431 needs a minimum of 1 mA of cathode • current ). • Optocoupler for the output feedback signal. • Resistive dividers • Output sensing and divider network impedance needs to be as high as possible Vsense = 17 Rlower Rupper + Rlower Vout = 7.4 k 49.0 k + 7.4 k 19V = 2.5 V TND324/D Rev.1 – September 2007 Bias networks Psense = Vo 2 19 2 = = 6.3 mW Rupper + Rlower 57 .3k The goal was to keep the bias current losses on the secondary to less than 20 mW. VRin = 1 mA • 1 kΩ = 1 V PRin = 1 mA² • 1 kΩ = 1 mW PTL431=(Vo-VRin-Vopto)•1 mA =(19 V- 1 V- 1V)•1 mA = 17 mW PTSECONDARY Side = 24.3 mW The primary side controller bias current = 2 mA Pcontroller = ICC • Vcc= 2 mA • 13 V = 26 mW The total losses due to bias currents are: PTotal = Psense + PRin + PTL431 + PController 6.3 mW + 1 mW + 17 mW + 26 mW = 50.3 mW 18 TND324/D Rev.1 – September 2007 Snubber/clamp losses RDC snubber 1 V clamp 2 P R = L LK • Ipk • Freq • 2 V clamp − V out • n Zener clamp 1 Vdc − Vz 2 P Z = Ipk L LK • Freq 2 Vz − Vout • n Where: LLK is the transformer leakage inductance Ipk is the transformer peak primary current Freq is the SMPS operating frequency VZ is the zener break down voltage Vclamp is the RDC snubber clamp voltage Vout is the output voltage N is the transformer turns ratio Vdc is the SMPS HV dc bus 19 TND324/D Rev.1 – September 2007 Losses summary PTstand-by = PSwitching+PGate+PStart-up+PBias With 667 kΩ start-up resistors. PTstand-by = 1.33 W + 38 mW + 160 mW + 50.3 mW =1.58 W With HV start-up PTstand-by = 1.33 W + 38 mW +9.75 mW + 50.3 mW = 1.43 W Using Fixed frequency will not get us to the low standby power requirements. 20 TND324/D Rev.1 – September 2007 Agenda • Regulatory requirements • Sources for standby power losses • Methods to lower the standby power consumption • Measured results versus calculated results • Conclusion 21 TND324/D Rev.1 – September 2007 Methods to lower the standby power consumption • Switching losses • Frequency foldback • Skip cycle operation • Startup circuits • Bias circuits 22 TND324/D Rev.1 – September 2007 Frequency foldback Operating frequency =65 kHz → 24 kHz P = 1 • 390 pF • 325 V 2 • 24 kHz = 494 mW 2 ☺ 62% reduction in standby power losses, compared to Example 1 where the PSW = 1.33 W VCO 2.5V + FB With 667 kΩ start-up resistor PTSTANDBY = PSWITCHING + PGATE + PSTART_UP+ PBIAS = 494 m W + 14 mW + 160 mW + 50.3 mW = 720 mW - Clock 1R 1V PWM R Q + CS S - With HV start-up 494 m W + 14 mW + 9.75 mW + 50.3 mW = 568 mW 2R PWM Latch Set Dominant 23 TND324/D Rev.1 – September 2007 Skip cycle P = 1 / 2 • C OSS • V DS • Freq • D SKIP 2 24 _ CYCLE TND324/D Rev.1 – September 2007 Skip cycle with start-up resistors Skip cycle switching loss calculation DSKIP_CYCLE= 7% (measured) P= 1 2 2 • 390pF • 325 V • 65 kHz • 0.07 = 93 mW EQ 18: ( With 667 kΩ start-up resistors) PTSTANDBY_Skip = PSWITCHING • D + PGATE • D + PSTART_UP+ PBIAS = 93 mW + 1.4 mW + 160 mW + 50.3 mW = 304 mW With HV start-up 93 mW + 1.4 mW + 9.75 mW + 50.3 mW = 155 mW Frequency foldback with HV start-up PTSTANDBY frequency foldback = 568 mW Frequency foldback with 667 kΩ start-up resistor PTSTANDBY = 720 mW 25 TND324/D Rev.1 – September 2007 Soft skip cycle Skip cycle operation can lead to audible noise due to the instantaneous peak current which causing a mechanical resonance with the snubber capacitor and magnetic winding, and core . Soft skip primary current waveform •Soft skip reduces the high instantaneous peak current by ramping up the primary current • This reduces the audible noise •This increases the skip duty cycle •Increasing the standby power 26 TND324/D Rev.1 – September 2007 Agenda • Regulatory requirements • Sources for standby power losses • Methods to lower the standby power consumption • Measured results versus calculated results • Conclusion 27 TND324/D Rev.1 – September 2007 Standby power results with start-up resistors 667 kΩ start-up resistors Vin 230 Vac 28 Fixed Frequency (65 kHz) Frequency Foldback (65 kHz→24 kHz) Skip cycle (65 kHz) Calculated- 1.58 W Measured-1.7 W Calculated- 720 mW Measured- 710 mW Calculated- 304 mW Measured- 320 mW TND324/D Rev.1 – September 2007 Standby power results with a HV start-up 29 Vin Skip with HV Start-Up (65 kHz) 230 Vac Calculated-155 mW Measured- 160 mW Soft Skip with HV Start-Up (65 kHz) Measured- 190 mW TND324/D Rev.1 – September 2007 Conclusion • Regulatory requirements worldwide are driving the reduction of standby power consumption • Identification of sources for standby power losses: • Switching losses •Bias circuits • Gate charge losses •Snubbers • Start-up circuits • Identification of methods to lower the standby power • Switching losses •Startup circuits • Frequency foldback •Bias circuits • Skip cycle operation • Very good correlation between calculated and measured results 30 TND324/D Rev.1 – September 2007