Datasheet DPC200 EN

Differential Pressure Controller DPC200
Diagraphm element with differential transformer
Measuring ranges: 0...50, 0...500, 0...1000, 0...2000, 0...4000 [Pa]
LCD-Display
Analog output 0...10 V
Controlling mode or measuring mode selectable
Controlling mode with PI algorithm
2 setpoints adjustable
Selectable measurements (differential pressure or volume flow)
Selectable units (metric or imperial)
Maximum output voltage adjustable
Open Collector Alarm output (measuring and control mode)
Compact plastic housing IP 54; UL 94 HB
Supply voltage 10...30 Vdc or 24 Vac (+/-15%)
Application
The differential pressure controller DPC200 measures low pressure of non-aggressive gases, particulary of
air.
The customer can use an analog signal (0...10V). The device offers two different settings. On the one hand
the output signal stands for a pressure proportional signal during measuring mode or volume flow square root
signal.
And on the other hand the output signal stands for a PI closed-loop control signal for differential pressure
during control mode or volume flow during control mode.
This static pressure transducer with controller is primarily intended for air conditioning systems, room
pressure control and filter control with continuously varible speed fans.
The DPC has an additional alarm output (open collector) for limit value monitoring or for filter monitoring next
to the analog output.
Electrical connection
DPC200
1
2
3
∆P
4
Dimensions [mm]
+ 10...30 Vdc or 24 Vac (±15%) excitation
- GND (return)
+ 0...10 Vdc output
- GND (return)
5
6
7
8
Alarm output: Open Collector
dry contact
open: Setpoint 1
close: Setpoint 2
Alarm output
high ohm:
alarm off
low ohm:
alarm on
maximal customer circuit 30 Vdc / 30 mA
Differential Pressure Controller DPC200
Technical data
Measuring medium:
Measuring principle:
Air or non-aggressive gases
Silicon diaphragm with spring and differential transformer
Measuring ranges:
0...50 Pa, 0...500 Pa, 0...1000 Pa, 0...2000 Pa, 0...4000 Pa
Overpressure protection:
Static pressure:
0,2 bar
Max. 0,2 bar
Pressure connections:
Case:
Hose line ø5 mm and ø6 mm
UL 94 HB; Case polyamid, cover ABS
Supply voltage:
10...30 Vdc or 24 Vac ± 15 %
Electronic protection against reversed polarization
Current consumption:
Output:
Alarm output:
Approx. 10 mA @ 10Vdc; 12 mA @ 24 Vdc
0...10 V
(Imax = 0,5 mA @ 10 Vdc, Imax = 2 mA @ 20 Vdc)
Open Collector, max. 30 V / 30 mA
Display:
LCD-Display, 2x16 characters
Mode:
Control:
Setpoints:
Measuring mode or controlling mode
PI algorithm
2 setpoints adjustable within software,
Setpoints are selectable with floating contact input
Protection class:
Ambient temperature:
Storage temperature:
Weight:
Mounting:
IP 54 acording EN 60529
-10...+50 °C
-25...+60 °C
Approx. 250 g
Vertical, position dependence by turning of 90°: approx. 25 Pa
Interference emmission:
According EN 61000-6-2, EN 61000-6-3, CE
limits of accuracy:
Zero error:
Sum of linearity and hysteresis
(depends on measuring range):
Temperature drift, zero point:
Temperature drift, span:
± 0,75 %
± 0,5 % ... ± 1 %
± 0,3 % / 10 K
± 0,2 % / 10 K
Part number p/n
Differential Pressure Controller DPC200-EP50
Measuring range: 0...50 Pa
p/n
2570
Differential Pressure Controller DPC200-EP500
Measuring range: 0...500 Pa
p/n
2572
Differential Pressure Controller DPC200-EP1000
Measuring range: 0...1000 Pa
p/n
2574
Differential Pressure Controller DPC200-EP2000
Measuring range: 0...2000 Pa
p/n
2576
Differential Pressure Controller DPC200-EP4000
Measuring range: 0...4000 Pa
p/n
2578
Mounting set M-DS
With screws, bleeders an 2 m plastic tube
p/n
25110
Arthur Grillo GmbH · Am Sandbach 7 · 40878 Ratingen
Telefon 0 21 02 - 47 10 22 · Telefax 0 21 02 - 47 58 82
www.grillo-messgeraete.de · [email protected] · www.sensor-store.de
December 2014