OPTOTRONIC® OT 30/220-240/12 P Constant Voltage LED Power supply for 12V LED - Modules 1. Technical Data Nominal Voltage Input Voltage Line Current, nominal Mains Frequency Power Factor Interface IP Rating Max Out Power 220 – 240 Vac 198 – 264 Vac 0,19A@230 Vac 50 / 60 Hz > 0.95 @ 230 Vac None IP 66 30 Watt Output Voltage Efficiency Ambient Temperature Ta Max. Case Temperature at Tc Max. Cable Length Max load per circuit breaker B10 Max load per circuit breaker B16 Max load per circuit breaker C10 12,5 Vdc (- 0,5V/+0,5V) 85% @ 230 Vac -25°C to +55°C +80°C 10m 13 21 21 2. Connection Schemes (+) 12V (-) GND red black LED Module 220 – 240V AC OT 30/220-240/12 P 2 3. Safety + + 2 - OT 30/220-240/12 P LED Module 30 Watt OT 30/220-240/12 P 2 220 – 240V AC 220 – 240V AC 2 + + - - OT 30/220-240/12 P LED Module 30 Watt LED Module 60 Watt OT 30/220-240/12 P 2 Power supplies can be connected in parallel on the primary side, but not on the secondary side L N L N ~ ~ ~ ~ ~ ~ + OT 30/220-240/12 P ~ ~ LED Module + OT 30/220-240/12 P ~ ~ LED Module + OT 30/220-240/12 P ~ ~ LED Module + OT 30/220-240/12 P LED Module + OT 30/220-240/12 P LED Module + OT 30/220-240/12 P LED Module The installation of two or more OPTOTRONIC® OT 30/220-240/12 P Power supplies with common “-“ or “+” wiring is forbidden. OSRAM AG www.osram.com 2012-10-12 AA416100055 Steinerne Furt 62, 86167 Augsburg, Germany No. 1, North Industrial Road 528000 Foshan Guangdong, P.R. China OPTOTRONIC® OT 30/220-240/12 P Constant Voltage LED Power supply for 12V LED - Modules Wiring and Connection Ensure that the LED module load is within the range of rated voltage, current and power supply (see Technical data) Maximum output cable length is limited by EMI and cross diameter Use output cable sections adequate to the load demand The luminaire manufacturer is responsible for providing the required clearances and creepage distances and also for protection against electrical shock, especially for the line and load wires Please avoid direct exposure of sunlight and in case of exposure to UV rays, protect the cables with suitable silicone sheath. Earth Connection OT 30/12 P is a “Protection Class II” power supply, therefore ground connection is not required Mounting and Environmental protection The control gear is a build in type for luminaire integration Maximum permissible ambient temperature must not be exceeded. Make sure there is adequate space to avoid a build-up of heat. In critical installations the temperature at tc has to be controlled 2 General Note Power supplies must be installed by a qualified electrician Disconnected from mains supplies before wiring work For further information see also “OPTOTRONIC – Technical guide” at www.osram.com OSRAM AG www.osram.com 2012-10-12 AA416100055 Steinerne Furt 62, 86167 Augsburg, Germany No. 1, North Industrial Road 528000 Foshan Guangdong, P.R. China