Inlet Duct for Cisco 7009 - CNLTD142A3

2
1
THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.
INLET DUCT
TOP BOX
ADJUSTABLE
BRACKETS
PANDUIT PART NO. WEIGHT
SIDE BRACKET
UPPER-RIGHT
60.1 LBS/EACH
24.3 kg/EACH
CNLTD142A3
SIDE BRACKET
UPPER-LEFT
SIDE
BRACKET
SPAN
(REFERENCE
NOTE #4)
B
SIDE DUCT
ASSEMBLY
23.0
583.10
FOR USE WITH PANDUIT NET-ACCESS
SWITCH CABINETS (N*** OR CN***)
CISCO 7009
SWITCH
(REFERENCE)
23.3
NOTES:
1. VISIT OUR CATALOG ONLINE AT
WWW.PANDUIT.COM FOR A LIST OF
CURRENT PARTS APPLICABLE FOR
USE WITH THIS PRODUCT.
2.PARTS SUPPLIED:
1 - SIDE BRACKET - UPPER RIGHT
1 - SIDE BRACKET - UPPER LEFT
1 - SIDE BRACKET - LOWER RIGHT
1 - SIDE BRACKET - LOWER LEFT
4 - ADJUSTABLE BRACKETS
1 - SIDE DUCT ASSEMBLY
1 - INLET DUCT - TOP BOX
1 - INLET DUCT - BOTTOM BOX
1 - MOUNTING HARDWARE KIT
3. DIMENSIONS IN PARENTHESES
ARE METRIC (mm).
4. SIDE BRACKETS ADJUST FROM
24.25" TO 26.1" (616-663).
592.58
SIDE BRACKET
LOWER-LEFT
INLET DUCT
BOTTOM BOX
SIDE BRACKET
LOWER-RIGHT
5.25
133.35
3 RU
(TYPICAL)
35.00
14 RU OF SPACE
IS NEEDED
BETWEEN
INLET DUCTS
889.00
20 RU
TITLE
INLET DUCT FOR CISCO 7009
A
A
(CNLTD142A3)
CUSTOMER DRAWING
18.3
4.7
464.77
ITEM REVISION NAME
11V233AY/04
118.97
DATASET FILE NAME
11V233AY_DC/04A
MATERIAL:
D10100DA/15
N/A
DRAWING NUMBER:
04A
03/06/13
RELEASED TO PRODUCTION
PJST
11V233AY
11V233AY
DRAWN BY
REV
DATE
BY
CHK
B
APR
DESCRIPTION
2
ECN
PJST
DATE
CHK
SIZE
SCALE
05/08/12
N/A
1
SHT 1 OF 4
A
2
1
THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.
DEVICE
KEEP-OUT AREA
RU 43 - 45
45 RU NET-ACCESS
N*** TYPE
CABINETS
DEVICE
KEEP-OUT AREA
RU 40 - 42
42 RU NET-ACCESS
N*** TYPE
CABINETS
B
B
DEVICE CAN BE
INSTALLED IN
RU 4 - 42
DEVICE CAN BE
INSTALLED IN
RU 4 - 39
DEVICE
KEEP-OUT AREA
RU 1 - 3
DEVICE
KEEP-OUT AREA
RU 1 - 3
TITLE
INLET DUCT FOR CISCO 7009
A
A
(CNLTD142A3)
NOTES:
1. FOR NEW NET-ACCESS (N***) CABINETS, THERE ARE NO
DEVICE KEEP-OUT AREAS. THE ONLY RESTRICTION ON THE
SWITCH PLACEMENT IS THAT 3 RU MUST BE LEFT OPEN
ABOVE AND BELOW THE SWITCH.
CUSTOMER DRAWING
ITEM REVISION NAME
11V233AY/04
DATASET FILE NAME
11V233AY_DC/04A
MATERIAL:
D10100DA/15
N/A
DRAWING NUMBER:
04A
03/06/13
RELEASED TO PRODUCTION
PJST
11V233AY
11V233AY
DRAWN BY
REV
DATE
BY
CHK
APR
DESCRIPTION
2
ECN
PJST
DATE
CHK
SIZE
SCALE
05/08/12
N/A
1
SHT 2 OF 4
A
2
1
THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.
45 RU NET-ACCESS
SWITCH CABINET
45 RU NET-ACCESS
SWITCH CABINET
(CN***)
FRONT EQUIPMENT
RAILS NEED TO
BE POSITIONED IN
THE FULL FORWARD
POSITION.
B
SPACING FOR
TOP OF CABINET
SPACING FOR
BOTTOM OF CABINET
2 RU
3 RU
3 RU
SIDE
DUCT
3 RU INLET
DUCTING
B
FRONT TO
BACK EQUIPMENT
RAIL DEPTH
MUST BE
25" - 26"
7009 CRADLE
(REFERENCE)
3 RU INLET
DUCTING
14 RU
3 RU'S MUST
BE RESERVED
ABOVE AND BELOW
THE 7009 SWITCH
FOR THE 7009
DUCT TO BE
INSTALLED.
SWITCH MUST
BE 5 RU
FROM BOTTOM.
7009 CRADLE
(REFERENCE)
SWITCH MUST
BE 19 RU FROM
TOP.
3 RU
CISCO 7009
SWITCH
(REFERENCE,
PORT SIDE OF
SWITCH FACES
COLD AISLE)
14 RU
SIDE
DUCT
3 RU
2 RU
FRONT OF CABINET
(FACES COLD AISLE)
VERTICAL
BLANKING
PANEL
TITLE
INLET DUCT FOR CISCO 7009
A
A
(CNLTD142A3)
CUSTOMER DRAWING
ITEM REVISION NAME
1. VERTICAL BLANKING PANELS MUST BE USED WITH THIS PRODUCT
TO PREVENT EXHAUST RECIRCULATION.
11V233AY/04
DATASET FILE NAME
11V233AY_DC/04A
MATERIAL:
D10100DA/15
N/A
DRAWING NUMBER:
04A
03/06/13
RELEASED TO PRODUCTION
PJST
11V233AY
11V233AY
DRAWN BY
REV
DATE
BY
CHK
APR
DESCRIPTION
2
ECN
PJST
DATE
CHK
SIZE
SCALE
05/08/12
N/A
1
SHT 3 OF 4
A
2
1
THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.
42 RU NET-ACCESS
SWITCH CABINET
42 RU NET-ACCESS
SWITCH CABINET
(CN***)
SPACING FOR
BOTTOM OF CABINET
3 RU
FRONT TO BACK
EQUIPMENT RAIL
DEPTH MUST BE
25" - 26"
B
B
3 RU INLET
DUCTING
3 RU'S MUST BE
RESERVED ABOVE
AND BELOW THE
7009 SWITCH FOR
THE 7009 DUCT
TO BE INSTALLED.
14 RU
SWITCH MUST
BE 5 RU
FROM BOTTOM
7009 CRADLE
(REFERENCE)
3 RU
FRONT EQUIPMENT
RAILS NEED TO
BE POSITIONED IN
THE FULL FORWARD
POSITION.
SIDE
DUCT
2 RU
CISCO 7009
SWITCH
(REFERENCE,
PORT SIDE OF
SWITCH FACES
COLD AISLE)
FRONT OF CABINET
(FACES COLD AISLE)
A
VERTICAL
BLANKING
PANEL
TITLE
INLET DUCT FOR CISCO 7009
A
(CNLTD142A3)
CUSTOMER DRAWING
ITEM REVISION NAME
11V233AY/04
1. VERTICAL BLANKING PANELS MUST BE USED WITH THIS PRODUCT
TO PREVENT EXHAUST RECIRCULATION.
DATASET FILE NAME
11V233AY_DC/04A
MATERIAL:
D10100DA/15
N/A
DRAWING NUMBER:
04A
03/06/13
RELEASED TO PRODUCTION
PJST
11V233AY
11V233AY
DRAWN BY
REV
DATE
BY
CHK
APR
DESCRIPTION
2
ECN
PJST
DATE
CHK
SIZE
SCALE
05/08/12
N/A
1
SHT 4 OF 4
A