Gateway EPA126: PVSP109--WW-ENG

SmartZone™ Gateway EPA126
S pe c i f i c a t i o n S H E E T
specifications
The Gateway EPA126 is installed as part of a primary/secondary topology and provides support for
up to six connected power devices, 12 environmental sensors and two access control devices all
through a single IP address. The gateway will allow for expansion of additional power devices, without
need for additional network ports, using the Gateway EPAX18 Expansion Unit that connects to the
base unit. The Gateway EPA126 consolidates all data captured from the connected power devices
and sensors and displays baseline operational data through a web interface or via SmartZone™
Software platforms. The gateway supports keypad or card reader devices to provide cabinet access
control. The gateway supports the "open" Simple Network Management Protocol (SNMP) to allow
monitoring for conditions that warrant administrative attention via any network management system
that supports the SNMP protocol, as well as supporting HTTP/HTTPS protocols for remote
management capabilities.
technical information
Dimensions:
Weight:
Packaging:
Mounting:
18 in. x 4.5 in. x 1.7 in. (465mm x 114mm x 44 mm)
4.76 lbs. (2.16Kg); 6.75 lbs. (3.06Kg) packaged
1.98 lbs. (0.9Kg)
19" rack mountable, housed in a 1RU metal case
key features and benefits
Centralized device
management
Connects up to six connected power devices, 12 environmental sensors and two access control devices into one intelligent
gateway to consolidate monitoring and management of operational data, simplify troubleshooting, and allow faster polling
of data
Single IP address
Allows all connected power devices and sensors to be combined through one single gateway IP address, reducing the
need for separate IP ports, IP capital costs, and management overhead
Primary/secondary
network topology
Houses the intelligence and power supply for connected devices within the gateway itself to simplify the network
architecture and lower overall power consumption
Access and
control security
Powers access control card readers on cabinets and manages encrypted access data to support smart card technologies
and other readers that enhance data center security
Scalable design
Allows Gateway EPA126 to be attached to the Gateway EPAX18 Expansion Unit to provide additional power device
inputs through the gateway’s single IP address, enabling cost-effective monitoring scalability and growth
SNMP enabled
Uses open SNMP protocol to provide alerts (traps) on potential service impacting power and environmental conditions
to mitigate operational downtime
HTTP/HTTPS
web interface
Provides authentication safeguards to securely allow users to configure, monitor, and control the gateway through
remote management
SmartZone ™ Software
platform integration
Consolidates power and environmental data to be utilized by SmartZone™ Software platforms for real-time monitoring
and display, management, and automated documentation
applications
The SmartZone™ Gateway EPA126 is an innovative, SNMP based gateway that simplifies the management of power devices and sensors with
one IP address, significantly reducing the number of IP addresses needed in the data center. This management information can then be displayed
via an internal web interface or utilized by SmartZone™ Software platforms for real-time monitoring, management, and automated reporting of
operational metrics. SmartZone™ Gateways are scalable solutions, ideally suited to brownfield or greenfield data centers and telco areas.
When coupled with the SmartZone™ Gateway EPAX18 Expansion Unit, the number of power devices that can be monitored increases from 6 to
24, significantly improving flexibility and scalability.
The SmartZone™ Gateway EPA126 supports up to six connected power devices, 12 environmental sensors and two access control devices. To
enhance cabinet security, the Gateway EPA126 supports keypads or HID card readers, which, when used with electronic handles, provide secure
access to the cabinet.
w w w. pa n d u it.c o m
SmartZone™ Gateway EPA126
Gateway EPA126 test data
Power Supply
Cable Wire
Input Power
100~240 VAC
Input Connector
2 x IEC C14 Inlet
Power Consumption
(Max) 40W
Additional Information
Isolated supply
Internal PSU
Dual
Operating Environment
Operating Temperature
32°F to 113°F (0°C to 45°C)
Storage Temperature
14°F to 158°F (-10°C to 70°C)
Operating Humidity
15% to 85% RH
Storage Humidity
5% to 90% RH
MTBF
>100,000 Hrs.
Connectivity and Networking
Network Type
Ethernet (802.3u)
Network Connection
RJ45
Link Speeds
10/100 Mbps with auto negotiation
Network Indications
Connection LED (Green); Network Speed LED (Yellow)
Sensors
Number of Inputs
12 sensor inputs
Input Connector
8-way RJ45
Parameters Monitored
Temperature, humidity, smoke, door contact, shock, water, PIR, airflow sensors, and
any 0-10 VDC output sensor
Temperature Monitoring Range
32°F to 140°F (0°C to 60°C)
Temperature Monitoring Accuracy
±5% Standard Transducer @ 68°F (20°C)
Humidity Monitoring Range
30% to 90% relative humidity
Humidity Monitoring Accuracy
±5% RH @ 77°F (25°C)
Analogue Resolution
12 Bit A/D for analogue inputs
Additional Information
Inputs are not isolated; auto detection of supported sensors
Access and Control
Access
2 ports that support 2x5 Keypad or HID Card Reader
Control
4 relay output ports for controlling flashing beacons, or electronic handles
PDU Monitoring and Control
Number of Inputs
6 inputs for connected power monitoring devices
PDU In/Out Connector
RJ45
Parameters Monitored
Volts, amps, total kVA, total kWh, total power factor, and frequency
Voltage Monitoring Range
0V to 500V
Current Monitoring Range
0A to 65A
kWh Monitoring Range
0 kWh to 429496729 kWh
kWh Monitoring Accuracy
Dependent on PDU
kWh Monitoring Accuracy
Dependant on PDU
2
SmartZone™ Gateway EPA126
Gateway EPA126 test data (continued)
Output Relays
Cable Wire
Number of Outputs
4
Output Connectors
WeidMuller (Output 1and 2), Screw lock Pheonix Contact (Output 3 and 4)
Output Connections
Normally Open, Common, Normally Closed
Maximum Switching
48V at 1A (Resistive Load)
Additional Information
12V DC Output fused at 1AMP available on Weidmuller connector
Monitoring and Configuration
Outputs 1 and 2 offer a 12+ VDC supply fused at 1 Amp
The following monitoring and configuration methods
are provided
Web management interface via HTTP or HTTPS (Secure); Configurable SNMP and
email alarm messages
Compliance
UL 60950-1 2nd edition, CAN/CSA-C22.2 No. 60950-1-07 Incl. Amd 1,
CAN/CSA-CISPR 22-10, FCC Part 15B.Emissions
LCD Status Monitor
The optional backlit LCD status monitor can display
the following
Summary page displaying configured PDUs and inputs 1 and 2, all 6 digital inputs
and all 4 PDUs, alternative display via selector switches
The following system information is also available
Firmware version, IP address, sub-net mask, gateway, MAC address
Additional Information
Backlit, powered from unit (no additional power source required)
Front Panel Indicators
Green LED Network
Ethernet connection present (flashing indicates traffic present)
Yellow LED Network Speed
Off indicates 10Mbps network; On indicates 100Mbps network link
Green LED CPU Status
Flash indicates correct operation of the Gateway EPA126
Red LED Alarm Status
One or more sensor input has exceeded a pre-set threshold
Blue LED
Internal low voltage power supply is within range
Yellow LED AC Feed A
Presence of AC power on input Feed A
Yellow LED AC Feed B
Presence of AC power on input Feed B
Rear Panel Indicators
Green LED CPU Status
Flashing indicates PDU Expansion Units CPU alive
Blue LED Power ON
Internal low voltage power supply is within range
Red LED Alarm Status
One or more sensor input has exceeded a pre-set threshold
part numbers
Gateway EPA126
Cable Wire
ZAEI-01
SmartZone™ Gateway EPA126 – UK-IEC power cable
ZAEI-01-99
SmartZone™ Gateway EPA126 – no power cable
ZAEI-01-NA
SmartZone™ Gateway EPA126 – NEMA 5-15 power cable
ZAEI-01-UNI
SmartZone™ Gateway EPA126 – IEC-IEC power cable
Gateway EPAX18 Expansion Unit
ZAEIPEXP01
SmartZone™ Gateway EPAX18 Expansion Unit – UK-IEC power cable
ZAEIPEXP0199
SmartZone™ Gateway EPAX18 Expansion Unit – no power cable
ZAEIPEXP01NA
SmartZone™ Gateway EPAX18 Expansion Unit – IEC - NEMA 5-15 power cable
ZAEIPEXP01UNI
SmartZone™ Gateway EPAX18 Expansion Unit – IEC power leads (2x IEC-IEC)
3
SmartZone™ Gateway EPA126
part numbers (continued)
Sensors
ZAPDUMOD-03
LCD Display Module with Selector Switches
ZAPDUMODKIT
External LCD Display Kit with Case Enclosure
FLABEA-01
Flashing Beacon with No Sounder
FLABEA-02
Flashing Beacon with Sounder
ZEAIR-02
Airflow Sensor
ZECRDRKIT-01
HID Access Control Card Reader
ZEDIC05-01
Digital Input Sensor
ZEDL05-01
Door Contact Sensor (micro switch type)
ZEDL05-02
Door Contact Sensor (magnetic type)
ZEKPKIT-01
Keypad Kit
ZEPIR-04
PIR Sensor
ZESMA05-01
Smoke Detector
ZESS04-01
Shock Sensor
ZETHL-10
Humidity Sensor
ZETHL-11
Temperature/Humidity Sensor
ZETHL-12
Temperature Sensor
ZETHL-13
External Temperature Sensor
ZEWD3-05
Water Sensor (contact type)
ZEWS-03-03
Water Sensor (rope type)
Gateway EPA126 dimensions
1.260
[32.00]
1.677
[42.60]
.138
[3.50]
18.455
[468.50]
1.677
[42.60]
19.016
[483.00]
Dimensions are in inches. [Dimensions in brackets are metric].
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT CANADA
Markham, Ontario
[email protected]
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
[email protected]
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
[email protected]
Phone: 65.6305.7575
PANDUIT JAPAN
Tokyo, Japan
[email protected]
Phone: 81.3.6863.6000
PANDUIT LATIN AMERICA
Guadalajara, Mexico
[email protected]
Phone: 52.33.3777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
[email protected]
Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
For more information
Visit us at www.panduit.com
Contact Customer Service by email: [email protected]
or by phone: 800.777.3300
©2014 Panduit Corp.
All rights reserved.
PVSP109--WW-ENG
5/2014