C-Trip, AC

UL-Series - UL489 Miniature Molded Case Circuit Breaker - 3 pole C-Trip - AC
Standard Pack: 4
Weight:
0.3-32A:
1.74kg (3.83lb.)
40-63A:
1.98kg (4.37lb.)
Calibration Temperature
40ºC (104ºF)
Ambient Temperature
-25ºC to +55ºC (-13ºF to 131ºF )
Storage Temperature
-40ºC to +70ºC (-40ºF to 158ºF )
Terminal Torque (min/max)
2 Nm (17.7 lb.in.) / 2.5Nm (22.2 lb.in)
Minutes
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
0.3A Through 10A Rated Current
1.05-1.35xIN
60
40
0.3 - 63A/ 240V AC, 0.3-32A/ 480Y/277V AC*
Current/ Voltage Rating
10
Tripping time t
Three Pole
60
40
Seconds
LISTED
C.B.
E329510
1.05-1.35xIN
Rated
Voltage
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
480Y/277V AC
240V AC
240V AC
240V AC
240V AC
Minutes
US
Type/
Cat. No.
3C03UL
3C05UL
3C1UL
3C1.6UL
3C2UL
3C3UL
3C4UL
3C5UL
3C6UL
3C8UL
3C10UL
3C12UL
3C13UL
3C15UL
3C16UL
3C20UL
3C25UL
3C30UL
3C32UL
3C40UL
3C50UL
3C60UL
3C63UL
10
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
4
1
10
Tripping time t
C
Rated
Current
0.3A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Electrical Life
6000 switching cycles ON/ OFF
Mechanical Life
10000 switching cycles ON/ OFF
Vibration Resistance
> 15g according to DIN EN 60069-2-59 during a load
4
1
0.4
10-1
4x10-2
Seconds
with I1 = 1.05 x IN
Resistance to mechanical shocks 25g @ 11ms
*One device dual voltage ratings.
10-2
4x10-3
10-3
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
51.5 mm
12A Through 63A Rated Current
37.5 mm
25.5 mm
6
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
7
45 mm
34.5 mm
8
52.5 mm
3 Pole
Short Circuit Interrupting Capacity
AC
52.5 mm
36.5 mm
105.3 mm
36.8 mm
1. Hold for a minimum of 100ms at surge of 5 times rated current.
2. Trip in under 100ms at 10 times rated current.
4
14.5 mm
30.5 mm
51.5 mm
68.4 mm
No.
Poles
Type
03-32A
33-63A
2-3
AC
10kA @ 120, 240,
10kA @ 120
480Y/277V
240V