Specification sheet

Features:
CB245A
Battery Charger
• Input: Single-phase 115 - 230 -277 VAC
• Output: Battery charging 24 VDC; 5 A
• Suited for the following battery types:
Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option)
• Automatic diagnostic of battery status. Charging
curve IUoUo, constant voltage and current
• Switching technology, output voltage 28.8 VDC
• Three charging levels: Boost, Trickle, Recovery.
• Protected against short circuit, inverted polarity, over load.
• Signal output (contact free) for fault battery state
• Protection degree IP20 - DIN rail mountable
INPUT
Cat. No.
CB245A
BATTERY
OUTPUT
Input Data
Nominal Input Voltage (2 x VAC)
Input Voltage range (VAC)
Inrush Current (Vn and In Load) I²t
Frequency
Input Current
Internal Fuse
External Fuse (recommended)
115 ~ 230 ~ 277 VAC
90 ~ 305 VAC
≤ 16 A ≤ 5 msec.
47 ~ 63 Hz ±6%
3.3 A - 115 VAC; 2.2 A ~ 2300 AC
4A
10 A (MCB curve B)
GENERAL DATA
Battery Output (Battery Care)
Boost charge (25°C) (typ. at In)
Max. time Bust Charge (tpy. at In)
Min. time Bust Charge (tpy. at In)
Trickle charge (25°C) (typ. at In)
Recovery Charge
Charging. Max Ibatt (In)
Efficiency (50% - In)
Charging current limiting ladj
Quiescent Current
Charging Curve automatic: IUoUo
Detection of element in short circuit
Short-circuit protection
Over Load protection
Over Voltage Output protection
Jumper Configuration battery type
(V cell) Ni-Cd (optional)
28.8 VDC
15 h
1 min.
27.5 VDC
2 ~ 18 VDC
5 A ±5%
89%
20 – 100 % ln
≤5 mA
3 stage
Yes
Yes
Yes
Yes
2.23;2,25;2,27;2,3;
1,41–1,5 (20 elem.)
ENVIRONMENT
General Data
Insulation voltage (In /Out)
Insulation voltage (In / PE)
Insulation voltage (Out / PE)
Protection Class (EN/IEC 60529)
Protection class
Reliability: MTBF IEC 61709
Pollution Degree Environment
Connection Terminal Blocks screw Type
Dimensions (W-H-D)
Weight
3000 VAC
1605 VAC
500 VAC
IP20
I, with PE connected
> 300.000 hours
2
2,5mm (24–14AWG)
65x115x135 mm (2.56 x 4.53 x 5.32 in)
0.65 Kg approx. (1.43 lbs.)
SAFETY & EMC
Climate Data
Ambient temperature (operation)
De Rating Ta > 50°C
Ambient temperature Storage
Humidity at 25°C no condensation
Cooling
-25 - +70°C (-13~158°F)
- 2.5%(In) / °C
-40 – +85°C (-40~185°F)
95% to 25°C
Auto Convention
Norms and Certifications
Conforming to:
OTHERS
IEC/EN 60335-2-29,EN60950/UL1950, Electrical safety, 89/336/EEC,
EMC Directive, 2006/95/EC (Low Voltage),DIN41773 (Charging cycle),
Emission:IEC 61000-6-4,Immunity: IEC 61000-6-2.CE
Signal Output (free switch contact)
Main or Backup Power
Low Battery
Fault Battery
Yes
Yes
Yes
Type of Signal Output Contact
Max. current can be switched (EN60947.4.1):
Max. DC1: 30 VDC 1 A; AC1: 60 VAC 1A
Min.1mA at 5 VDC
Resistive load
Min load
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
182
CB245A
Battery Charger
Technical Features
The CB series battery chargers are designed with advanced multistage battery charging method, completely automatic and suited Jumper for Battery Type Selection
to meet the most advanced requirements of battery
Open
manufacturers. The Battery Care concept is base on algorithms
Lead
that implement rapid and automatic charging, battery charge 1 2 3 4 6 7
Sealed
optimization during time, flat batteries recovery and real time
Lead
Low
diagnostic during installation and operation. The Real Time 1 2 3 4 6 7
Autodiagnostic system, monitoring battery faults such as,
Sealed
elements in short circuit, accidental reverse polarity connection,
Lead High
disconnection of the battery, they can easily be detected and 1 2 3 4 6 7
Gel
removed by help of Blink Code of Diagnosis Led; during the
installation and after sell. Each device is suited for all battery 1 2 3 4 6 7 Battery
types, by means of jumpers it is possible setting predefined curves
Gel
for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option). They are
Battery (1)
programmed for two charging levels, boost and trickle. A rugged 1 2 3 4 6 7
NiCd casing with bracket for DIN rail mounting provide IP20 protection
NiMh (1)
degree. They are extremely compact and cost-effective.
1 2 3 4
6
7
1 2 3 4 5 6 7 8 9 10
– + – +
ADJ.
MAINS
LOW BATTERY
OR
OR BATTERY
BACKUP REPLACEMENT
MAINS
OR
BACKUP
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
START
L N
Jumper for Functional Setting
Charging
Automatic multi-stage charging and real time diagnostic allow
fast recharge and recovery of deep discharged batteries, adding
value and reliability to the system hosting. Type of charging is
Voltages and current stabilized IUoUo. The state of charging
battery and Autodiagnosis of the systems are identified by a
flashing code on a Diagnosis LED and Fault Battery LED:
State
Auto
diagnosis
Trickle
Boost
Recovery
Reverse polarity
Battery No connect
Element in Short C.
Replace Battery
1 Blink/sec
2 Blink/sec
5 Blink/sec
1 Blink
2 Blink
3 Blink
5 Blink
Battery
Fault LED
OFF
OFF
OFF
ON
ON
ON
ON
1 2 3 4
6
7
Fast Charge
Enable2
1 2 3 4
1 2 3 4
6
6
7
7
Fast Recovery
Charge (2)3
1
2
3
Jumper present: life test enabled.
Jumper present: fast test enabled.
Jumper present: fast recovery charge
enabled only for size 3. Possibility to
recharge the battery also when the
voltage is close to zero with the
maximum power of the device.
Wiring Diagram
Battery
In VAC
Mains or Backup
Battery Low or
Battery Replacement
CB Charging Diagram
Voltage
Voltage / Current
Charging
Type
Diagnosis LED
Battery Life
Test On1
Current
Recovery Charge
Fast / Boost Charge
Tickle / Float Charge