AN9842: Implementing Tip and Ring Protection Circuitry For the HC5518X Ringing SLIC Family

Implementing Tip and Ring Protection Circuitry
For the HC5518X Ringing SLIC Family
TM
Application Note
September 1999
AN9842.1
Authors: Richard Whitehead, Dick Tung
Introduction
The secondary protection must protect the T and R ports
from the “let through” voltages and currents. Although
secondary protection schemes are application dependent,
Figure 1 shows a typical implementation for a single stage
ringing SLIC where through SLIC ringing is used. The circuit
usually consists of fuses, PTCs (poly switch), RFI
capacitors, diode bridges, and TVS devices such as the
Intersil SGT27S10. This combination of protection circuitry
must clamp the T and R ports to ground when a fault
condition is present that exceeds the maximum output
capabilities of the ringing SLIC. When the fault condition
disappears, normal operation must resume.
A very important segment of
the design of
telecommunications
equipment is proving
adequate surge protection
circuitry for the equipment terminals. System designers are
required to protect the system from secondary (let through)
disturbances as identified in GR-1089 - CORE, Issue 2,
Section 4. Developing the protection circuitry solution while
maintaining overall system performance and cost can often
be challenging. This application note describes circuitry
which could be used to meet the GR-1089, Section 4
requirements for the HC5518X family of ringing SLICs.
The “resettable” PTCs are current limiting devices which
increase in resistance when an applied fault condition
exceeds the specified trip limits of the PTC. When the PTC
is “tripped,” it remains in a high impedance state until the
fault is removed. Capacitors C 1 and C 2 provide a low
impedance path to ground for RFI transients. The diode
bridge is used to clamp positive surges to ground and steer
negative transients to the TVS which turns “on” and clamps
the T and R terminals to ground. With the appropriate
selection of these protection components, secondary
protection requirements specified by GR-1089 can be met
while maintaining overall system performance.
Basic Protection Circuit Description
Figure 1 illustrates a basic concept for primary and
secondary protection of telecommunications equipment
terminals where ringing SLICs are used. Although the
following discussions focus primarily on second level surge
protection, it is interesting to briefly discuss primary
protection and “let through” surges as defined by GR-1089.
Primary surge protection usually consists of a 3 mil carbon
block or gas tube (GDT). These are voltage and current
limiting devices that will “let through” surges of up to 2.5kV
peak surge (lightning) and 600VRMS (60Hz) power line
cross. Let through surge currents can range from 500A peak
(2µs x 10µs) lightning to 1A (600V RMS) power cross.
Consult GR-1089 for additional details concerning let
through surges for secondary protection.
PRIMARY
PROTECTION
Suggested Protection Circuitry for
HC5518x
Utilizing operational specifications provided by the HC5518X
data sheet and the GR-1089 requirements, the circuit
illustrated in Figure 2 can be implemented to protect the
SLIC from secondary surge levels.
VBH (-85V)
SECONDARY PROTECTION
CROWBAR
CLAMP TVS
EXPOSED
COPPER
PLANT
PROTECTION
RESISTORS
AND FUSE
0.002µF
100V
CARBON
BLOCKS OR
GAS TUBES
0.002µF
100V
TIP
RSLIC18
0.1µF
100V
RING
RFI CAPS
FIGURE 1. BASIC PROTECTION CIRCUIT
1
CAUTION: These devices are sensitive to electrostatic discharge; follow proper IC Handling Procedures.
1-888-INTERSIL or 321-724-7143 | Intersil (and design) is a trademark of Intersil Americas Inc.
Copyright © Intersil Americas Inc. 2001. All Rights Reserved
Application Note 9842
The circuit in Figure 2 is recommended for applications
where the high battery voltage (VBH) can range up to -85V.
The HC5518X data sheet specifies 35Ω per leg for
protection resistance. As shown in Figure 2, RP has been
divided into 3 separate resistors and equals 35Ω. The total
resistance of the PTC and RPT on RPR should equal 15Ω.
The PTC represents 5Ω of RP (total) and limits the fault
current to the TVS/diode bridge and the HC5518X.
Additionally 10Ω,1W resistors are placed between the diode
bridge and the PTC. These resistors provide additional
current limiting to the diode bridge/TVS and the HC5518X.
Finally, 20Ω, 1/2W resistors are placed between the diode
bridge and the HC5518X to provide the final current limiting
function to the SLIC. This arrangement provides the
necessary current limiting to the system, selection of lower
wattage resistors, and minimizes affects on circuit
performance.
To understand the selection of the protection devices an
examination of the requirements placed upon the HC5518X,
the TVS and the PTC should be reviewed.
HC5518X Protection Requirements During Fault
Conditions
1. HC5518X’s Trip and Ring ports must survive 100VPEAK
“residual” surges above ground or below VBH for 1µs
during 2/10 lightning tests. This represents the typical “let
through” lightning surge from the protection circuitry that
the SLIC will encounter.
2. HC5518X’s Tip and Ring ports must survive 3VPEAK “residual” surges above ground or below VBH during AC
power cross tests. This represents the typical “let
through” AC power cross surge from the protection circuitry that the SLIC will encounter.
TVS Selection
TVS devices are solid state SCR type structures that are
available in fixed or gate controlled breakover voltages
(VBO). The gate controlled version is best suited for the
ringing SLIC application since its gate can be tied to the
battery voltage enabling the TVS to track variations in
the battery supply. A “stopper” diode is placed in series
with the gate of the TVS to prevent the VBH power supply
from being shorted to ground whenever a fault condition
energizes the SCR protection device. Additionally, in multiline systems where power supplies are very robust, the
“stopper” diode serves to protect the SCR and prevent
disruption of service on the other lines. The Intersil
SGT27S10 gated TVS was selected using the following
criteria.
3. HC5518X must survive Tip and/or Ring faults to ground.
HC5518X Operational Conditions
1. Loop Current = 15mA to 45mA
2. Maximum ringing voltage = 83.4VPEAK (59VRMS)
3. Maximum On Hook Ringing Current = 42mARMS (5REN).
PTC must not open.
4. Maximum Off Hook Ringing Current = 254mARMS (5REN
+ RLOOP). PTC must not open before ring trip.
5. VBH = -85V, VBL = -24V, RP = 35Ωs/leg.
Using the conditions above, the selection of the protection
resistance (RP), the TVS, and the PTC can be determined.
Protection Resistance Configuration
VCC
T
(TR600-150)
PTC
RP1
RPT
5Ω
10Ω
D3
BGND
TIP
AGND
VCC
20Ω
D1
RSLIC18
5Ω
10Ω
D4
D2
20Ω
RING
R
PTC
(TR600-150)
RPR
SG1
SGT27S10
D5
RP2
VBH
VBL
VBH
VBL
CG
0.1µF
200V
FIGURE 2. RSLIC18 PROTECTION CIRCUIT FOR V BH = -85V APPLICATION
2
Application Note 9842
Selection of TVS for Lightning and Power Line
Cross
HC5518X Protection Circuit Surge Testing
Procedure
10/1000 waveform = 1000V, 40A (GR-1089)
The HC5518 protection circuit as shown in Figure 2 was
tested to GR-1089 requirements. The HC5518 was exposed
to each fault condition in all of its operating modes. Table 1
shows the operating modes for the HC5518X device. Using
the circuit shown in Figure 2, the appropriate test signal
generator and sequencing control is applied to the T and R
ports at the PTCs. For lightning surge tests, Table 2
identifies the tests to be performed and the procedure. For
AC power cross tests, Table 3 gives the tests to be
performed and the procedure.
2/10 waveform = 2500V, 125A (GR-1089)
Peak line voltage to ground (40A peak current) = 25V
(measured)
Peak line to TVS gate voltage (40A peak current) = -15V
(measured)
Maximum Line to ground voltage = -90V (GR-1089)
Maximum Gate to line voltage = -90V (GR-1089)
TABLE 1. RSLIC OP MODE CONTROL
Maximum gate current (10ms) = 1A (GR-1089)
Gate Trigger Current (Igt) = 150mA
OP MODE
F2
F1
F0
E0
BSEL
Holding Current = 100mA
Forward Active
L
L
H
H
H/L
PTC (Positive Temperature Coefficient Thermistor)
Selection
Reverse Active
L
H
H
H
H/L
Low Power Standby
L
L
L
H
H/L
Ringing
H
L
L
H
H/L
Tip Open
H
H
L
H
H/L
Forward Loop Back
H
L
H
H
H/L
Power Denial
H
H
H
H
H/L
For the HC5518X protection circuitry the TR600-150 was
selected. As a general rule of thumb, the PTC should have
the lowest off state resistance possible. This allows for ease
of matching to minimize affects on system performance.
Additionally the TR600-150 resistance is specified as 6Ω
which comprises part of the total protection resistance for
the HC5518X.
PTC Specifications
PTC Resistance = 5Ω to 12Ω at 20oC
1 Hour Post Trip Resistance = 20Ω at = 20oC
Three HC5518Xs were tested to all of the fault conditions
listed in Tables 2 and 3. Pre and post data was recorded for
each of the surge tests. The governing criteria for pass or fail
is given in the last Item of each of the test procedures.
PTC Holding Current = 83mA at 70oC
Checking Ringing Capability
55 Second Time To Trip at 20oC = 350mA
Once the protection circuitry has been selected and tested,
the ringing capability of the SLIC should be evaluated for
possible limitations. The HC5518X ringing capability was
tested under conditions illustrated in Figure 3. The input
ringing signal (sinewave) applied to the VRS pin was
adjusted for maximum peak voltage swing on Tip and Ring
while applying 1, 3, and 5 REN loads. The results of the
evaluation are shown in Table 4.
55 Second Time To Trip at 70oC = 193mA
Maximum Operating Voltage = 60V
Maximum Interrupt Voltage = 600V
Maximum Interrupt Current = 3A
With the selected components as shown in Figure 2, the
protection circuitry can be prototyped and tested to
GR-1089 requirements. It should be understood that
HC5518X protection circuit is not limited to the
recommended selections but any alternative selection
would require retesting to GR-1089.
3
Surge Test Results and Conclusion
Three HC5518X devices passed all of the fault conditions
applied as recommended by GR-1089. After each fault
condition was removed, the devices under test returned to
their normal operating state that was selected. The
protection circuitry as recommended in Figure 2 can be used
to meet specific requirements for secondary fault protection
identified in GR-1089.
Application Note 9842
TABLE 2. LIGHTNING SURGE TESTS
VOPEN
(RMS)
ISHORT
(AMP)
RS
(Ω)
WAVEFORM
(µs)
TEST
CONDITIONS
NO.
OF TESTS
EXPECTED
CURRENT
±1kV
100
10
10/1000
Tip to Source, Ring to Gnd
25 times
40A
±1kV
100
10
10/1000
Ring to Source, Tip to Gnd
25 times
40A
±1kV
100
10
10/1000
Tip and Ring to Source
25 times
40A
±2.5kV
500
5
2/10
Tip to Source, Ring to Gnd
10 times
125A
±2.5kV
500
5
2/10
Ring to Source, Tip to Gnd
10 times
125A
±2.5kV
500
5
2/10
Tip and Ring to Source
10 times
125A
TEST PROCEDURE FOR TEST NO. 1 TO 12
1. With PTC in circuit.
2. Collect pre-test data on open tip and ring voltage and loop current readings with 600Ω load for VBH and VBL mode and record the data.
3. Set the scope settings.
4. Store the VP waveforms on scope screen when first applying the test signal and record the data.
5. Continue the surge test until it is complete.
6. Collect post-test data on open tip and ring voltage and loop current readings with 600Ω load for VBH and VBL mode and record the data.
7. The DUT passes the test, if the difference between the pre and post-test data is less than 5%. Otherwise, the DUT fails the test.
TABLE 3. AC POWER CROSS TESTS
VOPEN
(RMS)
ISHORT
(AMP)
RS
(Ω)
TEST
CONDITIONS
TEST
DURATION
EXPECTED
CURRENT
50
0.330
150
Tip to Source, Ring to Gnd
15 minutes
300mA
50
0.330
150
Ring to Source, Tip to Gnd
15 minutes
300mA
50
0.330
150
Tip and Ring to Source
15 minutes
300mA
100
0.170
600
Tip to Source, Ring to Gnd
15 minutes
160mA
100
0.170
600
Ring to Source, Tip to Gnd
15 minutes
160mA
100
0.170
600
Tip and Ring to Source
15 minutes
160mA
200
0.330
600
Tip to Source, Ring to Gnd
1 sec, 60 times
320mA
200
0.330
600
Ring to Source, Tip to Gnd
1 sec, 60 times
320mA
200
0.330
600
Tip and Ring to Source
1 sec, 60 times
320mA
400
0.670
600
Tip to Source, Ring to Gnd
1 sec, 60 times
630mA
400
0.670
600
Ring to Source, Tip to Gnd
1 sec, 60 times
630mA
400
0.670
600
Tip and Ring to Source
1 sec, 60 times
630mA
600
1
600
Tip to Source, Ring to Gnd
1 sec, 60 times
950mA
600
1
600
Ring to Source, Tip to Gnd
1 sec, 60 times
950mA
600
1
600
Tip and Ring to Source
1 sec, 60 times
950mA
4
Application Note 9842
AC POWER CROSS TEST PROCEDURE
TEST PROCEDURE FOR TEST NO. 1, 2, 3, 4, 5, 6
TEST PROCEDURE FOR TEST NO. 7, 8, 9, 10, 11, 12
1.
With PTC in circuit.
1.
With PTC in circuit.
2.
Collect pre-test data on open tip and ring voltage and loop current 2.
readings with 600Ω load for VBH and VBL mode and record the data.
Collect pre-test data.
3.
Store the VP waveforms on scope screen when first applying the test 3.
signal and record the data.
Store the VP waveforms on scope screen when first applying the test
signal and record the data.
4.
Set storage scope to real time mode.
4.
Set storage scope to real time mode.
5.
Record the PTC time to trip data if PTC tripped.
5.
Record the thermal alarm data if SLIC went into thermal alarm within
1 minute.
6.
Record the thermal alarm data if SLIC went into thermal alarm.
6.
Replace the PTC with a 5Ω power resistor and set the timer to 1 second on, 2 seconds off.
7.
Collect the post-test data on open tip and ring voltage and loop cur- 7.
rent readings with 600Ω load for VBH and V BL mode and record the
data.
Collect the post-test data.
8.
The DUT passes the test, if the difference between the pre and post- 8.
test data are less than 5%. Otherwise, the DUT fails the test.
The DUT passes the test, if the difference between the pre and posttest data are less than 5%. Otherwise, the DUT fails the test.
VCC
VP
(TR600-150)
PTC
5Ω
RP1
RPT
10Ω
D3
BGND
TIP
AGND
VCC
20Ω
D1
REN
LOAD
RSLIC18
VRS
5Ω
VP
PTC
(TR600-150)
10Ω
D4
D2
20Ω
SG1
SGT27S10
RPR
D5
RP2
RING
VBH
CG
0.1µF
200V
VBL
D6
VBL
VBH
FIGURE 3. RINGING CAPABILITY TEST CIRCUIT
TABLE 4. RINGING CAPABILITY AT 1% THD
VBH
1 REN
3 REN
5 REN
-90V
87.5Vp
83.5Vp
80.5Vp
-85V
83.4Vp
82.0Vp
80.5Vp
-80V
77.0Vp
74.5Vp
71.0Vp
1 REN = 6kΩ + 8µF
5
3 REN = 2kΩ + 24µF
5 REN = 1.2kΩ + 40µF
Application Note 9842
Notes
6
Application Note 9842
Notes
7
Application Note 9842
All Intersil U.S. products are manufactured, assembled and tested utilizing ISO9000 quality systems.
Intersil Corporation’s quality certifications can be viewed at www.intersil.com/design/quality
Intersil products are sold by description only. Intersil Corporation reserves the right to make changes in circuit design, software and/or specifications at any time without
notice. Accordingly, the reader is cautioned to verify that data sheets are current before placing orders. Information furnished by Intersil is believed to be accurate and
reliable. However, no responsibility is assumed by Intersil or its subsidiaries for its use; nor for any infringements of patents or other rights of third parties which may result
from its use. No license is granted by implication or otherwise under any patent or patent rights of Intersil or its subsidiaries.
For information regarding Intersil Corporation and its products, see www.intersil.com
Sales Office Headquarters
NORTH AMERICA
Intersil Corporation
7585 Irvine Center Drive
Suite 100
Irvine, CA 92618
TEL: (949) 341-7000
FAX: (949) 341-7123
Intersil Corporation
2401 Palm Bay Rd.
Palm Bay, FL 32905
TEL: (321) 724-7000
FAX: (321) 724-7946
8
EUROPE
Intersil Europe Sarl
Ave. William Graisse, 3
1006 Lausanne
Switzerland
TEL: +41 21 6140560
FAX: +41 21 6140579
ASIA
Intersil Corporation
Unit 1804 18/F Guangdong Water Building
83 Austin Road
TST, Kowloon Hong Kong
TEL: +852 2723 6339
FAX: +852 2730 1433