EC centrifugal fan G1G170AB5380 ENU

EC centrifugal fan
G1G170AB5380
backward-curved, single-intake
with housing (large flange), Gas blower for condensing boilers
ebm-papst Landshut GmbH
Hofmark-Aich-Straße 25
D-84030 Landshut
Phone +49 (0) 871 707-0
Fax +49 (0) 871 707-465
[email protected]
www.ebmpapst.com
Nominal data
Type
G1G170AB5380
Motor
M1G074CF
Phase
1~
Nominal voltage
VAC
230
Frequency
Hz
50/60
Method of obtaining data
fa
Speed (rpm)
min-1
5830
Power consumption
W
360
Current draw
A
1.6
Min. ambient temperature
°C
-25
Max. ambient temperature
°C
55
Min. temp. of flow medium
°C
-25
Max. temp. of flow medium
°C
+80
Air flow
m3/h
645
Pressure increase
Pa
0
Sound pressure level
dB(A)
82
ml = Max. load · me = Max. efficiency · fa = Free air · cs = Customer specification · ce = Customer equipment
Subject to change
Data according to ErP Directive
01 Overall efficiency ηes
%
Actual
Req. 2015
58.8
45
02 Measurement category
A
03 Efficiency category
Static
04 Efficiency grade N
74.8
05 Variable speed drive
61
Yes
Data obtained at optimum efficiency level.
The ErP data is determined using a motor-impeller combination in a standardized measurement setup.
09 Power consumption Ped
kW
0.3
09 Air flow qv
m³/h
285
09 Pressure increase pfs
Pa
2000
10 Speed (rpm) n
min-1
6220
11 Specific ratio*
*
Specific ratio = 1 + pfs / 100 000 Pa
1.02
LU-57509
Webdatenblatt · Seite 1 / 2
ebm-papst Landshut GmbH · Hofmark-Aich-Straße 25 · D-84030 Landshut · Phone +49 (0) 871 707-0 · Fax +49 (0) 871 707-465 · [email protected] · www.ebmpapst.com
EC centrifugal fan
G1G170AB5380
backward-curved, single-intake
with housing (large flange), Gas blower for condensing boilers
Technical description
Weight
4.5 kg
Fan size
170 mm
Rotor surface
Painted black
Cover material
Polyflam RPP 374-ND CS1 (UL 97-V0)
Impeller material
Sheet aluminum
Housing material
Die-cast aluminum
Direction of rotation
Clockwise, viewed toward rotor
Degree of protection
IP20
Insulation class
"B"
Cooling hole/opening
On rotor side
Motor bearing
Ball bearing
Touch current according to IEC
60990 (measuring circuit Fig. 4,
TN system)
<= 3.5 mA
Electrical hookup
With plug
Motor protection
Thermal overload protector (TOP) internally connected
Approval
UL 507; CCC; CSA C22.2 No. 113
Webdatenblatt · Seite 2 / 2
ebm-papst Landshut GmbH · Hofmark-Aich-Straße 25 · D-84030 Landshut · Phone +49 (0) 871 707-0 · Fax +49 (0) 871 707-465 · [email protected] · www.ebmpapst.com