380 Volt DC Rack Mount Power Strips
High Voltage DC Rack Mount Power Strips with Fuse or Circuit Breaker Protection
PART: 74D-160FE12VE
The API Technologies 380VDC Rack Mount Power Strips are designed to be hard
wired into the main power infrastructure and provide a total of 30A or 60A of power
via Anderson Power Products connectors. The outlets are divided up into load banks
containing a choice of outlets based on size and are protected by a choice of fuses or
UL1077 breakers.
Features
380 Volts DC with of 30A or
60A options
Traditional DC power distribution units are mounted horizontally. In order save
valuable rack space for other critical devices, we created a design with a slim 0U
package that is mounted vertically as shown in the image below.
Overvoltage protection with a
choice of either Fuses or circuit
breakers
The API Technologies 380VDC Power Strip is a key component in modern DC
Data Center Solutions. 380VDC has the best balance of economics and safety for
standardized components. Using DC power in Data Centers reduces total cost of
ownership (TCO) by
1.73” wide saves valuable “U”
space. Available with or without a
power entry cord.
•
•
•
•
•
Reducing the number of power conversions lowers HVAC costs
Extends life of critical infrastructure
Lower infrastructure costs for data center space needs
Lower CAPEX on equipment
Lower OPEX maintenance and operating costs
By having a DC Data Center operators can simplify
the integration of on-site energy generation and
storage from alternative energy sources such as
wind and solar.
Mounted Virtically to save critical real
estate in the data center.
Panel Indicator with Poweron, LEDs
EMI filtering to protect against
noise and interference from other
electronic devices.
This product can be modified in
color, shape, outlet style, power
inputs, and more.
Basic Power Strip 1U Specifications
Part Number
Input Power
Output Power
KVA
Receptacle
Dimensions
W x H x D inch
Temp
range
Breakers
Input Plug/
Cord
74D-160FE12VE
380 VDC 60A
Max Total
380 VDC 60A
Total Load
22.8
3 x 4 APP
SAF-D-Grid
33 x 1.73 x 3.25
0 - 50 C
(3) x 20A 2
Pole Fuse
5’ (1.5m), #8/3
Type W cord
74D-160BE12VE
380 VDC 60A
Max Total
380 VDC 60A
Total Load
22.8
3 x 4 APP
SAF-D-Grid
33 x 1.73 x 3.25
0 - 50 C
(3) 2P-20A
UL1077
Circuit
Breaker
5’ (1.5 m), 3C
6AWG Type W
Cable
74D-160FE42VE
380 VDC 60A
Max Total
380 VDC 60A
Total Load
22.8
3 x 14 APP
SAF-D-Grid
70 x 1.73 x 3.25
0 - 50 C
(3) x 20A 2
Pole Fuse
10’ (3m), 3C
6AWG Type W
Cable
74D-160BE42VE
380 VDC 60A
Max Total
380 VDC 60A
Total Load
22.8
3 x 14 APP
SAF-D-Grid
70 x 1.73 x 3.25
0 - 50 C
(3) 2P-20A
UL1077
Circuit
Breaker
10’ (3m), 3C
6AWG Type W
Cable
74D-130FE18VC
380 VDC 30A
Max Total
380 VDC 30A
Total Load
11.4
2 x 9 APP
SAF-D-Grid
33 x 1.73 x 3.25
0 - 50 C
(2) x 5A 2
Pole Fuse
Connector
APP Saf-D-Grid
74D-130BE18VC
380 VDC 30A
Max Total
380 VDC 30A
Total Load
11.4
2 x 9 APP
SAF-D-Grid
33 x 1.73 x 3.25
0 - 50C
(2) 2P/5A
UL1077
Circuit
Breaker
Connector
APP Saf-D-Grid
74D-130FE24VC
380 VDC 30A
Max Total
380 VDC 30A
Total Load
11.4
3 x 8 APP
SAF-D-Grid
66 x 1.73 x 3.25
0 - 50 C
(3) x 10A 2
Pole Fuse
Connector
APP Saf-D-Grid
74D-130BE24VC
380 VDC 30A
Max Total
380 VDC 30A
Total Load
11.4
3 x 8 APP
SAF-D-Grid
0 - 50 C
(3) 2P/10A
UL1077
Circuit
Breaker
Connector
APP Saf-D-Grid
66 x 1.73 x 3.25
It has been reported that
a well designed DC data
center can save at least
15% in capital cost, and
20% in installation costs
and reduces the facility
footprint by at least 25%.