A. Input Characteristics: 1) Voltage: (100-127)/(200-250)VAC 2) Frequency: 50/60 Hz. 3) Line Current: 2 X 20A Maximum 4) Load Capacity: 2.30/4.60 KVA / INPUT; 4.60/9.20 KVA TOTAL 5) Overload Protection: (2) 2P/20A UL489 Circuit Breaker 6) Power Cord: NONE 7) Connector: 2X IEC 60320C20 8) Indicators: Power-on, LED LABEL B. Output Characteristics: 1) Voltage: (100-127)/(200-250)VAC 2) Current: 40A (Total Combined Load) 3) Outlets: 2x 12 IEC C13 C. Mechanical Characteristics: 1) Material: CRS 2) Finish: Powder Coat, Black, Fine Texture 3) Lettering: Silk-Screen, White/Epoxy 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: 1) Temperature: 32 - 122F (0 - 50C) C20 INPUT TYP 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, UL60950-1, CE CHANGE NOTICE 0 REV 33 in / 838.2 mm 0243-ENG 1.73 in / 43.9 mm 50 3.25 in / 82.6 mm 2) RoHS: Compliant to Directive 2002/95/EC DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 2/22/2008 Spectrum Management Systems 24X C13, DUAL INPUT, 0U PDU THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-240BUXEN-00 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA