72A 132BAXEN 10

A. Input Characteristics:
1) Voltage: 200-250VAC
2) Frequency: 50/60 Hz.
3) Line Current: 32A Maximum
4) Load Capacity: 7.36 KVA
5) Overload Protection: (2) 2P/16A UL489 Circuit Breaker
6) Power Cord: 10' (3m), #10AWG(5.25mm 2 )/3
7) Connector: IEC309-32A
8) Indicators: Power-on, LED
B. Output Characteristics:
1) Voltage: 200-250VAC
2) Current: 32A (Total Combined Load)
3) Outlets: 2x 12 IEC C13
C. Mechanical Characteristics:
1) Material: CRS
L
2) Finish: Powder Coat, Black, Fine Texture
3) Lettering: Silk-Screen, White/Epoxy
4) Storage Temp.: -(13) - 149F (-25 - 65C)
D. Operating Environment:
1) Temperature: 32 - 122F (0 - 50C)
2) Relative Humidity: 0 - 95% (Non-Condensing)
IEC309-32A
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, UL60950-1, CE
2) RoHS: Compliant to Directive 2002/95/EC
66 in / 1676.4 mm
3.25 in / 82.6 mm
0
REV
1.73 in / 43.9 mm
CHANGE NOTICE
2672-ENG
INFORMATIONAL LABEL
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
ANGLES ± 030'
DATE
4/30/2008
Spectrum
Management Systems
24X C13 0U PDU
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-132BAXEN-10
CODE IDENT
NO:
STATE COLLEGE,
PENNSYLVANIA