1. Input Characteristics a) Voltage: 200-250VAC b) Frequency: 50/60 Hz. c) Current: 30A Maximum (24A derated NA) d) Load Capacity: 4.8KVA e) Overload Protection: 2x 2P/15A UL498 Circuit Breaker f) Power Cord: 10’ (3m) 3C/10AWG g) Connector: L6-30P 2. Output Characteristics: a) Voltage: Single Phase, 200-250VAC b) Current: 15A per branch c) Outlets: 8x C13 per branch d) Two branch circuits 3. Mechanical Characteristics: a) Material CRS/G40 Galv. Coating b) Finish: Black Powder Coat c) Lettering: White Silk-Screen d) Storage Temp: -13 to 149F (-25 to 65C) 4. Operating Environment: a) Temperature: 32 to 122F (0 - 50C) b) Relative Humidity: 0 to 95% (Non-Condensing) c) Elevation: 0 to 10,000FT (0 to 3048m) 5. Regulatory Conformance: a) Safety Agency: UL/cUL, UL60950-1 2nd Edition, CE b) RoHS: Compliant to Directive 2002/95/EC 15 34 16 " 887.98 6. Power Meter 13 a) Displays AC Volts, Amps, Watts, and Power Factor 16 " 20.64 b) User-selectable display modes: continuous auto cycling, or fixed reading c) True-RMS readings of complex voltage and current waveforms 35.960 913.38 .500 12.70 DETAIL A SCALE 2 : 1 .250 6.35 1.730 43.94 3.809 96.74 REV 00 LABEL PLACEMENT DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. ECN 002057-SPMS CHANGE NOTICE 3.251 82.57 33.000 838.20 DRAWN: JWH TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL ± 1/64" DECIMAL .XX ± .02 DECIMAL .XXX ±.010 Management Systems ANGLES ± 0.30 DATE 11/22/2010 Spectrum THIRD ANGLE PROJECTION SHEET: 1 OF 1 METERED PDU, 30A, 200-250V 72A130BMPEA-10 ENGINEER: LA STATE COLLEGE, PENNSYLVANIA