LITTELFUSE 235001

Axial Lead and Cartridge Fuses
Designed to UL/CSA Standards
RoHS
Pb
5 x 20 mm Fast-Acting Fuse 235 Series
U® L
®
• Designed to UL/CSA/ANCE 248 Standard.
• Available in Cartridge and Axial Lead Format.
• Available in ratings of 0.100 to 6 amperes.
• RoHS compliant and Pb-free version available, add XP suffix to
standard catalog number
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
100%
135%
200%
Opening
Time
4 hours, Minimum
1 hour, Maximum
5 second, Maximum
INTERRUPTING RATING:
0.10-1A
10,000 amperes at 125 VAC, 0.7-0.8 power factor
35 amperes at 250 VAC, 0.7-0.8 power factor
1.25A-3.15A 10,000 amperes at 125 VAC, 0.7-0.8 power factor
100 amperes at 250 VAC, 0.7-0.8 power factor
4A-6A
10,000 amperes at 125 VAC, 0.7-0.8 power factor
RoHS compliant and Pb-free version available, add XP suffix to
standard catalog number
Catalog
Number
235.100
235.125
235.200
235.250
235.300
235.400
235.500
235.600
235.700
235.800
235 001
235 1.25
235 01.6
235 002
235 02.5
235 003
235 004
235 005
235 006
424
Ampere
Rating
.100
.125
.200
.250
.300
.400
.500
.600
.700
.800
1
1.25
1.6
2
2.5
3
4
5
6
cycles –65°C to +125°C)
Vibration: MIL-STD-202F Method 201A
Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative
ORDERING INFORMATION:
Nominal
Voltage Resistance
Rating Cold Ohms
250
8.40
250
5.75
250
3.15
250
2.25
250
1.60
250
1.08
250
0.455
250
0.318
250
0.263
250
0.195
250
0.153
250
0.106
250
0.0775
250
0.0600
250
0.0438
250
0.0348
125
0.0248
125
0.0185
125
0.0150
ENVIRONMENTAL SPECIFICATIONS:
Operating temperature: -55˚C to 125˚C
Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5
Nominal
Melting I2t
A2 Sec.
0.00160
0.00280
0.00890
0.0170
0.0330
0.0600
0.0710
0.115
0.160
0.260
0.480
1.12
2.08
2.72
5.59
8.62
17.60
28.15
48.60
humidity (95%) and elevated temperature (40°C) for 240 hours.
Salt Spray: MIL-STD-202F Method 101D, Test Condition B
PHYSICAL SPECIFICATIONS:
Material: Body: Glass
Cap: Nickel Plated Brass
Leads: Tin Plated Copper
Terminal Strength: MIL-STD-202F Method 211A,
Test Condition A
Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A
Terminal strength: MIL-STD-202F Method 211A, Test Condition A
Product Marking: Cap 1: current and voltage rating.
Cap 2: Agency approval markings.
Packaging: Available in Bulk (v=5, H=100, M=1000 pcs/pkg) or on
Tape/Reel (MRET1=1000 pcs/reel).
w w w. l i t t e l f u s e . c o m
Axial Lead and Cartridge Fuses
Designed to UL/CSA Standards
RoHS
Pb
5 x 20 mm Fast-Acting Fuse 235 Series
U® L
®
Agency Approvals
20+0.5
Agency Approvals
E10480
JDYX
File No.
Cert. Class No.
029862
LR1422-01
H
D
J
1A – 3A 250V 100A
4A & 5A 125V 10000A
6A
125V 500A
5.1+0.6
0235.100 XE2
to
0235.400 XE2
100mA – 400mA
500mA – 3A
4A – 6A
0235.500 XE2
to
0235006.XE2
100mA – 6A
5.1+0.6
6.0 MAX
22.5 MAX
40
0.65
5.8 MAX
22.5 MAX
40
0.65*
All dimensions in mm
Notes:
* Ratings above 6.3A
ø0.8 mm dia lead
1 For RoHS compliant parts
add suffix 'XP'
2 For RoHS compliant parts
add suffix 'P'
11
Average Time Current Curves
AXIAL LEAD AND
CARTRIDGE FUSES
®
Listed File No.
Guide No.
1A – 3A 250V 100A
4A & 5A 125V 10000A
6A
125V 500A
0.200A
0.250A
0.300A
0.400A
0.500A
0.600A
0.700A
0.800A
1A
1.25A
1.6A
2A
2.5A
3A
4A
5A
6A
U® L
G
C
I
0.100A
0.125A
Certificate No. SU05001-3007
SU05001-2002
SU05001-2003
5.2+0.1
-0.2
02350001
10000
1000
100
TIME IN SECONDS
Certificate No. Cartridge
NBK290502-E10480
NBK280602-E10480
NBK290502-E10480
Leaded
NBK290502-E10480
NBK280602-E10480
NBK290502-E10480
Ampere Range
10
1
0.1
0.01
0.1
1
10
100
1000
CURRENT IN AMPERES
w w w. l i t t e l f u s e . c o m
425