General Cable Brand THHN

SPEC 5290A
Aluminum Building Wire
May, 2015
THHN/THWN-2 High Speed (HS)
PVC, Low-Voltage Power
600 V, UL Type THHN/THWN-2, Single Conductor, Aluminum
Features:
Product Construction:
Conductor:
• Low friction Nylon jacket provides easy pulling
• 1/0 AWG and larger are rated for cable tray use
• Rated Gasoline and Oil Resistant II
• Resistant to abrasion, acids, alkalines, ozone,
and water
• For THHN/THWN-2 applications, the conductor
is appropriate for wet or dry locations not to
exceed 90°C
• Sequential foot markings every 2 feet for easy
measuring
• Sunlight-resistant for 1/0 and larger, black only
Print:
For 6 AWG thru 1 AWG:
• GENERAL CABLE® MI (MM)/(YYYY) LOW
FRICTION THHN/THWN-2 (UL) 4 AWG
(21.2 mm2 LOGO) COMPACT AL GRI AND GRII
SUN RES 600 V VW-1 OR AWM MADE IN USA
For 1/0 and larger, black only:
• GENERAL CABLE® MI (MM)/(YYYY) LOW
FRICTION THHN/THWN-2 (UL) 1/0 AWG
(53.5 mm2 LOGO) COMPACT AL GRI AND GRII
SUN RES FOR CT USE 600 V OR AWM MADE
IN USA
• 6 AWG thru 700 kcmil bare annealed stranded
aluminum alloy (8000 Series) per ASTM B800,
ASTM B801 and ASTM B836
Insulation:
• Premium-grade flame-retardant, heat- and
moisture-resistant Polyvinyl Chroride (PVC)
Jacket:
• Tough Polyamide (Nylon)
Compliances:
Industry Compliances:
• ASTM B800, B801 and B836
• UL Standard 83 – THHN/THWN-2
• ICEA S-95-658/NEMA WC70
• NEC® Article 310
• RoHS Compliant
Flame Test Compliances:
• UL 2556 VW-1 rated through 1 AWG
• UL 2556 CT USE 1/0 and larger
Applications:
• General purpose building wire for services,
feeders and branch circuits
• Conduit and raceways
• 1/0 and larger for cable tray use
INSULATION
THICKNESS
SIZE
NUMBER
OF WIRES
JACKET THICKNESS
NOMINAL
CABLE O.D.
ALUMINUM
WEIGHT
mm²
6
13.3
7
0.030
0.762
0.005
0.127
0.239
6.071
25
36
38
55
55
4
21.2
7
0.040
1.016
0.006
0.152
0.305
7.747
39
57
61
89
75
2
33.6
7
0.040
1.016
0.006
0.152
0.360
9.144
63
91
90
131
100
1
42.4
8
0.050
1.270
0.007
0.178
0.412
10.465
79
115
119
173
115
1/0
53.5
10
0.050
1.270
0.007
0.178
0.451
11.455
99
145
145
211
135
2/0
67.4
12
0.050
1.270
0.007
0.178
0.468
12.395
125
182
177
258
150
3/0
85
16
0.050
1.270
0.007
0.178
0.535
13.589
125
230
216
314
175
199
mm
INCHES
mm
INCHES
mm
kg/km
LBS/
1000 FT
AMPACITY(1)
90°C
AWG or
kcmil
INCHES
LBS/
1000 FT
NET
WEIGHT
kg/km
TYPE THHN/THWN-2 90°C WET OR DRY LOCATIONS
4/0
107
19
0.050
1.270
0.007
0.178
0.584
14.834
290
265
386
205
250
127
23
0.060
1.524
0.008
0.203
0.650
Phone: 888-593-3355
16.510
235
342
317
461
230
300
152
22
0.060
1.524
0.008
0.203
0.702
17.831
282
411
373
543
260
350
177
26
0.060
1.524
0.008
0.203
0.743
18.872
329
479
428
623
280
400
203
37
0.060
1.524
0.008
0.203
0.795
20.193
376
547
469
682
305
500
253
37
0.060
1.524
0.008
0.203
0.872
22.149
471
685
574
835
350
600
304
61
0.070
1.778
0.009
0.229
0.971
24.663
565
822
696
1013
385
750
380
61
0.070
1.778
0.009
0.229
1.066
27.076
70
102
852
1240
435
www.generalcable.com
Dimensions and weights are nominal; subject to industry tolerances.
(1) Ampacities per 2014 NEC Table 310.15(B)(16).
Phone: 888-593-3355