Product datasheet QTP-FC 1X55 QUICKTRONIC | ECG for circular FL 16 mm Areas of application _ Emergency lighting systems acc. to EN 50172 / DIN VDE 0108-100 _ Open-plan offices, corridors and storage rooms _ Public buildings _ Suitable for luminaires of protection class I __ Product benefits _ Long lamp life _ No adverse effect from frequent on/off switching _ Automatic restart after lamp replacement _ Perfect lamp start for applications with motion sensors _ Separate installations thanks to optional cable clamp for K2 and K3 casings _ VDE/VDE EMC certified system Product features _ Supply voltage: 220…240 V _ Line voltage: 198…264 V _ Line frequency: 0 Hz | 50 Hz | 60 Hz _ Lamp start with optimum filament preheating _ Energy Efficiency Index EEI: A2 BAT _ Automatic shutdown of defective lamps and at end of life (EoL) _ Lamp operation: to EN 60929 _ Safety: to EN 61347-2-3 June 13, 2016, 08:09:09 QTP-FC 1X55 © 2016, OSRAM GmbH. All rights reserved. Page 1 of 4 Product datasheet Technical data Electrical data Input voltage AC 198…264 V Nominal voltage 220…240 V Mains frequency 50…60 Hz Input voltage DC 176…264 V Operating frequency 40…50 kHz Max. ECG no. on circuit breaker 10 A (B) 11 1) Max. ECG no. on circuit breaker 16 A (B) 19 1) 1) Type B Light technical data Starting time 1.0 s 1) 1) If there is a temporary interruption in the power supply (< 0.5 s), the lamp will start within 0.3 s Dimensions & weight __ Length 103.0 mm Width 67.0 mm Height 31.0 mm Mounting hole spacing, length 94.0 mm Mounting hole spacing, width 67.0 mm Product weight 135.00 g Cable cross-section, output side 0.5…1.5 mm² Cable cross-section, input side 0.5…1.5 mm² Temperatures & operating conditions Ambient temperature range -20…+50 °C Permitted rel. humidity during operation 5…85 % June 13, 2016, 08:09:09 QTP-FC 1X55 © 2016, OSRAM GmbH. All rights reserved. Page 2 of 4 Product datasheet Lifespan 50000 h 1) ECG lifetime 1) At T case = 75°C at T point / 10% failure rate c Capabilities Suitable for fixtures with prot. class I / II End of lamp life safety shutdown EOL T.2 Certificates & standards Approval marks – approval VDE / VDE-EMC / ENEC 10 / GOST / RCM EEI – Energy Label A2 BAT Standards Acc. to EN 61347-2-3/IEC 61347-2-3/Acc. to EN 55015:2006 + A1:2007/CISPR 15/Acc. to EN 61000-32/IEC 61000-3-2/Acc. to EN 61547/IEC 61547 Protection class III Download Data File Certificates ENEC-VDE-Marks approval __ Declarations of conformity Declaration of conformity QTP-FC Installation/Operation notice Technical guide - ECGs for T5-lamps Operating instructions EAC QTP-FC Logistical Data Product code Product description Packaging unit (Pieces/Unit) Dimensions (length x width x height) Volume Gross weight 4008321537041 QTP-FC 1X55 Shipping carton box 20 355 mm x 96 mm x 220 mm 7.50 dm³ 3240.33 g The mentioned product code describes the smallest quantity unit which can be ordered. One shipping unit can contain one or more single products. When placing an order, for the quantity please enter single or multiples of a shipping unit. Disclaimer Subject to change without notice. Errors and omission excepted. Always make sure to use the most recent release. June 13, 2016, 08:09:09 QTP-FC 1X55 © 2016, OSRAM GmbH. All rights reserved. Page 3 of 4 Product datasheet QTP-FC 1X55 QUICKTRONIC | ECG for circular FL 16 mm Product name Lamp group Nominal current Nominal wattage + Power loss Luminous flux at 35 °C Number of lighting outlets QTP-FC 1X55 DULUX L 55 W 0.26 A 59.00 W 4800 lm 1 DULUX L 55 W CONSTANT 0.26 A 59.00 W 4800 lm 1 DULUX L 55 W XT 0.26 A 59.00 W 4800 lm 1 FC 55 W 0.26 A 59.00 W 4200 lm 1 __ June 13, 2016, 08:09:09 QTP-FC 1X55 © 2016, OSRAM GmbH. All rights reserved. Page 4 of 4