MJ-4A(TM) and MJ-4B(TM) Voltage Regulator Control Panel Installation and Operations Manual Quick Alert High Band Reverse Power Flow In Band Raise/ Lower Low Band Cancel Reset Remote Auto Inhibit Tap Control Status Max Min Save Change Remote Disabled Alert Menu Op Count Maintenance Accu/Stat MJ – 4A Data Port Line Drop Compensation Regulation Setting Band width Voltage Level Time Delay Resis tance Voltage Reduction Control VLC Neutralite Drag Hands Test Reset Tap Control Power Normal Auto Raise Off (By pass Position) External Ground 120 VAC Reac tance Voltage Limit Control VRC Off +/- Off ( By pass Position ) Manual Remote / Local External Sensing Power 0.75A 6.0A 6.0A (By pass Position) Lower U2 P2 Load Voltage (unscaled) Ground Voltage Fuses Manual No. 21-115-527-023 rev02 Siemens Energy, Inc. DANGER Hazardous voltage and high-speed moving parts. Will cause death, serious personal injury, or equipment damage. Always de-energize and ground equipment before maintenance. Read and understand this instruction manual before using equipment. Maintenance should be performed only by qualified personnel. The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions. Follow all safety instructions contained herein. IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes at any time without notice of obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material, or both, the latter shall take precedence. QUALIFIED PERSON For the purposes of this manual, a qualified person is one who is familiar with the installation, construction, or operation of the equipment and the hazards involved. In addition, this person has the following qualifications: (a) is trained and authorized to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices. (b) is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety procedures. (c) is trained in rendering first aid. NOTE These instructions do not purport to cover all details or variations in equipment, not to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local sales office. The contents of the instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Power Transmission & Distribution, Inc. The warranty contained in the contract between parties is the sole warranty of Siemens Power Transmission & Distribution, Inc. Any statements contained herein do not create new warranties or modify the existing warranty. DANGER WARNING CAUTION Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. 1 Introduction........................................ 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 About This Manual ............................... 1 Features of the MJ-4A & MJ-4B Control Panels .................................................... 1 Mounting on Siemens Regulators ...... 2 Mounting on Cooper Regulators......... 2 Mounting on GE Regulators ................ 2 Mounting onto LTCs ............................. 2 Support Documentation ...................... 2 Siemens Website.................................. 2 Control Panel Type................................ 2 2 Using the MJ-4A & MJ-4B Operator Panel and Controls ............................ 3 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 Introduction to the Front Panel............ 5 Sixteen-Character Display Screen ...... 5 Data Display .......................................... 5 Indicators .............................................. 8 Switches ...............................................10 Binding Posts .......................................11 Fuses.....................................................11 Terminal Strip Connections ............... 12 Local Data Port.................................... 14 3 Viewing and Changing MJ-4A & . . MJ-4B Data Items ............................ 15 3.1 3.2 3.3 3.4 3.5 Viewing Data Items ............................ 15 Understanding Menus ....................... 15 Using the Menu Selection Keys to View Data Items ........................................... 15 Changing Data Items.......................... 16 Using the Fast-Path Keys to View/ Change Data Items ............................. 17 4 Setting Up the MJ-4A & MJ-4B Control Panel.................................... 18 4.1 4.2 4.3 Setup—Overview................................ 18 Setup for Retrofit Panels .....................19 Defining Your Regulator— the <CONFIGURE> and <ADV CONFIGURE> Menus...........................19 4.4 Setting Control Levels— the <REGULATOR> Menu................... 28 4.5 Activating Data Logging— the <LOG SETUP> Menu .................... 31 4.6 Password Security Protection— the <PASSWORD> Menu.................... 32 4.7 Communications Definition— the <COMMUNICATIONS> Menu...... 35 4.8 Regulator Maintenance— the <MAINTENANCE> Menu ............. 37 4.9 Hardware Configuration— the <DIAGNOSTICS> Menu ............... 37 4.10 Setting up the Quick Key.................... 38 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data ...............39 5.1 5.2 5.3 5.4 Source and Load Definitions ............. 39 P2 Voltage Calculation........................ 39 Meter Data—the <METER> Menu...... 39 Demand Data— the <DEMAND> Menus ...................... 41 5.5 Event Log - the <EVENT LOG> Menu 41 5.6 Interval Log — the <INTERVAL LOG> Menu .................................................... 42 5.7 Operation Counter Data the <COUNTERS> Menu..................... 43 5.8 Alerts—the <Alert> Menu................... 44 5.9 Harmonics Data— the <HARMONICS> Menu .................. 45 5.10 Local Data Port— the <COMMUNICATIONS> Menu ...... 45 5.11 VRC Status - the <REGULATOR> Menu . .............................................................. 45 6 MJ-4A & MJ-4B Control Panel Automatic Mode...............................46 6.1 6.2 6.3 6.4 6.5 MJ-4A & MJ-4B Control Modes......... 46 Overview of Automatic Control Algorithm ............................................ 47 Voltage Sensing and Correction ........ 48 Voltage Limit Control.......................... 48 Reverse Power Flow ........................... 48 7 Software for Communicating with the MJ-4A & MJ-4B Control Panel ........54 7.1 7.2 Communications Software ................ 54 Uploading New MJ-4A & MJ-4B Software .............................................. 54 8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting ...............................55 8.1 8.2 8.3 8.4 8.5 8.6 8.7 Introduction......................................... 55 Visual Inspection................................. 55 Troubleshooting Based on Alert Messages ............................................ 56 Voltage and Current Calibration ........ 56 MJ-4A & MJ-4B Self Testing .............. 57 Communications Module Troubleshooting.................................. 57 Tap Tracking ........................................ 57 A Specifications ...................................58 B Physical Installation on Siemens Regulators.........................................59 C Regulator Control Diagrams............61 D Menu Parameters .............................63 Siemens Energy, Inc. D.1 D.2 D.3 <CONFIGURE> Menu: Leading and Lagging Regulators....... 63 <REGULATOR> Menu: Line Drop Compensation ................... 63 <CONFIGURE> Menu: Transformer Polarity ........................... 65 E Hazards of Bypassing a Regulator off Neutral ..............................................69 F Communications Module Installation. . ..........................................................70 G Menu Structure Quick Reference....72 H MJ-4A & MJ-4B Firmware Versions.... .. ......................................................... 74 I Terminal Strip Wiring.......................75 J MJ-4A & MJ-4B Jumpers and Battery Replacement..................................... 76 J.1 J.2 MJ-4A & MJ-4B Jumpers ................... 76 Battery Replacement........................... 77 K Terminal Strip Connections.............78 L MJ-4A & MJ-4B Operating Procedures........................................81 1 Introduction 1 Introduction The MJ-4A(TM) and MJ-4B(TM), here after referred to collectively as MJ-4(TM) is a Voltage Regulator Control Panel, which is a members of the Siemens Accu/Stat® series of digital controls, designed for use with many regulators and load tap changer models. Note: This manual describes features embodied in MJ-4 software version 4.10 Although the MJ-4 Control Panel includes some new functions, its operational characteristics are similar to those of earlier-model Accu/Stat MJ-1A, 2A, 3, 3A, MJ-X, and MJXL controls. It is electrically and mechanically interchangeable with these controls. This section briefly describes the standard MJ-4 Control Panel features and functions. Voltage Reduction Control, Voltage Limit Control, six Power Flow modes, and Data Logging are all standard features of the MJ-4 Control Panel. In addition to manual and automatic voltage monitoring and control, the MJ-4 Control Panel also offers full remote monitoring and control capability. Via a communications link, a remote operator can monitor operating conditions and adjust setpoints or command tap changes—just as if he/she were locally operating the controls. When equipped with an optional Communications Module, the MJ-4 Control Panel provides remote communications and SCADA (Supervisory Control And Data Acquisition) compatibility. Please refer to the MJ-4 Communications Module Installation Manual for an in-depth treatment of the Communications Module. The regulator control function has two operating modes— manual and automatic. Remote control can be enabled or disabled for each of these operating modes. The operating modes and remote control settings are described in Section 2.5. • Manual control. In Manual mode, the operator directly controls the regulator tap changer and uses this mode to enter regulator setpoints for automatic control. • Automatic control. In Automatic mode, the microprocessor controls the regulator tap changer, based on setpoints stored in memory. • Remote control. If enabled, this setting permits a remote operator to change operational values and setpoints as well as to monitor operational values. If disabled, a remote operator can only monitor operational values. 1.1 About This Manual This manual is designed to help you become acquainted with all aspects of the MJ-4 Control Panel. The manual starts with the operator panel and controls, followed by physical installation considerations, setup procedures, day-to-day operations, and finally, troubleshooting. The Appendices provide further information about MJ-4 Control Panel operation and setup. Siemens Energy, Inc. 1.2 Features of the MJ-4A & MJ-4B Control Panels Display Panel and Operator Controls Operator input to the MJ-4 Control Panel is accomplished through a set of touch-keys. MJ-4 output is presented in plain text through a sixteen-character alphanumeric display panel. For status items, such as Voltage Reduction and Voltage Limit, indicators provide a quick-glance summary of MJ-4 Control Panel operating conditions. Metering The MJ-4 Control Panel maintains and presents operational data to help you monitor system operation. Instantaneous and demand values (along with minimum and maximum for each) are readily available. Data Logging The Data Logging function maintains historical data for subsequent review and analysis. This data can be very useful in the assessment of load characteristics by time of day or season; the reconstruction of system problems; and the improvement of the overall efficiency of the power distribution system. Voltage Limit Control Voltage Limit Control (VLC) automatically maintains regulator output voltage within preset high and low limits. Line Drop Compensation Line Drop Compensation (LDC) models the resistive and reactive voltage drop of the line. The resulting model is used by the microprocessor to correct regulator output voltage for the effects of line drop between the regulator and the load. Voltage Reduction Control Voltage Reduction Control (VRC) reduces output voltage and can be activated automatically, manually, or remotely. Reverse Power Flow Detection and Operation In many systems, power only flows in one direction; however, in some systems power flow reverses from time to time. To accommodate power flow reversal, the MJ-4 Control Panel monitors power flow direction and adjusts its operation accordingly. Six different Power Flow Modes allow flexibility in selecting a control algorithm which best matches the power flow needs of the system. 1 1 Introduction Communications 1.7 The MJ-4 panel provide local communications via the front-panel data port, and supports remote communications with the MJ-4 Communications Module. In addition to this manual, Siemens provides a number of supporting documents that provide details about the use of Siemens regulators and control products. Barrier Terminal Strips Contact your Siemens representative or visit the Siemens T&D website for a complete list of Application Notes and other supporting documentation. Terminal contacts on the back of the MJ-4 Control Panel allow for external control over certain functions such as VRC activation and tap changing. These terminals can be used to provide an electrical interface to a SCADA system for remote control applications and/or other desired control functions. 1.3 Mounting on Siemens Regulators The MJ-4 Control Panels are mechanically and electrically compatible and interchangeable with earlier MJ, IJ and SJ series and earlier control units. They can be mounted in the existing enclosure by simply swinging the control to be replaced outward on its hinges, disconnecting the polarized disconnect switch (PDS), then removing the unit and inserting the new unit. (See Appendix B.) 1.4 Mounting on Cooper Regulators A retrofit kit is available for mounting the MJ-4 Control Panels on Cooper regulators. The kit includes all of the necessary hardware and complete instructions for mounting and connecting the MJ-4 to the regulator. The retrofit is accomplished without the necessity of replacing the waterproof housing. See the Retrofitting Cooper Regulators Application Note for details. Contact your Siemens representative for ordering information. 1.5 Mounting on GE Regulators 1.8 Support Documentation Siemens Website The Siemens website contains information about all of the Siemens transmission and distribution products, including regulators and controls. All voltage regulator products can be located on the Voltage Regulator product page after navigating to the Siemens PT&D website below: http://www.usa.siemens.com/energy Browse this section for information about the regulators, regulator accessories, upgrades, downloadable files, and more. 1.9 Control Panel Type There are two models of Voltage Regulator control panels described in this manual: the MJ-4A and the MJ-4B. The MJ-4A has discrete three position switches for the Auto-Manual functionality and Raise/Lower. The MJ-4B has push buttons for the above functionalities. This manual is written describing the features of the control panel in general and in specific sections the differences between the MJ-4A and MJ-4B are explained. A retrofit kit is available for mounting the MJ-4 Control Panel on GE regulators. The kit includes all of the necessary hardware and complete instructions for mounting and connecting the MJ-4 to the regulator. The retrofit is accomplished without the necessity of replacing the waterproof housing. See the Retrofitting GE. Regulators Application Note for details. Contact your Siemens representative for ordering information. 1.6 Mounting on Load Tap Changers A retrofit kit is available for mounting the MJ-4 Control Panels on LTCs. The kit includes all of the necessary hardware and complete instructions for mounting and connecting the MJ-4 to the LTC. Contact your Siemens representative for ordering information. 2 Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Quick Key Quick Indicators 16 Character Display Change Keys Alert High Band Remote Disabled Reverse Power Flow In Band Remote Auto Inhibit Raise/Lower Low Band Menu Selection Scroll Keys Tap Control Status Menu Alert Status Fast Path Key Cancel Reset Change Max Min Save Alert Op Count Maintenance Accu/Stat MJ – 4A Data Port Data Port Regulator Fast Path Keys Bandwidth VRC Active Indicator Line Drop Compensation Regulation Setting Voltage Level Time Delay Resistance Voltage Reduction Control VLC Neutralite Neutrallite Indicator Drag Hands Test Neutralite Test Key Reset Power Normal Auto Off (By pass Position) (By pass Position) External Tap Control Remote / Local Ground 120 VAC 6.0A 0.75A Fuses Remote/Auto Manual Switch (By pass Position) Lower Manual External Sensing External Power Binding Posts Line Drop Compensation Fast-Path Keys U2 P2 Load Voltage (unscaled) VLC Indicator Drag Hands Reset U2 P2 Key Raise Lower Switch Voltage Calibration Binding Posts Power 6.0A VLC Select Fast-Path Key Remote / Local button Raise Off Off Power Switch Reactance Maintenance Fast Path Key Voltage Limit Control VRC VRC Select Fast Path Key +/- Op Counter Fast Path Key Ground Voltage Power Fuse Sensing Fuse External Power Fuse Figure 2.1 MJ-4A Front Panel Siemens Energy, Inc. 3 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Quick Key Quick Indicators 16 Character Display Change Keys Alert High Band Remote Disabled Reverse Power Flow In Band Remote Auto Inhibit Raise/Lower Low Band Tap Control Status Regulator Fast Path Keys Cancel Reset Change Max Min Save Alert Maintenance Accu/ Stat MJ – 4B Line Drop Compensation Regulation Setting Voltage Level Time Delay Resistance Voltage Reduction Control VRC Select Fast Path Key +/- Reactance Op Counter Fast Path Key Maintenance Fast Path Key Line Drop Compensation Fast-Path Keys Voltage Limit Control VLC VRC Neutralite Neutrallite Indicator Neutralite Test Key Op Count Data Port Bandwidth VRC Active Indicator Menu Alert Status Fast Path Key SIEMENS Data Port Menu Selection Scroll Keys Drag Hands Test Reset VLC Select Fast-Path Key VLC Indicator Drag Hands Reset Tap Control Remote / Local button Power Switch Auto / Manual button Power Normal Remote / Local Raise Raise Off (By pass Position) Auto / Manual External Lower External Sensing U2 P2 Load Voltage (unscaled) Power External Power Fuse 6.0A 0.75A Fuses 6.0A Lower Voltage Calibration Binding Posts External Power Binding Posts Ground 120 VAC U2 P2 Key Ground Voltage Power Fuse Sensing Fuse Figure 2.2 4 MJ-4B Front Panel Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls 2.1 Introduction to the Front Panel The Front Panel (Figure 2.1and 2.2) provides access to all controller information. Configuration settings, setpoint adjustments, and data requests are entered through a set of large touch-keys. Front panel output devices include a number of indicator lights (LEDs) and a sixteen-character alphanumeric display screen. The front panel is logically divided into three areas from top to bottom: The top third of the front panel contains various indicator lights, an RS-232 serial port for local data communication, and a sixteen-character display screen. Also included in this area are touch-keys for the selection and modification of setpoints and data. The keys to the right of the display screen select specific readings or settings; the keys below the display screen can be used to change the selected value. This section also contains the Quick, Op Count, and Messages fast-path keys. The middle third of the front panel includes a group of special fast-path keys that provide direct access to frequently-used functions (Regulation Setting, Line Drop Compensation, Voltage Reduction Control, Voltage Limit Control, Neutralite Test, and Drag Hands Reset). In the bottom third, the MJ-4A Panel has mode and raise lower switches, whereas the MJ-4B panel has mode push buttons for the same, both panels have a power switch, binding posts for the attachment of external power and metering equipment, and controller fuses. 2.3.1 Menu Selection and Change Keys Use the Menu Selection and Change keys, located in the top third of the front panel, to view and change controller setpoints and data items. To view a specific data item, you must first select the Menu that contains that item. For example, meter readings are selected from the <METER> Menu; setpoints are selected from the <REGULATOR> Menu. Once the correct Menu is selected use the Scroll keys to step through the data items in that Menu until the desired data item is viewed on the display screen. (For details about the Menus, see Chapter 3 and Appendix G.) Menu Key Menu Press this key once to return to the top of the current Menu. To return to the start of all Menus from any position in any Menu press this key twice. Scroll Keys This chapter describes each of the front panel controls and explains how you can use them to select, view, and change stored data. For more detailed information about the functions provided by these controls, read chapters 4 and 5. 2.2 Sixteen-Character Display Screen The microprocessor presents information to the operator by way of a sixteen-character alphanumeric display screen. This display screen presents both alphabetic and numeric characters in plain text, eliminating the need for special codes. The display screen uses high contrast, active LED technology that is easy-to-read in direct sunlight as well as in low light conditions. 2.3 Data Display Front panel touch-keys provide easy access to all data stored in MJ-4 Control Panel memory. To view or change a given data item you must first display it. Two types of touch-keys are provided to help you display a data item: • Use the menu selection keys to view any stored data item grouped by Menu Headings. • Use the fast-path keys to jump directly to frequentlyused data items without scrolling. Siemens Energy, Inc. These triangular keys surround the Menu key. Their shape indicates the direction of scrolling performed by the key. Use the right and left Scroll keys to scroll across Menu headings and move the cursor when in Change mode. Use the up and down Scroll keys to scroll through data items within a column and change settings when in Change mode. Change Key C hange Use this key to place the panel in the Change mode. In Change mode, you can make changes to setpoints and other stored configuration information. 5 2 Using the MJ-4A & MJ-4B Operator Panel and Controls To change an item: 1. View the item using either the menu selection keys or the fast-path keys. 2. Press the Change key. The displayed data item flashes to indicate that it can be changed. 3. Use the Scroll keys to make the desired change. Save Key S a ve After using the Change key and the Scroll keys to modify a data item, press the Save key to record the change and exit the Change mode. The displayed data item will stop flashing. Special Use: While viewing any max/min screen, press Save to view the Time/Date stamp for the max/min item. Cancel/Reset Key C a n ce l R e se t The function of this key depends upon the function currently being performed: • If the microprocessor is in Change mode, press the Cancel/Reset key to exit the Change mode and cancel any changes. (The data item will revert to its previous setting.) • If you are viewing a max or min value, press the Cancel/Reset key to reset the item to the present meter value. • If you are viewing Tapmax/Tapmin data items, press the Cancel/Reset key to reset them to the current tap position. (See Section 5.7, <COUNTERS> Menu.) • If you are viewing an ALERT, press the Cancel/Reset key to acknowledge the Alert. (SeeSection 5.8, <ALERTS> Menu.) Max/Min Key M ax M in Use this key to view max/min values for meter parameters. First view the desired data item, then press the Max/ Min key to view the maximum value. Press the Max/Min key again to see the minimum value, Press the Max/Min key a third time to exit the Max/Min mode without resetting the values. 6 Max/Min data items are displayed for a short period of time, after which the display returns to the current value. The length of this period can be selected by the operator. (See Section 4.3.24, Min/Max Time Out.) For example, if you wish to see the minimum load voltage since the last reset, use the Menu Selection keys to select Vld from the Meter Menu. The current voltage value is displayed on the screen. Press the Max/Min key. The maximum value will display for a short time. Press the Max/ Min key again to view the minimum value. To clear max/min values, see Cancel/Reset Key description. To display max/min Time/Date stamp, see the Save key Special Use description. 2.3.2 Fast-Path Keys Fast-path keys are shortcuts that provide direct access to frequently used data items. Once you have selected a data item with a fast-path key, use the Change, Scroll, and Save keys to view and change the data item just as you would do with the menu selection keys. Many of the data items selected by the fast-path keys have both forward and reverse values. For example, if you press the fast-path key labeled “Voltage Level”, the data item “Fwd Volts” appears on the display screen. Press the key again to view the reverse value. “Rev Volts” is displayed. Press the key repeatedly to alternate the display between forward and reverse values. Regulation Setting Fast-Path Keys: Voltage Level Key V o lta g e L e ve l The Voltage Level setpoint defines the output voltage you want the regulator to maintain. Use this key to view the Voltage Level setpoint. Once you display the Voltage Level, press the Change key to modify the value. Bandwidth Key B and w id th The Bandwidth setpoint defines a voltage range (on either side of the Voltage Level setpoint) which you consider to be acceptable. When regulator output voltage falls outside this value, the MJ-4 Control Panel activates the tap changer motor to restore the voltage to an in-band condition. Use this key to view the Bandwidth setpoint. Once you display the Bandwidth, press the Change key to modify the value. Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Time Delay Key T im e D e la y The Time Delay setpoint defines the amount of time you want the controller to wait (after regulator output voltage has fallen outside the Bandwidth limit) before activating the tap changer motor. Use this key to view the Time Delay setpoint. Once you display the Time Delay, press the Change key to modify the value. Line Drop Compensation Fast-Path Keys Line Drop Compensation (LDC) defines your estimate of the voltage drop between the regulator and the load center. The MJ-4 control program adjusts regulator output voltage to compensate for this drop. Specify both Resistive and Reactive components of Line Drop Compensation. See Appendix D.2 for instructions about calculating the line drops. Resistance Key Press this key to view the contents of the <ALERTS> Menu. If any Alert messages are active, press this key repeatedly to step through them in order of priority. If no Alerts are active, the message “No Active Alerts” will be displayed. Section 5.8 contains additional information on how to determine the meaning of the various Alerts, and how to acknowledge them. Press the Cancel/Reset Key to acknowledge the messages. Voltage Reduction Control (VRC) Key VRC S e le ct Press this key to view the Voltage Reduction Control data items. The first data item in that function is VRC status. Press this key repeatedly to step through the VRC settings (Local % reduction, Stage 1-3, VRC Remote, etc.) and then return to VRC Mode and repeat the sequence. See Section 4.4.3 for a discussion of these data items. Voltage Limit Control (VLC) Key R e sista n c e VLC S e le c t Press this key to view the Resistive LDC component. Once you display the Resistive LDC, press the Change key to modify the value. Reactance Key R eacta n c e Press this key to view the Reactive LDC component. Once you display the Reactive LDC, press the Change key to modify the value. +/- Polarity Select Key + /- Press this key to view the VLC Enable data items. Press the VLC key repeatedly to step through the VLC - Upper Voltage setpoint, and the VLC - Lower Voltage setpoint and then repeat the sequence. See Section 4.4.4 for a discussion of these data items. Operation Counter (Op Count) Key Op C ount Press this key to select the <COUNTERS> Menu. The first parameter displayed is the Total Operations count. Press this key repeatedly to step through the <COUNTERS> Menu data items. See Section 5.7 for a discussion of this Menu. Maintenance Key While in the Change mode, press this key to define the polarity of either the Resistive or Reactive LDC component. M a in te nance Other Fast-Path Keys Alert Key A le rt Siemens Energy, Inc. Press this key to view the Overall Contact status screen from the <MAINTENANCE> menu. Press the key repeatedly to scroll through the contact status screens and the settings for the maintenance algorithm. 7 2 Using the MJ-4A & MJ-4B Operator Panel and Controls U2 P2 Key U2 P2 Press this key to enable or disable automatic tap changes of the regulator. The Auto Disabled LED indicates whether or not automatic tap operations will occur. Raise and Lower Keys Press this key to toggle between the U2 and P2 voltages when the setting under <ADV CONFIGURE> menu U2/ P2 out is set to Toggle. Neutralite Test Key Test R a is e Low er The Raise and Lower keys are present in the MJ-4B Panel. The MJ-4A panel has discrete switch for the same functionality. Press this key to illuminate the Neutralite Indicator. This is an LED test. While Automatic tap operations are disabled, the Raise and Lower keys are active. Press and Hold the Raise key to increase the tap position. Press and Hold the Lower key to decrease the tap position. Drag Hands Reset Key 2.4 R e se t Indicators The front panel also provides user information via individual status indicators. These indicators provide a direct means of assessing operational status. Alert LED Press this key to reset the electromechanical drag hands on the Position Indicator to the present tap changer position. This also resets the electronically stored max/min tap position values (viewable from the display). Quick Key Q u ic k Press this key to view the items stored in the Quick List. The user-defined Quick Key can display up to 15 different commonly refered to screens. See Section 4.10 for how to setup this functionality. Remote/Local Key R e m o te / L o ca l Press this key to enable or disable remote control of the control panel. The Remote Disabled LED indicates the status of Remote control. Auto / Manual Key The Auto/Manual key is present in the MJ-4B Panel. The MJ-4A panel has discrete switch for the same functionality. A u to / M anual 8 This indicator is illuminated whenever one or more alerts are active. The indicator may either flash or remain on steadily. • If flashing, it indicates that one or more alert conditions are active and have not yet been acknowledged. • If the Alert Indicator glows steadily, it means that a previously-acknowledged alert condition continues to exist. To acknowledge an Alert, view the Alert screen with the Alert button and then press the Cancel/Reset button. Reverse Power Flow LED The Reverse Power Flow (RPF) indicator is illuminated when the microprocessor senses reverse power flow. The indicator will either be off, on, or flashing depending upon both Power Flow mode and Current direction (see Section 4.3.11 and Table 2.1 below. Table 2.1 Reverse Power flow Indicator Status Power Flow Mode RPF Indicator Status Reverse Current1 Forward Current1 Neutral R On Off Idle R On Off Co-Gen On Off Bi-Dir On Off F Lock Flashing Off R Lock On Flashing 1. (Real component) exceeds 1% rated current for 5 seconds Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls When the real component of load current drops below 1% of rated current, the RPF indicator continues to display its previous state. Table 2.2 Band Indicator Status Power Flow Mode Band Indicator Status RPF active and current magnitude exceeds I Threshold % RPF or FPF with current magnitude below I Threshold %, but not = 0 FPF active and current magnitude exceeds I Threshold % F Lock Flash On solid On solid R Lock On solid On solid Flash If the real component of current is less than 1% when the MJ-4 Control Panel is powered up, the RPF LED is OFF (indicates forward). Remote Auto Inhibit LED This indicator is illuminated when automatic tap changes are inhibited. Either the remote operator has sent an automatic inhibit command, the Automatic Inhibit contacts have been activated, or a local operator has pressed the Auto/Manual pushbutton. Remote Disabled LED This indicator is illuminated when Remote control is disabled. When Remote control is enabled a remote operator can change the settings, configuration, and control the regulator remotely. When Remote control is disabled, a remote operator can only view the status of the control panel. Only a local operator can change the Remote control status by using the Remote/Local Switch pushbutton. In the above table, the indicator that is flashing or is on solid is the respective Band Indicator (High, Low, or In Band). If all band indicators are off, it is an indication that Voltage Limit Control (VLC) is active, and compensated regulator output voltage is higher than the VLC upper limit, or lower than the VLC Lower limit. MJ-4A & MJ-4B Band Indicators VLC Upper Indicator VLC Upper Band Indicator LEDs 1v Three Band Indicators, “High", "In Band,” and “Low,” are located at the top of the front panel. The microprocessor continuously compares load voltage (corrected for line drop) against the Voltage Level and Bandwidth setpoints. The Band Indicator LEDs show the results of this comparison (see Table 2.2). “In Band” indicates that regulator output voltage is within voltage and bandwidth setpoints. “High” indicates that regulator output voltage is out-oflimits on the high side. "High" Band Indicator "In-Band" Indicator Voltage Level Setpoint “Low” indicates that regulator output voltage is out-of-limits on the low side. In all power flow modes except Neutral Reverse, if one of the three Band Indicators is flashing, it is an indication that tap changes are being inhibited by the control program. In Neutral Reverse, the flashing Band Indicator in conjunction with a Reverse Power Flow condition may mean that the control program is returning the tap position to Neutral. Table 2.2 Power Flow Mode Neutral R "Low" Band Indicator VLC Lower Figure 2.3 RPF active and current magnitude exceeds I Threshold % RPF or FPF with current magnitude below I Threshold %, but not = 0 FPF active and current magnitude exceeds I Threshold % Flash Flash On solid Idle R Flash Flash On solid Co-Gen On solid Flash On solid Bi-Dir On solid Flash On solid Siemens Energy, Inc. 1v VLC Lower Indicator Band Indicator Status Band Indicator Status Bandwidth Band Indicators and VLC Indicators Raise / Lower LED Indicator The Raise / Lower indicator remains on continuously whenever the tap changer motor is raising or lowering the tap position. The Raise / Lower indicator can be configured to Flash whenever the tap changer motor is lowering the tap position. By choosing the setting under the<ADV CONFIGURE> menu LowerLED. 9 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Voltage Limit Control LED Indicators Auto/Manual Push button (MJ-4B) The Voltage Limit Control (VLC) indicators illuminate to indicate that VLC is active. With the VLC upper limit activated, the VLC Upper indicator is illuminated. If the VLC lower limit is activated, the VLC Lower indicator is illuminated. This push button determines whether the MJ-4B Control Panel is under manual control or microprocessor control. Note that the ultimate determination of the point of control can be changed remotely if Remote Disabled is not activated. If VLC is active, and Vld is within 1 volt of the VLC limit, the appropriate VLC and Band Indicator will both be illuminated. Tap Control Modes • Manual / Auto Disabled (By-Pass Position), The operator has control of the regulator’s tap changer motor; automatic tap changes are disabled. In this mode, a local operator can use the Raise and Lower switches or push buttons to adjust the tap position or a remote operator could control the tap motor. • Auto Enabled. The microprocessor has control of the tap changer motor and local manual tap changes are disabled. Voltage Reduction Control Active Indicator LED This indicator is illuminated whenever Voltage Reduction Control is in effect. The VRC LED indicator flashes a unique pattern to indicate which stage, step, or set is active, depending upon the VRC Mode as described in Table 2.3. (See Section 4.4.3 for more information.) Table 2.3 VRC Indicator Flash Patterns Flashing Pattern Remote / Local Push button VRC Modes Remote (MJ-X) Remote (MJ-3A) Auto Stage-1 Step 1 Set 1 long-short-short Stage-2 Step 2 Set 2 long-shortshort-short Stage-3 Step 3 On Local Active long-short This push button determines whether the MJ-4 Control Panel is under local control or remote control. Note that the ultimate determination of the point of control is established manually; this switch setting cannot be overridden from a remote location. • Remote Disabled. In this mode, a remote operator can obtain MJ-4 Control Panel data. However, the remote operator cannot make configuration changes or exercise control of the tap changer motor. • Remote Enabled. In this mode, a remote operator has access to all functions available to the local operator, including the ability to override automatic control of the tap changer motor. • This push button is common for both the MJ-4A & MJ-4B Panels. Neutralite Indicator The Neutralite indicator illuminates when the tap changer is in the Neutral position. The Neutralite indicator also illuminates when the Neutralite Test key is pressed and held. 2.5 Switches Power Switch This three-position switch selects the power source for the MJ-4 Control Panel. • In the upper (Normal) position, the regulator Utility (tertiary) winding provides power through the polarized disconnect switch (PDS). • In the lower (External Source) position, the External Source terminals (described below) provide power. • In the middle (Off) position, the Control Panel is turned off. This is also called the By-Pass Position. Raise and Lower Switches / Push buttons When the Auto Disabled LED is ON, this discrete switch or push buttons activate the tap changer motor to raise or lower the tap position. Tap Control Switches (Mode Select Switches) Auto/Off/Manual Switch (MJ-4A) In the MJ-4A panel, the 3 position discrete switch,has the Center = OFF, Down = Manual and Up = Auto functionalities. When in Auto, the panel may be switched between Auto-Remote or Auto-Local modes by pressing the Remote / Local push button. 10 Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Switch Positions for Bypassing The front panel switches must be in the following positions before bypassing the regulator. • Auto / Manual - OFF (MJ-4A) Auto / Manual - Remote Auto Inhibit LED=ON(MJ-4B) • Remote Switch - Remote Disabled LED is ON • Power Switch - OFF Cal” or “P2 Cal” in the <DIAGNOSTICS> menu defines the voltage (U2 or P2) you can read at these binding posts. The binding posts are dual banana-style receptacles. Note that the voltage measured at these binding posts is not turns-ratio corrected. By contrast, the metered voltage presented on the display screen (under <METER>) is corrected by control-program software. (See Section 4.3.7 and Section 4.3.8 for configuring the voltage transformer U2/P2 turns ratio). DANGER 2.6 WARNING Possible explosion if bypassed while not on neutral. Will cause death, serious injury, or property damage. Voltage applied at calibration terminals may energize regulator with high voltage through voltage transformer. To prevent: Could result in death or serious injury. Place regulator in neutral position before bypassing and disable control panel. See Appendix E for details. To prevent: Do not connect any voltage source at the voltage calibration terminals. Binding Posts Front panel binding posts are dual banana-style receptacles on standard 0.74 inch centers. 2.7 External Source Binding Posts Power Fuse These binding posts can be used to apply 120 V external power to the MJ-4 Control Panel when the power source switch is in the External Source position. The binding posts are dual banana-style receptacles. This 6.0 Amp fuse protects the MJ-4 Control Panel circuit and the tap changer motor circuit. Ensure that any voltage source attached to these binding posts is properly polarized. This 0.75 Amp slow-blow fuse protects the MJ-4 Control Panel sensing circuit. Note: External Power Source Protection Fuse CAUTION Fuses Sensing Fuse This 6.0 Amp fuse protects the MJ-4 Control Panel circuit and the tap changer motor circuit when powered through the external source binding posts. WARNING Improper external power connection will place 120V on the ground circuit. May result in minor or moderate injury including equipment damage. To prevent: Observe proper polarity of external power supply. Hazardous voltage present on various control leads when regulator is energized. Could result in death or serious injury including equipment damage from contact with live line conductors. To prevent: Voltage Calibration Binding Posts Bypass the regulator and de-energize before removing accessory items from the control box. These binding posts can be used with an external voltmeter to monitor regulator P2 or U2 voltage. Displaying “U2 Siemens Energy, Inc. 11 2 Using the MJ-4A & MJ-4B Operator Panel and Controls 2.8 Terminal Strip Connections Complete descriptions of all terminal contacts are provided in Appendix K. Terminal strips are located on the lower back side of the MJ-4 Control Panel. These terminals can be used to provide access to certain microprocessor and other control functions. Necessary jumpers are installed at the factory and there is no need to add or change any of them unless you need to access the electrical signals present there. The terminal strips include four terminal pairs for VRC control and external inhibit function. The terminal strips include the Current Circuit terminal pair. Each terminal strip contact is screw type, to facilitate connection and disconnection of external wiring. Current Circuit Terminal Contacts The nominal 200 mA secondary of the regulator current transformer (CT) is routed through these terminals labeled C and C2. This terminal pair is provided with a removable shorting bar to accommodate auxiliary apparatus. These terminals are shorted at the factory and must remain shorted unless an appropriate external device is attached. DANGER Open CT secondary will result in high voltage at CT terminals. Will result in death or serious injury including equipment damage. To prevent: Do not operate with CT secondary open. Short circuit or apply burden at CT secondary (C2-C) during operation. 12 Siemens Energy, Inc. 2 Using the MJ-4A & MJ-4B Operator Panel and Controls Power and Motor Control Terminal Contacts A simplified schematic drawing of the power and motor control terminal connections is shown in Figure 2.3 below . Connections for External Motor Power Power Switch On PDS-U2 P2B External Source (Line) P2B External P2B 12 11 10 P2B 9 P3A Motor Power Control Relay K7 Remote P3A Remote/Auto/Manual Switch P3A 9 8 7 U 12 U6 10 U7 9 U U6 11 U6 Connections for External Motor Power (Automatic Only) U6 12 External Power (or connect Relay between U and U6) 11 10 U7 9 U U6 U6 U7 REM-STAT R/M Com External Power (or connect Relay between U6 and U7) Status of Remote/Auto/Manual Switch Switch Position REM to COM MAN to COM Remote Closed Open Auto Open Open Manual Open Closed Status Outputs MAN-STAT Manual Connections for "Terminal Block" (T.B.) Remote Control Automatic "Lower" Relay* K5 Automatic "Raise" Relay* K4 U-REM P2B Manual Tap Raise/Lower Switch 5 J22 P2B Raise Off 4 J21 P2B J21 3 Lower 6 K22 K22 7 7 K21 P2B J22 4 J21 3 U-REM 6 P2B T.B. Remote Enable/Disable of Automatic Operations U-REM 5 Relay Contacts 3 U-REM P2B *Auto relays disabled when R/A/M switch is in Manual position T.B. Remote Control for R/A/M Switch in Remote U-REM 5 T.B. Remote J22 Raise 4 U-REM 6 T.B. Remote Lower K22 7 K21 8 Relay Contacts Open - Disable Close - Enable K21 8 8 "J" Current Sense P2A "K" Current Sense P2A 9 PDS-J 10 PDS-K Note: The dotted-lineconnections between terminals represent the default (factory installed) jumpers. T e rm in a l R e m o te c o n tro l c o n n e c tio n s fo r M J -4 A On P D S- U 2 P 2B External Source (Line) Connections for External M otor Power (Autom atic O nly) Connections for External M otor Power Power Switch P 2B External P 2B P 2B 12 11 10 9 U 12 U6 11 U6 10 U7 9 U U6 U6 U7 12 External Power (or connect R elay betwe en U and U 6) 11 10 9 U U6 U6 U7 External Power (or connect R elay between U 6 and U 7) M otor Pow er C ontrol R elay K7 C o n n e ctio n s fo r " Te r m in al B lo c k" (T. B .) R e m o te C o n trol Autom atic "Lower" R elay* K5 Autom atic "R aise" R elay* K4 T.B. R em ote Enable/Disable of Autom atic O perations P 2B P 2B * Auto rela ys disa bled w h e n R /A/M s w itch is in M an u al p o sitio n P 2B P 2B J2 2 J22 4 4 J2 1 J21 3 3 K22 K22 7 7 K21 R elay Contacts O pen - Disable Close - Enable K2 1 8 8 "J" Current S ense P 2A "K" Current S ense P 2A 9 P D S-J 10 P D S-K N ote: T he dotted-lin econnections betwe en terminals represent the default (factory installed) jumpers. T e rm in a l R e m o te c o n tro l c o n n e c tio n s fo r M J -4 B Figure 2.4 Simplified Schematic of “Terminal” Remote Control Connections Siemens Energy, Inc. 13 2 Using the MJ-4A & MJ-4B Operator Panel and Controls 2.9 Local Data Port The Local Data Port on the front panel supports connection to a PC or other communications device. It transfers data in either direction: the MJ-4 Control Panel can provide meter and status information to an external device, and the control program can be configured from an external device. Jumpered for DTE 1 2 3 The Local Data Port supports data transmission at standard data rates from 300 to 19200 baud, inclusive, using the 2200 communications protocol enhanced with MJ-4 data fields. The physical interface is a standard 9-pin D-type subminiature connector. The pinouts match the PC-AT™ RS-232 port connector (see Table 2.4): Table 2.4 “DTE” Pin Number(s) J23 J22 1 2 3 1 2 3 J23 J22 1 2 3 BT1 1 2 3 J23 J22 Local Data Port Pinouts Signal Description 1 2 3 “DCE” Pin Number(s)* MJ-4 output 3 2 MJ-4 Input 2 3 Signal Ground 5 5 DCD, DSR, CTS ) -- (no connection) -- (no connection) Jumpered for DCE Figure 2.5 Data Port Jumper Locations * indicates factory default settings. The MJ-4 jumpers on the main circuit board are internal. See Appendix J for procedure. Normally, only pins 2, 3, and 5 are needed to communicate through the Data Port. See Appendix J for other jumper locations and default settings. When using a straight-through cable, the Local Data port should be jumpered as “DCE” for connection to a terminal device (such as a notebook or laptop computer); and as “DTE” for connection to a modem. By default, the Local Data Port is jumpered as DCE. When repositioning jumpers, use proper Electro-Static Discharge (ESD) precautions. If possible, use an ESD wrist strap. If no wrist strap is available, touch a grounded surface before beginning. (Two accessible ground points are the screw jacks of the Data Port connector.) Figure 2.4 shows the jumper location for the Data Port connections. The device used for communications must be configured to match the following Data Port items in the <COMMUNICATIONS> Menu. • DatPortBaud • Data Parity • DataPortAddr - If addressing is on, use the Comm Addr parameter as the Data Port address. 14 Siemens Energy, Inc. 3 Viewing and Changing MJ-4A & MJ-4B Data Items 3 Viewing and Changing MJ-4A & MJ-4B Data Items 1. The MJ-4 Control Panel stores a considerable amount of data. Some of the data items are setpoints used to control the tap changer; others are meter readings and logged historical data that can be used to monitor system activity. All of the major data items can be displayed on the 16-character screen. The setpoints and other configuration items can be displayed and changed from the front panel. This chapter describes how data items are organized, how to view a specific data item, and, if applicable, how to change it. 3.1 Viewing Data Items 2. The MJ-4 Control Panel provides two techniques for viewing data items: Setup Menus define the environment. In general, these Menus are only used at installation. Examples include: • the <CONFIGURE> Menu, which defines the regulator and its application. • the <REGULATOR> Menu, which defines setpoints. • the <LOG SETUP> Menu, which defines logging preferences, etc. Operational Menus contain daily operational information that can help you monitor system performance. Examples include: 1. Use Menu Selection keys and Scroll keys to view any data item. • the <METER> Menu, which provides rms meter readings. 2. Use Fast-path keys to view certain frequently-used data items. • the <DEMAND> Menus, which provide Demand data. • the <LOG> Menu, which contains historical data. 3.2 Understanding Menus MJ-4 Control Panel information is organized into lists (Menus) of related data. Each specific piece of information in MJ-4 memory is known as a data item. To view or change a specific data item, you must select the Menu that contains the desired item. Appendix G provides a Menu Structure Quick Reference for help in locating a specific data item. 3.3 Using the Menu Selection Keys to View Data Items This section describes how the Menu Selection and Scroll keys can be used to view data items. Think of the Menu arrangement as a table of data items on a sheet of paper as illustrated in Table 3.1. For example, the <LOG SETUP> Menu contains data items that you can use to define logging requirements. To define logging requirements, view the <LOG SETUP> Menu; then display the particular data item from that Menu. As another example, the <METER> Menu contains meter-reading data. To determine the present load voltage meter reading, view the <METER> Menu and then the Load Voltage data item from that Menu. The <METER> Menu is considered the home position in the MJ-4 Control Panel's menu structure. Each column of the table has a heading (Menu name). Since you are viewing this “table” through a 16-character window, you must scroll through the table to view the desired data item. The following scrolling rules apply: • At the heading level, scroll through the Menu headings with the left and right Scrolling keys. • Within a selected menu, use the up and down Scrolling keys to step through the various data items. MJ-4 Control Panel Menus are divided into two major categories: Structure of MJ-4 Menus Table 3.1 ... <FW DEMAND> <REV DEMAND> <COUNTERS> ... data item 1 data item 1 data item 1 data item 1 data item 1 data item 2 data item 2 data item 2 data item 2 data item 2 data item 3 data item 3 data item 3 data item 3 data item 3 . . . . . . . . . . Siemens Energy, Inc. 15 3 Viewing and Changing MJ-4A & MJ-4B Data Items If you are not sure where you are in the Menu structure, press the Menu key once to return to the top of that menu. Press the Menu key again to return to the <METER> Menu or home position. Viewing a specific data item with the Menu Selection keys is a two-step process: 1. 2. View the Menu that contains the desired data item by stepping left and/or right through the Menu structure. Use the ½ key to move left and the ¾ key to move right. Data items are grouped according to function so you can readily determine which Menu contains the desired data item. (See the Menu Structure Quick Reference in Appendix G for help in locating a specific data item.) View the desired data item by stepping up or down through the Menu until you see the data item name and its value on the display screen. Use the À key to move down in the list; use the ¿ key to move up in the list. Example Suppose you want to view the regulator Forward Time Delay setpoint. This data item is contained in the <REGULATOR> Menu: 1. Press the Menu key twice to return to the <METER> Menu. 2. Press the ¾ key multiple times to step through several menus. When <REGULATOR> appears on the display screen, you are positioned in that Menu and you can view its data items. 3. 16 Press the À key multiple times to step down through the various data items in the Menu (Fwd Volts, Fwd BW, and so on) until “Fwd Delay nnnS” appears. “nnn” will be the currently stored value (in seconds) for Forward Time Delay. 3.4 Changing Data Items To change data, you must first view it, as described above. Then press the Change key. The displayed value flashes to indicate that a Change will be accepted and to indicate the data that is to be changed. Press the ¿ and À keys to sequence through the acceptable values. When the desired value is displayed, press the Save key to complete the change. The procedure for changing configuration parameters is slightly different from the procedure for changing alphanumeric ones. Examples of each type of change follow: Changing Configuration Parameters In some cases, you will be choosing from one of several alphabetic settings (for example, the <CONFIGURE> Menu asks you to select among three System types: WYE, DELTA LAG, and DELTA LEAD). Example Suppose you want to change the system type from Delta Lag to Wye. You know (perhaps from checking the Menu Structure Quick Reference Appendix G) that the System data item is in the <CONFIGURE> Menu, so you must first scroll to that Menu. 1. Press the Menu key twice to return the display to <METER>. 2. Press the ¾ key to step through the Menus until <CONFIGURE> is viewed. 3. Press the À key until Syst: appears. In this example, the display screen would indicate that the present setting is Syst:DELTA LAG. 4. Press the Change key. DELTA LAG flashes to indicate that it is the data to be changed. Note: The underscore in this section of the manual denotes flashing. 5. Press the À key to see the next option. Syst:DELTA LEAD appears on the screen. 6. Press the À key again to see another option. Syst:WYE appears. Since this is the option you want, press the Save key to complete the change. Syst: WYE continues to appear, but WYE no longer flashes. This indicates that the change has been accepted. Siemens Energy, Inc. 3 Viewing and Changing MJ-4A & MJ-4B Data Items Changing Alpha or Numeric Settings The process of changing alpha or numeric settings is similar to that of changing configuration parameters, except that there are more choices because there may be multiple characters to change, and each character may range in value from 0 to 9, and/or A-Z. Example Suppose you want to change the regulator Forward Volts setpoint from 123.0 volts to 122.5 volts. Setpoints are contained in the <REGULATOR> Menu, so you need to view that Menu. 1. Press the Menu key twice to return the display to the <METER> Menu. 2. Press the ¾ key repeatedly until <REGULATOR> is viewed. 3. Press the À key until FwdVolts: 123.0 appears. 4. Press the Change key to activate Change mode. (The flashing digit indicates the digit to be changed.) FwdVolts: 123.0 appears. Note: the underscore in this section of the manual (in this case under the 0) denotes flashing. 5. Press the ¿ key five times to increment the digit from 0 to 5. 6. Press the ½ key to step left one digit. FwdVolts: 123.5 appears. The digit 3 is flashing to indicate that it can be changed. 7. Press the À key to decrement the digit from 3 to 2. 8. Press the Save key to make the change take effect. FwdVolts: 122.5 appears. The flashing stops to indicate that the change is complete. Siemens Energy, Inc. 3.5 Using the Fast-Path Keys to View/ Change Data Items Fast-path keys are the labeled keys on the middle portion of the MJ-4 Control Panel, such as the Voltage Level key. Use the Fast-path keys as a shortcut to certain frequentlyused data items. Simply press the fast-path key and the desired data item appears immediately. After viewing an item with a fast-path key, the change procedure is the same as the one just described. In the previous example, the Voltage Level fast-path key would replace steps 1-3 and save a number of key strokes. 17 4 Setting Up the MJ-4A & MJ-4B Control Panel 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.1 Setup—Overview Communications Definition MJ-4 Control Panel setup procedures allow you to customize the control panel to your needs and to the environment in which it is installed. You can describe specific regulator parameters and power-flow conditions, and define automatic-mode operation. Previous generation controllers used dip switch settings and jumpers for this purpose. With the MJ-4 Control Panel, simply use front panel touchkeys and the display screen to define the operating environment. Also, the MJ-4 communication facilities in conjunction with the MJXplorer software can be used to set up the MJ-4 Control Panel. In this step, use the <COMMUNICATIONS> Menu to define communications parameters (baud rate, unit address, etc.). This chapter describes each of the setup parameters, and explains how they are defined. The Communications Module Instruction book contains additional detail and background information to help you make the proper selections. The setup process for the MJ-4 Control Panel consists of several steps: Configuration In this step, use the <CONFIGURE> Menu to describe the regulator and the power distribution system. Use the <ADV CONFIGURE> Menu to adjust optional or advanced settings if desired. Setpoints In this step, use the <REGULATOR> Menu to define Automatic Mode setpoints (voltage level, bandwidth, time delay, etc.). Logging Requirements In this step, use the <LOG SETUP> Menu to define data logging requirements (what values you want logged, how often, under what conditions, etc.). Security Definition In this step, use the <PASSWORD> Menu to define passwords and to activate security protection. Table 4.1 Note: Depending upon the version of software in your MJ-4 Control Panel, your menus may be slightly different than those described. If your control panel does not support all of the features described, please contact your Siemens representative for details about obtaining the latest version of the software. The <CONFIGURE> Menu DATA ITEM TapChngr Type Syst DeltaPwr Utility Pol Vprimary Max U2 PT P2 PT CTratio I FullLoad PwrFlow Basis volts NeutOvRun Reset Min/Max? DESCRIPTION Tap Changer Type Regulator type System wiring configuration Delta power configuration Utility winding polarity Maximum primary voltage Utility winding turns ratio Potential Transformer turns ratio Current Transformer turns ratio Regulating Device Full Load Rating Power flow modes Controller nominal voltage level Neutral Over Run Reset all min/max readings VALID INPUTS SIEMENS, GE, LTC, LTC.5, or COOP SD, DD, or QD STRAIGHT or INVERTED WYE, DELTA LAG, DELTA LEAD OPEN or CLOSED NORM, REV 65K (for regulators) or 650K (for LTC transformers) 1500 to 65,500:100 to 150 1500 to 65,500:100 to 150 50 to 7200:0.0 to 9.5 50 to 7200 F LOCK, R LOCK, IDLE R, BI-DIR, NEUT R, CO-GEN 115, 120, or 125v 0.0 to 3.0 seconds N or Y DEFAULT SIEMENS STRAIGHT WYE OPEN NORM 65K 7200:120 7200:120 200:0.2 200 F LOCK 120 2.0 N INC ------------1 Volt 1 Volt 1:0.1 1 Amp ----0.1 sec --- Vers Microprocessor software version NN.NNNN --- --- Memo1 User-supplied text Up to 10 Characters Reg. Serial# --- Memo2 User-supplied text Up to 10 Characters Tested by --- 18 Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel Table 4.2 The <ADV CONFIGURE> Menu DATA ITEM Meter Volts I Threshold % I Shift I Load Max PT Threshold Time Date Format Daylight Savings Dmd Type Dmd Time DmdSubperiods Min/Max t.o. Screen t.o. Quick t.o. QuickDispTim Auto Variamp Soft Variamp DESCRIPTION Display Primary or Secondary volts Tap change minimum current Current shift for reverse power flow Max. Load Current (for Overcurrent) Tap change low voltage limit Time of day Date Date format Daylight Savings Time Method for determining Demand Demand Period length (minutes) Number of Demand subperiods Min/Max display timeout (seconds) Show default display screen(min.) Quick menu display timeout second Quick menu slideshow time second Automatic Variamp Protection Software Variamp setting VALID INPUTS SEC, PRI 0% to 10% 0° to 359° 0% to 350% 0 to 134 HH:MM:SSA/P NN/NN/NN MO/DA/YR or DA/MO/YR ON or OFF THERMAL or WINDOW 1 to 999 1 to 99 (For Sliding Window mode only) 1 to 99 1 to 99 1 to 59 1 to 10 ON or OFF ON or OFF DEFAULT SEC 0% 0° 350% 90 ----MO/DA/YR ON THERMAL 30 6 15 5 10 2 OFF OFF INC --1% 1° 1% ------------1 Minute 1 1 Second 1 Minute 1 Second 1 Second ----- R Limit L Limit Raise Limit (Alert & Soft Variamp) 10, 8¾, 7½, 6¼, 5 10 --- Lower Limit (Alert & Soft Variamp) 10, 8¾, 7½, 6¼, 5 10 Slave-Master --- Put two tap changers in locked step OFF, MA, SL, S2 OFF --- Tap Alert Enable or disable tap alerts ENABLE or DISABLE ENABLE --- Alrt M= C= S= Metering, Control, & System alerts Y (to enable) or N (to disable) Y, Y, Y --- Tap Resync Synchronizes tap position at Neutral ON or OFF OFF --- CommAutoInh Turns SCADA auto inhibit on or off ON or OFF OFF --- DspScr Defines default display screen <METER>, TapContr, Vld, Vcomp, Ild, or TotalOps <METER> --- LowerLED Raise Lower Indicator Functionality Solid, Blink Solid --- P2 Calc P2 Calculation ON,OFF ON --- U2/P2out Load Voltage Terminal Locking Vload, Toggle, U2, P2 Vload --- I Dir Bias Current BiasFunctionality None, Fwd, Rev, NeutT None --- Bias % Current Bias Percent 0 to 10% 0% --- Remote Btn Remote / Local Button Functionality Enabled, Disabled Enabled --- 4.2 Setup for Retrofit Panels If you are retrofitting either a G. E. or Cooper regulator for use with the Siemens MJ-4 Control Panel, please refer to the respective Application Note. Contact your Siemens representative for details. 4.3 Defining Your Regulator— the <CONFIGURE> and <ADV CONFIGURE> Menus When the MJ-4 Control Panel is delivered pre-installed on a regulator, many of the configuration variables are already set. However, the MJ-4 Control Panel provides a wide range of additional variables that can be used to make the regulator perform more effectively in your system. Variables in the <CONFIGURE> Menu are summarized in Table 4.1; variables in the <ADV CONFIGURE> Menu are summarized in Table 4.2; both menus are explained in the following pages. Siemens Energy, Inc. Figures 4.1 to 4.4 show typical Siemens regulator nameplates. Refer to these figures for information that can be obtained from Siemens regulator nameplates CAUTION Use of incorrect drawings or Schematics Could result in minor or moderate injury including damage to the regulator or control components Use the Example diagram for illustration purposes. Refer to the regulator nameplate for the proper control diagram to use with a particular installation 19 4 Setting Up the MJ-4A & MJ-4B Control Panel SIEMENS 5/8% Step-Voltage Regulator Single Phase Type JFR TapChngr SIEMENS Serial No. 60 Hz 55 C Rise 95 BIL Class 0A 76.2 kVA 7620 volts 10% in 32 - 5/8% Steps 100 Amps Fluid PCB co ntent : Less tha n 1 p pm at tim e of manufacture Untanking Hgt Untanking Wgt 114 in. 937 lbs. % Regulation Max Amps = = 10 100 8 3/4 110 7 1/2 120 6 1/4 135 Oil Total Wgt 5 160 = = Control & M otor Volts Connect E-P2 * 127 V P2-P3 121 V P2-P3 123 V P2-P4 118 V P2-P4 124 V P2-P5 125 V P2-P6 121 V P2-P7 Control Panel Conn PA P14A Control to to Volts 20 27 120 V 21 120 V 20 23 120 V 20 21 120 V 23 20 125 V 21 20 20 125 V 25 21 125 V Reverse Power Flow - Connect Source Side Voltage Transformer per Table 2. U2PT: 7620:121 62 gals 1598 lbs. * Control diag : Nameplate : Forward Power Flow - Connect Load Side Voltage Transformer per Table 1. Load Volts 10% 8000 7620 7200 6930 5000 4330 2500 I FullLoad 100 ASTM D-3487 Type II Mineral Oil Insulating Fluid : CTratio 100:0.2 SOURCE SL S LOAD L CT 100 : 0.2 AMPS E1 C3 E3 P13 P14 P15 Tap Changer Reversing Switch Tap Changer Preventive Autotransformer K M 0 Control Panel Conn Control & M otor Source Volts Volts Connect PB P14B Control 10% E-P12 * to to Volts 120 V P12-P13 20 120 V 8000 20 120 V P12-P14 7620 20 20 120 V 120 V P12-P15 7200 20 20 120 V Aluminum conductor in shunt winding. Aluminum conductor in series winding. A B 1 23 456 7 8 P7 P6 P5 P4 P3 E2 Utility Pol NORM (E2 to right of P terminals) CT sec conn C2 to C3 Do not by-pass unless on neutral and control switch on panel is off See instruction book before placing in service. P2PT: 7620:120 S i e m e n s P o w e r T r a n s m i s s i o n & D ist r i b u t i o n , I n c . Made in U S A Jackson, MS 21-115905-002 Figure 4.1 Typical Siemens Regulator Nameplate for older ANSI Type B (Inverted) Regulator Note: Items are not highlighted on actual nameplate TapChngr SIEMENS I FullLoad 328 Type STRAIGHT CTratio 400:0.2 Utility Pol NORM (E2 to right of U Terminals) U2PT: 7620:124 P2PT: 7620:124 Figure 4.2 20 Typical Siemens Regulator Nameplate for ANSI A (Straight) regulator without a Load Side PT. Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel SIEMENS 5/8% Step-Voltage Regulator TapChngr SIEMENS Serial No. Single Phase Type JFR 60 Hz 55 C Rise 95 BIL Class OA 167 kVA 7620 volts 10% in 32 - 5/8% Steps 219 Amps Insulating Fluid : ASTM D-3487 Type II Mineral Oil Less than 1 ppm PCB Untanking Hgt = 131 in. Oil = 91 gals. Untanking Wgt = 1126 lbs. Total Wgt = 2100 lbs. ANSI TYPE "A" U2PT: 7620 : 125 % Regulation Max Amps 7970 V 7620 V 7200 V Load Volts 10% 7970 7620 7200 10 210 219 232 * Volt Tran Sec conn P2 to P3 - 120 V P4 - 120 V P5 - 120 V 8 3/4 230 241 255 7 1/2 251 263 278 6 1/4 Control Contr Panel Volts P to P14 to 20 20 120 20 20 120 20 20 120 Type STRAIGHT CTratio 250:0.2 SOURCE 5 283 296 313 I FullLoad 219 335 351 371 * Aux volts Motor Conn U2 to Volts U3 117 U4 125 U4 118 LOAD L S CT E1 250 : 0.2 C3 AMPS M SL Tap Changer Reversing Switch P5 P4 P3 E3 K B A 8 7 65 4 3 2 1 0 Tap Changer Preventive Autotransformer U7 U6 U5 U4 U3 E2 Control diag : 21-203-980-414 Nameplate : 21-115-907-435 P2PT: 7620 : 120 CT sec conn C2 to C3 Copper conductor in shunt winding. Aluminum conductor in series winding. Tank withstands full vacuum DATE: Utility Pol NORM (E2 to right of U Terminals) Do not by-pass unless on neutral and control switch on panel is off See instruction book before placing in service. S i e m e n s P o w e r T r a n s m i s s i o n & D is t r i b u t i o n , I n c . Ja ckson , MS Made in U S A Figure 4.3 21-115-907-010 Typical Siemens Regulator Nameplate for ANSI Type A (Straight) regulator Note: Items are not highlighted on actual nameplate. SIEMENS 5/8% Step-Voltage Regulator TapChngr SIEMENS Serial No. Single Phase Type JFR 60 Hz 55 C Rise 95 BIL Class 0A 76.2 kVA 7620 volts 10% in 32 - 5/8% Steps 100 Am ps Insulating Fluid : ASTM D-3487 Type II Mineral Oil Less than 1 ppm PCB Untanking Hgt = 117 in. Oil = 64 gals. Untanking Wgt = 682 lbs. Total W gt = 1431 lbs. ANSI TYPE "B" % Regulation 7620 V Amps Load Volts 10% 8000 7620 7200 5000 4330 2500 10 100 8 3/4 110 Control & Motor Volts Connect E-P2 * P2-P3 122 V P2-P4 122 V P2-P4 115 V P2-P5 122 V P2-P6 122 V P2-P7 118 V 7 1/2 120 6 1/4 135 5 160 Control Panel PA P14A to to 23 21 23 21 20 25 20 23 20 23 20 27 Conn Control Volts 120 V 120 V 120 V 125 V 125 V 125 V I FullLoad 100 Type INVERTED CTratio 100:0.2 SOURCE S LOAD L SL CT E1 100 : 0.2 C3 AMPS Tap Changer Reversing Switch K M 0 Tap Changer Preventive Autotransformer A B 8 76 5 4 3 2 1 P7 P6 P5 P4 P3 E2 Control diag : 21-203-980-468 Nameplate : 21-115-905-464 U2PT: 7620: 122 P2PT: 7620: 122 CT sec conn C2 to C3 Copper conductor in shunt winding. Aluminum conductor in series winding. Tank withstands full vacuum DATE: Utility Pol NORM (E2 to right of P Terminals) Do not by-pass unless on neutral and control switch on panel is off See instruction book before placing in service. S i e m e n s P o w e r T r a n s m i s s i o n & D ist r i b u t i o n , I n c . Made in U S A Jackson, MS 21-115905-002 Figure 4.4 Typical Siemens Regulator Nameplate for ANSI Type B (Inverted) Regulator Note: Items are not highlighted on actual nameplate. Siemens Energy, Inc. 21 4 Setting Up the MJ-4A & MJ-4B Control Panel The <CONFIGURE> Menu 4.3.5 4.3.1 The Utility Pol data item allows you to correct for polarity differences between the CT winding and the Utility (Tertiary) winding. TapChngr (Tap Changer Type) The TapChngr data item defines the tap changer mechanism type. Tap changer mechanisms vary among regulating device suppliers. This data item allows the MJ-4 to be configured specifically for the connected tap changer device. 4.3.2 Type (Regulator Type) The Type data item defines the step-voltage regulator type. The designations “straight” (ANSI Type: A) and “inverted” (ANSI Type: B) are frequently used to denote the difference. See Figures 4.1 to 4.4 for examples. Since November, 1995, the regulator type is identified by either an ANSI Type A or B designation. Older nameplates did not include this information and the type must be determined from the schematic diagram on the regulator nameplate. “STRAIGHT” design characteristics: (See Figure 4.2 and 4.3) • The source (‘S’) bushing is connected to the tap changer reversing switch and to one end of the main winding. • The load (‘L’) bushing is connected via the preventive autotransformer to the moving contacts of the tapchanger. • The utility (tertiary) winding leads are labeled U3, U4, U5, ... etc. “INVERTED” design characteristics: (See Figures 4.1 and 4.4) • The source (‘S’) bushing is connected via the preventive autotransformer to the moving contacts of the tap changer. • The load (‘L’) bushing is connected to the tap changer reversing switch and to one end of the main winding. • Utility (tertiary) winding leads are labeled P3, P4, P5, ... etc. 4.3.3 System (Regulator Installation) The System data item defines whether the regulator is Delta or Wye-connected. See Appendix D, section D.1 for guidance in determining which regulator is leading and which is lagging (for Delta-configured regulators). 4.3.4 DeltaPwr (Delta Power) The Delta Pwr item defines the wiring arrangement for Delta-connected systems. Specify either Open or closed. The setting does not matter for a Wye-connected system. 22 Utility Pol (Utility Polarity) To define the Utility Polarity, view Utility Pol; then, 1. If you have a single-phase Inverted-type regulator, specify Utility Pol:Norm. 2. If you have a single-phase Straight-type regulator, see Appendix D, section D.3. 4.3.6 Vprimary Max The Vprimary Max setting defines the maximum voltage on the primary side of the U2 PT and P2 PT ratios. Set 650k for LTC transformers; use the default of 65k for voltage regulators. 4.3.7 U2 PT (Utility (tertiary) Winding) The U2 Potential Transformer ratios are used by the control program to scale the voltages supplied by the regulator to the basis voltage (nominal 115, 120, or 125 V). Many regulators are built with transformer turns ratios that do not provide the exact basis voltage (115, 120, or 125 V) to the controller. Previous generation controllers include a tapped sensing transformer to correct the voltage. Instead of using a sensing transformer, the MJ-4 corrects the voltage mathematically, using the U2 PT turns ratio. Determine the turns ratio for the regulator from the regulator’s nameplate. The U2 PT data item defines the turns ratio of the winding that appears at the U2 terminal on the Polarized Disconnect Switch (PDS). To define the turns ratio, you must first determine which column in the nameplate describes the “U2” secondary for a given primary voltage. The U2 pin is attached to the regulator Utility Winding. The U2 lead provides the power to the controller, and is always present. It is often labeled Motor Conn. or Control & Motor on the nameplate. See Figure 4.1 to 4.4 for examples. View U2 PT, then specify the turns ratio exactly as it is specified on the regulator nameplate (e.g., 7620:121). The microprocessor will correct the reference voltage to the basis voltage (115, 120, or 125 V). 4.3.8 P2 PT (Potential Transformer) The P2 PT data item defines the turns ratio of the Potential Transformer appearing at the P2 terminal on the Polarized Disconnect Switch (PDS). Note: For regulators with no potential transformer, set the P2 ratio to the same value as the U2 ratio. Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel Many regulators are built with transformer turns ratios that do not provide the exact basis voltage (115, 120, or 125 V) to the controller. Previous generation controllers include a tapped sensing transformer to correct the voltage. Instead of using a sensing transformer, the MJ-4 corrects the voltage mathematically, using the P2 PT turns ratio. The turns ratio for a given regulator can be determined from the regulator’s nameplate. 4.3.11 To define the turns ratio, you must first determine which column in the nameplate describes the “P2” secondary for a given primary voltage. P2 describes the pin on the Polarized Disconnect Switch (PDS, or jack plug). The P2 pin is attached to the regulator Potential Transformer secondary (if present), and is usually labeled Control Volts on the nameplate. See Figures 4.1 to 4.4 for examples. This section provides an introduction to each of the modes, and describes how to select the desired mode. See Chapter 7 for a detailed discussion of the operational differences between the modes. Note: For an ANSI type B regulator, the utility winding tap leads are labeled P3, P4, P5, ...etc. and the P2 lead is connected to the U2 terminal on the PDS. View P2 PT, then specify the turns ratio exactly as it is specified on the regulator nameplate (e.g., 7620:121). The microprocessor will correct the reference voltage to the basis voltage (115, 120, or 125 V). Default value is 120 V. If an inverted (Type B) regulator has a source-side Potential Transformer, the utility (tertiary) winding leads are labeled P3, P4, etc., and the P2 lead is connected to the “U2” terminal on the PDS. The source-side PT leads are now labeled P12, P13, etc., and the P12 lead is connected to the P2 terminal on the PDS in the control box. Note also that no reverse power flow relay is required. The microprocessor senses the reversal and applies the appropriate polarity. 4.3.9 CTratio (Current Transformer Ratio) The Current Transformer ratio defines scaling for current measurements. View CTratio: then specify the ratio exactly as specified on the nameplate. See Figures 4.1 to 4.4 for examples. Power Flow Modes The Power Flow Mode data item allows you to specify which control program algorithm will be used under reverse power flow conditions. Systems which experience power flow reversals have unique control requirements. The MJ-4 Control Panel senses the reversal and modifies its operation based on the Power Flow Mode selected. Forward Locked Mode This mode of operation (F LOCK) is intended for use in systems where reverse power flow is not anticipated. Tap changes are inhibited under reverse power flow conditions. Reverse Locked Mode This mode of operation (R LOCK) is intended for use in systems where forward power flow is not anticipated. Tap changes are inhibited under forward power flow conditions. For this mode a Source-side Potential Transformer is no longer required. See Sections 5.1 and 5.2. Bi-directional Mode This mode of operation (BI-DIR) is intended for use in systems where reverse power flow is anticipated and voltage regulation is desired under both forward and reverse power flow conditions. For this mode a Source-side Potential Transformer is no longer required. See Sections 5.1 and 5.2. Idle Reverse Mode This mode of operation (IDLE R) is intended for use in systems where reverse power flow is to be treated as an abnormal situation. When reverse power flow is recognized, the regulator idles at the last tap position held before the reversal. Neutral Reverse Mode The primary side of this ratio is also used by the control program to define the CT primary rating. This rating and the I Threshold % define a tap change deadband for use during certain reverse power flow conditions. (I Threshold % is described below.) This mode of operation (NEUT R) is intended for use in systems where reverse power flow is to be treated as an abnormal situation. When power flow reversal is recognized, the regulator returns the tap changer to the neutral tap position. 4.3.10 Co-Generation Mode I Full Load This item specifies the Full Load Current for use in determining when an Overcurrent condition occurs. Typically, the Full Load Current setting is the same as the CT Primary (the first number of the CT Ratio screen), though this is not always the case. Locate the regulator’s Full Load Current specification on the upper right side of the nameplate (just below the “Class” specification). The regulator nameplate shows the Full Load Current as “XXX Amps.” Enter the value for the Full Load Current setting into the MJ-4. See Figures 4.1 to 4.4 for examples. Siemens Energy, Inc. This mode of operation (CO-GEN) is for use in systems where consumer-generated power may sometimes flow from the consumer to the Utility. Under reverse current flow conditions, forward regulation is allowed, using reverse Line Drop Compensation settings. 4.3.12 Basis volts (Basis Volts) The Basis Volts data item defines whether the MJ-4 control program is to convert the regulator transformer sec- 23 4 Setting Up the MJ-4A & MJ-4B Control Panel ondary voltage to 115, 120, or 125 volts. See U2 PT and P2 PT data items above. Also see Section 5.3.2. The <ADV CONFIGURE> Menu 4.3.13 NeutOvRun (Neutral Overrun) 4.3.17 Meter Volts (Meter Scaling) The Neutral Overrun data item keeps the tap motor on for a specified amount of time when making a tap change into the neutral tap position. This ensures that the reversing switch is always closed in order to prevent the contacts from corroding due to capacitive discharge. For regulators with a TLG mechanism set to 2.0 seconds. For regulators with a TLF mechanism set to 1.7 seconds. The Meter Volts data item determines which voltage is presented on the display screen. You can choose either the Primary side (system voltage—e.g., 7620 V) or the Secondary side (120 V nominal). 4.3.14 Min/Max Reset Specify PRI if you wish to monitor the system-level voltage; specify SEC if you wish to monitor voltage scaled to the nominal 120 volt range. Voltages in the <METER> Menu are displayed according to the Meter Volts setting. The Min/Max Reset data item resets Meter and Demand max/min values in the microprocessor to current instantaneous values. This function is useful when setting up the microprocessor for the first time, or when you want to reset electronically-maintained values. Note: Power and energy calculations are always derived from the system-level voltage and are not affected by the Meter Volts setting. Note: Do not use this function unless you want to reset all Meter and Demand min/max values; to reset selected values, use the Cancel/Reset key described in Chapter 2. The I Threshold % data item defines a threshold for load current magnitude, below which automatic mode tap changes are inhibited. This threshold is defined as a percentage of the CT primary rating. (See CTratio above.) To request that Meter and Demand Max/Min values be reset, view Reset Max/Min; use the Change key and the Scroll keys to change the default N(o) to Y(es). Then press the Save key to complete the change process. For example, in the case of a regulator with a CTratio of 200:0.2, the CT primary rating would be 200 A. If you specify I Threshold % = 4, you are defining a low current threshold of 8 A. (4%*200 A = 8 A). 4.3.15 Version To set the low current threshold, view I Threshold %: and specify a percentage of the full scale CT primary rating. Main Processor software version NN.NNNN. This data item displays the installed version of the microprocessor control program. 4.3.16 Memo 1 and Memo 2 These two data items allow you to record installation-specific information that can be viewed at a later time. For example, you might wish to use one Memo to document the regulator’s serial number, and the other Memo to document its location. This information could then be viewed by a remote operator via a communications link. To enter data into these data items, view the <CONFIGURE> Menu; then use the Scroll keys to view Memo 1 or Memo 2. The display screen responds by flashing the “blank” character () in the leftmost position of the tencharacter Memo field. This indicates the character to be changed. Use the ¿ and À keys to step through the alpha and numeric characters until the desired character is presented on the display screen. Then press the ¾ key to move the cursor to the next character to the right, and so on until all ten characters of the Memo have been entered. When you have completed entering the Memo, press the Save key to complete the change. Valid characters are A-Z; 0-9; space; comma; semi-colon; period; dash; slash; ampersand (&), and the # character. Default is for Memo 1 to contain the regulators serial number and for Memo 2 to contain the initials of the control panel tester. 24 4.3.18 I Threshold % (Low Current Threshold) 4.3.19 I Shift (Current Shift) The I Shift data item compensates for system current-tovoltage phase differences. Consult the factory for proper application of this data item. (Note: This data item is primarily intended for use with Load Tap Change (LTC) transformers.) 4.3.20 I Load Max (Maximum Load Current) This item specifies the Maximum Load Current as a percentage of the Full Load Current. When the load current (Ild) exceeds the Maximum Load Current, the MJ-4 activates the Overcurrent Alert condition. 4.3.21 PT Threshold (Potential Transformer Threshold) The PT Threshold data item defines a low-voltage threshold. This parameter allows you to specify a voltage level below which automatic mode tap changes will be inhibited. 4.3.22 Time and Date Items Time (Time of Day) The Time data item allows you to set the real-time clock. Specify the present time, TIME: HH:MM:SS A/P (e.g., 04:34:54P). Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel Date The Date data item allows you to set the real-time calendar. Use the format selected in the Format item. If the format defined below is MO/DA/YR, enter the date as 09/30/ 07. Format The Format item allows you to set the format for the Date. Daylight Sav (Daylight Savings Time) The Daylight Sav data item automatically adjusts the clock for the time changes on the second Sunday in March and lfirst Sunday in November. 4.3.23 Demand Methods Demand values are system parameters that have been averaged over a user-defined time period. Demand values are accumulated separately for both forward and reverse power flow conditions. Demand values can be viewed in the Forward and Reverse <DEMAND> Menus. (See Chapter 5.) The MJ-4 Control Panel accumulates demand values for Load Voltage, Source Voltage, Compensated Voltage, Load Current, kW, kVAR, and kVA. In addition, Power Factor is stored whenever a new kVA maximum or minimum is recognized. periods and specify the number of subperiods as a number between 1 and 99. Thermal Method The Thermal method is typical of the characteristic time lag of mechanical or thermal devices as they absorb electrical energy. It is based on the Code for Electricity Meters, ANSI C12-1975, which defines the interval of a thermal demand meter as the time required for the meter to indicate 90% of a change in the load. Demand values are updated once each second. For example, if you specify DmdTime = 15, the demand meter indicates 90% of a steady load fifteen minutes after the load is applied. In the next fifteen minutes, it responds to 90% of the remainder of the total load. As a result, the load is constantly averaged and transient variations are not reflected. Note: The Demand Subperiod data item is ignored by the Thermal method. 4.3.24 Min/Max t.o. (Min/Max Time Out) The Min/Max t.o. data item defines the length of time that the Min/Max data items will be presented at the display screen. At the end of this period, the display returns to the present value. • system power up. To specify the Min/Max timeout period, view Min/Max t.o.; use the Change key and the Scroll keys to define the number of seconds in the time-out period. Then press the Save key to complete the change process. • when demand configuration items are changed. 4.3.25 Screen t.o. (Screen Time Out) • when power flow direction changes. Demand calculations are reset at the following times: When a demand value is reset, dashes ‘-’ appear on the display screen until completion of the first demand period. The MJ-4 Control Panel provides two methods of computing demand: the Sliding Window method and the Thermal averaging method. Sliding Window Method The Screen t.o. data item defines the length of time that any data item is displayed. At the end of the timeout period, the display returns to the default display defined by the DspScr data item. 4.3.26 Quick t.o. (Quick Time Out) The Quick t.o. data item defines the length of time that the Quick List data items will be presented at the display screen. At the end of this period, the display returns to the previous screen. See section 4.9. The Sliding Window (or rolling interval) method divides the time interval into subperiods. Meter values are individually recorded once each second. At the end of each subperiod an average value is derived for each Meter value; the values for the oldest subperiod are discarded and new demand values are calculated. 4.3.27 QuickDispTim (Quick Display Time) The DmdTime parameter specifies the number of minutes in the period; the DmdSubperiods parameter specifies the number of subperiods in the demand period. For example, a DmdTime of 30 minutes and a DmdSubperiod of 6 subperiods defines a thirty minute sliding window that moves every five minutes. 4.3.28 Auto Variamp To use the Sliding Window method, view Dmd Type and specify WINDOW. Then view DmdTime and specify the length of the period in minutes (1 to 999); view DmdSub- Siemens Energy, Inc. The QuickDispTim data item defines the length of time that each data item in the Quick List will be displayed before moving to the next item when the Quick List is in its slide show mode. See section 4.9. The Auto Variamp data item enables a capability that automatically reduces the tap position based on the average load current over the last 10 minutes compared to the I Full Load. For example, if the regulator is at 105% of its rated current on average for the last 10 minutes, the regulator will not be permitted to move past 14 raise or lower and it will move to 14 raise or lower if it is on a higher tap. If the regulator is at 140% of its rated current on average 25 4 Setting Up the MJ-4A & MJ-4B Control Panel for the last 10 minutes, the regulator will not step past 8 raise or lower and it will move to 8 raise or lower if it is on a higher tap. When planning to overload a regulator use either the Soft Variamp or the knobs on the position indicator. Auto Variamp is for protection in case of accidental overload only. The Variamp limits are defined in the voltage regulator instruction manual. 4.3.29 Soft Variamp (Software Variamp) 4.3.34 Tap Resync The Tap Resync data item determines whether the electronic tap position will resynchronize itself to neutral when the tap changer is on the neutral tap. Turning this data item OFF results in better tap tracking and the control will not adjust its tap position according to the neutral signal. Turning this data item ON will require the neutral signal status to precisely match the electronically tracked tap position and the timing of the operations counter or the maintained tap position will be purposely discarded. The Soft Variamp data item is a software implementation of Vari-Amp knobs on the position indicator. If set ON, then R Limit % and L Limit % will prohibit tap raise/lower past that position. The regulator will be limited by both the Vari-Amp knobs and the Soft Variamp. The actual boundary will be the most restrictive combination of the two (e.g., knobs limit R to 10%, L to 7.5% and software limit R to 5% and L to 8.75%. In this case the limits would be R at 5% and L at 7.5%). 4.3.35 CommAutoInh (Communications Auto Inhibit) 4.3.30 R Limit, L Limit 4.3.36 DspScr (Default Display Screen) These items set the Tap Position Raise and Lower Limit values; the control uses the limit values to check for “raise/lower limit reached” Alert conditions. Configure these parameters to match the Vari-Amp settings on the side of the Tap Position Indicator Dial mounted on the regulator. (For most applications, the Vari-Amp settings are at 10%.) If the Tap Position reaches or exceeds the R Limit Setting, the control activates the “R Limit Reached” Alert. Likewise, if the Tap Position reaches or exceeds the L Limit Setting, the control activates the “L Limit Reached” Alert. If the Screen Timeout period expires as defined by Screen t.o., the display will change to show the default display screen set by this data item. The following display screens are available: <METER> (default), TapContr (switch position), Vld (load bushing voltage), Vcomp (compensated voltage at load center), Ild (load current), and Total Ops. The first keypress made after a control has timed out will change the screen back to <METER>. The Comm Auto Inhibit data item provides a way to change the state of the Auto Inhibit status at the control panel. This can be used if the Auto Inhibit state is turned on remotely and the communications link goes down; in this event, someone can go to the controls location and enable automatic operation again. 4.3.37 Lower LED The R Limit/L Limit settings are always used for alerting— these limit settings only prevent tap raise/lower operations from exceeding the limits if Soft Variamp setting is turned ON. In the MJ-4A and MJ-4B panels, the Raise and Lower LEDs have been combined to one single LED. When lowering the Tap position the user may chose to have the LED glow solid or blink by chosing the setting. The Raising of the tap position will be indicated by the LED glowing solid,The default setting for the Lower LED is solid. 4.3.31 Slave-Master 4.3.38 P2 Calc The Slave-Master data item defines how to place controls in locked-step with each other. Whenever the Master makes a tap change it tells the slave to make a matching tap change and waits for it to do so. Contact your Siemens representative for information about this custom application. P2 Calculation can be enabled or disabled from the P2 Calc screen. P2 Calculation should be enabled for regulators that have no PT. For regulators with voltages on both the Load and Source bushing, the P2 calculation may be disabled, so that when the sensing fuse is blown that voltage in the meter menu will be indicated by dashes.The defualt is for P2 Calculation to be enabled. 4.3.32 Tap Alert The Tap Alert data item enables or disables all tap alerts, including: R Limit Reached, L Limit Reached, Neut Sig Err, Tap Pos ???, and Tap Track Err. 4.3.33 Alrt M=? C=? S=? The Alrt data item permits groups of alerts to be turned off and on. Metering (M) alerts include Low Current, Low PT Thresh, Over Current, and High Voltage. Control (C) alerts include Auto Inhibit, Pseudo Manual, and Not in Auto. System (S) alerts include NV RAM Reset, Low Battery, and Self Test Fault. Press change and use the left/right and up/ down arrows to adjust the M, C, and S alert settings. 26 4.3.39 U2/P2 Out When measured with a multi-meter, the Load Voltage(unscaled) terminals on the front panel have been locked to show the Load side voltage by default. The load voltage will vary depending on the user defined power flow mode and the power flow direction. The terminals may be locked to show exclusively U2 or P2 only, or the terminals can be configured to toggle between the two voltages with successive key presses of the U2 P2 Key. Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.3.40 Current Bias The user may choose None, Fwd, Rev or NeutT for current flow modes. The Bias percent is selected from the following Bias % data item. 4.3.41 Bias Percent The minimum Bias percent is 0% and the maximum is 10%. The user may chose to use any value between the maximum and minimum in increments of 1%. This functionality is only in effect when the power flow mode is BiDirectional and Current Bias is not selected as “None”. Note that, the Bias percent must be greater than the I Threshold %. Typically, I Threhold % should be set to 0%. For a detailed description, see Section 6.5.3 4.3.42 Remote Btn The functionality of the Remote / Local button can be enabled or disabled from this screen. When Enabled, pressing the Remote/Local button will cause the control to function as described in Section 6.1; when set to Disabled, the control can enter the Manual, Off, or AutoRemote modes. The Auto-Local mode is disabled. This Feature is not available in the MJ-4B Panel, if a user attempts to change the setting on a MJ-4B, the display would show “N/A IN MJ4B” . Siemens Energy, Inc. 27 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.4 Setting Control Levels— the <REGULATOR> Menu MJ-4 Control Panel when operating in Automatic Mode. Variables in the <REGULATOR> Menu are summarized in Table 4.3 and described in detail in the following sections. The <REGULATOR> Menu defines setpoints used by the Table 4.3 The <REGULATOR> Menu DATA ITEM DESCRIPTION VALID INPUTS DEFAULT INCREMENTS Forward power flow Fwd Volts Voltage setpoint level 106.0 to 134.0 120.0 0.1 Volt Fwd BW Bandwidth setpoint 1.0 to 6.0 2.0 0.5 Volt Fwd Delay Time delay setpoint 10 to 180 45 1 Second Fwd Comp(R) Voltage compensation (Resistive) - 24 to + 24 0 1 volt Fwd Comp(X) Voltage compensation (Reactive) - 24 to + 24 0 1 Volt Rev Volts Voltage setpoint level 106.0 to 134.0 120 0.1 Volt Rev BW Bandwidth setpoint 1.0 to 6.0 2.0 0.5 Volt Rev Delay Time delay setpoint 10 to 180 45 1 Second Rev Comp(R) Voltage compensation (Resistive) - 24 to + 24. 0 1 volt Rev Comp(X) Voltage compensation (Reactive) - 24 to + 24 0 1 Volt VRC Stat* Present VRC % reduction 0.0 to 10.0 --- --- VRC Mode: Voltage Reduction Control mode OFF, LOCAL, REMOTE, AUTO OFF --- Alt Delay Alternate time delay for voltage reduction 1 to 180 5 1 Second Reverse power flow Voltage Reduction Control VRC Input Special Applications VRC1 In VRC1 contact configuration VRC, X-COMP VRC --- VRC2 In VRC2 contact configuration VRC, ALTDELAY, LO XBATT, AUTO INH VRC --- LOCAL VRC% Local mode VRC percent reduction 0 0.1% VRC Stage 1 First stage % reduction 0.0 to 10.0 0 0.1% VRC Stage 2 Second stage % reduction 0.0 to 10.0 0 0.1% VRC Stage 3 Third stage % reduction 0.0 to 10.0 0 0.1% VRC Remote MJ-X or MJ-3A emulation mode MJ-X --- MJ-3A VRC% MJ-3A % reduction 0 0.1% VRC: Local Mode 0.0 to 10.0 VRC: MJ-X remote mode VRC: Remote Mode MJ-X or MJ-3A VRC: MJ-3A remote mode 0.0 to 10.0 VRC: Automatic mode AutoVRC set1 VRC setting #1 for Auto VRC 0.0 to 10.0 0 0.1% AutoVRC set2 VRC setting #2 for Auto VRC 0.0 to 10.0 0 0.1% AutoVRC1 %I % Load current #1 for Auto VRC 20 to 150 150 1% AutoVRC2 %I % Load current #2 for Auto VRC 20 to 150 150 1% VLC Enable Voltage Limit Control OFF, ON OFF --- VLC Upper Upper limit 106.0 to 134.0 134.0 0.1 V VLC Lower Lower limit 106.0 to 134.0 106.0 0.1 V Voltage Limit Control *VRC Stat is a view-only item. It appears in the <REGULATOR> menu for viewing convenience. 28 Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.4.1 Regulator Setpoints Time Delay Setpoint Regulator setpoints define the operating limits for Automatic mode operation. Two sets of limits are maintained: one for forward power flow conditions and another for reverse power flow conditions. The Time Delay setpoint defines the amount of time the controller will wait before commanding a tap change. Voltage Level Setpoint The Line Drop Compensation (LDC) data item defines the assumed voltage drop between the regulator and the load center. Settings are expressed in volts. The Voltage Level setpoint defines the nominal level you wish the regulator to maintain. Bandwidth Setpoint The Bandwidth setpoint defines the voltage range within which the regulator output is maintained. It is divided equally above and below the Voltage Level setpoint. For example, a Bandwidth of 6 volts with a Voltage Level setpoint of 120.0 volts specifies that any load voltage between 117 volts and 123 volts is “in band.” VRC Mode:OFF Line Drop Compensation To specify LDC values, view Fwd Comp (R) for the Forward Resistive component and Fwd Comp (X) for the Forward Reactive component. In systems with reverse power flow, view Rev Comp (R) and Rev Comp (X) to specify the Reverse components. A Line Drop Calculator software application is available on the Siemens website. This application automatically calculates the LDC values when the system parameters are entered. VRC Mode:Remote VRC Mode:Local Local VRC%:XX.X 4.4.2 VRC Mode:Aut/Rem VRC Remote:MJ3A VRC Remote:MJ-X AutoVRCset1:XX.X AutoVRC1 %I:XX.X MJ-3A VRC%XX.X VRC Stage1:XX.X AutoVRCset2:XX.X AutoVRC2 %I:XX.X VRC Stage2:XX.X VRC Stage3:XX.X Figure 4.5 4.4.3 Flow Chart of VRC Modes Voltage Reduction Control Items Voltage Reduction Control (VRC) is used to reduce output voltage. When activated, VRC has the effect of lowering the Voltage Level setpoint. Voltage reduction is accomplished in one or more discrete steps which are defined as a percentage of the voltage level setpoint (Fwd Volts, Rev Volts). VRC operates immediately to reduce output voltage without waiting for completion of the Time Delay. The following sections describe each of the VRC menu items, and explain how to set them. ALT Delay When the VRC2 In item is set for ALT DELAY, an alternate time delay is used before commanding a tap change when the VRC2 contacts are closed. When the VRC2 contacts are open, the standard (Fwd Delay) time delay is used. VRC Status The VRC Status data item displays present VRC information in the display panel. It can be directly accessed with the VRC fast-path key, or viewed from the <REGULATOR> Menu. Siemens Energy, Inc. Information displayed includes: percent reduction presently in effect (nn.n%), the VRC mode (L - Local, A - Automatic, R - Remote), and the present step/stage (0-3). For example, if VRC is presently at 5%, Remote, and MJ-X mode Stage 3, the display panel would show VRC Stat =05.0%R3. VRC1 In This item defines which feature is implemented when the external terminal block contacts (VRC1) are closed. Select VRC to enable remote Voltage Reduction Control. Choose X-COMP to enable reactive compensation polarity control. When VRC1 contacts are closed, the LDC polarity is reversed. VRC2 In This item defines which feature is implemented when the VRC2 contacts are closed. Choose VRC to enable remote Voltage Reduction Control. Choose ALTDELAY to use the ALT Delay feature described above. Choose LO XBATT to use these terminals for monitoring status change (close to open or vice versa). Choose AUTO INH to inhibit the processor from making automatic tap changes. 29 4 Setting Up the MJ-4A & MJ-4B Control Panel VRC Mode MJ-3A Mode (“Pulsed” Input) This data item defines the VRC mode of operation. Select the desired mode, using the VRC Mode data item. Four options are provided: OFF, LOCAL, REMOTE, and AUTO/ REM (see Figure 4.4). This mode simulates MJ-3A VRC; it uses only one external contact(VRC1). MJ-3A VRC users can achieve compatibility with existing controllers using this mode. VRC Mode: OFF Disables VRC function. VRC Mode: LOCAL When Local mode is selected, VRC activates immediately to reduce output voltage by the amount specified in the Local VRC % data item. To enable VRC Local mode, view VRC Mode and select LOCAL. View Local VRC % and define a reduction amount between 0.0% and 10.0% in 0.1% increments. VRC Mode: REMOTE (via Terminal Contacts) To use MJ-3A mode, view VRC Remote and select MJ-3A. Then select MJ-3A VRC% and specify the reduction value. The single MJ-3A VRC% value defines a total reduction value which control program logic subdivides into 33%, 67% and 100% steps. To achieve a reduction equal to 100% of the MJ-3A VRC% specification, activate the VRC1 contact for more than three seconds (“latched”). To achieve partial voltage reduction, “pulse” the VRC1 contact momentarily (a “pulse” is 300 msec. to 3 seconds). See Table 4.5 below. Table 4.5 When this mode is selected, VRC is conditioned to activate VRC upon closure of external contacts. These contacts, which specify the reduction amount, are connected to terminals (labeled VRC1 and VRC2) at the rear of the controller. See Appendixes I and K. Note that VRC Mode: Remote works differently than VRC Mode: Local. When you enable VRC Mode: Local, voltage reduction begins immediately. When you enable VRC Mode: Remote, the microprocessor is only conditioned to activate VRC. Voltage reduction does not occur until the VRC contacts are activated. To enable VRC Remote mode, view VRC Mode and select REMOTE. Then to activate voltage reduction, you must close the appropriate VRC contacts. Remote mode is further subdivided into MJ-X mode, and MJ-3A mode (compatible with the previous-generation control). Both modes use the VRC terminal pairs; the difference is in the way the terminal pairs are used. MJ-X Mode (“Static” Inputs) In MJ-X mode, you can specify up to three Stages of voltage reduction—each with a different reduction value. View VRC Remote and select MJ-X. Then view VRC Stage1, VRC Stage2, and VRC Stage3 to set the VRC percentage reduction values. Two terminal pairs (VRC1 and VRC2) on the external terminal block are used to trigger the three Stages (see Table 4.4). Table 4.4 VRC Indicator Flashing Pattern for MJ-X Mode 30 Stage VRC Terminal Pairs VRC LED flashing pattern Stage 1 VRC1 active; VRC2 in-active long-short Stage 2 VRC1 in-active; VRC2 active long-short-short Stage 3 VRC1 active; VRC2 active long-short-shortshort MJ-3A Mode VRC Reduction VRC1 Terminal Pair VRC Reduction VRC LED flashing pattern first pulse 33% of specified value long-short second pulse 67% of specified value long-short-short third pulse 100% of specified value long-short-short-short fourth pulse 0% not flashing latched 100% of specified value long-short-short-short unlatched none none For example, if you specify Fwd Volts=120 V, and MJ-3A VRC% = 10%, the total reduction value is 12 V. This 12 V reduction value is further subdivided into thirds, so a single pulse would result in a 4 V reduction; a second pulse would produce an 8 V reduction, and a third pulse would produce a total of 12 V reduction. Contact activation of three seconds or longer is considered to be a “latched condition” and would (in this example) produce a full 12 V reduction. Automatic Mode VRC with Remote Override In Automatic mode, voltage reduction is activated automatically whenever load current exceeds a predefined percentage. There are two automatic VRC setpoints (AutoVRC1 and AutoVRC2). When load current exceeds the percentage specified in either of the AutoVRC %I data items, regulator output voltage is reduced by the percentage specified in the corresponding AutoVRCset data item. Only one set is active at a time; they are not additive. AutoVRC remains active until the load current falls below a value that is the lower of: AutoVRCn% · (1-2 · AutoVRCsetn(%)) or Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel 90% · AutoVRCn% · (rated current). 4.5 Example 1 AutoVRC1%I = 60%; AutoVRCset1 = 3%. I turn-off threshold = lower of: 60% · (1-2 · (3%)) · rated current = 56.4% · rated current or 90% · (60%) · rated current = 54% · rated current Auto VRC will remain active until load current drops to 54% of rated current. Example 2 AutoVRC1%I = 80%; AutoVRCset1 = 7%. I turn-off threshold = lower of: 80% · (1-2 · (7%)) · rated current = 68.8% · rated current Activating Data Logging— the <LOG SETUP> Menu The MJ-4 Control Panel can record status information that will help reconstruct past occurrences. Two logs are maintained: an Event Log, and an Interval Log. Event Log records are stored when predefined Events occur; Interval Log records are stored at predefined time intervals. See Table 4.6; default settings are in bold. This section describes how to define your logging requirements. See Chapter 5, Reading and Interpreting MJ-4 Control Panel Data, for guidance on how to retrieve logged data. Table 4.6 The <LOG SETUP> Menu DATA ITEM Auto VRC will remain active until load current drops to 68.8% of rated current. To choose Automatic mode VRC, view VRC Mode and select AUT/REM. Use AutoVRCset1 and AutoVRCset2 to specify the reduction amount. Use AutoVRC1 %I and AutoVRC 2%I to specify the low current threshold. VALID INPUT Enable event logging On or OFF Event = Tap Define Tap Change as event On or OFF Event = Neut. Define Tap at neutral as event On or OFF Event = NN R Define Tap raise to step NN as event On or OFF NN=16 Event = NN L Define Tap lower to step NN as event On or OFF NN=16 Event = VLC Define VLC activation as event On or OFF Event = VRC Define VRC as event On or OFF Event = PwrFlow Define power flow reversal as event On or OFF Event = PwrCyc Define system power up as event On or OFF or 90% · (80%) · rated current = 72% · rated current DESCRIPTION Log Event Event = Cfg Define configuration change as event On or OFF AutoVRC settings are overridden by contact closures on terminal block contacts VRC1 and VRC2. Event = Alert Define any Alert activation as event On or OFF 4.4.4 Clr Event Log? Clear All Event Data Y or N Clr IntervLog? Clear All Interval Data Y or N Log Interval Enable Interval logging On or OFF ResLogMinMax Reset min/max values at start of interval On or OFF Log min/max Panel will log Instantaneous or Demand Min/Max values Inst, Dmd Interval Logging Interval NNhrNNmin Voltage Limit Control Voltage Limit Control (VLC) defines limits for load voltage. When VLC is active, the microprocessor compares load voltage with VLC setpoints. If load voltage changes to a value above VLC Upper, or below VLC Lower, limiting occurs immediately —that is, without waiting for the Time Delay timer to count down. The appropriate LED indicator (VLC Upper/VLC Lower) illuminates to alert the operator that Voltage Limiting is in effect. • To activate/deactivate VLC, view VLC Enable; then use ON or OFF. • To set the Upper VLC setpoint, view VLC Upper; then enter a value between 106.0 and 134.0 volts. • To set the Lower VLC setpoint, view VLC Lower; then enter a value between 106.0 and 134.0 volts. Note that the upper and lower limits must not overlap. For example, if VLC Lower is 115, VLC Upper cannot be changed to a value less than 115 V.) 4.5.1 Event Logging The Event Log captures present readings when an Event occurs. You can determine which Events cause logging activity by selecting the ones you want from the <LOG SETUP> Menu. When that Event occurs, the following readings will be logged: Event Date and Time, Event Cause, Event ID plus present values for: Vld, Siemens Energy, Inc. Ild, 31 4 Setting Up the MJ-4A & MJ-4B Control Panel Power Factor, Tap position, Power (KW, KVAR, KVA), Vsrc To activate Events Logging, view Log Event; then select ON. You must also define which events are to be logged. To activate logging for a specific Event, view the appropriate Event = data item, and select ON for that Event. The Event logs contain the 1000 most recent events. 4.5.2 Interval Logging The Interval Log records data at specific time intervals, as defined in the <LOG SETUP> Menu. At the end of each interval, the following readings are logged: 4.6 MJ-4 security allows unrestricted read access to any data item while providing password security against changes and resets. 4.6.1 1. A Level 1 password enables the change/reset function; if a valid Level 1 password is entered, any data item (which is not further protected by Level 2) can be changed or reset. 2. A Level 2 password is associated with a specific Menu. When a Menu is protected at Level 2, the Level 2 password must be entered before changes/ resets can be made to data items within that Menu. Present, max, min, and demand values for: Ild KVAR Instantaneous value of Vsrc Instantaneous value of Power Factor Power Factor at KVAmax Power Factor at KVAmin Present, max, and min values for Tap Position Total Operations To activate Interval logging, view Log Interval; then select ON. Overview MJ-4 password protection is a hierarchical system, consisting of a “System Key” that provides a level of protection for the security system itself, and two Levels of security for MJ-4 data items: Interval Date, Time, and Interval ID Vld KW KVA Password Security Protection— the <PASSWORD> Menu Entering any Level 2 password provides access to all Level 1 protected data items as well as to data items contained in Menus that are protected by that specific Level 2 password. In other words, when a Level 2 (Menu) password has been entered, the change/reset function is enabled for any data item that is not protected by another Level 2 password. Either Level can be activated independent of the other. To define the time between logs, view Interval; then specify the time as HHhrMMmin. Security activation and password assignment are separate functions. In other words, even though you have assigned a password to a Level, password checking can be active or inactive for that Level. To reset the minimum and maximum values at the start of each interval, view ResLogMinMax; then select ON. With this flexible structure you can set up a security system with: Interval logging is synchronized to the time of day. Interval logging occurs when “seconds” is zero. For 15 and 30 minute intervals, the MJ-4 logs data at even quarter and half-hour increments, respectively. For a 1-hour setting, the MJ-4 logs data on the hour. For 4 and 6-hour settings, the MJ-4 logs data synchronized to 12:00:00 midnight. • A single Level 1 password. • A Level 1 password with additional Level 2 passwords for specific Menus. • No Level 1 password, but one or more level 2 (Menu) passwords. • No passwords at all. • Passwords defined, but password checking temporarily disabled. The Interval logs contain the 1000 most recent intervals. 4.5.3 Clearing Event/Interval Log Data To clear the entire Event Log, view the Clr Event Log item, toggle to Y, then press the Save key. To clear the entire Interval Log, view the Clr IntervLog item, toggle to Y, then press the Save key. The default configuration for the password security system is with all password protection disabled (except for the <DIAGNOSTIC> Menu). Control of the security system requires the use of a “System Key,” which protects the changing of passwords and the activation and de-activation of the two security Levels. To ensure proper control of the MJ-4 security system, you may wish to designate one individual as security adminis- 32 Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel trator. This person would be responsible for establishing the password protection scheme and for making changes to the passwords as necessary; He/she would be the only individual requiring knowledge of the “System Key.” The “System Key” not only allows the user to change the security system, it also acts as a top level password which allows access to all change/reset functions. Once the “System Key” is entered and until the session is ended, the security system is effectively disabled. Contact a Siemens representative if your passwords are forgotten. Table 4.7 4.6.2 The <PASSWORD> Menu The <PASSWORD> Menu serves three purposes: 1. To enter passwords so that you can change/reset password-protected data items. 2. To define passwords. 3. To activate and de-activate security checking. Table 4.7 below describes the data items in the <PASSWORD> Menu and their default settings. The <PASSWORD> Menu Data item Description Value The following data items are used to enter passwords Enter PW: Prompts operator for a password End Session ? End password access to protected data items xxxx System Key: Prompt for entering and changing of the System Key N or Y xxxx 0123 The following data items are visible only after System Key has been accepted. Level 1 Level 1: Level 1 PW: OFF or ON Enable Level 1? Level 1 password xxxx 1111 Level 2 Configure: Enable password for <CONFIGURE> Menu changes OFF or ON Config PW: Password for <CONFIGURE> Menu xxxx 2222 Regulator: Enable password for <REGULATOR> Menu changes OFF or ON Reg. PW: Password for <REGULATOR> Menu xxxx 2222 Enable password for <METER> Menu changes OFF or ON Password for <METER> Menu xxxx 2222 Meter: Meter PW: Demand: Demand PW: Alert: Alert PW: Counters: Counters PW: Log Setup: Log Set PW: Enable password for <DEMAND> Menu changes OFF or ON Password for <DEMAND> Menu xxxx 2222 Enable password for <ALERTS> Menu changes OFF or ON Password for <ALERTS> Menu xxxx 2222 Enable password for <COUNTERS> Menu changes OFF or ON Password for <COUNTERS> Menu xxxx 2222 Enable password for <LOG SETUP. Menu changes. OFF or ON Password for <LOG SETUP> Menu xxxx 2222 Enable password for <EVENT LOG> and <INTERVAL LOG> Menus. OFF or ON Password for <EVENT/INTERVA>L xxxx 2222 Harmonics: Enable password for <HARMONICS> Menu. OFF or ON Harm. PW: Password for <HARMONICS> Menu xxxx 2222 Enable password for <COMMUNICATIONS> Menu. OFF or ON Password for <COMMUNICATIONS> Menu xxxx 2222 Ev/Intv: Ev/Intv PW: Comm: Comm PW: Mntn Mntn PW Enable password for <MAINTENANCE> Menu ON or Off Password for <MAINTENANCE> Menu xxxx 3333 Diagnostics: Enable password for <DIAGNOSTICS> Menu. ON or Off Diagnos. PW: Password for <DIAGNOSTICS> Menu xxxx 3333 Bold denotes default values Siemens Energy, Inc. 33 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.6.3 Setting Up the MJ-4A & MJ-4B Security System. Entering the System Key To make changes to the security system itself, a “System Key” must first be entered. The System Key is a special password that allows the security administrator to change passwords and to enable/disable Level 1 and Level 2 protection. To enter the System Key, view the System Key xxxx data item from the <PASSWORD> Menu; then press Change. The display screen responds by flashing “” in the leftmost position of the four-character password field. This denotes the position in which a character is to be entered. (The remaining character positions contain “.”) Use the ¿ and À keys to select the desired character. Then press the ¾ key to move the cursor to the next character to the right, and so on, until all four characters of the password have been entered. To complete the process, press the Save key. When a valid System Key has been entered, “Sys Key Accepted” appears in the display screen. Re-definition of the security system is then possible. Access to security system re-definition continues until the definition session is: In addition to defining passwords for a given level, you must also enable that level before password checking takes place. When password checking is enabled for a given Level, entry of a valid password will be required before you can change/reset any data item that is protected at that Level. Password checking is enabled for each level separately. In other words, you can enable or disable password protection for Level 1, for Level 2, or for both Levels. If password checking for a given Level is disabled, any data item at that Level can be changed or reset without use of the password. To activate password checking for Level 1, view the Level 1 parameter; then change the OFF to ON. To activate password checking for Level 2, you must specify each Menu for which you wish security to be enabled. For example, to enable Level 2 security for the <CONFIGURE> Menu, view CONFIGURE: from the <PASSWORD> Menu; then change the OFF to ON. Changing the System Key To change the System Key, (assuming you have not yet entered the System Key): 1. Enter the present System Key. After all four characters have been selected, press Save. The words “Sys Key Accepted” will appear in the display screen. After a short period, the words “System Key” will be displayed. • Manually terminated by selection of End Session Y(es) in the <PASSWORD> Menu. • Automatically terminated by expiration of the Screen timeout period. 2. Press the Change key to indicate that you wish to make a change. Because of the security exposure possible during a security system definition session, you should always use the End Session facility when changes are complete to ensure against unauthorized security system re-definition changes. 3. Enter the new key. After all four characters have been selected, press Save. The words, “Re-enter xxxx” will appear. 4. Verify correct entry by entering the new System Key once again. After all four characters have been selected, press Save. Changing Passwords After entering the System Key (see above), scroll down to view Password and Password Enable/Disable items. To change a Level 1 password, view Level 1 PW: in the <PASSWORD> Menu and use the Change, Scroll, and Save keys to enter the new password. Passwords may consist of any of the following characters: 0-9 and A-Z. To change a Level 2 password, you must view the Menu associated with that password from the <PASSWORD> Menu. For example, to define a password for the <CONFIGURE> Menu view Config. PW;, then use the Change, Scroll, and Save keys to enter the new password. You may use the same Level 2 password for several Menus, or you may use a different Level 2 password for each Menu. Enabling/Disabling Password Checking After entering the System Key (see above), scroll down to view Password and Password Enable/Disable items. 34 If your first and second attempts do not match, you will see the words, “Verify failure” and you will be returned to step 2. When you have successfully entered the new System Key twice in succession, the display screen responds with “Sys Key Changed.” 4.6.4 Using the MJ-4A & MJ-4B Control Panel With Password Security Activated MJ-4 Security does not restrict data reading. However, if password security is active, you must first enter the proper password before you can change or reset protected data. If you attempt to change a password-protected item without first entering the proper password, the display screen responds “PW NOT ENTERED” and you must use the <PASSWORD> Menu to enter the appropriate password. Note that a Level 2 password includes Level 1 access privileges. Therefore, data items that are only Level 1 protected can be changed or reset after you enter either the Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel Level 1 password or a Level 2 password. Data items contained in Menus that are password protected by Level 2 passwords can only be changed or reset after you enter the Level 2 password for that Menu. Entering passwords You can go directly to the <PASSWORD> menu and enter the password(s) you want, or when viewing a specific menu item, press Cancel/Reset or Change. If password protection is enabled for this menu, you are prompted to enter the password. (If you see the password prompt, skip step 1 below.) 1. Use the Menu and Scroll keys to view the <PASSWORD> Menu. Press the À key. The display screen responds: “Enter PW xxxx”. 2. Press the Change key. The display screen responds by flashing “” in the leftmost position of the four character password field. This represents the character to be entered. 3. Use the ¿ and À keys to step through the alpha and numeric characters until the desired character is presented in the display screen. 4. Press the ¾ key to move the cursor to the next character to the right, and so on until all four characters of the password have been entered. 5. When you have completed entering the password, press the Save key. (If you started in the <PASSWORD> menu, go to step 6. Otherwise, go to step 7.) 6. 7. If you entered a valid password, the MJ-4 briefly displays “PW Accepted” , and then displays “Enter PW”. This allows you to enter additional passwords. (You may wish to enter additional passwords if, for example, you have enabled both Level 1 and Level 2; or if you have enabled Level 2 and have different passwords for each Menu.) When you have entered all passwords, you can use the Menu and Scroll keys to view the data item(s) you wish to change or reset. Skip step 7. If you enter the correct password, the MJ-4 briefly displays, “PW Accepted” and then returns to the screen you were viewing when you started this process. If you enter a valid password, but not the correct password for this menu, the MJ-4 displays “Enter PW:” again. This process repeats until you enter the correct password for this menu. Once a password has been accepted, changes and resets are permitted for the remainder of the session. To end the session, view End Session in the <PASSWORD> Menu, and use the Change, Scroll, and Save keys to change the default N(o) to Y(es). If you leave the session enabled (un-terminated) the MJ-4 automatically terminates it when the screen time-out period expires (see <CONFIGURE> Menu Screen t.o. data item). Siemens Energy, Inc. 4.7 Communications Definition— the <COMMUNICATIONS> Menu The <COMMUNICATIONS> Menu provides data items for setting up local communications and remote communications via the Communications Module. These data items are described in the following sections. 4.7.1 Setting Up the Local Data Port The Local Data Port must be set up for proper operation. The <COMMUNICATIONS> Menu contains the Data Port setup items described in Table 4.8: Table 4.8 <COMMUNICATIONS> Menu Setup Data Items DATA ITEM DESCRIPTION INPUTS DatPortBaud: Local Data Port transmission rate 300, 1200, 2400, 4800, 9600, or 19200 Data Parity: Local Data Port Parity Setting EVEN, NONE DataPorAddr: Enables/Disables Addressing for Data Port OFF, ON Reg Id: Regulator Identification Number (Note that this is NOT the address for Data Port Communications.) NNNNN 2200 protocol address for the specific unit NNN (Range 0-255 See Table 4.8) Comm Addr: (Range 0-32765) Note: Default values shown in bold type. To change the baud rate for the data port, view DatPortBaud under the <COMMUNICATIONS> Menu and select one of the options (300, 600, 1200, 4800, 9600, or 19,200). To change the parity for the data port, view Data Parity under the <COMMUNICATIONS> Menu and select one of the options (EVEN or NONE). To enable or disable addressing for the data port, view DataPortAddr under the <COMMUNICATIONS> Menu and select one of the options (OFF or ON.) Disable addressing for local communications with MJXplorer or a Data Reader. To change the Regulator Identification, view Reg Id under the <COMMUNICATIONS> Menu and set the desired Reg Id value. For extracting data and generating reports using the MJXplorer software, the Reg Id value appears prominently at the top of the reports. If collecting data from multiple controls, select a different value of Reg Id for each MJ-4 unit. To set the Communications unit address, view Comm Addr under the <COMMUNICATIONS> Menu. Enter the desired address. 35 4 Setting Up the MJ-4A & MJ-4B Control Panel The “Comm Addr” screen shows the communications address for the MJ-4 unit. For the Data Port, the usable address ranges are listed in Table 4.9 below. Note that the MJ-4 is device type “1”, and its group address is 254. Table 4.9 Table 4.10 Communications Module Configuration Items Data Port Addresses DATA ITEM DESCRIPTION SELECTIONS Protocol: Communications Module Protocol DNP3.0, 2200, 2200NOA, MJ3A A, MJ3A B1, MJ3A B2, 2179, and Special Address Range Function 0 Wild Card Address All controls on system respond. 1 to 200 Unique Device Address When an address in this range is sent, only the control that has that unique address responds. Comm Baud: Communications Module transmission rate 300, 1200, 2400, 4800, 9600, or 19,200* 201 to 254 Device Type, Group Address Any control with the corresponding group address (which is determined by the control’s device type) receive and execute commands with no return response. Comm Parity: Communications Module Parity NONE, EVEN, ODD Comm Addr: Communications Module Address NNNNN (range: 0 - 32765) Resync Time: Communications Module resync time (in characters). Used for Communications Module protocols 2200 and 2179 to determine when one message ends and another message begins. NNN (range 0-250, 1) Tx En Delay: Communications Module Transmit Enable Delay (in milliseconds). Specifies the amount of time between the RTS output being activated and the start of transmit (output) data. NNN (range 0-250) DNP dl Confirm DNP Data Link Confirm Y or N CM SW RepeatEn Enable software autorepeat in Comm Module (MJ-3A protocol only) Y or N Host Addr Host Address for Unsolicited Responses NNN (range 0-65535) CM Unsolicited Unsolicited Responses Y or N AutoInhEnRemRL Auto Inhibit Enables Remote Raise/Lower Y or N DNPset select a predefined or custom DNP point set DNPcfg, 2.x3, 2.x4, etc. CM Vers Comm Module software version N.NNNN 255 4.7.2 Broadcast Address How Used All controls on the system receive and execute commands, with no return response. Using the Communications Module The Communications Module provides remote communications capability for the MJ-4 Control Panel. The Communications Module is a plug-in option offering choices of communications protocols and physical interfaces. Since the Communications Module Installation Manual describes the configuration items in detail, they are listed only for reference in Table 4.10 Note: Default values shown in bold type. Note: If both the Data Port and the Communications Module are simultaneously set up for remote communications, then the Data Port restrictions on the value of the “Comm Addr” data item must apply. * 36 See Comm Module Instruction Manual for limitations on 19,200 baud. Siemens Energy, Inc. 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.8 Regulator Maintenance— the <MAINTENANCE> Menu The information contained within the <MAINTENANCE> menu should be used for information purposes only. All voltage regulator maintenance should be completed as described in the Maintenance section of the Siemens Voltage Regulator Manual. The <MAINTENANCE> Menu allows the user to enable an algorithm which will approximate wear and tear on the Tap changer contacts for Siemens Regulators. The menu allows the user to chose a Tap Changer Type, indicate presence of Balance winding and define the Range of Regulation. The other items in this menu include items which show statuses of the Tap changer contacts, and the operations on the contact(s). The statuses update based on the accumulated losses due to wear and tear. The status are classified into EXCELLENT, GOOD, WORN, and REPLACE. The Moving contacts have a common status screen while the Stationary contacts have one screen each. The contact op counters update as operations are added on the individual contacts. The first screen in the <MAINTENANCE> menu is the ConsOv screen which is a status screen, it shows the status of the most worn contact(s). Each of the individual contacts’ status or operations maybe cleared by pressing the Cancel Reset button. If a user wishes to clear all statuses and op counts at once then this can be done by pressing Cancel-Reset key on the ConsOv screen. If the Maintenance approximation algorithm is disabled, all statuses and contact op counts show “N/A”.. If the MaintainRcrds? data item is changed to “Y” then the algorithm is enabled and would update the statuses and opcounts. The Maintenance menu is password protected by default. The default password of “3333” must be entered before changing settings or resetting any statuses and contact op counters. The last screen in the maintenance menu is the OP_DUR screen. This screen indicates the last measured op counter pulse duration in seconds which is useful when adjusting the TapInPulse time for TapIn=Pulse under <Diagnostics> (i.e. the Tap Chgr is set to Custom or GE). The Maintenance Menu also has a fast path key on the front panel. Press this key to view the status and settings screens of the Maintenance menu; repeat the key press to scroll through the Maintenance menu. Siemens Energy, Inc. 4.9 Hardware Configuration— the <DIAGNOSTICS> Menu The <DIAGNOSTICS> Menu includes the MJ-4 hardware configuration items in addition to the calibration and MJ-4 internal test items. See Section 8 for information about the test and calibration items: U2 Cal P2 Cal C/C2low C/C2med C/C2high The MJ-4 provides three hardware configuration items to assure compatibility between the MJ-4 electronics (hardware) and the MJ-4 control program software. The hardware configuration items are listed in Table 4.11 below: Table 4.11 Hardware Configuration Items DATA ITEM MP BD VERS: PWR BD VERS: MP MASK VERS: DESCRIPTION MJ-4 Main Processor Board Version For MJ-X Compatibility. MJ-4 Microprocessor Mask Version The Hardware configuration items are initialized at the factory. Normally, these items will not need to be changed or updated. For all MJ-4 units, the “MP MASK VERS:” item is factory set. “0C” is the default setting and the operator/installer should not change this value. The <DIAGNOSTICS> Menu also includes the Serial Number and Product Revision code for the MJ-4 Control Panel. These are set at the factory and cannot be changed. Refer to the Communications Module Instruction Manual for information about the Comm Module items: CM Test? CM TestStat The configurable tap changer control settings are also contained in the <DIAGNOSTICS> Menu. Contact your Siemens representative for more information before adjusting these settings. 37 4 Setting Up the MJ-4A & MJ-4B Control Panel 4.10 Setting up the Quick Key The Quick Key provides access to the customizable Quick List. The Quick List can be used to step through a series of up to 15 user-set menu items. The Quick List allows creation of a custom menu with the minimal amount of effort. Any changes to the menu parameters must be done using normal configuration and operation procedures. Certain menus cannot be added to the Quick List including: Password Menu, Log Menu(s), Alert Menu. Adding Items to the Quick List: Use the scroll keys to display the desired menu item to be added. Press the +/- key. Press the Quick Key. Repeat to add more screens to the Quick List. Items are stored in the order that you add them. Removing Items from the Quick List: Press the Quick Key repeatedly to display the desired menu item to be removed. Press the +/- key. Press the Quick Key. Press the Cancel/Reset key. Viewing the position of Items in the Quick List: Press the Quick Key repeatedly to display the desired menu item. Press the left arrow key to display the item’s position in the menu stack. Repositioning Items in the Quick List: Press the Quick Key repeatedly until the desired item is displayed. Press the Change Key. Press the Up and Down arrow keys to move the item up and down one position at a time. When finished, no further key presses are necessary. Press the Quick Key repeatedly to cycle through the new order. Displaying Items in the Quick List: Press the Quick Key repeatedly to step through the Quick List. The display will flash from bright to dim to signify that the Quick List is being displayed. When finished, press the Cancel/Reset key to exit the Quick List, or if no keys are pressed for the amount of time specified in the Quick t.o. data item, the Quick List will be automatically exited. The first keypress used to enter the Quick List will always display the Tap Contr screen (showing switch position) before the actual Quick List is displayed itself. While in the Quick List, press the right arrow key to begin a slideshow that automatically steps through the Quick List. Each screen is displayed for the amount of time specified by the QuickDispTim data item. To stop the slideshow and exit the Quick List press the Cancel/Reset key. 38 Siemens Energy, Inc. 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data The MJ-4 Control Panel microprocessor maintains a considerable amount of operational information—both present and historical: • Meter data—instantaneous, minimum, and maximum operational information. • Log data—historical meter data, recorded at specific times. • Demand data—demand data, continuously updated. • “L” bushing voltage is the “Load voltage. With power flowing in the reverse direction, the “S” bushing voltage is the “Load” voltage and the “L” bushing voltage is the “Source” voltage. The table below shows which MJ-4 parameters represent the “S” and “L” readings for each power-flow condition. Table 5.1 Power Flow Mode Vld Vsrc Power Flow Direction Bi-Dir, Neut R. Idle R “L” “S” Forward Counter data—tap change history. Bi-Dir, Neut R. Idle R “S” “L” Reverse • Harmonics data—harmonic analysis data. F Lock, Co-Gen “L” “S” Forward • Communications data—Local Data Port status. F Lock, Co-Gen “L” “S” Reverse R Lock “S” “L” Forward R Lock “S” “L” Reverse Data is available through the front-panel display screen, the local port, or the communication port (if so-equipped). This chapter lists the data items that are maintained by the microprocessor, and tells you how to retrieve them. 5.1 Source and Load Definitions In the following paragraphs, the term “Source” is defined as the connection point from which real power is flowing. The term “Load” refers to the connection point into which real power is flowing. In addition, for purposes of the following discussion, U2 and P2 refer to the terminals with the U2 and P2 labels at the MJ-4 Polarized Disconnect Switch (which may or may not match the regulator leads with the same labels). For a Straight regulator, the “S” bushing potential is provided to U2 via the tertiary winding, while the “L” bushing PT connects to P2. Under forward power flow conditions the source voltage is read at U2 and the load voltage is read at P2. Under reverse power flow conditions, the source voltage is read at P2 and the load voltage is read at U2. If no PT is present, P2 voltage is calculated, see 5.2. For an Inverted regulator with no Source Side PT, the “L” bushing potential is provided to U2 via the tertiary winding. Under forward power flow conditions, the load voltage is read at U2; no source voltage is available. However, an estimated value is calculated, see the P2 Calculation section below. Under reverse power flow conditions, the source voltage is read at U2; no load voltage is available. However, an estimated value is calculated, see the P2 Calculation section below. For an Inverted regulator with a Source Side PT, the “L” bushing potential is provided to U2 via the tertiary winding and the “S” bushing potential is provided to P2 via the Source Side PT. Under forward power flow conditions, the load voltage is read at U2; the source voltage is read at P2. Under reverse power flow conditions, the load voltage is read at P2, the source voltage is read at U2. For applications which require regulation in reverse power flow, users generally select the bi-directional power flow mode. In bi-directional mode with power flowing forward, the “S” bushing voltage is the “Source” voltage and the Siemens Energy, Inc. 5.2 P2 Voltage Calculation This feature provides a calculated value of the “P2” bushing voltage when a measured value is unavailable. When the the P2 voltage reading is less than 50 volts and the P2 Calc setting is enabled under the <ADV CONFIGURE> menu, the MJ-4 automatically calculates the P2 voltage. The MJ-4 displays the calculated P2 value as “Vsrc” or Vld” according to Table 5.1. If the P2 Calc is disabled, then the P2 Value is not calculated. The MJ-4 must know the tap position for the “P2 Calculate” feature to work. See sections 5.7 and 5.8 for information about the tap position and the tap position message. 5.3 Meter Data—the <METER> Menu The Meter data items present operating values such as Voltage, Current, Power, etc. on the display screen. Unless otherwise specified, Meter data includes rms, maximum and minimum values. To view Meter data, use the Menu Selection keys to view the <METER> Menu; then use the ¿ and À keys to sequence through the data items. To view a maximum or a minimum data item, you first view the instantaneous data item and press the Max/Min key. Pressing the Max/Min key once displays the maximum value. To view the minimum value press the Max/ Min key twice. To reset Maximum/Minimum data values, first view the rms value, then press the Max/Min key, and then the Cancel/Reset key. 5.3.1 Viewing Min/Max Time and Date Stamps To view the time and date of occurrence for a minimum or maximum data item, first view the desired min/max data item. With the min/max data item displayed, press the Save key to view the associated time and date stamp. While the time and date stamp is in view, if you press the À key, the first metered data item for the menu will be 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data displayed. Pressing the ¿ key displays the last metered data item. An example for displaying min/max time and date stamps is shown below: power flow conditions, load current includes regulator excitation current which could be approximately 10% higher or lower than actual load current. Action View Vcomp data item in <METER> Menu. Press Max/Min key once. Press the Save key before timeout. Press the À key. PF Lead, PF Lag (Power Factor) 5.3.2 Display Shows Vcomp = 121.2 F Vcomp = 124.3 Fmax 061798 21:26:45 Vld = 122.5F Table 5.2 Meter Data Items <METER> MENU DATA ITEMS Ild1 PF1 KVA1 KW1 KVAR1 Freq1 KWhr2 KVARhr2 PF = Viewing the <METER> Menu Data Table 5.1 summarizes the <METER> Menu data items. The remainder of the section defines the data items in detail. Vld1 Vs1 Vcomp1 This is the present line power factor, derived from the fundamental frequencies only, using the relationship Measured rms regulator load voltage Measured rms regulator source voltage Regulator load voltage corrected for line drop using LDC parameters Measured rms load current Power factor Apparent regulator power load Real power measured at the regulator Reactive power measured at the regulator Line frequency Forward and Reverse Real energy Forward and Reverse Reactive energy (lead & lag) Watts Volts * Amps Three values are recorded for Power Factor: instantaneous, maximum (most leading), and minimum (most lagging or least leading). kVA (Apparent Power) The kVA data item displays the present kVA load on the regulator. The CT of a regulator is always located in the “L” bushing lead. The MJ-4 calculates the kVA per Table 5.3. Table 5.3 Regulator kVA Load Regulator Type Forward Power Flow Reverse Power Flow ANSI A Straight kVA = Vld x Ild kVA = Vs x I(“L”) ANSI B (Inverted) kVA = Vld x Ild kVA = Vs x I(“L”) 1. Instantaneous, Max, and Min values 2. Time-cumulative value — no Max/Min Note: For reverse power flow, Ild is current flowing into the regulator and will differ from actual load current by the amount of excitation current of the regulator. Vld (Load Volts) kW (Real Power) The Vld data item displays the rms load voltage. The value displayed is either the basis voltage (nominal 120 V) or the system primary voltage. (See Meter Volts as defined in the <CONFIGURE> Menu Meter Volts data item, Chapter 4.) The Forward and Reverse kW data items display the real portion of the present kVA load on the regulator. Vs (Source Volts) The Vs data item displays the rms source voltage. The value displayed is either the basis voltage (nominal 120 V) or the system primary voltage. (See Meter Volts in the <CONFIGURE> Menu, Chapter 4.) Vcomp (Line Drop Compensation Volts) The Vcomp data item displays the rms voltage present at the theoretical load center. This is the voltage the microprocessor compares with the voltage setpoint to determine when tap changes are required. The value displayed is either the basis voltage (nominal 120 V) or the system primary voltage. (See Meter Volts in the <CONFIGURE> Menu, Chapter 4.) Ild (Load Current) The Ild data item displays the rms regulator current in amperes. Note: the Current Transformer is typically located in the Load Bushing lead. Therefore, under reverse 40 Real Power = kW = 1 n n Vn(t) x In(t) 1 The kW is displayed as a positive quantity when power flow is into the load, or as a negative quantity when power flow is into the source. kVAR (kVAR) The kVAR data item displays the reactive portion of the present kVA load on the regulator. Reactive Power = kVAR = 1 n n V(t) x I(t+90º) 1 + = lagging, - = leading Freq (Line Frequency) The Freq data item displays the line frequency in Hertz (present, max, min). Siemens Energy, Inc. 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data kWhr F and kWhr R (Forward and Reverse Real Energy) The Forward and Reverse kWhr data items display Kilowatt Hour values. They are accumulated separately for forward and reverse power flow conditions. kWhr is updated once per second, using the formula: kWHRnew = kWHRold + kW*1/3600(hours) kVARhr F and kVARhr R (Forward and Reverse Reactive Energy) The kVARhr F and kVARhr R data items display Kilovar Hour values. They are accumulated separately for forward and reverse power flow conditions. The kVARhr is updated once per second, using the formula: kVARnew = kVARold + kVAR*1/3600(hours) The microprocessor computes and accumulates kVARhr values for each of the four quadrants of the voltage/current phase-angle relationships. These parameters are presented as shown in Figure 5.1. kVAR (reactive power) kVA -kW (reverse) +kVAR (forward) -PF (leading) II I III IV +kW (forward) +kVAR (forward) +PF (lagging) -kW (reverse) kW (real power) -kW (reverse) -kVAR (reverse) +PF (lagging) Figure 5.1 5.4 +kW (forward) -kVAR (reverse) -PF (leading) Power Quadrant Conventions Demand Data— the <DEMAND> Menus Demand measurements are time integration functions of the metered values. The MJ-4 Control Panel performs demand calculations for the following data items: voltage, current, power factor and power. Demand data is maintained separately for forward and reverse power flow conditions (see Table 5.4). During forward power flow conditions, the microprocessor does not accumulate reverse measurements. During reverse power flow conditions, the microprocessor does not accumulate forward measurements. You can select one of two methods of measuring demand: the Sliding Window method and the Thermal Averaging method. (See DmdType in Section 4.3.23.) Vld1,2 Vs1 Fdmd Fdmd FdmdVcomp1 Fdmd Ild1 PFKVAmax PFKVAmin Fdmd KW1 FdmdKVAR1 FdmdKVA1 Load Voltage demand Source Voltage demand Compensated Load Voltage demand Load Current demand Power Factor @ max KVA Power Factor @ min KVA Real Power demand Reactive Power demand Apparent Power demand 1. Instantaneous, min and max data available 2. For each Forward Demand Data Item there is a corresponding Reverse Demand Data Item. For example, Rdmd Vld. To retrieve Demand data, select the appropriate <FW DEMAND> or <REV DEMAND> Menu; then use the ¿ and À keys to sequence through the Demand data items. To view the minimum and maximum values for a given Demand data item, first view the present value; then use the Max/Min key to display the respective maximum and minimum values recorded since the last reset. Demand calculations are initialized at the time of system power up, when configuration items are changed, and on any power flow reversal. Un-initialized data items are presented as dashes (—) on the display screen. Demand values remain un-initialized until completion of the first subperiod. Power factor is stored whenever a new kVA maximum or minimum demand value is reached. These Power Factor values are reset when kVA max or kVA min values are reset. 5.5 Event Log - the <EVENT LOG> Menu The MJ-4 can be set up to record meter data at the time of an “Event.” Events can include: power up, parameter changes, tap changes, etc. Use the <LOG SETUP> Menu to enable the Events you want logged. (See Section 4.5). Table 5.5 describes the data that is to be logged whenever an Event occurs. Table 5.5 <EVENT LOG> Data Items <EVENT LOG> Data items Event: Date: Time: Cause: Vld Vsrc Ild PF KWld KVAR KVAld Tap 1. Siemens Energy, Inc. Demand Data Items Table 5.4 Event number1 Date Time Cause of Event (Message, tap change, etc.) rms regulator load voltage rms regulator source voltage rms regulator load current Present Power Factor Present Real power Present Reactive power Present Apparent power Tap position NNNNNNN NN/NN/NN NN:NN:NN CAUSE NNNN.N NNNN.N NNNN.N N.NN NNNNN ±NNNNN NNNNN NN Raise/lower The Event number is a sequential number used for maintaining and referencing the <EVENT LOG> 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data To access log data, view the <EVENT LOG> Menu with the Menu Selection keys; then use the ¿ and À keys to sequence through the log entries. New Events that occur while Events are displayed are saved, but not made available for viewing until you return to the Menu level and subsequently scroll into the <EVENT LOG> Menu again. Meter data for all of the Events can be retrieved via the display screen on the front panel. Data for the 200 most recent Events is stored and can also be retrieved via the front-panel Data Port or the Communication Port. 5.5.1 Viewing Event Data To quickly go from viewing one Event to viewing the previous or next Event, use the ½ or ¾ keys. For example, if the screen being viewed is [Event: 20], press the ½ key once to view the [Event: 19] screen. From the [Event: 19] screen, press the ¾ key once to view the [Event: 20] screen again. 5.5.2 Clearing Individual Events from the Event Log Table 5.6 describes the data that is logged at the conclusion of each interval. Table 5.6 Interval Log Data Items INTERV: Interval number1 DATE: Interval date TIME: Interval time Vld Secondary2 Load voltage — rms, Max, Min, Dmd Vsrc Source voltage — rms Ild Load current — rms, Max, Min, Dmd PF Power Factor — Present, PFKVA max, PFKVA min KWld Real power — Present, Max, Min, Demand KVAld Apparent power — Present, Max, Min, Demand Tap = Tap position Tapmax = Maximum tap position Tapmin = Minimum tap position Total ops = Total tap changes 1. The Interval number is a sequential number used for maintaining and referencing the interval log. 2. Secondary only — even if PRI selected in Meter Volts data item. Since you can now view all of the <EVENT LOG> data from the front panel, or download it via the data port, it is unnecessary to delete individual <EVENT LOG> items. The MJ-4 no longer supports deleting individual log records. If the <EVENT LOG> memory is full, the oldest record is overwritten when a new event occurs. If the specified interval elapses while you are viewing <INTERVAL LOG> data, the MJ-4 saves the new data, but it is not available for viewing until you return to the Menu level and subsequently scroll into the <INTERVAL LOG> Menu again. Data for all of the Intervals can be viewed from the <INTERVAL LOG> Menu. Data for the 800 most recent Intervals is stored and can also be retrieved through the front-panel Data Port or the Communication Port. 5.6 5.6.1 Interval Log — the <INTERVAL LOG> Menu The MJ-4 Control Panel can be set up to record data at the completion of a predefined interval of time. Use the <LOG SETUP> Menu to define the time interval and to activate Interval logging. (See Section 4.5). Interval logging occurs when “seconds” is zero on the internal clock. For certain interval period selections, interval logging is tied to the time-of-day. For 15 and 30 minute interval settings, the MJ-4 logs data at even quarter and half-hour increments, respectively. For a one-hour setting, the MJ-4 logs data on the hour. For four and six-hour settings, the MJ-4 logs data synchronized to 12:00:00 midnight. Viewing Interval Data To quickly go from viewing one Interval to viewing the previous or next Interval, use the ½ or ¾ keys. For example, if the screen being viewed is [Interval: 20], press the ½ key once to view the [Interval: 19] screen. From the [Interval: 19] screen, press the ¾ key once to view the [Interval: 20] screen again. 5.6.2 Clearing Individual Intervals from the Interval Log Since you can now view all of the <INTERVAL LOG> data from the front panel, or download it via the data port, it is unnecessary to delete individual <INTERVAL LOG> items. The MJ-4 no longer supports deleting individual log records. If the <INTERVAL LOG> memory is full, the oldest record is overwritten when a new interval log occurs. 5.6.3 Resetting Min/Max Values at Each Interval In <LOG SETUP>, set ResLogMinMax to ON to reset min/max values at the start of each interval. With this feature enabled, MJ-4 logs the min/max values that occur during each interval. 42 Siemens Energy, Inc. 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data 5.7 Operation Counter Data the <COUNTERS> Menu Operation counters record the stepping operations of the regulator tap changer (see Table 5.7). Table 5.7 Total Ops Reset Reset Elapsed Ops 24 HR Ops 30 Day Ops MTD Ops Last Month YTD Ops Last Year Tap Tap Control Tapmax Tapmin Counter Data Items The total number of tap changes2 Date of last Elapsed Ops counter reset Time of last Elapsed Ops counter reset Total number of tap changes since last reset1 Number of tap changes in the past 24 hours1 Number of tap changes in the past 30 days1 Number of tap changes this month1 Number of tap changes last month1 Number of tap changes this year1 Number of tap changes last year1 Present position of the tap changer1 Remote or Local based on the mode setting Maximum tap position since last reset1, 3, 4 Minimum tap position since last reset1, 3, 4 1. To reset, use Cancel/Reset key. 2. To change value, use the Change/Scroll/Save keys. 3. Tap position is determined by the “dead reckoning” method (see below) 4. To view, use Max/Min key. To retrieve Tap Changer data, use the Menu Selection keys to access the< COUNTERS> Menu; then use the ¿ and À keys to sequence through the data. Siemens Energy, Inc. Dead Reckoning for Siemens Regulators The control program keeps track of the regulator tap position by means of a “dead reckoning” procedure, analogous to navigational dead reckoning. Dead reckoning must start from a known position. MJ-4 dead-reckoning begins at Neutral (U12 active, if Tap Resync is ON) or when an operator inputs a tap position value. Subsequently, when the microprocessor requests a tap raise/lower (J/K), and the regulator makes the tap change (asserting Operations Count signal U10), the control program updates the tap position value. By this procedure, the MJ-4 maintains continuous tap position information. If, for some reason, a tap change command is not confirmed within an appropriate period of time, a Message condition is raised and dead reckoning is discontinued until the tap changer once again signals Neutral. Similarly, a Message condition is activated if an Operation count signal is received when no tap change command was issued; or if the U12 PDS lead signals that the tap changer has passed through neutral at a time when the assumed dead-reckoning position is not neutral. Note: For application on other manufacturer’s regulators and LTC apparatus, the MJ-4 implements a similar dead reckoning procedure for tap tracking. The details of the tap tracking approach for these applications are included in the Tap Tracking Application Note. 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data 5.8 Alerts—the <Alert> Menu If the Alert name is flashing, acknowledgment is required. Alerts represent exception conditions. A Alert condition may be presently active, or it may have been active at some earlier time. When a Alert occurs, the MJ-4 stores it in the <ALERT> Menu, and illuminates the Alert LED Indicator. 5.8.1 Viewing Alerts If the Alert indicator is flashing, it denotes that a Alert has occurred. Use either the Alert fast path key or the Menu and Scroll keys to view the <Alert> Menu. Use the down arrow key to scroll through the Alerts. Table 5.8 5.8.2 Acknowledging an Alert To acknowledge the Alert, press the Cancel/Reset key. If the Alert condition is still active, the Alert name will stop flashing but the Alert indicator will remain on (steady) until the condition clears. If multiple Alerts have occurred, you can step through them, one at a time using the Alert key or the ¿ and À keys. The Alert indicator will continue to flash until all Alerts have been acknowledged. The conditions listed in Table 5.8 activate ALERT status. The conditions are listed in priority sequence from highest priority at the top to lowest priority at the bottom. Alert Data Items Alert Name Description Duration Ack. Type Low Current Low Current reading-- Magnitude below 1% full scale. Continuous Auto-clear Auto Inhibit Automatic mode inhibited from either terminal block or communication link Continuous Auto-clear Pseudo Manual A remote tap raise/lower operation has been requested (via Communications Module) Continuous Auto-clear Tap Track Error6 The dead reckoning procedure has detected an inconsistency between its assumed tap changer position and the position signaled by the PDS. Momentary ACK required Neutral Signal Error The MJ-4 senses that the Neutral signal remains active though the tap change input indicates that the tap has moved from Neutral. Momentary ACK required Tap Position ???? The MJ-4 does not know the present tap position (based on the dead reckoning algorithm). Continuous Auto-clear Low PT Threshold The MJ-4 detects a Vld voltage below the PT Threshold setting. Continuous Auto-clear Over Current The current exceeds the threshold determined by: I Load Max(%) x I FullLoad Continuous ACK required NV RAM Reset The non-volatile (battery-backed) Static RAM appears to have lost some or all of its data. Momentary ACK required Low Battery The back-up battery is below the minimum threshold and should be replaced. Continuous Auto-clear High Voltage Maximum PT voltage exceeded (145 Volts for U2 and/or P2) Continuous ACK required Not in auto Auto/Manual switch is in Manual Continuous Auto-clear R Limit Reached Raise Limit Reached. Tap position has reached or exceeded the value specified in “R Limit” item Continuous Auto-clear L Limit Reached Lower Limit Reached. Tap position has reached or exceeded the value specified in “L Limit” item Continuous Auto-clear Self Test Fault The MJ-4 self test found an error condition Continuous ACK required Notes for Table 5.8: 1. Alert status is in effect if any Message condition is active. If the Alert status is the result of more than one condition, the Message Indicator will flash until all Alerts requiring acknowledgment have been acknowledged. Whenever the Alert Indicator is flashing, it is an indication that the contents of the <ALERT> Menu should be reviewed. 2. Continuous - Condition lasts indefinitely. (May persist after Alert is acknowledged.) 3. Momentary - Condition lasts briefly. 4. ACK required - The MJ-4 keeps the Alert active until you acknowledge it. 5. Auto-clear - The MJ-4 automatically clears the Alert when the condition ceases. 6. The Tap Track Error alert can be disabled, if desired. See Table 4.2 on page 17. 44 Siemens Energy, Inc. 5 Reading and Interpreting MJ-4A & MJ-4B Control Panel Data 5.9 Harmonics Data— the <HARMONICS> Menu Harmonics data are calculated for load voltage, source voltage, and load current. The <HARMONICS> Menu contains the data items listed in Table 5.9: Table 5.9 <HARMONICS> Menu Data Items Vld THD = NNN.N% Vs THD =: NNN.N% Ild THD =: NNN.N% Show Harm: ODD, EV/OD Show As: %TOTAL, %FUND, RMS VAL. Vld 1st = NNN.N%T Vld 1st = NNN.N V Vld 3rd = NNN.N%F : Vld 31st = NNN.N% F Vs 1st = NNN.N%T Vs 1st = NNN.N V Vs 3rd = NNN.N%F. Vs 31st = NNN.N%F : Ild 1st = NNN.N%T Ild 1st = NNNN A Ild 3rd = NN.N%F : Ild 31st:NN.N%F 5.10 The <COMMUNICATIONS> Menu contains Local Data Port status. See Section 4.7 for configuring <COMMUNICATIONS> Menu items, such as baud rate, parity, address, etc. The <COMMUNICATIONS> Menu displays the status items listed in Table 5.10: Table 5.10 DATA ITEM Use the Menu and Scroll keys to view the <HARMONICS> Menu. Use the ¿ and À keys to step through the data items. Show Harm: Odd Ev/Odd Show odd harmonics only Show both even and odd harmonics. Show As: Show harmonics as percentage of total signal magnitude. Show harmonics as percentage of the fundamental. Show harmonics as signal magnitude. %TOTAL. %FUND. RMS Val. Use the ¿ and À keys in the <HARMONICS> Menu to view the harmonics data. The harmonics data items appear after configuration items Show Harm and Show As. The harmonics data items always include the rms and % Total values for the fundamental (i.e., the 1st harmonic). Data for even harmonics is only shown if configuration item Show Harm is set for EV/OD. Data for harmonics above the 1st harmonic are shown as % Total, % Fundamental, or rms depending on which is selected in the Show As configuration item. Siemens Energy, Inc. <COMMUNICATIONS> Menu Status Items Data Stat = Bold denotes default The first set of data items in the <HARMONICS> Menu are the three Total Harmonics Distortion values for: load voltage (Vld THD: NNN.N%), source voltage (Vs THD: NNN.N%), and load current (Ild THD: NNN.N%). The second set of data items in the <HARMONICS> Menu are Show Harm: and Show As:. These data items allow you to select the format of the data to be viewed: Local Data Port— the <COMMUNICATIONS> Menu 5.11 DESCRIPTION Communications status conditions GoodRX A “good” message (no errors) has been received Inact; Data Port is inactive LocCtl MJ-4 is in local control (commlink control is inhibited) FE RX Framing Error in received message OE RX Overrun Error in received message NE RX Noise Error in received message PE RX Parity Error in received message CSE RX Checksum Error in received message PTE RQ Point Type Error (invalid point type requested) CME RX Command Error (invalid command) received PNE RX Point Number Error (Invalid point number) received VRC Status - the <REGULATOR> Menu The VRC Status items indicate the present level of Voltage Reduction Control (VRC). The VRC Status item is indicated as: VRC Stat = XX.X%MY where: XX.X% is the amount of voltage reduction (0.0% to 10.0%) M is the VRC Mode where: L = Local R = Remote A = Auto (w/Remote Override) Y is the presently active VRC step for: Local - not applicable Remote - 1, 2, or 3 Auto - 1 or 2 This data item can be accessed using the VRC Select fastpath key. 6 MJ-4A & MJ-4B Control Panel Automatic Mode 6 MJ-4A & MJ-4B Control Panel Automatic Mode This Chapter covers operating principles of the MJ-4 control program and describes the various functions performed by the microprocessor. It contains the information you may need when deciding between the various options described in Chapter 4 (Setting Up the MJ-4 Control Panel) and Chapter 5 (Reading and Interpreting MJ-4 Control Panel Data). 6.1 MJ-4A & MJ-4B Control Modes 6.1.1 Summary of the MJ-4A Control Modes The regulator control function has four operating modes: local manual control, local automatic control, remote control, and Off. Manual control can only be performed locally. Select the operating mode with the Remote-Auto/Off/ Manual switch as shown in Figure 6.1. Auto Off (By-Pass Position) Remote / Local Manual Figure 6.1 Auto/Manual Switch (Shown in Off position) Manual mode Place the Auto/Off/Manual Switch in the down position to activate the Manual mode. In Manual mode, you can use the Tap Raise/Lower switch (on the MJ-4A front panel) to control the tap position directly. Status information is available via the remote communications link, but the remote operator cannot change settings or otherwise operate the MJ-4A Control Panel. The MJ-4A Control Panel remains in the Pseudo-Manual mode for a predefined time period after receipt of the last remote tap raise/lower command. When the time period has elapsed, if the MJ-4A Control Panel has Remote Auto Inhibit disabled, it resumes its normal automatic control operations. If Remote Auto Inhibit is enabled, it maintains its tap position until it recieves another raise/lower command or until Remote Auto Inhibit is disabled. Auto-Local mode With the Auto/Manual switch in the up position, if the Remote/Local key is pressed so that the Remote Disabled LED is on, the control Panel will be in the Auto-Local mode. In this mode, the MJ-4A executes its normal tap control algorithm. Status information is available via the remote communications link, but the remote operator cannot change settings or otherwise operate the MJ-4A Control Panel 6.1.2 Summary of the MJ-4B Control Modes The regulator control function has four operating modes: manual and automatic control, each with remote control enabled or disabled. Select the operating mode with the Remote and Auto/Manual switches as shown in the figure below. R e m o te / Local A u to / M anual Figure 6.1b Remote/Local and Auto/Manual Switches Manual mode (By-Pass Position) No operation of the tap changer can occur: remotely, locally, or automatically. Push the Auto/Manual Switch so that the Auto Disabled LED is illuminated to activate the Manual mode. In Manual mode, you can use the Tap Raise and Lower keys (on the MJ-4B front panel) to control the tap position directly. Auto-Remote mode Automatic mode With the Auto/Manual switch in the up position, the Remote/Local key may be pressed so that the Remote Disabled LED is off, putting the control Panel into the Auto-Remote mode. Push the Auto/Manual Switch so that the Auto Disabled LED is not illuminated to activate the Automatic mode. In Automatic mode, the MJ-4B executes its normal tap control algorithm. In this mode, the MJ-4A executes its automatic tap control algorithms, unless overridden remotely. Status information is available via the remote communications link. A remote operator can request a tap raise or lower via the communications link, change settings and remotely operate the control program. For direct control via terminal strip connections see Figure 2.4. Remote Control Enabled Off (By-Pass Position) When the remote operator initiates the tap raise/lower, the MJ-4A enables its “Pseudo-Manual” operating mode. The Pseudo-Manual alert condition is activated, and local automatic operations are disabled until the remote-commanded tap raise/lower is completed. 46 Push the Remote / Local push button so that the Remote Disabled LED is not illuminated to enable remote control (Auto-Remote mode). In this mode, the MJ-4B executes its automatic tap control algorithms, unless overridden remotely. A remote operator can request a tap raise or lower via the communications link. When the remote operator initiates the tap raise/lower, the MJ-4B enables its “Pseudo-Manual” operating mode. The Pseudo-Manual alert condition is activated, and local automatic operations are disabled until the remote-commanded tap raise/ lower is completed. Siemens Energy, Inc. 6 MJ-4A & MJ-4B Control Panel Automatic Mode The MJ-4B Control Panel remains in the Pseudo-Manual mode for a predefined time period after receipt of the last remote tap raise/lower command. When the time period has elapsed, if the MJ-4B Control Panel is in Automatic mode, it resumes its normal automatic control operations. If the MJ-4B Control Panel is in Manual mode, it maintains its tap position until it recieves another raise/lower command or until it is placed back into Automatic mode. Remote Control Disabled In this mode, status information is available via the remote communications link. In addition, the remote operator can change settings and remotely operate the control program. The panel may also be allowed to work in Auto-Local mode wherin it will perform automatic control operations. Table 6.1 Table 6.1 summarizes the four operating modes. Summary of Control Mode Operation MJ-4A and MJ-4B Switch Positions Remote Control Enabled Remote Control Disabled 6.2 With the panel remaining in Auto, Push the Remote/Local push button so that the Remote Disabled LED is illuminated to disable Remote control. Status information is available via the remote communications link, but the remote operator cannot change settings or otherwise operate the MJ-4B Control Panel. Manual Automatic 1. Automatic Operation Disabled 1. Automatic Operation Enabled 2. Comm link tap control override 2. Comm link tap control override 3. Comm Link Raise/Lowers Enabled 3. Comm Link Raise/Lowers Enabled 4. Comm Link Auto/Manual control Enabled 4. Comm Link Auto/Manual control Enabled 5. Tap Raise and Lower Switches Enabled 5. Tap Raise and Lower Switches Disabled 1. Automatic Operation Disabled 1. Automatic Operation Enabled 2. No comm link tap control override 2. No comm link tap control override 3. Comm Link Raise/Lowers Disabled 3. Comm Link Raise/Lowers Disabled 4. Comm Link Auto/Manual control Disabled 4. Comm Link Auto/Manual control Disabled 5. Tap Raise and Lower Switches Enabled 5. Tap Raise and Lower Switches Disabled Overview of Automatic Control Algorithm 8. Monitored load current 9. Load power factor The automatic control algorithm maintains the output voltage within its prescribed limits while following a control hierarchy. 10. Power flow operating mode Normal algorithm operation is as follows. When voltage falls outside the allowed range (defined by voltage level set point ± ½ bandwidth), the delay timer is started. If voltage is out of range at the end of the delay period, the tap change motor is energized. When the voltage is back within range, the tap change motor is deactivated. (Hysteresis is included to prevent oscillations.) Because coinciding events might introduce conflicts, an operational hierarchy must be established. This hierarchy is maintained when the unit is under automatic control. Manual mode always takes precedence over automatic control. In automatic mode, the control program processor controls the tap changer motor. The control algorithm takes the following into account: 1. Calculated or monitored regulator output voltage 2. Voltage-level set point 3. Bandwidth set point 4. Resistance line drop compensation set point 5. Reactance line drop compensation set point 6. Voltage limit control set points 7. Voltage reduction control setpoints Siemens Energy, Inc. 11. Power flow direction. Conflicts are resolved according to the following priority scheme (from highest to lowest): 1. Automatic tap change inhibit (implemented with terminal strip jumpers or Comm Link command). 2. Current inhibit (determined by I % Threshold of configuration setting; as % of full scale CT rating). 3. Current Bias Section 6.5.3) 4. Voltage Limit Control (defined in regulator settings). 5. Voltage Reduction Control. 6. “Normal” regulator control operation. setting and Bias Percent (see 47 6 MJ-4A & MJ-4B Control Panel Automatic Mode 6.3 Voltage Sensing and Correction Voltage Sensing The control program monitors the regulator output voltage signal from one of the following sources: • a voltage transformer, “VT” [also known as a potential transformer or “PT”], integral to the regulator, which is turns-ratio corrected to deliver 120 VAC at the nominal system voltage. • the utility winding of the regulator, which generally requires correction to deliver 120 VAC at the nominal system voltage. The control program senses regulator output (i.e., “load”) voltage depending on power flow operating mode (see Table 6.2): Table 6.2 Regulator Output Voltage Sensing Regulator Design ANSI Type Winding Used for Voltage Sensing Forward Power Flow Operation Reverse Power Flow Operation A (Straight) Voltage transformer Utility winding B (Inverted) Utility winding Voltage transformer Since the control program routinely senses both the voltage transformer and the utility winding, it is a straightforward process for the control program to select which source is “active” (depending on power flow mode and regulator design). If a voltage transformer is not installed on the regulator, then the control will calculate the voltage on that side of the regulator based on the utility winding voltage and tap position. Software Voltage Measurement Correction The monitored output voltage is scaled appropriately to the nominal basis voltage in two steps. The first voltage scaling is performed through a step-down transformer. The second scaling takes place in the software algorithm after the voltage is converted to a numeric representation. Software scaling corrects the nominal input voltage level to the numeric representation of the basis voltage. The basis voltage value is user configurable. The choices are 115, 120 and 125 V. The default basis voltage is 120 V. 6.4 Voltage Limit Control The voltage limit control (VLC) function monitors regulator output voltage and compares it to maximum and minimum voltage limit set points. If the VLC function is active, the control program inhibits tap changes that would cause the voltage to go above the VLC upper or below the VLC lower voltage. If VLC is activated while the voltage is outside of the VLC limit range, the tap position is incremented/decremented until the voltage is within the defined VLC range. 48 Limiting and/or runback may occur if one of the following happens: 1. The source voltage changes dramatically, 2. The load on the regulator changes significantly, or 3. The VLC function is enabled when the limit conditions are exceeded. Note: The VLC function uses the Vld (i.e., the load voltage at the regulator) to determine whether or not to limit or runback. The VLC algorithm senses one regulator bushing for forward power flow, and the other regulator bushing for reverse power flow. (See Forward/Reverse Operation modes, below). The maximum voltage limit set point is adjustable from 106.0 volts to 134.0 volts in 0.1 volt steps. The minimum voltage limit set point is adjustable from 106.0 volts to 134.0 volts in 0.1 volt steps. The control program will not allow these limits to be set so that they overlap one another. If regulator output voltage falls outside limits, VLC acts to return regulator voltage within limits. Return begins immediately, (i.e., without regard to the time delay setting), while avoiding a hunting condition, (i.e., VLC will not force a tap change which would activate the basic control algorithm and force the regulator outside limits once again). VLC activates when load voltage is within one volt of the upper/lower limit to prevent the voltage from going outside prescribed limits. 6.5 Reverse Power Flow Systems where power flow reversals occur have unique regulation control requirements. For systems of this type, the MJ-4 senses the reversal and adjusts its operation accordingly. When power flow direction changes, the MJ-4A & MJ-4B control algorithm takes the following factors into account: 1. Power Flow direction, 2. Forward or Reverse operating mode, and 3. Power Flow Mode as selected from the <CONFIGURE> Menu. These factors are discussed in greater detail below: 6.5.1 Power Flow Direction The microprocessor determines power flow direction by continually monitoring the real power (kW) reading and the real component of current. The real component of current represents the component of the current which is in phase with the load voltage signal. The MJ-4 Control Panel indicates forward power flow when the real power (kW) is positive and the real component of current is greater than 1% of the full scale current. Siemens Energy, Inc. 6 MJ-4A & MJ-4B Control Panel Automatic Mode Reverse power flow is indicated when the real power is negative and the real component of current is greater than 1% of the full scale current. To avoid excessive switching between Forward and Reverse Operation (defined below), the microprocessor delays five seconds after the occurrence of a current flow reversal before switching from forward to reverse, and vice-versa. As an example, assume current is flowing in the forward direction. When load current magnitude drops through zero and increases to a magnitude that exceeds 1% rated current in the reverse direction, the microprocessor delays five seconds and then considers reverse power flow to be in effect. Reverse power flow remains in effect until current direction becomes forward once again and its magnitude exceeds 1% of rated current in the positive direction for five seconds. At that time, the microprocessor considers forward power flow conditions to have resumed. Power flow direction is indicated on many of the metering screens. “F” indicates forward power flow, “R” indicates reverse power flow. “F” is shown when: kW > 0 and |Ireal| > 1% (of full scale) for 5 seconds minimum. “R” is shown when: kW < 0 and | Ireal | > 1% (of full scale) for 5 seconds minimum. If the real current magnitude is below the 1% threshold, the last known power flow direction remains in effect. If the real current magnitude is below the 1% threshold after power up or unit reset, the MJ-4 defaults to forward power flow operation. It is possible for Reverse Power Flow conditions to occur in regulators with no source-side voltage input (e.g., no “Source-Side PT” for Siemens Inverted Regulators). In this case, the MJ-4 uses the calculated source-side voltage for performing reverse power flow regulation. See sections 5.1 and 5.2 for details on source-side voltage calculation. When determining power flow direction, the system takes into account the current-to-voltage phase relationship associated with the system as specified in the <CONFIGURE> Menu (System, Utility Polarity, and I [current] Shift parameters). 6.5.2 Forward/Reverse Operation The MJ-4 Control Panel accommodates power flow reversals by alternating between “Forward” and “Reverse” modes. Because the microprocessor monitors (or derives) the voltage on both sides of the regulator, it can reverse modes by simply reversing its definition of “source” and “load.” • In Forward Operation mode, the microprocessor senses the “L” Bushing (or derives the “L” Bushing voltage from the “S” Bushing voltage and the knowledge of the tap position) to determine load voltage and controls the tap changer on the basis of the Forward setpoints (Voltage, Bandwidth, Time Delay, Line Drop Compensation). During Forward Operations, “forward” Meter data is displayed. • In Reverse Operation mode, the microprocessor senses the “S” Bushing (or derives the “S” Bushing Siemens Energy, Inc. voltage from the “L” Bushing voltage and the knowledge of the tap position) to determine load voltage and controls the tap changer on the basis of the Reverse setpoints (Voltage, Bandwidth, Time Delay, Line Drop Compensation). During Reverse Operations, “reverse” Meter data is displayed. The following parameters determine whether the tap change motor is energized to raise the tap position or to lower it: 1. Power flow direction, 2. Forward/reverse operation, 3. Out-of-band status, 4. Power flow mode (see below for details). Tables 6.3 and 6.4 on the next page summarize the tap change direction for each Power Flow mode 6.5.3 Current Bias and Bias Percent This option is only in effect when the power flow mode is Bi-Directional. For this special operation, the Bias percent must be greater than the I Threshold%. Typically I Threhold % should be set to 0%. The operation of this feature is described below, categorized into direction and magnitude of current flow. Current is greater than the Bias percent (no change in prior functionality): • Forward Power Flow: tap changes will occur based on the Load bushing voltage. • Reverse Power Flow: tap changes will occur based on the Source bushing voltage. Current is less than the Bias Percent (new functionality): • None: no tap changes will occur. • Fwd: tap changes will occur based on Load bushing voltage. • Rev: tap changes will occur based on Source bushing voltage. • NeutT: tap changer will run to Neutral Tap. 49 6 MJ-4A & MJ-4B Control Panel Automatic Mode 6.5.4 Power Flow Modes Idle Reverse, and Co-generation. Your selection of one of these determines which algorithm the control program uses under reverse power flow conditions. The MJ-4 supports six Power Flow Modes: Forward Locked, Reverse Locked, Bidirectional, Neutral Reverse, Table 6.3 Tap Changer Direction Power Flow Mode Line Drop Compensation Values Bi-Dir F Power Flow Direction Forward Reverse • • • R Neut R MJ-4 Internal Operation Forward Reverse • • Idle R • • Co-Gen • R (See Table 6.4) F Lock • F • F R Lock • R • R Return to Neutral* Forward • • F Reverse Forward • • F Forward • • F Tap Change Control See Table 6.4 None (tap idles) • Forward • Forward • Forward • Forward • Reverse • Reverse * If tap position is not known, Neut R operates same as Idle R. Table 6.4 Tap Change Control Operation Forward Reverse “Vcomp” location “L” Bushing “S” Bushing Out of Band High Lower Raise Out of Band Low Raise Lower Voltage Setpoint Fwd Volts Rev Volts Bandwidth Setpoint Fwd BW Rev BW Time Delay Setpoint Fwd Delay Rev Delay F* Fwd Comp (R) Fwd Comp(X) R* Rev Comp (R) Rev Comp (X) Line Drop Compensation (R = Resistance, X = Reactance) *For Co-gen mode when in Reverse Power Flow mode, use Forward Voltage, BW, and Time Delay setpoints, but use Reverse Line Drop Compensation values. 50 Siemens Energy, Inc. 6 MJ-4A & MJ-4B Control Panel Automatic Mode F LOCK (Forward Locked Mode) R LOCK (Reverse Locked Mode) This mode of operation is intended for use on systems where reverse power flow is not anticipated. Tap changes are inhibited under reverse power flow conditions. This mode of operation is intended for use on systems where forward power flow is not anticipated. Tap changes are inhibited under forward power flow conditions. In this mode, the controller always operates in forward mode. The tap changer operates unless reverse current magnitude exceeds the I Threshold % setpoint, at which time further tap changes are inhibited. The tap changer resumes operation when the reverse current drops below the I Threshold % setpoint. In this mode, the controller always operates in reverse mode. The tap changer operates unless forward current magnitude exceeds the I Threshold % setpoint, at which time further tap changes are inhibited. The tap changer resumes operation when forward current magnitude drops below the I Threshold % setpoint. In this mode, if power flow does reverse, Demand values are not computed. In this mode, when power flow is Forward, Demand values are not calculated. View Pwr Flow: F LOCK on the <CONFIGURE> Menu. View Pwr Flow: R LOCK on the <CONFIGURE> Menu. Reverse Current Forward Current Tap changes inhibited Reverse Current Tap changer operates Tap changer operates Tap changes resume Tap changes resume Forward Current Tap changes inhibited Band indicators on RPF indicator off RPF indicator flashing RPF indicator on RPF indicator flashing Band indicators flashing I Threshold % 1% 0 1% 1% Current Figure 6.2 Forward Locked Mode Siemens Energy, Inc. 0 1% I Threshold % Current Figure 6.3 Reverse Locked Mode 51 6 MJ-4A & MJ-4B Control Panel Automatic Mode BI-DIR (Bi-directional mode) IDLE R (Idle Reverse) This mode of operation is intended for use on systems where reverse power flow is anticipated and voltage regulation is desired under either forward or reverse power flow conditions. This mode of operation is intended for use on systems where reverse power flow is an abnormal situation. Under reverse power flow conditions, the regulator idles at the last tap position. In this mode, the tap changer operates when current magnitude exceeds the I Threshold % setpoint. The tap changer operates in forward mode when forward current magnitude exceeds the I Threshold % setpoint, and in reverse mode when reverse current magnitude exceeds the I Threshold % setpoint. In this mode, the controller always operates in forward mode. When forward current magnitude drops below the I Threshold % setpoint, tap changes are inhibited and the regulator idles at the last tap position. Tap changer operation resumes when forward current magnitude exceeds the I Threshold % setpoint. I Threshold %, must be set to a minimum of 1%(when I Dir Bias is not in use; i.e. I Dir Bias = None). See Section 6.5.1 for more details. Select Pwr Flow: IDLE R on the <CONFIGURE> Menu. When I Dir Bias is in use, I Threshold should be set to 0%. Reverse Current Forward Current View Pwr Flow: Bi-dir on the <CONFIGURE> Menu. Tap Changes Inhibited Reverse Current Reverse Operation Forward Operation Forward Current Tap Changes Inhibited Forward Operation RPF indicator off RPF indicator on Band indicators flashing 1% RPF indicator off RPF indicator on 0 1% I Threshold % Current Band indicators flashing Figure 6.5 I Threshold % 1% 0 1% Idle Reverse Mode I Threshold % Current Figure 6.4 52 Bi-directional Mode. Siemens Energy, Inc. 6 MJ-4A & MJ-4B Control Panel Automatic Mode NEUT R (Neutral Reverse) CO-GEN (Co-generation) This mode of operation is intended for use on systems where reverse power flow is an abnormal situation. This mode of operation is for use on systems where power flows from Utility to consumer at certain times and from consumer to Utility at other times. In this mode, the tap changer operates whenever current magnitude (either forward or reverse) exceeds the I Threshold % setpoint. In this mode, the controller always operates in the forward mode. When current magnitude drops below the forward I Threshold % setpoint, tap changes are inhibited. When the reverse current magnitude exceeds I Threshold % setpoint for ten seconds, the tap changer resumes operation and returns the tap changer to the neutral position without stopping. The tap changer then remains at the neutral position until forward current magnitude once again exceeds the I Threshold % setpoint. If, while the tap changer is returning to neutral, the forward current magnitude increases above the I Threshold % setpoint, normal forward tap changer operation resumes. Neutral Reverse mode is dependent upon the MJ-4 tap tracking algorithm. If the tap position is unknown to the microprocessor, the tap changer idles at the last held position. View Pwr Flow: NEUT R on the <CONFIGURE> Menu. Reverse Current Forward Current In this mode, the controller always operates in Forward mode. Forward Line Drop Compensation values are used when forward current magnitude exceeds the I Threshold % setpoint. Reverse Line Drop Compensation values are used when reverse current magnitude exceeds the I Threshold % setpoint. Tap changes are inhibited when current magnitude is between the I Threshold % setpoints. View Pwr Flow: CO-GEN on the <CONFIGURE> Menu. Reverse Current Forward Operation with Reverse LDC Forward Current Tap Changes Inhibited RPF indicator off RPF indicator on Return to neutral after ten seconds Tap Changes Inhibited Forward Operation Forward Operation with Forward LDC Band indicators flashing I Threshold % 1% 0 1% I Threshold % Current Continue return to neutral RPF indicator on RPF indicator off Band indicators flashing I Threshold % 1% 0 1% Band indicator LEDs on Figure 6.7 Co-generation Mode I Threshold % Current Figure 6.6 Neutral Reverse Mode Siemens Energy, Inc. 53 7 Software for Communicating with the MJ-4A & MJ-4B Control Panel 7 Software for Communicating with the MJ-4A & MJ-4B Control Panel 7.1 Communications Software Siemens has developed a Windows-based communications software application called MJXplorer. All configuration and data can be downloaded to a PC via the RS-232 Data Port located on the front of the MJ-4 Control Panel or through an optional Communication Module. Downloaded data can then be saved and imported to other commonly-used software, including spreadsheet applications. 7.2 Uploading New MJ-4A & MJ-4B Software Siemens offers a software application, called MJXtra, for uploading new versions of software to the Control Panel. Through a simple set of windows and pull-down menus, you confirm the communications settings and transmit the new software via the front-panel Data Port. In addition to downloading, MJXplorer software can modify configuration information and upload the information to the MJ-4 Control Panel. The MJXplorer software and operating instructions are available from Siemens. Contact your Siemens Power Transmission & Distribution representative for details. Another program called DNP Configure can be used to define a custom set of DNP points for a control panel that has a communications module. This program is also available from Siemens. Contact your Siemens representative for details. All software is available on the Siemens website listed in section 1.8. 54 Siemens Energy, Inc. 8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting 8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting 8.1 Introduction • Power and Sensing fuses MJ-4 Control Panel service is primarily accomplished at the factory. However, certain basic procedures can be accomplished in the field. This chapter outlines a set of procedures whose major objectives are to: • External Source fuse (if External Source Terminals are used to power the unit) • Fuse connectors not mated properly 1. Ensure that the fault is inside the MJ-4 (and not in external connections or connected equipment). • Jumpers not in their correct positions 2. Ensure that the fault is not due to improper jumper arrangements or some other user-correctable condition. • Terminal Strip connectors not mated properly • Terminal Strip connector jumpers missing or screws not tightened properly 3. Determine whether the fault can be locally repaired (e.g., by replacing a fuse). CAUTION Troubleshooting approaches depend upon the problem. Among other indicators, you should consider: • Visual review of the unit. • Alerts (see Table 8.1 below). 8.2 120 volts on terminal block, leads, and inside control panel housing. May result in minor or moderate injury including equipment damage. Disconnect all power sources before making connections to the terminal block or opening the control panel housing. Visual Inspection Check: Table 8.1 Alert Messages Alert Name What to Check Low Current Check E1 and C2 wiring. Check calibration on the Current inputs. Auto Inhibit This alert does not indicate a fault condition. It indicates that Automatic Inhibit has been activated (either via the communications link or via the Automatic Inhibit Input terminals Tap Track Error May indicate a temporary fault condition (failure to detect a transition on one of several input lines.) Check PDS signals J, K, U10 and U12. Neutral Sig. Err May indicate a temporary fault condition (failure to detect a transition on one of several input lines.) This alert could also indicate a problem with the Neutralite™ input signal. Check the Neutral (PDS-U12) input. Tap Pos ???? May indicate a temporary fault condition (failure to detect a transition within the allowed time period on one of several input lines.) Check the Neutral (PDS-U12) and Operations Counter (PDS-U10) inputs. Low PT Thresh Overcurrent NV RAM Reset This alert does not necessarily indicate an MJ-4 fault condition. Check to see whether this alert condition goes away when both U2 and P2 are above the PT Threshold. This alert does not (normally) indicate an MJ-4 fault condition. Ensure that this Alert goes away when an in-range current (0-200 mA) is applied at C2/E1. May indicate a temporary fault condition. If condition appears repeatedly, replace the unit. Low Battery Indicates that it is time to replace the Lithium Battery. If condition persists after a good battery is installed, check that the battery was installed properly. If fault persists, consult the factory. High Voltage May indicate a temporary system fault condition. If condition persists when in-range voltages (90-140 VAC) are applied to both PDS-U2 and PDS-P2 inputs, perform calibration. Not in Auto Indicates that Remote-Auto/Off/Manual switch is in Manual. R Limit Reached, L Limit Reached These alerts indicate that the tap position has reached or exceeded the pre-set threshold. These alerts may occur during normal operation due to system conditions. If these alerts occur when system conditions do not warrant it, their occurrence could indicate an MJ-4 failure. Verify the MJ-4 can automatically raise and lower tap position. Self Test Fault This alert indicates a failure of one or more MJ-4 self tests. Consult your Siemens representative for instructions. Siemens Energy, Inc. 55 8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting 8.3 Troubleshooting Based on Alert Messages Alert messages can be used to help diagnose both system problems (ones which include both regulator and controller), and internal MJ-4 problems. Table 8.1 provides suggestions for troubleshooting an MJ-4 Control Panel using information from the <ALERTS> menu. Note that faults identified as “temporary” may be due to transient conditions within the system and may not be internal MJ-4 faults. Note that faults identified as “temporary” may be due to transient conditions within the system and may not be internal MJ-4 faults. 8.4 Voltage and Current Calibration The MJ-4 Metering functions are calibrated at the factory. Periodically check calibration, and, if needed, recalibrate the MJ-4: 8.4.1 Checking the U2 Voltage Calibration Note: You can check the U2 voltage calibration while the panel is installed on a regulator. To check U2 calibration, apply an AC voltage (in the range of 115 to 135 VAC) from U2 to E. Monitor the Voltage Calibration/Test Terminals with a true RMS voltmeter. View the “U2 Cal” screen on the MJ-4 (i.e., goto <DIAGNOSTICS> menu and press down arrow once to show “U2 Cal”.) Verify that the “U2 Cal” reading matches the applied voltage (within ± 0.5 VAC) If calibration is off, recalibrate (see below.) 8.4.2 Checking the P2 Voltage Calibration Note: If the regulator provides the “source” voltage signal, you can check the P2 voltage calibration while the panel is installed on the regulator. (If the regulator lacks a “source” voltage signal, then there is no need to calibrate the P2 input.) To check P2 calibration, apply an AC voltage (in the range of 115 to 135 VAC) from P2 to E. Monitor the Voltage Calibration/Test Terminals with a true RMS voltmeter. View the “P2 Cal” screen on the MJ-4 (i.e., goto <DIAGNOSTICS> menu and press down arrow twice to show “P2 Cal”) Verify that the “P2 Cal” reading matches the applied voltage (within ± 0.5 VAC) If calibration is off, recalibrate (see below.) 8.4.3 Checking the Load Current Calibration Note: To check the current calibration, remove the panel from the tap changer apparatus, connect an external ammeter, and apply an external AC current source. To check C/C2 Low calibration, apply a nominal 5 mA AC current at C2/E1 and verify that “C/C2low” reads within ±0.2 mA of the applied value (as displayed on external Ammeter connected at C/C2.) 56 To check C/C2 Medium calibration, apply a nominal 80 mA AC current at C2/E1 and verify that “C/C2med” reads within ± 0.5 mA of the applied value (as displayed on external Ammeter connected at C/C2.) To check C/C2 High calibration, apply a nominal 140 mA AC current at C2/E1 and verify that “C/C2high” reads within ± 0.7 mA of the applied value (as displayed on external Ammeter connected at C/C2.) 8.4.4 Calibrating the U2 Voltage Connect an external true rms voltmeter at the front panel “Voltage Calibration/Test Terminal.” Apply the nominal calibration voltage (per Table 8.2.) Display the “U2 Cal” screen. To calibrate, press the Change key, then the À or ¿ key to make the value shown on the MJ-4 display agree with the external voltmeter value. When the change is complete, press the Save key. Note: If password protection is in effect, you must enter the password to enable calibration. The default password for the <DIAGNOSTICS> Menu is “3333” . 8.4.5 Calibrating the P2 Voltage Connect an external true rms voltmeter at the front panel “Voltage Calibration/Test Terminal.” Apply the nominal calibration voltage (per Table 8.2.) Display the “P2 Cal” screen. To calibrate, press the Change key, then the À or ¿ key to make the value shown on the MJ-4 display agree with the external voltmeter value. When the change is complete, press the Save key. Note: If password protection is in effect, you must enter the password to enable calibration. The default password for the <DIAGNOSTICS> Menu is “3333” . 8.4.6 Calibrating the Load Current Note: To calibrate the current, disconnect the panel from the tap changer apparatus. Remove onboard jumper J1 (see Figure J.1) and Terminal Strip jumper at P3B-11 & 12. Connect an external ammeter, and apply an external AC current source, per Table 8.2. After calibration, replace J1 and Terminal Strip jumper at P3B-11 & 12. The Load Current (Ild) has three calibration set-points: C/C2 Low, C/C2 Medium, and C/C2 High. Calibrate all three setpoints with an external true rms ammeter connected at the rear panel (terminal strip contacts P3B-11 & 12.) Connect a (nominal) 0-200 mA AC current source at C/ C2 (terminal strip contacts P2A-5 & 7.) Apply the C/C2 Low calibration current (per Table 8.2). Use the Menu and Scroll keys to view the “C/C2low” screen. To calibrate, press the Change key, then the À or ¿ key to make the value shown at the MJ-4 display agree with the external ammeter value. When the change is complete, press the Save key. Siemens Energy, Inc. 8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting Note: If password protection is in effect, you must enter the password to enable calibration. The default password for the <DIAGNOSTICS> Menu is “3333” . Table 8.2 Repeat the above procedure for C/C2 Medium and C/C2 High. After calibration, replace J1 and Terminal Strip jumper at P3B-11 & 12. Voltage and Current Calibration Signal to Calibrate Test Signal Application Point Test Signal Measurement Point Nominal Calibration Signal Magnitude Tolerance MJ-4 Data Item <DIAGNOSTICS> Menu Conditions U2 U2 to E (P2A-8 & 6) Voltage Calibration Terminals 120 VAC (RMS) ±0.5 VAC U2 Cal U2/P2 key = U2 P2 P2 to E (P2A-4 & 6) Voltage Calibration Terminals 120 VAC (RMS) ±0.5 VAC P2 Cal U2/P2 key = P2 C/C2 Low C2 to E1 (P2A-5 & 7) C/C2 (P3B-11 & 12) 5 mA (RMS) ±0.2 mA C/C2low Note 1 C/C2 Medium C2 to E1 (P2A-5 & 7) C/C2 (P3B-11 & 12) 80 mA (RMS) ±0.5 mA C/C2med Note 1 C/C2 High C2 to E1 (P2A-5 & 7) C/C2 (P3B-11 & 12) 140 mA (RMS) ±0.7 mA C/C2high Note 1 Note 1: Prior to calibration, disconnect panel from regulator, and remove on-board jumper J1 (see Figure J.1) and Terminal Strip jumper at P3B-11 & 12. After calibration, replace J1 and Terminal Strip Jumper at P3B-11 & 12. 8.5 MJ-4A & MJ-4B Self Testing After reset, the MJ-4 runs through an internal diagnostics routine. The start-up diagnostics routine includes a front panel indicator test—the LED indicators simultaneously flash three times so that an operator can verify them. During the LED test, the MJ-4 displays “Testing...” on the front panel screen. The start-up diagnostics routine consists of several checks and internal tests, including a ROM (program memory) checksum calculation. The MJ-4 displays the results of the checksum test (PASS or FAIL) in the “Checksum=” item under the <DIAGNOSTICS> Menu. A checksum failure indicates a problem with the unit. A checksum or other self-test failure will activate the “Self Test Fault” message. If this message occurs, contact your Siemens Power Transmission & Distribution representative for instructions. 8.6 Communications Module Troubleshooting In the <DIAGNOSTICS> Menu, the MJ-4 Control Panel provides data items for testing the Communications Module and verifying its operation. Please refer to the MJ-4 Communications Module Installation Manual for verifying the Communications Module operations using the <DIAGNOSTICS> Menu data items. 8.7 Tap Tracking When viewing this alert, press the left arrow key repeatedly. On the right side of the screen two character error codes will appear. There could be between one and four of these codes. Note that the codes could have been gen- Siemens Energy, Inc. erated all at once or at any time since the alert was last cleared. The codes are: UX: occurs if algorithm can't tell direction tap change occurred or if operation count increases without calling for a raise or lower RS: occurs when neutral signal is on and tap pos is not neutral; panel resets tap position to neutral if Tap Resync is turned on TT: occurs if Tap Resync is on and bad neutral signal and tap position combo persists for more than 10 seconds OD: occurs if "tap_chg_ctr" goes down to zero before a tap change occurs. tap_chg_ctr = R/LOnTime + TapChgT/O Tap Changer control may be customized using the following settings from the <DIAGNOSTICS> menu. R/LOnTime: maximum time to keep the tap changer motor running before pausing for R/LOffTime. R/LOffTime: pause between tap changes for this amount of time. Fixed R/L On time:When in Auto mode, if this setting is “Y”, motor stays on for exactly R/L On time seconds. TapChgT/O: if the control runs the tap changer motor for R/LOnTime and no operations count occurs, then after this many more seconds a Tap Track Err OD alert is generated. TapIn: defines the operations count signal input line.TapInType: defines the operations counter type. TapInPulse: defines the minimum amount of time that an operations count signal must be present in order for the operations counter to increment (applies to Pulse type operations counters only). NeutralIn: defines the neutral signal input line. NeutralCount: number of Neutral positions (for LTC’s only). 57 Appendix A: Specifications A Specifications Operational Requirements Accuracy Temperature Metering accuracy*: ±0.5% over the -40°C to +85°C operating range. Operating: -40°C to +85°C Storage: -40°C to +85°C Humidity Operating: Relative humidity of 5% to 95% non-condensing Storage: Relative humidity of 5% to 95% non-condensing (U2 and P2 range) 80 to 145 volts RMS Frequency 45 to 65 Hz * Basic accuracy of the MJ-4A & MJ-4B (excludes Potential Transformer or Current Transformer errors). Electrical transient immunity The MJ-4A & MJ-4B Current Transformer (CT) withstands a sudden open circuit without damage to the control circuit. However, an open CT circuit can result in dangerously high voltage, and should be avoided. The MJ-4A & MJ-4B Control Panel is impervious to electrical transients as defined by the following: Surge: ANSI/IEEE C37.90.1-2002 All PDS and terminal strip connections High Energy Surge: ANSI/IEEE C62.41-1980 U2 and P2 inputs only Not susceptible to upset due to high radio frequency interference (RFI) defined by the following: RFI Susceptibility: ANSI/IEEE C37.90.2-1987. 58 Siemens Energy, Inc. Appendix B: Physical Installation on Siemens Regulators B Physical Installation on Siemens Regulators Physical installation consists of placing the MJ-4 Control Panel in its weatherproof housing and connecting the Polarized Disconnect Switch to the regulator. Customersupplied external connections to the terminal strip on the back of the unit are made as required. Begin by disconnecting and removing the panel you are replacing. Switch Settings for MJ-4A (See Chapter 2) As you prepare to install the MJ-4A Control Panel, the following switch settings should be observed: Normal/External power switch Auto/Manual switch Tap Raise and Lower switch OFF OFF OFF Switch Settingsfor MJ-4B (See Chapter 2) As you prepare to install the MJ-4B Control Panel, the following switch settings should be observed: Normal/External power switch Auto/Manual switch Tap Raise and Lower switches A wing-nut-secured, ten-position, male Polarized Disconnect Switch (PDS) provides the interface to the regulator sensing and control circuits. The PDS is compatible with previous generation AccuStat™ controllers. The PDS connections are: P2 C2 E E1 U2 J K U10 U11 High side of neutral position indicator switch. When closed to ground, indicates tap changer in neutral. (Turns on Neutralite). AC side of Potential Transformer, if present. High side of Current Transformer. Collective neutral return for the control panel, the Utility winding and PT winding. Low side of Current Transformer. AC high side of regulator Tertiary (Utility) winding. Provides: -Control Panel power source. -Voltage reference. -Voltage Phase reference for flow direction, -Power factor Output from the panel to Raise regulator tap position. Output from the panel to Lower regulator tap position High side of Op Counter switch. (closes to ground E) High side of regulator drag hands reset solenoid (returns to E) Replacing Older Control Units with the MJ-4A & MJ-4B Control Panel If the original control has modifications such as Auxiliary Transformer, Auxiliary CT, Reverse Power Flow Detector, Voltage Limit Control, or other accessories mounted in the Siemens Energy, Inc. will be Note 1: Some older controllers do not provide the necessary signals to support all MJ-4 functions. (i.e., tap position indication, operations counter, Neutralite, drag hands reset.) Note 2: The control being replaced may incorporate a jumper between the P2 and U2 terminals on the female (stationary) portion of the PDS. If and only if this jumper is present: 1. Remove the jumper. 2. Remove the P2 lead from the P2 screw terminal. Reconnect the P2 lead to the U2 screw terminal, leaving the P2 terminal vacant. OFF AUTO DISABLED OFF Polarized Disconnect Switch U12 enclosure, special engineering instructions required before the existing control is replaced. CAUTION Connecting of P2 and U2 lines from the regulator will cause a direct short circuit of the two voltage sources. Will result in severe internal damage. To Prevent: Do not connect the P2 and U2 leads to the same terminal. Note 3: To replace panel types UA-23, UA-24, UA-25 (also type UJ-1 used on S/N’s 9-0110-00159, 00163, and 00201) a special adapter mounting kit is required. To make use of this adapter kit (Cat. No. 1670) the MJ-4 Control Panel must be installed complete with its enclosure. Note 4: To replace panel types UJ-4 and UJ-5 with the MJ4, replace the ten-pin male portion of the PDS Supplied with the MJ-4 Control Panel with the seven-pin male PDS from the older control. Tape up the three unused leads U10 (operation counter), U11 (drag hand reset) and U12 (NeutraliteTM). Install a jumper wire from C1 to E on the female portion of the PDS. For this installation, the MJ-4 will not track the tap position and will not update the operations counters. Note 5: To replace controls other than those named, refer to the factory for special engineering instructions. Note 6: Regardless of the panel type being replaced, the MJ-4 Control Panel must be configured to operate with the particular regulator on which it is being installed. (See Chapter 4). 59 Appendix B: Physical Installation on Siemens Regulators Replacing existing MJ-4 Control Panels Field Maintenance: To replace an already-installed MJ-4 Control Panel, the procedure is similar to that described above. The MJ-4 is a state-of-the-art controller utilizing complex circuits and sophisticated components for the detection, processing and display of regulator parameters and the precise control and operation of the tap changer. Field maintenance is not recommended as special equipment and instrumentation are required for the proper calibration, testing and checking of the controller operation. It is strongly recommended that MJ-4 controller repair, testing, and calibration be performed only by Siemens authorized repair facilities. Polarized Disconnect Switch Plug the PDS from the new MJ-4 into the female PDS in the control enclosure. Terminal Strip Connector External devices are wired to a terminal strip connector at the back of the MJ-4 Control Panel. See Appendix K for pin-outs and signal descriptions. WARNING WARNING Hazardous voltage will be present on various control leads when regulator is energized. Could result in death or serious injury including equipment damage from contact with live line conductors. To prevent: Remove fuses before by-passing the regulator and leave the fuses out while the regulator is bypassed. 60 Use of unauthorized parts and/or unqualified personnel in the repair of this equipment could result in death or serious injury including electrical damage to equipment. To Prevent: Only authorized personnel should work on this equipment including installation, operation and maintenance. Siemens Energy, Inc. Appendix C: Regulator Control Diagrams C Regulator Control Diagrams Typical Control Diagrams - For Sample Reference Only Figure C.1 ANSI Type ‘A’ (Straight) Regulator Control Diagram Siemens Energy, Inc. 61 Appendix C: Regulator Control Diagrams Figure C.2 62 ANSI Type ‘B’ (Inverted) Regulator Control Diagram Siemens Energy, Inc. Appendix D: Menu Parameters D Menu Parameters D.1 <CONFIGURE> Menu: Leading and Lagging Regulators The following steps will help you determine which of the two regulators in a Delta configuration is “leading” and which is “lagging” on an open Delta installation: 1. 2. 3. 4. D = 2. • Ensure that there is load current on the line. Load current must be of sufficient magnitude to cause a definite response of the line drop compensation circuit. Normally, 25% of the regulator setting will be adequate. 5. Set the Remote/Auto/Manual switch to AUTO on both controllers. 6. Allow both regulators to run and come to rest in band. The regulator whose tap position is closest to maximum is the “lagging” regulator. The other regulator is the “leading” regulator. Single phase k = 2.0x • Current Transformer Rating Voltage Transformer Ratio Wye Connected k = 1.0x Adjust both front panel controls to the same settings: X=0.692 ohms/mile Determine compensation multiplier, k, as • Use the Configuration Keys to temporarily set both controllers to System type = WYE. This will be corrected in step 7. 2.0 V 120 V 0 Seconds 0V (+) 12 24 x 24 x 48 = 30 inches R=0.592 ohms/mile Disable automatic control of tap changer as follows: Set Raise/Lower tap switch to OFF. Set Remote/Auto/ Manual switch on both controllers to Manual. Bandwidth Voltage Level Time Delay Resistance Volts Reactance Volts 3 Current Transformer Rating Voltage Transformer Ratio Delta Connected k = 1.73x Current Transformer Rating Voltage Transformer Ratio EXAMPLE: The regulators involved are 3 - 333 kVA at 7.2 kV configured in a wye-connected three phase bank. (The CT primary for this regulator is 400 A.) k = 1.0 400 = 6.67 7200 / 120 Note: The amount of tapchange excursion can be made more or less, if desired, by appropriate adjustment of the reactance volts setting. Note: Multipliers for many common system voltages and regulator ratings are included in tables D.4 and D.5 below. 7. 3. Use the Configuration keys to set the System type to Delta Lead for the leading regulator and to Delta Lag for the lagging regulator, as determined in step 6. D.2 <REGULATOR> Menu: Line Drop Compensation There are several methods used to determine line drop compensation settings, The “Load Center” method is probably the most commonly used and most clearly illustrates the procedure. 1. Using knowledge of the distribution feeder and the tables below, establish the conductor resistance and reactance per mile of feeder. Determine the Line Drop Compensation Settings Resistive Compensation Setting = k x line length (mi) x resistance (ohms/mi) Reactive Compensation Setting = k x line length (mi) x reactance (ohms/mi) EXAMPLE: The line is 3 miles long. Resistance Setting = 6.67 x 3 x 0.592 = 12V Reactance Setting = 6.67 x 3 x 0.692 = 14V EXAMPLE: Conductor 4/0 ACSR, Regular Flat Spacing at 24 inches. Siemens Energy, Inc. 63 Appendix D: Menu Parameters Table D.1 Line Drop Compensation Table - Distribution Line Resistance and Reactance Ohms per Conductor per Mile at 60 Hz Copper - Hard Drawn Cond. Res. Size at 50oC MCM Aluminum - Steel Reinforced Reactance (See Note 1) Distance “D” Between Centers of Conductors 18” 24” 1000 .0685 .449 .484 30” .511 36” .533 42” .552 48” .568 54” .593 60” .595 Cond. Res. Size at 50oC MCM Reactance (See Note 1) Distance “D” Between Centers of Conductors 18” 1272.0 .0851 .421 24” 30” 36” 42” .456 .483 .505 .524 48” .540 54” .555 60” .567 750 .0888 .466 .501 .529 .550 .569 .585 .600 .612 954.0 .1128 .439 .474 .501 .523 .542 .553 .573 .585 600 .1095 .481 .516 .543 .565 .584 .600 .615 .627 795.0 .1373 .450 .485 .512 .534 .553 .569 .584 .596 500 .1303 .492 .527 .554 .576 .595 .611 .626 .638 556.5 .1859 .469 .504 .531 .553 .572 .588 .603 .615 400 .1619 .507 .542 .569 .591 .610 .626 .641 .653 477.0 .216 .479 .514 .541 .563 .582 .598 .613 .625 .636 350 .1845 .515 .550 .577 .599 .618 .634 .649 .661 397.5 .259 .490 .525 .555 .574 .593 .609 .624 300 .215 .525 .560 .587 .609 .628 .644 .659 .671 336.4 .306 .500 .535 .562 .584 .603 .619 .634 .646 250 .257 .536 .571 .598 .620 .639 .655 .670 .682 266.8 .385 .514 .549 .576 .598 .617 .633 .648 .660 .776 AWG AWG 4/0 .303 .546 .581 .603 .630 .649 .665 .630 .692 4/0 .592 .630 .665 .692 .714 .733 .749 .767 3/0 .382 .554 .589 .616 .638 .657 .673 .688 .700 3/0 .723 .670 .705 .732 .754 .773 .789 .804 .816 2/0 .481 .581 .616 .643 .665 .684 .700 .715 .727 2/0 .895 .690 .725 .752 .774 .793 .809 .824 .836 1/0 .607 .595 .630 .657 .679 .698 .714 .729 .741 1/0 1.12 .705 .740 .767 .789 .808 .824 .839 .851 1 .757 .609 .644 .671 .693 .712 .728 .743 .755 2 1.69 .714 .749 .776 .798 .817 .833 .848 .860 2 .964 .623 .658 .685 .707 .726 .742 .757 .769 4 2.57 .708 .743 .770 .792 .811 .827 .842 .854 6 3.98 .722 .757 .784 .806 .825 .841 .856 .868 4 1.518 .648 .683 .710 .732 .751 .767 .782 .794 6 2.41 .677 .712 .739 .761 .780 .796 .811 .823 8 3.80 .714 .749 .776 .798 .817 .833 .848 .860 Note: 1. 60 Hertz reactance in ohms per mile of each conductor of a single phase, or of a three phase, symmetrical triangular spacing. For other arrangements of conductors see below. The reactance for other frequencies is F/60 times the table values. Reactance values for copper wire are for concentric standard copper conductors. Reactance values for aluminum cable conductors are approximately correct. B A A B D = C The Siemens Line Drop Calculator software application simplifies the calculation of these parameters. Simply enter the system values and the application automatically calculates the resistive and reactive components for you. Enter these values in the <REGULATOR> menu, and the MJ-4 automatically compensates for the line drop when adjusting the output voltage of the regulator. 64 3 ABC C Contact your Siemens representative about obtaining this application. You may also download this application from the Siemens web site (see Section 1.8). After arriving at the website, select Products, and then the Voltage Regulator item. This application is available on the Download page. Siemens Energy, Inc. Appendix D: Menu Parameters Table D.2 Line Drop Compensation Table - Compensation Multipliers Regulator Operating Data Operating KV (Volt. Trans. Ratio Circuit Connection Regulator Operating Data Single Delta Single Delta 19.9 50 .60 .52 .30 5.0 100 5.00 4.33 2.50 (166/1) 100 1.20 1.04 .60 (40/1) 150 7.50 6.49 3.75 14.4 (120/1) Wye Operating KV (Volt. Trans. Ratio) Wye 167 2.40 2.08 1.20 200 10.00 8.66 5.00 200 2.40 2.08 1.20 250 17.50 15.15 8.75 334 17.50 15.15 8.75 50 .83 .72 .42 500 35.00 30.30 17.50 100 1.67 1.44 .83 625 35.00 30.30 17.50 200 3.34 2.88 1.67 668 35.00 30.30 17.50 300 5.01 4.32 2.49 835 35.00 30.30 17.50 400 6.68 5.78 2.52 4.16 100 5.76 4.98 13.8 50 .87 .75 .44 (34.7/1) 150 8.64 7.48 (115/1) 100 1.74 1.50 .87 200 11.53 9.97 5.76 150 2.61 2.25 1.31 250 20.20 17.48 10.10 200 3.48 3.00 1.74 4.32 334 20.20 17.48 10.10 500 40.40 34.96 20.20 7.62 50 1.57 1.36 .79 625 40.40 34.96 20.20 63.5/1) 75 2.36 2.04 1.18 668 40.40 34.96 20.20 100 3.15 2.72 1.57 835 40.40 34.96 20.20 150 4.72 4.08 2.36 219 7.87 6.82 3.94 2.5 200 20.00 17.30 10.0 328 12.60 10.90 6.30 (20/1) 300 30.00 25.96 15.00 438 12.60 10.90 6.30 400 40.00 34.60 20.00 548 12.60 10.90 6.30 500 70.00 60.55 35.00 668 70.00 60.55 35.00 7.2 50 1.67 1.44 .83 1000 140.00 121.10 70.0 (60/1) 75 2.50 2.16 1.25 1250 140.00 121.10 70.0 100 3.34 2.89 1.67 1332 140.00 121.10 70.0 150 5.00 4.33 2.50 1665 140.00 121.10 70.0 219 8.34 7.22 4.17 328 13.33 11.55 6.67 438 13.33 11.55 6.67 548 13.33 11.55 6.67 D.3.1 D.3 Current Rating Circuit Connection Current Rating <CONFIGURE> Menu: Transformer Polarity The relative polarity between the Utility (Tertiary or TV) winding and the Current Transformer (CT) must be specified in the <CONFIGURE> Menu Utility Pol: parameter. This section describes the method for determining the correct specification (NORM or REV) from examination of the Regulator nameplate. Single-Phase Regulators D.3.1.1 Single-Phase Inverted Design Regulators (ANSI type B) The Utility transformer polarity is always normal for SinglePhase Inverted Design Regulators. Specify Utility Pol:NORM. D.3.1.2 Single-Phase Straight Design Regulators (ANSI type A) without forced air cooling The Utility transformer polarity for Single-Phase Straight Design regulators can be determined from the regulator nameplate schematic diagram. The Utility winding taps are labeled Un -- Ux, E2. Siemens Energy, Inc. 65 Appendix D: Menu Parameters D.3.1.3 Single-Phase Straight design regulators (ANSI type A) with forced air cooling If the Un - - Ux taps are to the left of E2 with no taps to the right of E2, and the polarity mark is on one of the U taps, specify Utility Pol: NORM. (See Figure D.1.) Figure D.1 Left of E2 For these regulators, the Utility winding not only provides power to the controller — it also provides power for the forced air fan(s). The E2 tap is located between the Un - Ux terminals on the regulator’s nameplate schematic. The U5 tap is normally used for fan voltage and can be either to the left or to the right of E2. To determine whether the polarity is ‘normal’ or ‘reverse’, you must examine both the schematic diagram and the connection table on the nameplate. From the connection table, determine the tap to which U2 should be connected. Single-Phase Straight Design - Taps to the If the Un - - Ux taps are to the right of the E2, and the polarity mark is on the E2 tap, specify Utility Pol: REV. (See Figure D.2.) • If the tap to which U2 is connected and the polarity mark are to the left of E2 on the schematic, set UtilityPol:NORM. • If the tap to which U2 is connected is to the right of E2 on the schematic, set UtilityPol:REV. Examples For both of the examples on the next page, use the nameplate connection table shown in Table D.3: Figure D.2 Right of E2 Single-Phase Straight Design - Taps to the Table D.3 Nameplate for Single-Phase Straight Regulator with Cooling Fan Single Phase Straight Regulator with Cooling Fan Load Volts +/-10% Volt Tran Sec Conn P2 to Control Panel P to P14 to Basis Volts Aux Volts Motor Conn U2 to Volts Fan Connection U21 to U15 to Volts 14400 P3 - 120 20 20 120 U3 126 U3 U7 240 13200 P4 - 120 20 20 120 U4 126 U53 U7 242 7200 P5 - 120 20 20 120 U6 126 U6 U8 240 From the table, the system load voltage is 7200 volts; therefore, U2 would be connected to U6. Now check the connection diagram: 66 Siemens Energy, Inc. Appendix D: Menu Parameters EXAMPLE 1 (ref: Table D.3) D.3.2 Three-Phase Regulators In Figure D.3 below, U6 is to the left of E2. If your regulator nameplate looks like this, the proper specification is Utility Pol:NORM. Three-phase regulators may have either one or multiple utility windings. D.3.2.1 Single Utility Winding A single utility winding provides power for the control, the motor and the cooling fan. This utility winding may have the polarity mark at the Un — Ux terminals or at the U5 terminal, as shown in the examples of Figure D.5. Figure D.3 U6 to the Left of E2 EXAMPLE 2 (ref: Table D.3) In Figure D.4 below, U6 is to the right of E2. If your regulator nameplate looks like this, the proper specification is Utility Pol:REV. Figure D.5 Winding Three-Phase Regulator with a Single Utility To determine whether the polarity is ‘Normal’ or ‘Reverse,’ examine the connection table and schematic diagram. Figure D.4 U6 to the Right of E2 Siemens Energy, Inc. • If U2 is connected to a “U” terminal which is to the left of E2, then UtilityPol:NORM (see Figure D.6). • If U2 is connected to a “U” terminal which is to the right of E2, then UtilityPol:REV (see Figure D.7). 67 Appendix D: Menu Parameters D.3.2.2 Multiple Utility Windings Regulators with more than one utility winding utilize the “A” phase utility winding for control and motor power, and the “B” and “C” phase windings for fan(s) power. For this case, use the Single phase procedure, defined above for the “A” phase winding. Figure D.6 U2 Connects to a “U” Terminal (U7 or U8) Which is to the Left of E2 Figure D.7 U2 Connects to a “U” Terminal (U7 or U8) Which is to the Right of E2 68 Siemens Energy, Inc. Appendix E: Hazards of Bypassing a Regulator off Neutral E Hazards of Bypassing a Regulator off Neutral Deactivating the Control Panel Before Bypassing DANGER Operating regulator while bypassing will result in explosion. Will cause death, serious injury or property damage. Consult your voltage regulator instruction manual for bypassing instructions. To eliminate the possibility of inadvertent (and possibly catastrophic) tap operations during bypassing operations, it is mandatory that you completely disable the control panel. DANGER Place regulator in neutral position before bypassing and disable control panel. Operating regulator while bypassing will result in explosion. Proper regulator bypassing procedure is of critical importance. Regulators that are not in the neutral position when bypassed frequently fail. This failure is the result of extremely high circulating current inside the regulator caused by what is effectively a short circuit being placed across the series winding. The result of such a failure can be catastrophic. Methods of Determining Neutral Tap Position Since the tap changing mechanism is submerged in a tank full of oil, some external means of determining tap position is mandatory. Methods most commonly used include: • • The regulator tap Position Indicator provides first line indication of the neutral position. On modern regulators, the tap changing mechanism drives the regulator Position Indicator through gears or flexible shafts to provide an accurate, reliable indication of the regulator tap position. The MJ-4A & MJ-4B Control Panel is equipped with a neutral indicating light (Neutralite). A switch mounted on the tap changing mechanism actuates the light circuit. The circuit is activated when the regulator is in the neutral position. A test switch on the MJ-4A & MJ-4B Control Panel can be used to verify proper operation of the Neutralite. The Position Indicator and the Neutralite should all indicate neutral before you attempt to bypass the regulator. Methods other than the ones described above are also used; however, the ones described above are the most common and are recommended. Will cause death, serious injury or property damage. Place regulator in neutral position before bypassing and disable control panel. Disable the MJ-4A control panel as follows: 1. Disconnect the Polarized Disconnect Switch (PDS). or 2. Remove all MJ-4A fuses (Power, Sensing, and External Power); place MJ-4A power switch in Off position; place Remote/Off/Manual switch in Off position; and place the Tap Raise/Lower switch in Off position. Disable the MJ-4B control panel as follows: 1. Disconnect the Polarized Disconnect Switch (PDS) or 2. Push Auto/Manual switch until Auto Disabled LED is ON, and leave the Raise and Lower keys in Off position. Remove all MJ-4B fuses (Power, Sensing, and External Power); place MJ-4B power switch in Off position. The regulator must be placed in neutral before bypassing. If there is any doubt as to the location of neutral, the line should be dropped before bypassing the regulator. Siemens Energy, Inc. 69 Appendix F: Communications Module Installation F Communications Module Installation The MJ-4 Communications Module is mounted directly to the Main Processor board. There are two versions of the Communications Module: • Fiber Optic Communications Module, shown in Figure F.1. • RS-232/485 Communications Module, shown in Figure F.2. Refer to the MJ-4Communications Module Installation Manual (Siemens Manual # 21-115-527-024 for complete information on installing and testing the Communications Module. Figure F.2 Figure F.1 70 RS-232/485 Communications Module Fiber Optic Communications Module Siemens Energy, Inc. Appendix F: Communications Module Installation This page left intentionally blank. Siemens Energy, Inc. 71 Appendix G: Menu Structure Quick Reference G Menu Structure Quick Reference Table G.1 <METER> Max /Min Vld Max /Min Vs Max /Min Vcomp Max /Min Ild Max /Min PF Max /Min KVA Max /Min KW Max /Min KVAR Max /Min Freq KWHR F KVAR HR F lead KVAR HR F lag KWHR R KVAR HR R lead KVAR HR R lag Navigating the Menu and Fast-Path Keys <FW DEMAND> Max /Min F Dmd Vld Max /Min F Dmd Vs FDmdVcomp Max /Min Max /Min F Dmd Ild PFKVA max PFKVA min F Dmd KW F Dmd Max /Min KVAR Max /Min F Dmd KVA Max /Min <REV DEMAND> R Dmd Vld Max/Min R Dmd Vs Max/Min Max/Min RDmd Max/Min Vcomp R Dmd Ild PFKVA max PFKVA min R Dmd KW R Dmd Max/Min KVAR Max/Min R Dmd Max/Min KVA <COUNTERS> Op Count Total Ops Reset Date Reset time Elapsed Ops 24 Hr Ops 30 Day Ops MTD Ops Last Month Ops YTD Ops Last Year Ops Tap position Max/Min <REGULATOR> Fwd Volts Volt Level Bandwidth Fwd BW Fwd Delay Time Delay Fwd Comp (R) Fwd Comp (X) Reactance Rev Volts Rev BW Rev Delay Rev Comp(R) Rev Comp(X) Alt Delay VRC Stat VRC Select VRC1 In VRC2 In VRC Mode Local VRC% VRC Stage 1 VRC Stage 2 VRC Stage 3 VRC Remote MJ-3A VRC% AutoVRCset1 AutoVRCset2 AutoVRC1 %I AutoVRC2 %I VLC Enable VLC Upper VLC Lower 72 Resistance VLC Select <CONFIGURE> Tap Chngr Type Syst DeltaPwr Utility Pol VprimaryMax U2 PT P2 PT CT ratio I Full Load Pwr Flow (mode) Basis Volts NeutOvRun Reset Min/Max? Version Memo 1 Memo 2 <ADV CONFIGURE> Meter Volts I Threshold % I Shift I Load Max PT Threshold Time Date Format (Date) Daylight Sav Dmd Type Dmd Time Dmd Subperiods Min/Max t.o. Screen t.o. Quick t.o. QuickDispTim Auto Variamp Soft Variamp R Limit L Limit Slave-Master TapAlert Alrt Tap Resync CommAutoInh DspScr LowerLED P2 Calc U2/P2out I Dir Bias Bias % Remote Btn <ALERTS> 1st Alert Alert Select ... Last Alert Alerts: Low current Auto inhibit Tap track error Neutral sig. err. Tap position??? Low PT Thresh Overcurrent NV RAM Reset Low Battery High Voltage Not in Auto R Limit Reached L Limit Reached Pseudo Manual Siemens Energy, Inc. Appendix G: Menu Structure Quick Reference <LOG SETUP> Log Event Event = Tap Event = Neut Event = NN R Event = NN L Event = VLC Event = VRC Ev = PwrFlow Ev = Pwr Cyc Event = Cfg Event = Alert Clr EventLog? Clr Interv Log? Log Interval ResLogMinMax Log min/max Interval <EVENT LOG> Event:NNNNN ** Date Time Cause Vld Vsrc Ild PF KW KVAR KVA Tap Event:NNNNN-1: Date Time Cause Vld Vsrc Ild PF KW KVAR KVA Tap etc. Siemens Energy, Inc. <INTERVAL LOG> INTERV: NNNNN** Date Time Vld * Vs Ild * PF PF KVAmax PF KVAmin KW * KVAR * KVA * Tap Tapmax Tapmin Total Ops INTERV: NNNNN-1 Date Time Vld * Vs Ild * PF PF KVAmax PF KVAmin KW* KVAR* KVA* Tap Tapmax Tapmin Total Ops <HARMONICS> Vld THD Vs THD Ild THD Show Harm: Show As: Vld 1st ... Vld 31st Vs 1st ... Vs 31st Ild 1st ... st Ild 31 <COMMUNICATIONS> Data Stat DatPortBaud Data Parity DataPortAddr Reg Id Protocol Comm Baud Comm Parity Comm Addr Resync Time Tx En Delay DNP dl Confirm CM SW RepeatEn Host Addr CM Unsolicited AutoInhEnRemRL DNPset CM Vers <MAINTENANCE> ConsOv MaintainRcrds? TapChTy BAL WIND RangeofREG CON_AB CON_0 CON_1 CON_2 CON_3 CON_4 CON_5 CON_6 CON_7 CON_8 OPCNTA OPCNTB OPCNT0 OPCNT1 OPCNT2 OPCNT3 OPCNT4 OPCNT5 OPCNT6 OPCNT7 OPCNT8 OP_Dur <DIAGNOSTICS> U2 Cal P2 Cal C/C2low C/C2med C/C2high MP BD VERS PWR BD VERS MP MASK VERS Ser No. Product Rev. Checksum CM Test? CM TestStat Panel Type R/L OnTime R/L OffTime FixedR/LOntime TapChgT/O Tap In TapInType TapInPulse PreTapTime PostTapTime Neutral In Neutral Count <PASSWORDS> Enter PW End Session? System Key Level 1 Level 1 PW Configure Config PW Regulator Reg.PW Meter Meter PW Demand Demand PW Alert Alert PW Counters Counters PW Log Setup Log Setup PW Ev/Intv Ev/Intv PW Harmonics Harmonics PW Comm Comm PW Mntn Mntn PW Diagnostics Diagnostics PW 73 Appendix H: MJ-4A & MJ-4B Firmware Versions H MJ-4A & MJ-4B Firmware Versions This version of the MJ-4A & MJ-4B Installation and Operation Manual describes the MJ-4A & MJ-4B firmware Version 4.111. Version 4.111: Production release of MJ-4A & MJ-4B, Added Option for TLS and TLH in maintenance calculation. Version 4.11: Production Release of MJ-4A & MJ-4B. Version 4.10: Initial release fo MJ-4A & MJ-4B. 74 Siemens Energy, Inc. +P BAL Siemens Energy, Inc. U112 HS U12 3 J21 3 P2 4 J22 4 6 C2 5 E 6 U_REM U_REM 5 E1 7 K22 7 U2 8 K21 8 J 9 U7 9 K 10 U6 10 U10 11 U6 11 U11 12 U 12 Figure I.1 Terminal Strip Connections for Siemens Regulator 2 1 P2A 2 1 IN+ 3 IN 4 INHIB OUT OUT+ U12 P2 C2 E E1 U2 J K U10 U11 PDS 2 4 NO 3 C 6 5 6 VRC1+ VRC1 5 AUXIN+ AUXIN INHIB AUXOUT AUXOUT NC 2 AUXOUT INHIB 1 INHIB J30 1 8 STAT 7 MAN_ COM 8 R/M_ VRC2+ VRC2 7 STAT 9 REM_ J412 9 11 C P2SW 12 P3A C2 12 P3B 11 ICIRC+ ICIRC 10 C8_66A 10 I P2B Figure I.1 below shows the external connections for the MJ-XL terminal strip when connected to a Siemens Regulator. Appendix I: Terminal Strip Wiring Terminal Strip Wiring 75 Appendix J: MJ-4A & MJ-4B Jumpers and Battery Replacement J MJ-4A & MJ-4B Jumpers and Battery Replacement J.1 MJ-4A & MJ-4B Jumpers The locations of the MJ-4 jumpers and battery are shown in the drawing below. The table on the next page describes the jumpers and the default settings. 2 1 JP9 SIEMENS MJ 1 2 J2 Jumpered for DCE (Default) No Jumpers (Default) 1 2 3 Jumpered for DTE 1 2 3 1 2 3 J23 J22 1 2 3 J23 J22 1 2 3 1 2 3 J23 J22 Battery (BT1) Pins 1 & 2 No Jumper (Default) J1 1 2 Pins 1 & 2 Jumpered (Default) 2 1 J1 1 J9 2 2 Figure J.1 76 1 J9 MJ-4A & MJ-4B Jumpers. Siemens Energy, Inc. Appendix J: MJ-4A & MJ-4B Jumpers and Battery Replacement Table J.1 MJ-4A & MJ-4B Jumper Descriptions and Default Connections Jumper Default Shunt Location Description J1 Out This jumper shorts signals C&C2 (P3B-11&12). J1 is a redundant jumper, since MJ-4 ships from the factory with a terminal strip jumper across P3B-11&12. With either jumper installed, the terminal strip, the CT current path for the regulator is complete. Removing both the terminal strip jumper and the J1 jumper allow for an external "auxiliary apparatus" (e.g., an external current meter) to be connected in the CT current path. Caution: Open circuiting the C&C2 connections may damage the regulator Current Transformer (CT). Keep C&C2 shorted unless connected to an appropriate external current-handling device. J9 In J9 determines the signal path for the "External Source" power. With J9 installed, the External Source signal comes from the Yellow banana plug on the front panel. With J9 removed, the External Source signal comes from "J412" (P3B-9). Caution: Do not connect AC sources to both "J412" and the External Source (yellow) banana plug while J9 is installed. Be sure that J9 jumper is un-installed before making an AC Source connection to J412. J22 1-2 Selects DCE/DTE for MJ-4 data port. (See also J23.) 1-2: DCE (default) 2-3: DTE J23 1-2 Selects DCE/DTE for MJ-4 data port. (See also J22.) 1-2: DCE (default) 2-3: DTE The following jumpers are not installed: J2 (factory use only) JP9 (microprocessor reset for factory use). 2. Remove the MJ-4 from the weather-proof enclosure (i.e., lift it off of the hinges.) 3. Remove the side screws from the unit. (There are 4.) Battery Replacement 4. Curl back the cable clamp on the back of the unit and remove the cable bundle from the reusable cable clamp. 5. Note: Replace the MJ-4 battery within 1 month of an active "Low Battery" message to avoid data loss. Lift and move the rear cover away from the front panel. 6. Remove the coin-cell battery (BT1) from its socket. See Figure J.1 on the previous page for battery location. To replace the MJ-4 battery, you will: 7. Put the new coin-cell battery in the battery socket, making sure you have the proper orientation ("+" side up.) 8. Close the unit by reversing the steps outlined above. 9. Turn the power on and verify that the unit comes up and displays the <METER> menu heading. If the unit fails to come up, retrace the above steps to make sure that the battery has been properly oriented and inserted. Note: J.2 This section provides instructions for replacing the MJ-4 battery. 1. 2. 3. Remove the MJ-4 rear cover, Remove and replace the coin-cell battery. Close up the unit and reconnecting power. Replacement Battery Radio Shack carries replacement batteries for the MJ-4. The battery is a 3 volt coin-cell type Lithium cell, Panasonic BR2032 or equivalent. Replacement Procedure During the following procedure, use proper Electro-Static Discharge (ESD) precautions. If possible, use an ESD wrist strap. If no wrist strap is available, touch a grounded surface before beginning. (Two accessible ground points are the screw jacks of the Data Port connector.) 1. Turn off power to the MJ-4 and disconnect the PDS jack (the 10-contact connector with the two wingnuts.) Siemens Energy, Inc. 10. After replacing the battery, verify the Low Battery Message is no longer active. What is Backed Up? There are two types of memory on the control: an EPROM where all of the settings/configuration are stored, which does not require power to retain information, and the battery backed static RAM where the time/date, min/max values, tap position, data logs, and DNP Configure points are stored. The MJ-4 Panel has a Super capacitor, which ensures data in non-volatile memory be retained when the battery has to be replaced. Data is lost only when both the capacitor is fully discharged and the battery is dead. 77 Appendix K: Terminal Strip Connections K Terminal Strip Connections Table K.1 below describes the connections for terminal strip P2A. Table K.1 Connections for Terminal Strip P2A Pin Number Signal Name 1 HS For Cooper Regulators Only. "Hold Switch" connection. Applies power to tap changer to complete tap change after "Hold Switch" contact makes. Description I/O / Power Power 2 U112 For Cooper Regulators Only. Neutral Position Indication. When closed to AC hot, indicates tap changer is in neutral position. Turns on Neutralite. Input 3 U12* High side of neutral position indicator. When closed to AC ground ("E"), indicates tap changer is in neutral position. Turns on Neutralite. Input 4 P2* Potential Transformer output (if present). 5 C2* High side of Current Transformer. [C2 terminal at P3B-12 is normally externally jumpered to C at P3B-11.] Power/Sense Input 6 E* Neutral return for Control Panel, PT, and Utility winding. Chassis ground. Ground 7 E1* Low side of Current Transformer. Ground 8 U2* High side of Utility (Tertiary) winding. Control Panel derives "Normal" power from this signal. Provides voltage phase reference for power flow direction. 9 J* Terminal J - Tap Changer Motor Raise signal. Output 10 K* Terminal K - Tap Changer Motor Lower signal. Output 11 U10* High side of Operation Counter switch. Closes to E. Indicates when a tap change has occurred. 12 U11* High side of Regulator Drag Hands Reset solenoid. Returns to E. Used to reset the drag hands of the Tap Position Dial mounted on the regulator. Power/Sense Input Output * indicates standard "Polarized Disconnect Switch (PDS)" signals. For Siemens regulators, these ten signals connect to the corresponding pins of the PDS connector block. 78 Siemens Energy, Inc. Appendix K: Terminal Strip Connections Table K.2 below describes the connections for terminal strip P2B. See Table 2.5 for complete descriptions of these terminal connections. See Figure 2.3 for simplified schematic drawing of remote control connections. Table K.2 Connections for Terminal Strip P2B Pin Number Signal Name 1 BAL This signal is actually E, (AC return.) The intended application of this signal is in conjunction with +P to permit the MJ-4 sense voltages to be adjusted by the value present on an external transformer winding. The transformer winding is inserted into the MJ-4 circuit at +P and BAL. Ground 2 +P This signal connects to one side (the "ground" side) of the MJ-4 sense transformers. See description for BAL. Input 3 J21 This signal connects to the J Relay output of the MJ-4. Normally, this signal is jumpered to J22 to complete the MJ-4 Raise motor circuit. Alternatively, a relay (or switch contacts) can be connected across the J21/J22 contacts to provide external control over the MJ-4 automatic Raise motor circuit. Output 4 J22 This signal is wired to J [P2A-9]. J22 is normally jumpered to J21. Alternately, J22 can be connected to an external motor control signal. Input 5 U_REM (R) This signal gets AC power from U6 when the Remote-Auto/Off/Manual switch is in the Remote/Auto position. This signal is provided so that external relay contacts can be connected from Rem R to J22 (the Raise motor control signal). MJ-4A ONLY Power 6 U_REM (L) This signal gets AC power from U6 when the Remote-Auto/Off/Manual switch is in the Remote/Auto position. This signal is provided so that external relay contacts can be connected from Rem L to K22 (the Lower motor control signal). MJ-4A ONLY Power 7 K22 This signal connects internally to the K signal (Lower motor control). This signal is normally jumpered to K21, but it can be connected to an external motor control signal. Input 8 K21 This signal connects to the K Relay output of the MJ-4. Normally, this signal is jumpered to K22 to complete the MJ-4 Lower motor circuit. Alternatively, a relay (or switch contacts) can be connected across the K21/K22 contacts to provide external control over the MJ-4 automatic Lower motor circuit. Output 9 U7 This circuit provides AC power to K7, which provides power to the J and K relays. The J and K relays implement the MJ-4's automatic tap control operations. This signal is normally jumpered to U6, but it can be connected to an external AC source. [Alternatively, an external relay contact can be placed between the U6 and U7 contacts for external control of the MJ-4 automatic tap operations.] Power 10 & 11 U6 This signal provides AC power for both Remote and Manual tap control operations. This circuit provides AC power to the common of the Tap Raise/Lower switch when the Remote-Auto/Off/Manual switch is in the Manual position. This circuit provides the AC power to the Rem R and Rem L terminal block contacts when the Remote-Auto/ Off/Manual switch is in the Remote position. It is normally jumpered to U at the terminal block, but it can be connected to an external AC source. [Alternatively, an external relay contact can be placed between the U and U6 contacts for external control of the MJ-4 manual and remote operations.] Power 12 U This is the signal from U2, after the power switch (assuming the switch is in the "Normal" position.) This signal is normally jumpered to U6 at the terminal block unless an external circuit is used to feed U6. Power Siemens Energy, Inc. Description I/O / Power 79 Appendix K: Terminal Strip Connections Table K.3 below describes the connections for terminal strip P3A Table K.3 Connections for Terminal Strip P3A Pin Number Signal Name Description I/O / Power 1 &2 INHIB OUT+ & INHIB OUT- Inhibit Out is activated (closed) whenever the MJ-4 automatic mode operation is inhibited by either the Automatic Inhibit Input or by Communication link. Relay Output 3 AUXOUT C 4 AUXOUT NO 5&6 AUXIN+ & AUXIN- 7 Common contact of Auxiliary Relay. Output Normally-open contact of Auxiliary Relay. Output Auxiliary input contact pair. For future definition. Contact Closure Input MAN_STAT When closed to R/M COM it indicates that the MJ-4A is in the Manual Operating Mode. The RA/O/M switch is in the Manual position. MJ-4A ONLY Switch Closure Output 8 R/M COM Common contact of the SPDT Remote-Automatic/Off/Manual (RA/O/M) switch. [Use with Man_stat and Rem_stat.] MJ-4A ONLY Switch Closure Output 9 REM_STAT When closed to R/M COM it indicates that the MJ-4A is in the Remote Operating Mode. The RA/O/M switch is in the Remote-Auto position. MJ-4A ONLY Switch Closure Output 10 & 11 ICIRC+ & ICIRC- 12 P2SW Reserved for Circulating Current Input signal pair. (0 - 640 mA, AC.) Current Input P2 signal after the Power Switch. Used for externally monitoring the P2 voltage signal. Output Table K.4 below describes the connections for terminal strip P3B Table K.4 Pin Number 80 Connections for Terminal Strip P3B Signal Name Description I/O / Power 1 J30 2 AUXOUT NC Normally-closed contact of Auxiliary Output Relay. (See P3A-3.) Spare connection for future application. 3&4 INHIB IN+ & INHIB IN- INHIB IN directly disables the MJ-4 motor control relays. Through the microprocessor, this signal asserts Automatic Inhibit of motor Raise/Lower operations, and activates the Auto Inhibit Indicator. Contact closure (Input) 5&6 VRC1+ & VRC1- These contacts are used to activate VRC (both MJ-3ATM mode and MJ-X mode). They are also used for External Line Drop Compensation Polarity Control. Contact closure (Input) 7&8 VRC2+ &VRC2- These contacts are used to activate VRC Enable 2 for MJ-X mode. They are also used for Alternate functions: Alternate Time Delay and Low External Battery. Contact closure (Input) 9 J412 10 C8_66A 11 & 12 C & C2 Relay Output Alternate signal source for “External Power” if jumper J9 is removed. See Table J.1. Reserved for future application. C & C2 (P3B-11&12) provide access to the regulator current path for connecting auxiliary apparatus (e.g., an external current meter.) The current ranges from 0 to 640 mA nominal, into a low impedance load. C&C2 have redundant jumpers. As shipped from the factory, there is a jumper across the terminal strip pins, and there is an on-board jumper "J1". [Both the terminal strip jumper and on-board jumper (J1) need to be removed if external equipped is connected.] Caution: Open circuiting the C&C2 connections may damage the regulator Current Transformer (CT). Keep C&C2 shorted unless connected to an appropriate external current-handling device. Current Siemens Energy, Inc. Appendix L: MJ-4A & MJ-4B Operating Procedures L MJ-4A & MJ-4B Operating Procedures View/Set Time Delay Value 1. Press Time Delay Fast-Path key 2. Read time delay on display View Instantaneous Load Voltage (Vld) 3. Press Change key - right hand digit will flash 1. Press Menu key twice 4. 2. Press Down Arrow once Press Left Arrow key to move left on display or Right Arrow key to move right on display 3. Read voltage (Vld) on display 5. Press Up/Down Arrow key to increase or decrease time delay on display - flashing digit will change View/Reset Max/Min Values 6. Press Save key to save the new time delay value 1. View Meter value or tap position View/Set Line Drop Compensation Values 2. Press Max/Min key once 1. Press Resistance Fast-Path key 3. Read maximum value on display 2. Read resistive compensation voltage (R) on display 4. To reset maximum value on display, press Cancel Reset key once 3. Press Change key - right hand digit will flash 5. Press Max/Min key again 4. Press Left Arrow key to move left on display or Right Arrow key to move right on display 6. Read minimum value on display 5. 7. To reset minimum value on display, press Cancel Reset key once Press Up/Down Arrow key to increase or decrease compensation voltage on display - flashing digit will change 6. Press Save key to save the new resistive compensation voltage value Use the following instructions as a quick reference for performing many of the standard MJ-4 operating procedures. View/Set Forward Voltage Level Value 1. Press Voltage Level Fast-Path key 7. Press Resistive Fast-Path key again 2. Read Voltage Level on display 8. Read Reverse resistive compensation voltage (R) on display 3. Press Change key - right hand digit will flash 9. 4. Press Left Arrow key to move left on display or Right Arrow key to move right on display Repeat steps 3 to 6 above to set the resistive compensation voltage 5. Press Up/Down Arrow key to increase or decrease desired voltage on display - flashing digit will change 6. Press Save key to save the new Voltage Level View/Set Bandwidth Value 1. Press Bandwidth Fast-Path key 2. Read Bandwidth on display 3. Press Change key - right hand digit will flash 4. Press Left Arrow key to move left on display or Right Arrow key to move right on display 5. Press Up/Down Arrow key to increase or decrease desired bandwidth on display - flashing digit will change 6. Press Save key to save the new Bandwidth setting Siemens Energy, Inc. 10. Press Reactance Fast-Path key 11. Read the Forward reactive compensation voltage (X) on display 12. Repeat steps 3 to 6 above to set the Forward reactive compensation voltage 13. Press Reactance Fast-Path key again 14. Read Reverse reactive compensation voltage (X) on display 15. Repeat steps 3 to 6 above to set the Reverse reactive compensation voltage View Operation Counter Values 1. Press Operation Counter Select Fast-Path key (Op Count) 2. Read Total Ops count on display 81 Appendix L: MJ-4A & MJ-4B Operating Procedures 3. Press Op Count key repeatedly to step through remaining counter values View Messages 1. Press Messages Fast-Path key 2. Read and note active message on display 3. Press Messages key repeatedly to step through remaining active messages 4. While viewing message, press Cancel Reset key to acknowledge message 5. Note: Acknowledging message does not clear the fault that caused the message Configure the Control Panel 10. Press Down Arrow key to display the DATE item 11. Press Change key - the left hand digit will flash 12. Press Up/Down Arrow key to increase or decrease the value 13. Press Right Arrow to step to the next digit to be changed 14. Press Save key to save the new date Using a Voltmeter to Calibrate U2 or P2 Note: Do not use voltage readings at the Voltage Calibration (Test) terminals as an indication of the regulated load voltage 1. Connect true-rms-reading voltmeter to Voltage Calibration (Test) terminals 2. Press U2 P2 key to display U2 (or P2) Cal item on the display. 3. If voltmeter reading is not the same as U2 (or P2) Cal item, press Change 4. At password prompt, press Up/Down Arrow key to enter first digit of password (See Manual Chapter 4) 1. Press Menu key twice 2. Press Right Arrow key five times to view the <CONFIGURE> menu 3. Press Up/Down Arrow key to display the desired item. 4. Press Change key 5. Press Left Arrow or Right Arrow to step through digits in numeric values 5. Press Right Arrow key to step through remaining digits and enter values 6. Press Up/Down Arrow to toggle through text choices or to increase or decrease numeric values 6. Press Save key to submit password 7. Press Save key to save the new value 7. If password is correct, press Change key - right hand digit will flash 8. Repeat steps 3 through 7 for all desired configuration items 8. Press Up/Down Arrow key to increase or decrease value until U2 (or P2) Cal value is equal to the voltmeter value 9. Press Save key to save the new calibration value View/Set the Clock (Time and Date) 1. Press Menu key twice 2. Press Right Arrow key six times to view the <ADV CONFIGURE> menu 3. Press Down Arrow until the TIME item is displayed. 4. Press Change key - the left hand digit will flash 5. Press Up/Down Arrow key to increase or decrease the value 1. Display Tap= in <COUNTERS> menu 2. Press Change key 6. Press Right Arrow to step to next digit 3. 7. When all of the digits are set, press Right Arrow key until A or P is flashing Press Up/Down Arrow key until reading matches regulator Position Indicator value 4. Press Save key to save new value. 8. Press Up/Down Arrow key to toggle between A and P 9. Press Save key to save the new time 82 10. See Manual Chapter 6 for additional calibration procedures Set Tap Position Siemens Energy, Inc. Symbols +/- Polarity Select Key 7 A Acknowledging Messages 44 ADV CONFIGURE Menu 19, 24–26 Alerts Enable/Disable 26 Alrt M=? C=? S=? 26 ALT Delay 29 Apparent Power 40 Auto / Manual Key 8 Auto Variamp 25 Auto/Manual Switch 10 Automatic Mode 46 B Band Indicator LEDs 9 Bandwidth Key 6 Bandwidth Setpoint 29 Basis Volts 23 Battery Replacement 76 Baud 14 Bi-directional Mode 23 Binding Posts 11 Bypassing a Regulator 69 C Calculated voltage 39 Calibrate U2 or P2 82 Cancel/Reset Key 6 Change Key 5 Changing Alpha or Numeric Settings 17 Changing Configuration Parameters 16 Changing Data 16 Changing Passwords 34 Co-Generation Mode 23 Communications Auto Inhibit 26 Communications Definition 18 COMMUNICATIONS Menu 18, 35, 45 Communications Module 36 Communications Module Installation Fiber Optic 70 Compensation Multipliers 65 Configuration 18 CONFIGURE Menu 18, 22–24, 63, 65 Configure the Control Panel 82 Connections 75 Connections, Terminal Strip 78 Control Modes Automatic 46 Manual 46 Off 46 Remote 46 Supervisory Control Disabled 47 Supervisory Control Enabled 46 Cooper Regulators 2 COUNTERS Menu 43 Current Calibration 56 Current Circuit Terminal Block 12 Current Shift 24 Current Threshold 24 Current Transformer Ratio 23 D Data Display 5 Data Port address 14 Data Port Addresses 36 Date 25 Date Format 25 Daylight Savings Time 25 DCE 14 Dead Reckoning 43 DEMAND Menus 41 Demand Methods 25 Sliding Window 25 Thermal 25 DIAGNOSTICS Menu 37 Diagrams 61 Display Screen 5 Displaying Data 15 Distribution Line Resistance and Reactance 64 Download page 64 Downloading files 2 Drag Hands Reset Switch 8 Dsp Scr (Default Display Screen) 26 DTE 14 E EVENT LOG Menu 41 Clearing the Event Log 42 Displaying Event Data 42 Event Logging 31 External Power Source Protection Fuse 11 External Source Binding Posts 11 F Fast-Path Keys 6, 15, 17 +/- 7 Siemens Energy, Inc. Bandwidth 6 Messages 7 Operations Counter 7, 8, 9, 39 Quick Key 8 Reactance 7 Resistance 7 Time Delay 7 Voltage Level 6 Voltage Limit Control 7 Voltage Reduction Control 7 Field Maintenance 60 Format Date 25 Forward Locked Mode 23 Forward Reactive Energy 41 Forward Real Energy 41 Forward/Reverse Operation 49 Frequency 40 Full Load Current 23 Function display timeout 23 Fuses 11 K G Main Processor Board Version 37 Max/Min Key 6 Maximum Load Current 24 Memo 24 Menu Key 5 Menu Selection Key 15 Menu Selection Keys 5 Menus 15 Messages Acknowledging 44 Messages LED 8 MESSAGES Menu 44 METER Menu 39 Data Items 40 Meter Volts 24 Microprocessor Mask Version 37 Min/Max Reset 24 Min/Max Time and Date Stamps 39 Min/Max Time-out 25 MJ-4 Front Panel 5 MJXplorer 54 MJXtra 54 GE Regulators 2 H Hardware Configuration Items 37 HARMONICS Menu 45 Hazards 69 I I Threshold % 24 Idle Reverse Mode 23 Indicators 8 Motor Active 9 Neutralite 10 Reverse Power Flow 8 SC Disabled 9 Voltage Limit Control (VLC) 10 Voltage Reduction Control Active 10 Installation 59 Fiber Optic Communications Module 70 INTERVAL LOG Menu Clearing the Interval Log 42 Displaying Interval Data 42 Interval Logging 32 J Jumpers 76 Siemens Energy, Inc. kVAR 40 kW 40 L L Limit 26 Leading and Lagging Regulators 63 Line Drop Calculator 64 Line Drop Compensation 29, 40, 63 Load Volts 40 Local Data Port 14 LOG SETUP Menu 18, 31 Logging Requirements 18 Low Current Threshold 24 Lower Key 7, 8 LTCs 2 M N Navigating the Menu 72 Neutral Overrun 24 Neutral Reverse Mode 23 Neutralite Indicator 10 Neutralite Test Switch 8 Normal/External Source Switch 10 O Operating Procedures 81 Operation Counter Select Key 7 P P2 Calculation 39 P2 Potential Transformer 22 Parity 14 PASSWORD Menu 18, 32–35 Password Security Activated 34 PDS 59 Polarized Disconnect Switch 59 Potential Transformer 22 Potential Transformer Threshold 24 Power Flow Direction 48 Power Flow Modes 23, 50–53 Bi-directional 23, 52 Co-generation 23, 53 Forward Locked 23, 51 Idle Reverse 23, 52 Neutral Reverse 23, 53 Reverse Locked 51 Reversed Locked 23 Tap Changer Direction 50 Power Fuse 11 Q Quick Display Time 25 Quick Key 8 Customizing your Quick List 37, 38 Viewing the Quick List 38 Quick Reference 72 Quick reference 81 Quick Time Out 2, 25 R R Limit 26 Raise and Lower Switches 10 Raise Key 7, 8 Reactance Key 7 Real Power 40 Reference, quick 81 Regulator Control Diagrams 61 REGULATOR Menu 18, 28, 45, 63 Regulator Setpoints 29 Bandwidth 29 Time Delay 29 Voltage Level 29 Regulator Type 22 Remote Mode MJ-3A 30 MJ-X 30 Replacement, Battery 76 Replacing existing MJ-4 Control Panels 60 Replacing Older Control Units 59 Resistance Key 7 Retrofitting 19 Reverse Locked Mode 23 Reverse Power Flow 48 Reverse Power Flow LED 8 Reverse Reactive Energy 41 Reverse Real Energy 41 S Save Key 6 Schematic Diagrams 61 Screen Time Out 25 Scroll Keys 5, 15 Security Definition 18 Self Test 57 Sensing Fuse 11 Set Tap Position 82 Setpoints 18 Setup 18 Siemens Website 2 Slave-Master 26 Soft Variamp 26 Software Communications 54 Uploading 54 Source Volts 40 Specifications 58 Supervisory Control Switch 10 Support Documentation 2 Switch Settings 59 Switches 10 System Key 34 System Wiring Configuration 22 T Tap Alert 26 Tap Changer Type 22 Tap Position Limits 26 Tap Resync 26 Terminal Blocks 12, 60 Terminal Strip 75 Terminal Strip Connections 78 Thermal Method 25 Time Delay Key 7 Time Delay Setpoint 29 Siemens Energy, Inc. Time of Day 24 Top Terminal Block 12 Transformer Polarity 65 Single-Phase Regulators 65 Troubleshooting Alert Messages 55 Communications Module 57 Introduction 55 Messages 55 Tap Tracking 57 U U2 Potential Transformer 22 Utility Polarity 22 Utility Winding 67 V View Instantaneous Load Voltage 81 View Messages 82 View Operation Counter Values 81 View/Reset Max/Min Values 81 View/Set Bandwidth Value 81 View/Set Forward Voltage Level Value 81 View/Set Line Drop Compensation Values 81 View/Set the Clock (Time and Date) 82 View/Set Time Delay Value 81 Viewing Messages 44 Voltage Calibration 56 Voltage Calibration Binding Posts 11 Voltage Level Key 6 Voltage Level Setpoint 29 Voltage Limit Control 31, 48 Voltage Limit Control Select Key 7 Voltage Reduction Control 29 Voltage Reduction Control Active Indicator LED 10 Voltage Reduction Control Select Key 7 Voltage Sensing and Correction 48 Vprimary Max 22 VRC Mode 30 AUTOMATIC (with Remote Override) 30 LOCAL 30 OFF 30 REMOTE 30 VRC Status 29, 45 VRC1 In 29 VRC2 In 29 W Website 2 Siemens Energy, Inc. Siemens Energy Inc. P.O. Box 6289 Jackson, MS 39288 Manual No. 21-115527-023 rev02 1M 0200TD Printed in U.S.A. © 2009 Siemens Energy Inc.. SIEMENS is a registered trademark of Siemens AG.